2-UP-2026-011 SRU Mihalik-Thompson Stadium DHW Replacement Drawings.pdf

PDF 6 MB Posted

Attached to
Mihalik-Thompson Stadium DHW Replacement Project
Solicitation number
Not on record
Issued by
Butler County, Pennsylvania

About this file

This document is a construction drawing set prepared by McKim & Creed engineering firm for Slippery Rock University's Mihalik-Thompson Stadium Domestic Hot Water Replacement project located at 100 North Road, Slippery Rock, Pennsylvania 16057. The project involves replacing the existing domestic hot water heater and 180-kilowatt hot water storage tank with four new domestic hot water boilers, supplemented by new water filters, an expansion tank, a recirculation pump, and a master mixing valve integrated into the campus Building Management System. The drawings provide comprehensive electrical and plumbing construction documents, including demolition plans, power distribution plans, panelboard schedules, and detailed piping schematics. The project is governed by the 2021 International Energy Conservation Code, International Fuel Gas Code, International Building Code, International Existing Building Code, and International Plumbing Code adopted by Pennsylvania. A mandatory pre-bid conference with site visit is scheduled for October 27, 2026, at 11:00 AM at the Maintenance Center Conference Room, 100 Building & Grounds Road, Slippery Rock, Pennsylvania 16057, with electronic bids due no later than 11:00 AM EST on November 19, 2026, through the PennBid platform.

The construction documents specify that all electrical work shall comply with the National Electrical Code and be inspected and approved by local electrical inspection agencies, with the electrical contractor responsible for all necessary permits and fees including the Certificate of Electrical Inspection. All plumbing work shall conform to applicable ordinances and codes of authorities having jurisdiction, with the plumbing contractor similarly responsible for permits and certification. The electrical contractor provides a one-year warranty on all installed equipment and installation, with an additional five-year warranty on wiring devices. The plumbing contractor warrants all work for one year from the date of acceptance, with refrigeration compressors guaranteed for five years. All materials and equipment shall be new and of first quality bearing appropriate UL labels. The project documents indicate coordination among electrical, plumbing, and mechanical contractors, with specific responsibility allocations detailed in the general notes and specifications throughout the contract documents. Shop drawings for plumbing equipment and electrical systems must be submitted for engineer review a minimum of two weeks prior to fabrication to maintain the owner's construction schedule.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CS-001

REVISION DESCRIPTION DATE

DRAWN

PROJ. MGR.

DESIGNED

CHECKED

DATE

M&C PROJ. #

REV

CONSTRUCTION DOCUMENTS

w w w .m ck im cr ee d.

co m

R ee ds da le S tre et

, S ui te

Ph on e:

(4

) 4

-9

0, F ax

2)

-8

Pi tts bu rg h, P en ns yl va ni a

07510-0001

SR

U

- M

IH

A

LI

K T

H O

M

PS

O N

ST

A

D

IU

M W

A

TE

R H

EA

TE

R R

EP

LA

C

EM

EN

T

MEB

2026-08-28

DPA

COVER SHEET

JDJ

JDJ

SHEET

DRAWING SHEET INDEX

DESCRIPTION

CS-001 COVER SHEET

E-001

ED-111 ELECTRICAL FIRST FLOOR DEMOLITION PLAN

ED-401 ELECTRICAL FIRST FLOOR ENLARGED DEMOLITION PLAN

E-111 ELECTRICAL FIRST FLOOR POWER PLAN

E-401 ELECTRICAL FIRST FLOOR ENLARGED POWER PLAN

SLIPPERY ROCK UNIVERSITY

MIHALIK THOMPSON STADIUM WATER HEATER REPLACEMENT

100 NORTH RD

SLIPPERY ROCK, PA 16057

OWNER: SLIPPERY ROCK UNIVERSITY

1 MORROW WAY, SLIPPERY ROCK, PA 16057

CONTACT: JUAN PEREZ

PHONE: (724) - 738 - 2964

EMAIL: JUAN.PEREZ@SRU.EDU

PLUMBING & ELECTRICAL

ENGINEER:

MCKIM & CREED

CONTACT: MATTHEW BUTCH

PHONE: (412) - 489 - 9100

EMAIL: MBUTCH@MCKIMCREED.COM

SCALE:

LOCATION MAP

NTS1

SCALE:

SITE PLAN

NTS2

PROJECT LOCATION

PROJECT LOCATION

E-601 ELECTRICAL PANELBOARD SCHEDULE

P-001 PLUMBING DATA SHEET

P-111 PLUMBING PARTIAL OVERALL FIRST FLOOR PLAN

ELECTRICAL SYMBOLS, GENERAL NOTES, AND ABBREVIATIONS.

E-801 ELECTRICAL SPECIFICATIONS

P-401 PLUMBING FIRST FLOOR ENLARGED PLAN

P-601 PLUMBING DETAIL SHEET

P-602 PLUMBING DETAIL SHEET

P-801 PLUMBING SPECIFICATION SHEET

AutoCAD SHX Text I:\07510\0001\ENG\80-DRAWINGS\86-DESIGN\86P-PLUMBING\CS-001.DWG 09/01/2026 13:40:02 JAMAR JETER http://www.mckimcreed.com

FEEDER TAG - SEE FEEDER SCHEDULE

CONDUIT TURNED UP

CONDUIT TURNED DOWN

POWER SYMBOLS

FIRE ALARM HORNS/STROBES

6'-6"

6'-0"

4'-0"

FINISHED FLOOR

2'-0"

3'-6"

1'-6"

0'-0"

TOP OF

CTR CENTER OF

MOUNTING HEIGHT SCHEDULE

GENERAL SYMBOLS

WALL MOUNTED HANDICAPPED

TELEPHONE OUTLETS

ELECTRICAL RECEPTACLES IN

MECHANICAL/ELECTRICAL ROOMS

& ELEVATOR MACHINE ROOMS

ELECTRICAL RECEPTACLES

(U.N.O.) COMMUNICATIONS/DATA

OUTLETS (U.N.O.)

EMERGENCY DUPLEX RECEPTACLE

COMBINATION MOTOR STARTER

FURNISHED BY MC INSTALLED BY EC

MOTOR STARTER

FURNISHED BY MC INSTALLED BY EC

EQUIPMENT CONTROL PANEL

FINAL CONNECTION BY EC

DUPLEX RECEPTACLE

JUNCTION BOX

POKE-THRU. PROVIDE COMBINATION ELECTRICAL/DATA

DEVICE. SAME DEVICE IS SHOWN ON BOTH POWER AND

SYSTEMS PLANS.

SIMPLEX RECEPTACLE

QUAD RECEPTACLE

SPECIAL RECEPTACLE NEMA TYPE AS SHOWN

WALL FLR CLG

NOMENCLATURE:

+ 6" ABOVE COUNTER

+48 MOUNTED 48" A.F.F.

CR OVERHEAD CORD REEL

GFI GROUND FAULT INTERRUPTER

IG ISOLATED GROUND

TR TAMPER RESISTANT

WP WEATHER PROOF

# NUMERICAL NUMBER INDICATES THE NUMBER

OF DEVICES

EMERGENCY QUAD RECEPTACLE

CORE DRILL

POKE-THRU. PROVIDE DATA DEVICE. SAME DEVICE MAYBE

SHOWN ON BOTH POWER AND SYSTEMS PLANS.

POKE-THRU. PROVIDE ELECTRICAL DEVICE. SAME DEVICE

MAYBE SHOWN ON BOTH POWER AND SYSTEMS PLANS.

FURNITURE FEED

MOTOR CONNECTION, SINGLE PHASE

MOTOR CONNECTION, THREE PHASE

UNFUSED DISCONNECT SWITCH

FUSED DISCONNECT SWITCH

FAN

120/208V ELECTRIC PANEL

EXISTING PANEL

POWER CENTER PANEL

DEVICE SYMBOL

POWER DEVICE KEY

PUSH BUTTON

PUSH BUTTON - 3 POSITION

SPECIAL RECEPTACLE NEMA TYPE AS SHOWN

SPLIT WIRED RECEPTACLE

JJ

T

277/480V ELECTRIC PANEL

WIRING SYMBOLS

GND GROUND CABLE

UNDER FLOOR OR UNDER GROUND CONDUIT

AND WIRING

SURFACE CONDUIT AND WIRING

WIRING HOMERUN, INDICATES BRANCH CIRCUIT

CONDUIT AND WIRE TO PANELBOARD

SURFACE RACEWAY WITH 20 AMP DUPLEX OUTLETS

120 V SPACED AS INDICATED

CONCEALED CONDUIT AND WIRING

INDICATES PANEL NAME INDICATES CIRCUIT

NUMBER

M

M

CP

X

XXX

B1-3

XX-XXREFERENCE LIGHTING

FIXTURE SCHEDULE FOR

MOUNTING REQUIREMENTS

6'-8" AFF OR 6" BELOW

FINISHED CEILING,

WHICHEVER IS LOWER

(BOTTOM OF LENS; MIN.)

30 3

NF 3R

DISCONNECT SWITCH KEY

SIZE NO. OF POLES

NEMA TYPE

FUSED # OR NF

PR PRESENT LIGHTING FIXTURE, SWITCH, DEVICE, ETC., TO REMAIN.

PRN PRESENT LIGHTING FIXTURE, SWITCH, DEVICE, ETC., TO BE

REMOVED AND REPLACED WITH NEW.

PRR PRESENT LIGHTING FIXTURE, SWITCH, DEVICE, ETC., SHOWN AT

NEW LOCATION.

PRX PRESENT LIGHTING FIXTURE, SWITCH, DEVICE, ETC., TO BE

REMOVED AND OUTLET BOX EXTENSION INSTALLED FOR

SURFACE CONDUIT OR SMR AND WIRE EXTENSION TO NEW

OUTLET SHOWN. REINSTALL PRESENT LIGHTING FIXTURE,

SWITCH, DEVICE, ETC.

RPC REMOVE PRESENT FIXTURE, SWITCH, DEVICE, ETC., AND CAP

OUTLET.

RPP REMOVE PRESENT FIXTURE, SWITCH, DEVICE, ETC., PATCH THE

PLASTER IF IN PLASTER: CAP IF IN METAL OR WOOD.

RPR REMOVE PRESENT FIXTURE, SWITCH, DEVICE, ETC., TO BE

REMOVED AND RELOCATED.

RPX REMOVE PRESENT FIXTURE, SWITCH, DEVICE, ETC., WIRE AND

ALL RELATED EXPOSED RACEWAY INSOFAR AS IS POSSIBLE. ALL

DAMAGED SURFACES TO BE REPAIRED.

X REMOTE GROUND FAULT DEVICE

TOP OF

PANELBOARDS, CABINETS

TOP OF

DISCONNECT SWITCHES,

STARTERS, AND CONTACTORS

ACTUATING DEVICE ON LIGHT

SWITCHES, FIRE ALARM PULL

STATIONS, MANUAL MOTOR

STARTERS OR PUSH BUTTON

COUNTER TOP RECEPTACLE

MOUNT RECEPTACLE 6" ABOVE

COUNTER TOP OR BACKSPLASH

PENDANT MOUNTED

LIGHT FIXTURES

CENTER OF

CENTER OF

CENTER OF

XX

PP POWER POLE

ABBREVIATION DESCRIPTION:

ELECTRICAL ABBREVIATIONSELECTRICAL GENERAL NOTES

ABBREVIATION DESCRIPTION:

A/AMP AMPERE

AFCI ARC FAULT INTERRUPTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CURRENT

AL ALUMINUM

ANSI AMER. NATIONAL STANDARDS INSTITUTE

ASA AMERICAN STANDARDS ASSOCIATION

ASTM AMER. SOCIETY OF TESTING MATERIALS

AWG AMERICAN WIRE GAUGE

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

BL BLANK

BKR BREAKER

C CONDUIT

CB, C/B CIRCUIT BREAKER

CKT BKR -

CKT CIRCUIT

CCTV CLOSED CIRCUIT T.V.

CLG CEILING

CO CONVENIENCE OUTLET

CONN CONNECTION

CU COPPER

DB DIRECT BURIAL

DISC DISCONNECT

DN DOWN

DWG DRAWING

EA EACH

E.C. ELECTRICAL CONTRACTOR

EF EXHAUST FAN

EH ELECTRIC HEAT

EIA ELECTRONIC INDUSTRIES ASSOC.

EMT ELECTRIC METALLIC TUBING

XP EXPLOSION PROOF

E, EM EMERGENCY

ELEC ELECTRIC

EMT ELECTRIC METALLIC TUBING

EQ/EQPM EQUIPMENT

EUH ELECTRIC UNIT HEATER

EWC ELECTRIC WATER COOLER

EX EXISTING

F FIXTURE

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FCU FAN COIL UNIT

FDR FEEDER

FIXT FIXTURE

FL FLOOR

FLUOR FLUORESCENT

FSS FUSED SAFETY SWITCH

FT FEET

G, GND,GRD GROUND

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT INTERRUPTER

GTB GROUND TERMINAL BOX

HID HIGH INTENSITY DISCHARGE

HP HORSE POWER

HPF HIGH POWER FACTOR

HR HOMERUN

HTR HEATER

HVAC HEATING, VENTILATION, AIR

CONDITIONING CONTRACTOR

HV HIGH VOLTAGE

HZ HERTZ

ICEA INTERNATIONAL CABLE ENGR. ASSO.

IEEE INSTITUTE OF ELECTRICAL AND

ELECTRONIC ENGINEERS

IES ILLUMINATING ENGINEERING SOCIETY

IN INCH

INCAN INCANDESCENT

IR INFRA-RED

JB/JBOX JUNCTION BOX

K THOUSAND

KVA KILOVOLT-AMPERE

KW KILOWATT

KWH KILOWATT HOUR

LA LIGHTING ARRESTER

LCP LIGHTING CONTROL PANEL

LED LIGHT EMITTING DIODE

LTS LIGHTS

LTG LIGHTING

LV LOW VOLTAGE

MC METAL CLAD

M.C. MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MH MANHOLE

MLO MAIN LUGS ONLY

MISC. MISCELLANEOUS

MTD MOUNTED

MTG HGT MOUNTING HEIGHT

MTR MOTOR

N/A NOT APPLICABLE

NC NORMALLY CLOSED

NF NON-FUSED SAFETY SWITCH

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN THIS CONTRACT

NM NON-METTALIC

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OEM ORIGINAL EQUIPMENT MANUFACTURER

OSHA OCCUPATIONAL SAFETY AND HEALTH

ADMINISTRATION

P POLE

PBOX PULL BOX

PC PHOTOCELL

P.C. PLUMBING CONTRACTOR

PH / Ø PHASE

PNL PANEL

POS POSITION

PRI PRIMARY

PWR POWER

REC / RECPT RECEPTACLE

RGS RIGID GALVANIZED STEEL

RMC RIGID GALVANIZED METAL CONDUIT

RT RAIN TIGHT

SCHED SCHEDULE

SEC SECONDARY

SIG SIGNAL

SM SURFACE MOUNTED

SMR SURFACE MOUNTED RACEWAY

SP SPARE

SS SAFETY SWITCH

SW SWITCH

SWBD SWITCHBOARD

TEL / TELE TELEPHONE

TL TWIST LOCK

TP TAMPER PROOF

TX / XFMR TRANSFORMER

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UH UNIT HEATER

UL UNDERWRITERS' LABORATORIES, INC

UNO UNLESS NOTED OTHERWISE

V VOLTAGE

VT VAPOR TIGHT

W WIRE; WATT

W/ WITH

W/O WITHOUT

WP WEATHER PROOF

WT WATER TIGHT

1. ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH ALL APPLICABLE

ORDINANCES, CODES, AND REGULATIONS OF ALL AUTHORITIES HAVING

JURISDICTION. ALL ELECTRICAL WORK SHALL BE INSPECTED AND

APPROVED BY THE LOCAL ELECTRICAL INSPECTION AGENCY. THE

ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY FEES AND

PERMITS, INCLUDING THE CERTIFICATE OF ELECTRICAL INSPECTION.

2. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR

CONSTRUCTION SAFETY. ARCHITECT AND/OR ENGINEER SHALL ASSUME

NO RESPONSIBILITY FOR WORKMAN'S OR PEDESTRIAN'S SAFETY.

NOTHING IN THE CONTRACT DOCUMENTS SHALL BE CONSTRUED TO

INSTRUCT PROCEDURES OR COMPONENTS FOR PROJECT SAFETY.

3. WHERE A CONFLICT ARISES BETWEEN PLANS, SPECIFICATIONS, DETAILS,

SCHEDULES, APPLICABLE CODES OR REGULATIONS, THE MOST

STRINGENT SHALL APPLY.

4. NOTHING CONTAINED IN THE CONTRACT DOCUMENTS SHALL BE

CONSTRUED TO CONFLICT WITH ANY NATIONAL, STATE, MUNICIPAL, OR

LOCAL LAWS OR REGULATIONS GOVERNING THE WORK INDICATED OR

SPECIFIED. THE ELECTRICAL CONTRACTOR, AT NO ADDITIONAL

EXPENSE TO THE OWNER, SHALL SATISFY ALL SUCH REQUIREMENTS.

5. THE CONTRACT DOCUMENTS ARE COMPRISED OF DRAWINGS AND

SPECIFICATIONS. EACH ELECTRICAL BIDDER SHALL VISIT THE SITE TO

DETERMINE EXISTING CONDITIONS PRIOR TO SUBMITTING BID

PROPOSAL. BIDS SHALL BE BASED ON THE COMPLETE EXAMINATION OF

THE DRAWINGS, SPECIFICATIONS, AND EXISTING CONDITIONS. NO

CONSIDERATION SHALL BE GIVEN TO ANY CONTRACTOR WHO FAILS TO

DO SO.

6. THE WORK UNDER THIS CONTRACT SHALL INCLUDE THE FURNISHING OF

ALL NECESSARY MATERIALS, TOOLS, AND LABOR FOR A COMPLETE AND

WORKING INSTALLATION AS DEFINED BY THE PLANS AND

SPECIFICATIONS. THE ELECTRICAL CONTRACTOR SHALL WARRANT THE

WORK INDICATED AND SPECIFIED FOR A PERIOD OF ONE (1) YEAR. THE

WORK SHALL FUNCTION AS INTENDED, BE COMPLETE IN ALL DETAILS,

AND SHALL INCLUDE ALL INDICATED, SPECIFIED, OR REQUIRED

ACCESSORIES FOR A FUNCTIONING SYSTEM.

7. THE ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY LIGHT AND

POWER AS REQUIRED BY THE GENERAL CONDITIONS OF THE

SPECIFICATIONS.

8. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THEIR WORK WITH

ALL OTHER TRADES. ALL DEVICES PROVIDED BY OTHERS THAT REQUIRE

LINE VOLTAGE ELECTRICAL POWER SHALL BE CONNECTED BY THE

ELECTRICAL CONTRACTOR. POWER, PHONE, DATA, TV, AND SIMILAR

DEVICE OUTLET LOCATIONS SHALL BE COORDINATED WITH THE

ARCHITECTURAL INTERIOR LAYOUTS, THE GENERAL CONTRACTOR, AND

THE OWNER.

9. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE OWNER'S

PROJECT MANAGER PRIOR TO AND FOR SCHEDULING ANY

INTERRUPTION OF BUILDING UTILITIES.

10. THE ELECTRICAL CONTRACTOR AT THE SITE SHALL VERIFY ALL

DIMENSIONS AND EXISTING CONDITIONS PERTAINING TO THE

INSTALLATION OF THE ELECTRICAL SYSTEMS. WHERE A CONTRACTOR

UNCOVERS CONDITIONS NOT INDICATED ON THE PLANS OR IN THE

SPECIFICATIONS, THEY SHALL NOTIFY THE ARCHITECT PRIOR TO

PROCEEDING WITH ANY WORK. FAILURE TO NOTIFY THE ARCHITECT

SHALL MAKE THE CONTRACTOR RESPONSIBLE FOR ALL COSTS AND

CONSEQUENCES OF SUCH FAILURE.

11. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND REPRESENT THE

DESIGN/LAYOUT INTENT ONLY. THE ELECTRICAL CONTRACTOR SHALL

DETERMINE CIRCUITING, ROUTING, WIRING ETC., AS REQUIRED BY THE

SITE CONDITIONS AND ALL APPLICABLE CODES.

12. ALL WIRING SHALL BE CONCEALED IN FINISHED AREAS AS SPECIFIED.

USE EMT CONDUIT, MINIMUM 3/4" IN SIZE, UNLESS NOTED OR SPECIFIED

OTHERWISE.

13. THE FOLLOWING CONDUCTORS SHALL BE INSTALLED IN HEAVY WALL

CONDUIT:

13.1. WHERE REQUIRED BY THE NEC.

13.2. EXPOSED WIRING ON A ROOF - SEAL PROPERLY.

13.3. EXTERIOR, ABOVE GRADE WIRING.

14. FOLLOWING FEEDERS SHALL BE INSTALLED IN EMT:

14.1. BRANCH FEEDERS TO PANELS.

14.2. BRANCH RACEWAY RUN EXPOSED.

15. UPON THE COMPLETION OF WORK, THE E.C. SHALL PROVIDE ALL

PANELBOARDS WITH TYPED PANEL SCHEDULES TO CLEARLY DEFINE THE

EQUIPMENT SERVED.

16. UPON THE COMPLETION OF WORK, THE E.C. SHALL PROVIDE ALL

DISTRIBUTION EQUIPMENT WITH TYPED NAMEPLATES TO CLEARLY

DEFINE THE EQUIPMENT SERVED AND RECEPTACLE PLATES WITH

CIRCUITS SERVING EACH.

17. ALL HOMERUNS WITH MORE THAN SIX (6) TOTAL CONDUCTORS SHALL BE

A MINIMUM OF #10 AWG THWN WIRE UNLESS SPECIFICALLY SIZED

OTHERWISE.

18. ALL WORK SHOWN ON THE ELECTRICAL DRAWINGS SHALL BE

COMPLETED BY THE ELECTRICAL CONTRACTOR UNLESS SPECIFICALLY

NOTED OTHERWISE.

19. CONTRACTOR SHALL REMOVE DEMOLITION DEBRIS COMPLETELY.

CONTRACTOR SHALL SCHEDULE WITH THE OWNER THE TIME, LOCATION,

AND HAULING ROUTE.

20. CONTRACTOR SHALL CLEAN UP ALL DEBRIS AT THE END OF EACH WORK

DAY.

21. EXACT COUNTS/QUANTITIES FOR CONTRACT PURPOSES SHALL BE

VERIFIED IN THE FIELD BY THE CONTRACTOR AND INCLUDED AS PART OF

THE BASE BID.

22. VERIFY EXACT LOCATION OF ALL MECHANICAL AND PLUMBING

EQUIPMENT WITH THE MECHANICAL CONTRACTOR, PRIOR TO ROUGH-IN.

E.C. SHALL ALSO INCLUDE COORDINATION WITH DEVICES BY M.C.,

WIRING REQUIREMENTS, INTERCONNECTIONS, TERMINATIONS AND

PROVIDE AS REQUIRED.

23. ALL CONDUITS ROUTED IN EXPOSED AREAS SHALL BE MOUNTED TIGHT

TO THE UNDERSIDE OF THE STRUCTURAL STEEL. THIS APPLIES FOR ALL

BRANCH CIRCUIT AND FEEDER CONDUITS.

24. ALL HOLES AND OPENINGS CREATED TO EXTEND THE ELECTRICAL

SYSTEMS THROUGH FLOORS AND FIRE RATED ASSEMBLIES SHALL BE

FIRESTOPPED.

25. DURING THE BIDDING PROCESS, ELECTRICAL CONTRACTOR SHALL

REVIEW DRAWINGS AND SPECIFICATIONS OF ALL OTHER TRADES

(GENERAL, HVAC, AND PLUMBING). ALL ITEMS REQUIRING POWER

INDICATED ON THESE DRAWINGS BUT NOT INDICATED ON THE

ELECTRICAL DRAWINGS SHALL BE CONSIDERED A PART OF THE

ELECTRICAL CONTRACTOR'S WORK. THIS WORK SHALL BE INSTALLED

PER THE NEC AT NO ADDITIONAL COST TO THE OWNER.

26. WHERE CONDUIT SIZES HAVE BEEN OMITTED, THE CONTRACTOR SHALL

INSTALL THE CORRECT SIZES REQUIRED BY THE NEC AS DETERMINED

BY THE SIZE AND NUMBER OF WIRES TO BE INSTALLED. WHERE THE

NUMBER AND/OR SIZES OF HAVE BEEN OMITTED, THE CONTRACTOR

SHALL INSTALL THE REQUIRED NUMBER AND/OR SIZES AS DETERMINED

BY THE EQUIPMENT REQUIREMENTS OR FROM ADJACENT SECTIONS AND

CIRCUIT NUMBERS.

27. WIRE SIZE FOR BRANCH CIRCUITS SHALL BE ADJUSTED TO COMPENSATE

FOR VOLTAGE DROP CALCULATIONS AS REQUIRED BY NEC. IF CIRCUIT

RUN EXCEEDS 100FT. IN WIRE LENGTH, NEXT WIRE SIZE (E.G., #10 AWG,

ETC.) SHALL BE USED.

28. STARTERS, COMBINATION STARTERS, CONTACTORS, ETC. FOR

MECHANICAL EQUIPMENT SHALL BE PROVIDED BY THE MECHANICAL

CONTRACTOR. ALL POWER WIRING AND CONDUIT TO EQUIPMENT

TERMINALS SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR.

POWER TO MECHANICAL EQUIPMENT SHALL BE TURNED ON ONLY BY

THE MECHANICAL CONTRACTOR. MECHANICAL NAMEPLATE DATA SHALL

NOT BE COVERED BY ELECTRICAL DEVICES.

29. THE ELECTRICAL CONTRACTOR SHALL FURNISH SUBMITTALS IN

ACCORDANCE WITH THE SPECIFICATIONS. ALL SUBMITTALS SHALL BE

REVIEWED AND STAMPED BY THE ENGINEER PRIOR TO INSTALLATION.

30. THE ELECTRICAL CONTRACTOR SHALL PROVIDE AS-BUILT DRAWINGS

FOR THE ENTIRE PROJECT AS DEFINED IN THE SPECIFICATIONS.

SINGLE POLE SWITCH

NOMENCLATURE - X=:

M MANUAL MOTOR STARTER

X

REVISION DESCRIPTION DATE

DRAWN

PROJ. MGR.

DESIGNED

CHECKED

DATE

M&C PROJ. #

REV

CONSTRUCTION DOCUMENTS

w w w .m ck im cr ee d.

co m

R ee ds da le S tre et

, S ui te

Ph on e:

(4

) 4

-9

0, F ax

2)

-8 bu rg h, P en ns yl va ni a

07510-0001

SR

U

- M

IH

A

LI

K T

H O

M

PS

O N

ST

A

D

IU

M W

A

TE

R H

EA

TE

R R

EP

LA

C

EM

EN

T

MEB

2026-08-28

8/28/26

RDS

E-001

ELECTRICAL SYMBOLS,

GENERAL NOTES, AND

ABBREVIATIONS

ZBZ

ZBZ

AutoCAD SHX Text I:\07510\0001\ENG\80-DRAWINGS\86-DESIGN\86E-ELECTRICAL\E-001.DWG 08/28/2026 13:51:43 ZACHARY ZDROJEWSKI

EX. PADMOUNT TRANSFORMER

(FRONT)

EX. UTILITY METER

EX. EQUIPMENT PAD

SCALE:

ELECTRICAL FIRST FLOOR DEMOLITION PLAN

1/8" = 1'-0"1

DEMOLITION GENERAL NOTES

1. WHERE PRESENT EQUIPMENT IS NOTED TO REMAIN OR

LABELED “PR”, IT IS TO REMAIN IN THE PRESENT LOCATION.

2. ALL EXPOSED RACEWAYS, DEVICES, AND OTHER ELECTRICAL

EQUIPMENT THAT ARE NO LONGER A FUNCTIONING PART OF

THE ELECTRICAL SYSTEM OR ANY AUXILIARY ELECTRICAL

SYSTEM, SHALL BE DE-ENERGIZED, DISCONNECTED, AND

REMOVED. GENERALLY, THESE REMOVALS ARE NOT

SPECIFICALLY INDICATED ON THE DRAWINGS. THIS

CONTRACTOR SHALL PATCH ALL CEILING, WALL, OR FLOOR

OPENINGS LEFT BY THIS REMOVAL.

3. IF THE CONTINUITY OF ANY EXISTING CIRCUITS THAT ARE TO

REMAIN IS INTERRUPTED BY THESE ALTERATIONS, EVEN

THOUGH IT MAY NOT BE INDICATED, THE CONTRACTOR SHALL

RESTORE SUCH CIRCUITS, PROVIDING ALL NECESSARY

MATERIALS AND LABOR TO ACCOMPLISH THIS.

4. ITEMS INDICATED ON THE DRAWINGS THAT ARE TO BE

RELOCATED SHALL BE REMOVED, CLEANED, AND STORED

PRIOR TO RE-USE. ALL ITEMS INDICATED TO BE REMOVED &

RELOCATED SHALL BE REWIRED AS NECESSARY TO

ACCOMPLISH THE INTENDED FUNCTION.

5. EXISTING DEVICES AND OTHER ELECTRICAL EQUIPMENT NOT

SHOWN OR NOT INDICATED TO BE REMOVED OR REPLACED

SHALL REMAIN. IF REQUIRED, EXISTING WIRING SHALL BE

MODIFIED OR REPLACED TO SUIT THE NEW LAYOUT.

6. ALL REMOVED ELECTRICAL EQUIPMENT REQUESTED BY THE

OWNER SHALL BE TURNED OVER TO THE OWNER AND STORED

WHERE DIRECTED, IN THE CONDITION AS FOUND. ALL OTHER

REMOVED EQUIPMENT AND MATERIAL SHALL BECOME THE

PROPERTY OF THIS CONTRACTOR AND SHALL BE REMOVED

FROM THE PREMISES BY CONTRACTOR.

7. FOR THE DURATION OF THE CONTRACT, THIS CONTRACTOR

SHALL MAKE EVERY EFFORT TO KEEP ELECTRICAL OUTAGES

TO A MINIMUM. IN ORDER TO INTERRUPT CONTINUITY OF

ELECTRICAL SERVICE TO ANY PART OF THE BUILDING, IT SHALL

BE NECESSARY FOR THIS CONTRACTOR TO REQUEST

PERMISSION FOR SUCH OUTAGES BY LETTER. THE LETTER

SHALL STATE THE DATE OF PROPOSED OUTAGE, TIME IT SHALL

START, TOTAL OUTAGE TIME REQUIRED, AND REASON FOR THE

OUTAGE. THE REQUEST SHALL BE SUBMITTED A MINIMUM OF 14

DAYS BEFORE THE PROPOSED OUTAGE.

8. ALL ITEMS AND DEVICES SHOWN WITH DASHED LINES ARE

INTENDED TO BE DISCONNECTED & REMOVED.

9. ALL ITEMS SHOWN WITH SOLID LINES ARE INTENDED TO

REMAIN. E.C. SHALL MAKE ANY ADJUSTMENTS NECESSARY TO

MAINTAIN ITEMS & DEVICES, INCLUDING EXISTING WIRING.

REVISION DESCRIPTION DATE

DRAWN

PROJ. MGR.

DESIGNED

CHECKED

DATE

M&C PROJ. #

REV

CONSTRUCTION DOCUMENTS

w w w .m ck im cr ee d.

co m

R ee ds da le S tre et

, S ui te

Ph on e:

(4

) 4

-9

0, F ax

2)

-8 bu rg h, P en ns yl va ni a

07510-0001

SR

U

- M

IH

A

LI

K T

H O

M

PS

O N

ST

A

D

IU

M W

A

TE

R H

EA

TE

R R

EP

LA

C

EM

EN

T

MEB

KEY PLAN

2026-08-28

8/28/26

RDS

ED-111

ELECTRICAL

FIRST FLOOR

DEMOLITION PLAN

ZBZ

ZBZ

ED-401

AutoCAD SHX Text I:\07510\0001\ENG\80-DRAWINGS\86-DESIGN\86E-ELECTRICAL\ED-111.DWG 08/28/2026 13:50:03 ZACHARY ZDROJEWSKI

EX. PANEL LC

EX. TRANSFORMER TC EX. PANEL HC

EX. TELECOM PLYWOOD

BACKBOARD

EX. PANEL TS

EX. MSB (FRONT)

EX. LCC1

EX. EQUIPMENT PAD (TYP)

EX. PANEL LC-2

EX. TRANSFORMER TC2

MECHANICAL ROOM

EX. PANEL

(FIELD LIGHTING)

EX. WATER HEATER

(RPX)

EX. 180kW HOT WATER

STORAGE TANK (RPX) 1

SCALE:

ELECTRICAL FIRST FLOOR ENLARGED DEMOLITION PLAN

1/4" = 1'-0"1

REVISION DESCRIPTION DATE

DRAWN

PROJ. MGR.

DESIGNED

CHECKED

DATE

M&C PROJ. #

REV

CONSTRUCTION DOCUMENTS

w w w .m ck im cr ee d.

co m

R ee ds da le S tre et

, S ui te

Ph on e:

(4

) 4

-9

0, F ax

2)

-8 bu rg h, P en ns yl va ni a

07510-0001

SR

U

- M

IH

A

LI

K T

H O

M

PS

O N

ST

A

D

IU

M W

A

TE

R H

EA

TE

R R

EP

LA

C

EM

EN

T

MEB

KEY PLAN

2026-08-28

8/28/26

RDS

ED-401

ELECTRICAL

FIRST FLOOR ENLARGED

DEMOLITION PLAN

ZBZ

ZBZ

DEMOLITION GENERAL NOTES

1. WHERE PRESENT EQUIPMENT IS NOTED TO REMAIN OR

LABELED “PR”, IT IS TO REMAIN IN THE PRESENT LOCATION.

2. ALL EXPOSED RACEWAYS, DEVICES, AND OTHER ELECTRICAL

EQUIPMENT THAT ARE NO LONGER A FUNCTIONING PART OF

THE ELECTRICAL SYSTEM OR ANY AUXILIARY ELECTRICAL

SYSTEM, SHALL BE DE-ENERGIZED, DISCONNECTED, AND

REMOVED. GENERALLY, THESE REMOVALS ARE NOT

SPECIFICALLY INDICATED ON THE DRAWINGS. THIS

CONTRACTOR SHALL PATCH ALL CEILING, WALL, OR FLOOR

OPENINGS LEFT BY THIS REMOVAL.

3. IF THE CONTINUITY OF ANY EXISTING CIRCUITS THAT ARE TO

REMAIN IS INTERRUPTED BY THESE ALTERATIONS, EVEN

THOUGH IT MAY NOT BE INDICATED, THE CONTRACTOR SHALL

RESTORE SUCH CIRCUITS, PROVIDING ALL NECESSARY

MATERIALS AND LABOR TO ACCOMPLISH THIS.

4. ITEMS INDICATED ON THE DRAWINGS THAT ARE TO BE

RELOCATED SHALL BE REMOVED, CLEANED, AND STORED

PRIOR TO RE-USE. ALL ITEMS INDICATED TO BE REMOVED &

RELOCATED SHALL BE REWIRED AS NECESSARY TO

ACCOMPLISH THE INTENDED FUNCTION.

5. EXISTING DEVICES AND OTHER ELECTRICAL EQUIPMENT NOT

SHOWN OR NOT INDICATED TO BE REMOVED OR REPLACED

SHALL REMAIN. IF REQUIRED, EXISTING WIRING SHALL BE

MODIFIED OR REPLACED TO SUIT THE NEW LAYOUT.

6. ALL REMOVED ELECTRICAL EQUIPMENT REQUESTED BY THE

OWNER SHALL BE TURNED OVER TO THE OWNER AND STORED

WHERE DIRECTED, IN THE CONDITION AS FOUND. ALL OTHER

REMOVED EQUIPMENT AND MATERIAL SHALL BECOME THE

PROPERTY OF THIS CONTRACTOR AND SHALL BE REMOVED

FROM THE PREMISES BY CONTRACTOR.

7. FOR THE DURATION OF THE CONTRACT, THIS CONTRACTOR

SHALL MAKE EVERY EFFORT TO KEEP ELECTRICAL OUTAGES

TO A MINIMUM. IN ORDER TO INTERRUPT CONTINUITY OF

ELECTRICAL SERVICE TO ANY PART OF THE BUILDING, IT SHALL

BE NECESSARY FOR THIS CONTRACTOR TO REQUEST

PERMISSION FOR SUCH OUTAGES BY LETTER. THE LETTER

SHALL STATE THE DATE OF PROPOSED OUTAGE, TIME IT SHALL

START, TOTAL OUTAGE TIME REQUIRED, AND REASON FOR THE

OUTAGE. THE REQUEST SHALL BE SUBMITTED A MINIMUM OF 14

DAYS BEFORE THE PROPOSED OUTAGE.

8. ALL ITEMS AND DEVICES SHOWN WITH DASHED LINES ARE

INTENDED TO BE DISCONNECTED & REMOVED.

9. ALL ITEMS SHOWN WITH SOLID LINES ARE INTENDED TO

REMAIN. E.C. SHALL MAKE ANY ADJUSTMENTS NECESSARY TO

MAINTAIN ITEMS & DEVICES, INCLUDING EXISTING WIRING.

CONTRACTOR SHALL DISCONNECT AND REMOVE ELECTRICAL

EQUIPMENT (E.G., WIRING DEVICES, WIRING, CONDUIT, ETC.)

PERTAINING TO THE DEMOLISHED PLUMBING SYSTEM

EQUIPMENT. RESPECTIVE CIRCUIT BREAKER(S) SHALL BE

LABELED AS SPARE (I.E., IN EXISTING MSB, ETC.) AND REMAIN

FOR FUTURE USE. REFERENCE PLUMBING DEMOLITION

DRAWINGS FOR ADDITIONAL DETAILS.

EXISTING RIGID CONDUIT STUB-UP FOR THE DOMESTIC HOT

WATER STORAGE TANK TO BE DEMOLISHED SHALL BE CUT

AND REMOVED TO BE FLUSH WITH THE FLOOR. FLOOR SHALL

BE PATCHED AS REQUIRED.

DEMOLITION KEY NOTES

AutoCAD SHX Text I:\07510\0001\ENG\80-DRAWINGS\86-DESIGN\86E-ELECTRICAL\ED-401.DWG 08/28/2026 13:52:27 ZACHARY ZDROJEWSKI

EX. PADMOUNT TRANSFORMER

(FRONT)

EX. UTILITY METER

EX. EQUIPMENT PAD

SCALE:

ELECTRICAL FIRST FLOOR POWER PLAN

1/8" = 1'-0"1

REVISION DESCRIPTION DATE

DRAWN

PROJ. MGR.

DESIGNED

CHECKED

DATE

M&C PROJ. #

REV

CONSTRUCTION DOCUMENTS

w w w .m ck im cr ee d.

co m

R ee ds da le S tre et

, S ui te

Ph on e:

(4

) 4

-9

0, F ax

2)

-8 bu rg h, P en ns yl va ni a

07510-0001

SR

U

- M

IH

A

LI

K T

H O

M

PS

O N

ST

A

D

IU

M W

A

TE

R H

EA

TE

R R

EP

LA

C

EM

EN

T

MEB

KEY PLAN

2026-08-28

8/28/26

RDS

E-111

ELECTRICAL

FIRST FLOOR

POWER PLAN

ZBZ

ZBZ

E-401

AutoCAD SHX Text I:\07510\0001\ENG\80-DRAWINGS\86-DESIGN\86E-ELECTRICAL\E-111.DWG 08/28/2026 13:53:08 ZACHARY ZDROJEWSKI

EX. PANEL LC

EX. TRANSFORMER TC EX. PANEL HC

EX. TELECOM PLYWOOD

BACKBOARD

EX. PANEL TS

EX. MSB (FRONT)

EX. LCC1

EX. EQUIPMENT PAD (TYP)

EX. PANEL LC-2

EX. TRANSFORMER TC2

2 2 2 2

LC-37

M

LC-34

M

LC-32

M

LC-41

M

LC-39

M

3 4 3 4 3 4 3 4

MECHANICAL ROOM

EX. PANEL

(FIELD LIGHTING)

CP-1

WH-1

(TYP OF 4)

SCALE:

ELECTRICAL FIRST FLOOR ENLARGED POWER PLAN

1/4" = 1'-0"1

REFERENCE DRAWING E-601 FOR EXISTING PANELBOARD

MODIFICATIONS.

DISCONNECT SWITCH / MANUAL MOTOR STARTER SHALL BE

FURNISHED BY PLUMBING CONTRACTOR AND INSTALLED BY

ELECTRICAL CONTRACTOR. FINAL CONDUIT CONNECTIONS

FROM DISCONNECT SWITCH TO WATER HEATER TANK SHALL BE

LFMC.

METAL WATER PIPING FOR THE PROPOSED WATER HEATER

SYSTEM SHALL BE MECHANICALLY BONDED (VIA #3/0 AWG BARE

COPPER CONDUCTOR) TO THE BUILDING'S EXISTING

GROUNDING ELECTRODE SYSTEM (I.E., EXISTING GROUND BUS

BAR IN MSB, ETC.) IN ACCORDANCE WITH NEC ARTICLE

250.104(A). BONDED CONNECTIONS SHALL BE ACCESSIBLE

AFTER INSTALLATION. PIPING MAY BE BONDED TOGETHER FOR

ONE (1) SHARED HOMERUN BONDED CONNECTION TO THE

GROUNDING ELECTRODE SYSTEM.

METAL GAS PIPING FOR THE PROPOSED WATER HEATER

SYSTEM SHALL BE MECHANICALLY BONDED (VIA #10 AWG BARE

COPPER CONDUCTOR) TO THE BUILDING'S EXISTING

GROUNDING ELECTRODE SYSTEM (I.E., EQUIPMENT

GROUNDING CONDUCTOR UTILIZED FOR THE 120V POWER

SUPPLY CIRCUIT TO RESPECTIVE WATER HEATER, ETC.) IN

ACCORDANCE WITH NEC ARTICLE 250.104(B). BONDED

CONNECTIONS SHALL BE ACCESSIBLE AFTER INSTALLATION.

PIPING MAY BE BONDED TOGETHER FOR ONE (1) SHARED

HOMERUN BONDED CONNECTION TO THE GROUNDING

ELECTRODE SYSTEM.

KEY NOTES

REVISION DESCRIPTION DATE

DRAWN

PROJ. MGR.

DESIGNED

CHECKED

DATE

M&C PROJ. #

REV

CONSTRUCTION DOCUMENTS

w w w .m ck im cr ee d.

co m

R ee ds da le S tre et

, S ui te

Ph on e:

(4

) 4

-9

0, F ax

2)

-8 bu rg h, P en ns yl va ni a

07510-0001

SR

U

- M

IH

A

LI

K T

H O

M

PS

O N

ST

A

D

IU

M W

A

TE

R H

EA

TE

R R

EP

LA

C

EM

EN

T

MEB

KEY PLAN

2026-08-28

8/28/26

RDS

E-401

ELECTRICAL

FIRST FLOOR ENLARGED

POWER PLAN

ZBZ

ZBZ

AutoCAD SHX Text I:\07510\0001\ENG\80-DRAWINGS\86-DESIGN\86E-ELECTRICAL\E-401.DWG 08/28/2026 13:53:42 ZACHARY ZDROJEWSKI

DRAWN

PROJ. MGR.

DESIGNED

CHECKED

DATE

M&C PROJ. #

REV

CONSTRUCTION DOCUMENTS

w w w .m ck im cr ee d.

co m

R ee ds da le S tre et

, S ui te

Ph on e:

(4

) 4

-9

0, F ax

2)

-8 bu rg h, P en ns yl va ni a

07510-0001

SR

U

- M

IH

A

LI

K T

H O

M

PS

O N

ST

A

D

IU

M W

A

TE

R H

EA

TE

R R

EP

LA

C

EM

EN

T

MEB

2026-08-28

8/28/26

RDS

E-601

ELECTRICAL

PANELBOARD

SCHEDULE

ZBZ

ZBZ

EXISTING PANEL LC

POS

NO

LOAD

DESCRIPTION

COND

SIZE

WIRE

SIZE

LOAD

KVA

C/B

SIZE

PHASE C/B

SIZE

LOAD

KVA

WIRE

SIZE

COND

SIZE

LOAD

DESCRIPTION

POS

NOA B C

1 EX. LIGHTING - ROOM #121 EX. EX. 0.75 20/1 ● 20/1 0.75 EX. EX. EX. LIGHTING - ROOM #123 2

3 EX. LIGHTING - ROOM #121 EX. EX. 0.75 20/1 ● 20/1 0.75 EX. EX. EX. LIGHTING - ROOM #122 4

5 EX. RECEPTACLES - ROOM #121 EX. EX. 0.72 20/1 ● 20/1 0.75 EX. EX. EX. LIGHTING - ROOM #124 6

7 EX. FANS R-15, R-14 (ROOM #121) EX. EX. 0.50 20/1 ● 20/1 1.20 EX. EX. EX. JOHNSON DRYER ROOM #121 8

9 EX. FAN DAMPER R-16 (ROOM #122) EX. EX. 0.50 20/1 ● 20/1 0.50 EX. EX. EX. E-PHONE, HEAT CONTROL 10

11 EX. FAN DAMPER R-17 (ROOM #123) EX. EX. 0.50 20/1 ● 20/1 0.90 EX. EX. EX. RECEPTACLES - ROOMS #122, 123 12

13 EX. LIGHTING - OUTSIDE DOORS NORTH EX. EX. 0.50 20/1 ● 20/1 0.50 EX. EX. EX. FAN R-18 ROOM #124 14

15 EX. HOT WATER CIRCULATION PUMP ROOM #121 EX. EX. 0.50 20/1 ● 20/1 1.00 EX. EX. EX. TICKET BOOTH 16

17 EX. TICKET BOOTH EX. EX. 1.00 20/1 ● 20/1 1.00 EX. EX. EX. TICKET BOOTH 18

EX. CONCESSION STAND EX. EX.

3.60

60/3

● 20/1 SPARE 20

21 3.60 ● 20/1 1.00 EX. EX. EX. TICKET BOOTH 22

23 3.60 ● 20/3

1.20

EX. EX. EX. AIR COMPRESSOR ROOM #121

EX. SCORE BOARD EX. EX.

1.00

20/3

● 1.20 26

27 1.00 ● 1.20 28

29 1.00 ● 20/1 1.00 EX. EX. EX. TICKET BOOTH 30

31 EX. HOT WATER CIRCULATION PUMP MECHANICAL EX. EX. 0.50 20/1 ● 20/1 0.60 #12 3/4" WATER HEATER #3 (WH-1) 32

SPARE 30/2

● 20/1 0.60 #12 3/4" WATER HEATER #4 (WH-1) 34

35 ● SPACE 36

37 CIRCULATION PUMP (CP-1) 3/4" #12 1.02 20/1 ● SPACE 38

39 WATER HEATER #1 (WH-1) 3/4" #12 0.60 20/1 ● SPACE 40

41 WATER HEATER #2 (WH-1) 3/4" #12 0.60 20/1 ● SPACE 42

VOLTAGE: 208/120 VOLT, 3-PHASE, 4-WIRE A PHASE 12.12 LOCATION: MECHANICAL ROOM

SIZE/TYPE BUS: 250 AMP A.I.C.: 10kA B PHASE 12.00 MOUNTING: SURFACE

SIZE/TYPE MAINS: 225 AMP MCB C PHASE 12.27 SOURCE: EX. TRANSFORMER TC (30kVA)

CONNECTED

SUB-TOTAL (kva) 36.39 REMARKS: EXISTING PANELBOARD BY SIEMENS, PANEL TYPE P1, CAT. NO.P1C42QR225CBST

REUSE EXISTING CIRCUIT BREAKER FOR THE INDICATED BRANCH

CIRCUIT.

FURNISH AND INSTALL NEW BRANCH CIRCUIT BREAKER IN THE

AVAILABLE PANELBOARD SPACE AS SHOWN. NEW CIRCUIT

BREAKER'S AIC RATING SHALL MATCH OR EXCEED THE OVERALL kA

RATING OF RESPECTIVE PANELBOARD.

KEY NOTES

1 1. CONTRACTOR SHALL REPLACE ALL MODIFIED EXISTING

PANELBOARD CIRCUIT DIRECTORIES WITH UPDATED TYPEWRITTEN

CIRCUIT DIRECTORIES AS REQUIRED TO REFLECT FINAL AS-BUILT

CONDITIONS.

GENERAL NOTES

AutoCAD SHX Text I:\07510\0001\ENG\80-DRAWINGS\86-DESIGN\86E-ELECTRICAL\E-601.DWG 08/28/2026 13:54:27 ZACHARY ZDROJEWSKI

PROJ. MGR.

DESIGNED

CHECKED

DATE

M&C PROJ. #

REV

CONSTRUCTION DOCUMENTS

w w w .m ck im cr ee d.

co m

R ee ds da le S tre et

, S ui te

Ph on e:

(4

) 4

-9

0, F ax

2)

-8 bu rg h, P en ns yl va ni a

07510-0001

SR

U

- M

IH

A

LI

K T

H O

M

PS

O N

ST

A

D

IU

M W

A

TE

R H

EA

TE

R R

EP

LA

C

EM

EN

T

MEB

2026-08-28

8/28/26

RDS

E-801

ELECTRICAL

SPECIFICATIONS

ZBZ

ZBZ

AS BUILT DRAWINGS

CONTRACTORS SHALL SUPPLY A COMPLETE SET OF MARKED AS-BUILT DRAWINGS TO THE OWNER UPON COMPLETION OF THE

PROJECT.

WARRANTY

THE ELECTRICAL CONTRACTOR SHALL WARRANT ALL INSTALLED EQUIPMENT AND INSTALLATION FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE. PROVIDE ADDITIONAL MANUFACTURERS' WARRANTIES: WIRING DEVICES - 5 YEARS.

GENERAL ELECTRICAL REQUIREMENTS

THE WORK COVERED BY THIS DIVISION OF THE CONTRACT CONSISTS OF FURNISHING ALL LABOR, MATERIALS, EQUIPMENT, TRANSPORTATION AND APPLIANCES REQUIRED IN PERFORMING ALL OPERATIONS IN CONNECTION WITH THE ELECTRICAL

CONSTRUCTION WORK.

THIS CONTRACTOR SHALL VISIT THE SITE AND ACQUAINT THEMSELVES WITH EXISTING CONDITIONS BEFORE SUBMITTING THEIR

PROPOSAL.

ALL MATERIALS AND EQUIPMENT FURNISHED FOR THE PROJECT SHALL BE NEW AND OF FIRST QUALITY, PRODUCED BY MANUFACTURERS OF RECOGNIZED REPUTATION. ALL MATERIALS SHALL BE APPROVED BY UNDERWRITERS' LABORATORIES, INC.

THIS CONTRACTOR SHALL PROCURE ALL NECESSARY PERMITS, PAYING ALL ASSOCIATED CHARGES, AND FURNISHING THE OWNER WITH EVIDENCE OF THE PERMITS BEFORE COMMENCING THE CONTRACT WORK. FURTHERMORE, A FINAL ELECTRICAL INSPECTION CERTIFICATE SHALL BE FURNISHED TO THE OWNER BY THIS SUBCONTRACTOR PRIOR TO THEIR APPLICATION FOR FINAL PAYMENT. IT SHALL BE THIS SUBCONTRACTOR'S RESPONSIBILITY TO NOTIFY THE INSPECTION DEPARTMENT IN SUFFICIENT TIME THAT A COMPLETE ROUGH-IN INSPECTION MAY BE MADE. THE MATERIAL, EQUIPMENT AND INSTALLATION SHALL CONFORM

TO THE LATEST EDITIONS OF THE FOLLOWING:

· THE NATIONAL ELECTRICAL CODE (NFPA 70)

· THE NATIONAL FIRE PROTECTION ASSOCIATION

· THE NATIONAL ELECTRICAL SAFETY CODE

· AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)

· NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

· INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)

· THE FEDERAL OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA)

· INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE)

· BUILDING AND FIRE PREVENTION CODES

· INTERNATIONAL BUILDING CODE (IBC)

· INTERNATIONAL EXISTING BUILDING CODE (IEBC)

· INTERNATIONAL ENERGY CONSERVATION CODE (IECC)

SUBMIT SHOP DRAWINGS CLEARLY MARKED FOR ALL ITEMS OF MATERIAL AND EQUIPMENT AS SPECIFIED HEREIN. REVIEW THE SHOP DRAWINGS PRIOR TO SUBMISSION TO VERIFY THAT THEY ARE COMPLETE INCLUDING THE FOLLOWING MINIMUM

INFORMATION:

COMPLETE CONSTRUCTION DETAILS INCLUDING DIMENSIONS, MATERIALS AND FINISHES; DIAGRAMS OR ILLUSTRATIONS SHOWING PHYSICAL CHARACTERISTICS; PERFORMANCE DATA; DESCRIPTION OF OPERATION; NAME OF LABORATORY BY WHICH ITEM WILL BE LABELED, CERTIFIED OR LISTED, AND WHERE APPLICABLE, WIRING DIAGRAMS SHOWING THE CONNECTION OF ALL COMPONENTS OF RELATED EQUIPMENT. SUBMIT SHOP DRAWINGS FOR PANELBOARD BREAKERS, DISCONNECT SWITCHES AND

WIRING DEVICES. PROVIDE WARRANTY INFORMATION FOR ALL FURNISHED EQUIPMENT.

THE DRAWINGS ARE GENERALLY INDICATIVE AND DIAGRAMMATIC OF THE WORK TO BE INSTALLED. CAREFULLY INVESTIGATE THE STRUCTURAL AND FINISH CONDITIONS AFFECTING THE WORK AND ARRANGE ALL WORK ACCORDINGLY, FURNISHING NECESSARY

PARTS AND EQUIPMENT THAT MAY BE REQUIRED TO MEET THE VARIOUS CONDITIONS.

FIRE STOP OPENINGS AROUND ELECTRICAL PENETRATIONS IN FIRE RESISTANCE RATED WALLS, PARTITIONS, FLOORS OR CEILINGS. FURNISH AND INSTALL SLEEVES AND SEAL EACH CONDUIT OR CABLE AS REQUIRED TO PREVENT THE SPREAD OF FIRE OR THE PRODUCTS OF COMBUSTION AT ALL LOCATIONS DESIGNATED IN ARTICLE 300.21 OF THE NATIONAL ELECTRICAL CODE.

SEALS SHALL CONSIST OF BOTH CONDUIT AND CABLE FIRE STOPS AS MANUFACTURED BY O-Z/GEDNEY OR APPROVED EQUAL.

IRREGULAR OPENINGS SHALL BE SEALED WITH A SILICON FOAM SEALANT APPROVED AS A FIRE STOP AS MANUFACTURED BY

DOW CORNING, 3M, OR APPROVED EQUAL.

WHERE OPENINGS ARE REQUIRED IN WORK ALREADY IN PLACE, ALL CUTTING AND PATCHING SHALL BE DONE BY OR AT THE

EXPENSE OF THIS CONTRACTOR.

THE CONTRACTOR SHALL CONSULT WITH THE OWNER BEFORE CUTTING ANY OPENINGS, AND SHALL CUT SUCH OPENINGS IN AN APPROVED MANNER SO THAT THEY WILL NOT WEAKEN OR DAMAGE ANY STRUCTURAL PART OF THE BUILDING.

IDENTIFY ALL ITEMS OF ELECTRICAL EQUIPMENT, PROTECTIVE DEVICES, CONTROL DEVICES AND SIMILAR ITEMS BY NAME, FUNCTION AND/OR CONTROL. PROVIDE PHENOLIC NAMEPLATES WITH CHARACTERS NOT LESS THAN 1/4 INCH AND MINIMUM SIZE OF 1" X 3". FABRICATE USING TWO LAMINATED BLACK PLASTIC SHEETS BONDED WITH A MIDDLE SHEET OF WHITE PLASTIC AND CHARACTERS ENGRAVED IN ONE BLACK SHEET TO THE DEPTH OF THE WHITE PLASTIC. ATTACH NAMEPLATES WITH SHEET METAL

SCREWS, OR BOLTS AND NUTS.

PROVIDE UPDATED TYPE WRITTEN PANEL SCHEDULES IDENTIFYING BRANCH CIRCUITS SERVED FOR ALL MODIFIED AND NEW

PANELBOARDS.

ELECTRICAL DEMOLITION FOR REMODELING

WHERE PRESENT EQUIPMENT IS NOTED TO REMAIN OR LABELED "PR" IT IS TO REMAIN IN THE PRESENT LOCATION, BUT MAKE ALL REQUIRED ADJUSTMENTS TO PROVIDE FOR ALL NEW WIRING EXTENSIONS FROM SUCH OUTLETS OR EQUIPMENT.

ALL EXPOSED RACEWAYS, DEVICES, PANELBOARDS, AND OTHER ELECTRICAL EQUIPMENT THAT ARE NO LONGER A FUNCTIONING PART OF THE ELECTRICAL SYSTEM OR ANY AUXILIARY ELECTRICAL SYSTEM, SHALL BE DE-ENERGIZED, DISCONNECTED AND REMOVED. GENERALLY, THESE REMOVALS ARE NOT SPECIFICALLY INDICATED ON THE DRAWINGS. THIS CONTRACTOR SHALL

PATCH ALL CEILING, WALL OR FLOOR OPENINGS LEFT BY THIS REMOVAL.

IF THE CONTINUITY OF ANY EXISTING CIRCUITS THAT ARE TO REMAIN IS INTERRUPTED BY THESE ALTERNATIONS, EVEN THOUGH IT MAY NOT BE INDICATED, THE CONTRACTOR SHALL RESTORE SUCH CIRCUITS, PROVIDING ALL NECESSARY MATERIALS AND

LABOR TO ACCOMPLISH THIS.

ITEMS INDICATED ON THE DRAWINGS TO BE RELOCATED, SHALL BE REMOVED, CLEANED AND STORED PRIOR TO RE-USE.

EXISTING DEVICES AND OTHER ELECTRICAL EQUIPMENT NOT SHOWN OR NOT INDICATED TO BE REMOVED OR REPLACED, SHALL REMAIN AS IS IF SUCH DEVICES OR EQUIPMENT ARE NECESSARY FOR PROPER FUNCTIONING OF THE ELECTRICAL SYSTEM. IF

REQUIRED, EXISTING WIRING SHALL BE MODIFIED OR REPLACED TO SUIT THE NEW LAYOUT.

ALL REMOVED ELECTRICAL EQUIPMENT REQUESTED BY THE OWNER SHALL BE TURNED OVER TO THE OWNER AND STORED WHERE DIRECTED, IN THE CONDITION AS FOUND. ALL OTHER REMOVED EQUIPMENT AND MATERIAL SHALL BECOME THE

PROPERTY OF THIS CONTRACTOR AND SHALL BE REMOVED FROM THE PREMISES BY THEM.

FOR THE DURATION OF THE CONTRACT, THIS CONTRACTOR SHALL MAKE EVERY EFFORT TO KEEP ELECTRICAL OUTAGES TO A

MINIMUM.

IN ORDER TO INTERRUPT CONTINUITY OF ELECTRICAL SERVICE TO ANY PART OF THE BUILDING, IT WILL BE NECESSARY FOR THIS CONTRACTOR TO REQUEST PERMISSION FOR SUCH OUTAGES BY LETTER. THE LETTER SHALL STATE THE DATE OF PROPOSED OUTAGE, TIME IT SHALL START, TOTAL OUTAGE TIME REQUIRED AND REASON FOR THE OUTAGE. THE REQUEST SHALL BE

SUBMITTED A MINIMUM OF 14 DAYS BEFORE THE PROPOSED OUTAGE.

ACCEPTANCE TESTING

TESTING AGENCY: ENGAGE A QUALIFIED INDEPENDENT TESTING AND INSPECTION AGENCY TO PERFORM FIELD TESTS AND

INSPECTIONS AND PREPARE TEST REPORTS FOR SUBMISSION TO ENGINEER AND OWNER.

PERFORM EACH VISUAL AND MECHANICAL INSPECTION AND ELECTRICAL TEST STATED IN NETA ACCEPTANCE TESTING SPECIFICATION (ATS). CERTIFY COMPLIANCE WITH TEST PARAMETERS. PERFORM NETA TESTS AND INSPECTIONS FOR EACH OF

THE FOLLOWING NETA CATEGORIES AND PIECES OF EQUIPMENT.

· PANELBOARDS

· SWITCHES AND CIRCUIT BREAKERS

· GROUND FAULT SYSTEMS

CORRECT MALFUNCTIONING UNITS ON-SITE, WHERE POSSIBLE, AND RETEST TO DEMONSTRATE COMPLIANCE; OTHERWISE, REPLACE WITH NEW UNITS AND RETEST.

RACEWAYS

ALL WIRE AND CABLE SHALL BE INSTALLED IN RACEWAYS OR WIREWAYS AS HEREINAFTER SPECIFIED.

UTILIZE RIGID STEEL CONDUIT FOR RACEWAYS IN DAMP LOCATIONS OR WHERE OTHERWISE REQUIRED BY NEC. RIGID CONDUIT SHALL BE MADE OF HOT DIPPED GALVANIZED OR SHERARDIZED STEEL, CONFORMING TO THE REQUIREMENTS OF FEDERAL SPECIFICATION W-C-581, LATEST AMENDMENT. CONDUIT SHALL BEAR THE MANUFACTURER'S AND UNDERWRITERS' LABELS.

ASSEMBLE RIGID CONDUIT WITH THREADED COUPLING, WITH CONDUITS SCREWED TIGHT UNTIL ENDS BUTT IN THE CENTER OF COUPLING. MALE THREADS OF ALL LENGTHS THAT HAVE BEEN THREADED AT THE SITE SHALL BE COATED WITH A CONDUCTIVE INHIBITOR THOMAS & BETTS KOPR-SHIELD, OR APPROVED EQUAL, BEFORE THREADING INTO COUPLINGS OR FITTINGS. CONDUIT BUSHINGS FOR CONDUITS 1-INCH AND SMALLER MAY BE ZINC OR CADMIUM PLATED MALLEABLE IRON. THOSE FOR CONDUITS 1-1/4-INCH AND LARGER SHALL BE INSULATING MALLEABLE IRON TYPE B MADE BY THE O-Z/GEDNEY ELECTRICAL MANUFACTURING COMPANY, OR APPROVED EQUAL. LOCKNUTS UP TO AND INCLUDING 2-INCH IN SIZE SHALL BE GALVANIZED OF THE STANDARD WEIGHT TYPE. ALL LOCKNUTS 2-1/2 INCHES OR LARGER SHALL BE OF HEAVY DUTY CAST TYPE.

ELECTRICAL METALLIC TUBING MAY BE USED FOR ALL INTERIOR FEEDER RACEWAY RUNS. ELECTRICAL METALLIC TUBING SHALL BE ASSEMBLED WITH WATERTIGHT, COMPRESSION TYPE STEEL COUPLINGS AND FITTINGS WITH NYLON INSULATING THROATS BUILT INTO THE SETTING, AS MANUFACTURED BY ABB INSTALLATION PRODUCTS, OR APPROVED EQUAL. EMT COUPLINGS AND

FITTINGS SHALL NOT BE OF THE CAST CONSTRUCTION, OR SET SCREW TYPE.

PLASTIC CONDUIT SHALL BE MADE OF A HIGH IMPACT POLYVINYL CHLORIDE COMPOUND APPROVED FOR 90 DEGREES C.

CONDUCTORS, SHALL CONFORM TO NEMA SPECIFICATION C-2, AND FEDERAL SPECIFICATION WC-1094, AND SHALL BEAR AN

UNDERWRITERS' LABEL. PVC CONDUIT SHALL BE HEAVY WALL SCHEDULE 40.

ALL RACEWAYS SHALL BE UL APPROVED FOR INTENDED USAGE AND EACH LENGTH DELIVERED TO THE PROJECT SITE SHALL

BEAR UL MANUFACTURER'S LABEL.

FLEXIBLE STEEL CONDUIT (GREENFIELD) IN LENGTHS NOT EXCEEDING 48 INCHES SHALL BE USED FOR CONNECTION TO EQUIPMENT SUBJECT TO VIBRATION. IT SHALL CONFORM TO THE REQUIREMENTS OF FEDERAL SPECIFICATION WW-C566, LATEST

REVISION.

RACEWAYS SHALL BE CONTINUOUS FROM OUTLET TO OUTLET, AND FROM OUTLET TO CABINET, JUNCTION BOX OR PULL BOX, AND SHALL ENTER AND BE SECURED TO ALL BOXES IN SUCH A MANNER THAT EACH SYSTEM SHALL BE ELECTRICALLY CONTINUOUS

FROM SERVICE ENTRANCE TO ALL OUTLETS.

SURFACE METAL RACEWAYS: GALVANIZED STEEL WITH SNAP-ON COVERS. MANUFACTURER'S STANDARD ENAMEL FINISH IN

COLOR SELECTED BY ARCHITECT.

· MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS PROVIDE PRODUCTS BY ONE OF THE FOLLOWING.

· ABB INSTALLATION PRODUCTS

· WALKER SYSTEMS, INC; LEGRAND

· WIREMOLD COMPANY: LEGRAND

· HUBBELL & PANDUIT SIMILAR TO NMR

PANELBOARDS

PANELBOARDS SHALL COMPLY WITH NEMA PB1 AND BE OF THE DEAD FRONT TYPE, DOOR-IN-DOOR COVER, AND SHALL INCORPORATE SWITCHING AND PROTECTIVE DEVICES OF THE BOLT-ON, SINGLE AND MULTI-POLE, MOLDED CASE CIRCUIT BREAKER TYPE WITH INTEGRAL THERMAL-MAGNETIC TRIP ELEMENTS. EACH CIRCUIT BREAKER SHALL HAVE AN INDEX NUMBER PERMANENTLY INSTALLED ON OR NEAR IT, ODD NUMBERS ON THE LEFT AND EVEN NUMBERS ON THE RIGHT.

MINIMUM INTEGRATED SHORT CIRCUIT SHALL BE FULLY RATED AS INDICATED ON THE DRAWINGS. SERIES RATINGS ARE NOT

ACCEPTABLE.

PROVIDE TYPEWRITTEN PANELBOARD SCHEDULES IDENTIFYING LOADS. PROVIDE TYPEWRITTEN PANELBOARD SCHEDULES FOR

ALL EXISTING MODIFIED PANELBOARDS.

PROVIDE ADJUSTABLE MAGNETIC TRIP SEATING FOR ALL CIRCUIT BREAKER FRAME SIZES 200A AND LARGER.

WIRING DEVICES

WALL SWITCHES SHALL BE SPECIFICATION GRADE RATED AT 20 AMPERES, 277 VOLTS, A.C., SINGLE POLE AND THREE-WAY, HUBBELL CATALOG NO. 1221 AND 1223, OR APPROVED EQUAL.

DUPLEX RECEPTACLES SHALL BE SPECIFICATION GRADE RATED AT 20 AMPERES, 125 VOLT, A.C., 3-WIRE GROUNDING TYPE, HUBBELL CATALOG NO. 5362-1 OR APPROVED EQUAL.

GFCI TYPE DUPLEX RECEPTACLES SHALL HAVE INTEGRAL GROUND FAULT PROTECTION INTERRUPTION. THE GFCI RECEPTACLE SHALL BE RATED 20 AMPERES, 125 VOLTS, A.C., 3-WIRE GROUNDING TYPE. THE RECEPTACLE SHALL BE MANUFACTURED UNDER THE CURRENT REVISION OF UL 943 STANDARD FOR 2015 WHICH REQUIRES THE RECEPTACLE TO PERFORM SELF TEST MONITORING EVERY (3) HOURS OR LESS AND IF THE UNIT CAN NO LONGER PROVIDE GFCI PROTECTION IT SHALL DENY POWER TO THE UNIT AND PROVIDE VISUAL AND/OR AUDIBLE INDICATION. PROVIDE HUBBELL CATALOG NO. GFRST20 OR APPROVED EQUAL.

PROVIDE WIRING DEVICES SUITABLE FOR INTENDED USE AND WITH RATINGS ADEQUATE FOR LOAD SERVED.

FOR SINGLE RECEPTACLES INSTALLED ON AN INDIVIDUAL BRANCH CIRCUIT, PROVIDE RECEPTACLES WITH AMPERE RATING NOT

LESS THAN THAT OF THE BRANCH CIRCUIT.

PROVIDE WEATHER RESISTANT GFI RECEPTACLES WITH WHILE-IN-USE WEATHERPROOF COVERS FOR ALL RECEPTACLES

INSTALLED OUTDOORS OR IN DAMP OR WET LOCATIONS.

PROVIDE GFI PROTECTION FOR ALL RECEPTACLES INSTALLED WITHIN 6 FEET OF SINKS, FOR ALL RECEPTACLES INSTALLED IN

KITCHENS, AND FOR ALL RECEPTACLES SERVING ELECTRIC DRINKING FOUNTAINS.

FOR EACH FLUSH MOUNTED DEVICE, PROVIDE A SMOOTH NYLON, WHITE IN COLOR, COVER PLATE, HUBBELL SERIES P, OR

APPROVED EQUAL.

THIS CONTRACTOR SHALL COORDINATE THE PLAN LOCATIONS AND MOUNTING HEIGHTS OF OUTLETS WITH THE LOCATION OF EQUIPMENT FURNISHED BY OTHER TRADES. ALL OUTLETS INDICATED TO BE LOCATED AT CABINETS SHALL BE INSTALLED SIX (6) INCHES ABOVE BASE CABINET TOPS. ALL OUTLETS INDICATED TO BE LOCATED ADJACENT TO SINKS SHALL BE INSTALLED SIX (6)

INCHES ABOVE SINK TOP. VERIFY LOCATION WITH OWNER.

WALL SWITCHES ARE INDICATED ON THE DRAWINGS ON THE DOOR STRIKE SIDE OF THE DOORS; HOWEVER, IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO VERIFY FINAL DOOR SWING ARRANGEMENTS PRIOR TO LOCATING OUTLET BOXES FOR WALL SWITCHES. WALL SWITCH SHALL BE MOUNTED AT A TYPICAL AND CONSISTENT DIMENSION NO MORE THAN 12" FROM THE

OUTSIDE EDGE OF JAMB.

DETERMINE AT THE SITE THE LOCATION OF ALL RACEWAYS, OUTLETS AND EQUIPMENT. THE RIGHT IS RESERVED TO CHANGE THE LOCATION OF ANY ELECTRICAL OUTLET, CONTROL EQUIPMENT, OR MOTOR TO ANY POINT NOT OVER 5'-0" DISTANT FROM THE LOCATION SHOWN, WITHOUT EXTRA COST; ACCORDINGLY, DO NOT INSTALL BRANCH CIRCUIT WIRING LEADING TO THE LOCATION OF SUCH EQUIPMENT UNTIL THE LOCATION HAS BEEN APPROVED. SPACE ALL LIGHTING FIXTURES EVENLY ON CENTERS OR JOINTS OR CEILING TILES OR OTHER ARCHITECTURAL ELEMENTS, OR AS DIMENSIONED ON THE DRAWINGS.

OUTLET BOXES FOR CEILING OUTLETS AND FLUSH WALL OUTLETS SHALL BE NOT LESS THAN 1/16-INCH THICK PRESSED.

LABEL ALL FACEPLATES WITH TYPEWRITTEN LABEL INDICATING PANEL AND CIRCUIT SERVING OUTLET.

OUTLET BOXES

GALVANIZED STEEL AND SHALL BE OF AMPLE SIZE TO PROPERLY ACCOMMODATE THE CONDUCTORS PASSING THROUGH AND THE SPLICES CONTAINED THEREIN, AS REQUIRED BY NEC TABLE 314.16A. THEY SHALL BE NOT LESS THAN 4-INCH SQUARE OR OCTAGONAL AND 1-1/2 INCH DEEP. BOXES TO WHICH A 1-INCH RACEWAY, OR THREE OR MORE SMALLER RACEWAYS ARE CONNECTED SHALL NOT BE SMALLER THAN 4-11 /16 INCHES SQUARE AND 2-1/8 INCHES DEEP. WHERE TWO OR MORE SYSTEMS ENTER THE OUTLET BOXES, THEY SHALL BE AT LEAST 2-1/4 INCHES DEEP AND SHALL HAVE SEPARATORS PROPERLY LOCATED TO

DIVIDE ONE SYSTEM FROM ANOTHER.

ALL OUTLET BOXES IN FINISHED WALLS AND CEILING, OTHER THAN BRICK, MASONRY OR TILE, SHALL HAVE PLASTER COVERS THAT COME FLUSH OR SLIGHTLY UNDER THE PLASTER SURFACE. CEILING AND BRACKET OUTLET BOXES SHALL HAVE COVERS THAT REDUCE THE SURFACE OPENING TO APPROXIMATELY 2 INCHES AND SHALL HAVE EARS TAPPED FOR MOUNTING WIRING

DEVICES WHERE REQUIRED.

WHERE RACEWAYS ARE EXPOSED, OUTLET BOXES FOR WIRING DEVICES ON WALLS, PARTITIONS, OR STEEL FRAMEWORK, SHALL BE CROUSE HINDS OR APPROVED EQUAL TYPE FS OR FD CONDUITS AS REQUIRED WITH COVERS TO FIT. ALL OUTLET BOXES THAT

ARE EXPOSED TO WEATHER SHALL BE CAST ALUMINUM WITH GASKETED COVERS.

ALL LOCATIONS WHERE SWITCH OR RECEPTACLE OUTLETS OCCUR IN FINISHED BRICK, MASONRY OR GLAZED TILE WALLS, USE SPECIAL OUTLET BOXES DESIGNED FOR THIS TYPE OF WIRING. OUTLET BOXES SHALL BE AT LEAST 3-1/2 INCHES DEEP HAVING SQUARE CORNERS WITH SUPPORT EARS MOUNTED ON THE INSIDE OF THE BOX. KNOCKOUTS IN BOXES SHALL BE CENTERED 2-1/2 INCHES FROM FACE OF BOX TO ALLOW A SOLID PIECE OF 2-INCH BRICK OR TILE TO BE PLACED IN FRONT OF RACEWAY ENTERING BOX WITHOUT CUTTING. PROVIDE SPECIAL LARGER COVER PLATE FOR THIS TYPE OF OUTLET. BOXES SHALL BE MIDLAND ROSS MODEL GW-135, OR EQUAL. IF SPECIAL BOXES ARE FURNISHED BY OTHERS, THIS CONTRACTOR SHALL RECEIVE, STORE AND

INSTALL SUCH BOXES.

GROUNDING AND BONDING

ALL FEEDER RACEWAYS FOR PANELBOARD AND ALL OTHER CIRCUITS SHALL CONTAIN A SEPARATE EQUIPMENT GROUND WIRE WITH GREEN INSULATION, THE MINIMUM SIZE OF WHICH SHALL BE IN ACCORDANCE WITH ARTICLE 250.122 OF THE NATIONAL ELECTRICAL CODE. CONNECT THIS GROUND WIRE TO THE GROUND BUS AT THE SUPPLY END AND TO LOAD EQUIPMENT GROUND

BUS, CABINET OR FRAME.

WIRE AND CABLE

ALL CONDUCTORS SHALL BE OF SOFT DRAWN COPPER HAVING A CONDUCTIVITY OF AT LEAST 95%. CONDUCTORS #10 AWG AND SMALLER SHALL BE SOLID WITH 600 VOLT THHN/THWN INSULATION. CONDUCTORS #8 AWG AND LARGER SHALL BE STRANDED WITH 600 VOLT THHN/THWN INSULATION. ALL WIRE AND CABLE SHALL BE OF THE SINGLE CONDUCTOR TYPE UNLESS OTHERWISE INDICATED, AND SHALL BE COLOR CODED SO AS TO IDENTIFY EACH WIRE IN A RACEWAY OR CABLE. MINIMUM WIRE SIZE SHALL BE

#12AWG.

INSTALL BRANCH CIRCUITS IN RACEWAYS. WHERE PRACTICAL, HOMERUNS TO THE SAME PANELBOARD MAY BE GROUPED IN A SINGLE RACEWAY. NO MORE THAN THREE SINGLE PHASE, OR ONE THREE PHASE, 480/277 VOLT OR 208/120 VOLT CIRCUIT MAY BE ENCLOSED IN ONE RACEWAY UNLESS SPECIFICALLY SHOWN. DO NOT MIX VOLTAGE IN THE SAME RACEWAY.

THE NUMBER OF BRANCH CIRCUIT HOME RUNS IN EACH RACEWAY MAY BE INDICATED BY ARROWS ON THE DRAWINGS. SINGLE PHASE BRANCH CIRCUITS SHOWN IN SEPARATE RACEWAYS MAY BE GROUPED TOGETHER IN A SINGLE RACEWAY, WHERE EACH "HOT" WIRE IS INDICATED TO BE SUPPLIED BY A SEPARATE BUS BAR IN THE SUPPLYING PANEL, BUT ONLY TO THE EXTENT OF THREE CURRENT CARRYING CONDUCTORS PER RACEWAY. THREE PHASE HOME RUNS SHALL NOT BE COMBINED. VOLTAGE DROP

SHALL NOT EXCEED 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUIT WIRING.

PROVIDE ONE NEUTRAL CONDUCTOR FOR EACH PHASE WIRE HOME RUN TO A PANELBOARD. COMMON NEUTRALS ARE NOT

ALLOWED UNLESS INDICATED OTHERWISE.

SUPPORTING DEVICES

ALL FASTENINGS, SUPPORTS, HANGERS, CLAMPS, AND ANCHORS SHALL BE OF THE TYPE MADE FOR THE SPECIFIC PURPOSE FOR WHICH THEY ARE TO BE USED. PROVIDE TOGGLE BOLTS OR MACHINE BOLT FASTENINGS FOR HOLLOW TILE, TERRA-COTTA OR LATH CONSTRUCTION. USE MACHINE SCREWS FOR STRUCTURAL STEEL FASTENING, LEAD EXPANSION SHIELDS AND MACHINE SCREWS FOR SOLID MASONRY FASTENING, AND LAG SCREWS OR BOLTS FOR WOOD FASTENING. INSTALL ALL CONDUIT RIGIDLY AND FIRMLY TO PREVENT SWAYING, VIBRATION OR SAGGING, USING MALLEABLE OR WROUGHT STEEL HANGERS OR STANDARD DESIGN, PIPE CLAMPS, OR FABRICATED STEEL SUPPORTS OR APPROVED DESIGN, HANGERS FOR HORIZONTAL CONDUIT RUNS SHALL BE ADJUSTABLE CLEVIS TYPE. PERFORATED STRAP IRON HANGERS ARE NOT PERMITTED.

FASTENINGS AND ATTACHMENTS SUCH AS SCREWS, BOLTS AND NUTS, SHALL BE MADE WITH NONFERROUS METALS, GALVANIZED OR CADMIUM PLATED STEEL. ALL FASTENINGS AND ATTACHMENTS SHALL BE MADE WITH SUCH MATERIALS OR SO PROTECTED THEY WILL OFFER THE MAXIMUM PROTECTION AGAINST DETERIORATION FROM AGE, WEATHER AND DAMPNESS.

ALL EXTERIOR FASTENING DEVICES SHALL BE SERIES 300 STAINLESS STEEL.

SAFETY SWITCHES AND FUSES

FUSED SWITCHES SHALL CONTAIN REINFORCED FUSE CLIPS AND SHALL BE EQUIPPED WITH A COMPLETE SET OF FUSES. BOTH FUSE CLIPS AND FUSES SHALL BE CORRECT FOR THE CURRENT, VOLTAGE AND FUSE TYPE AS HEREAFTER SPECIFIED. FUSE CLIPS SHALL BE OF THE REJECTION TYPE TO ACCOMMODATE THE RK FUSE TYPES HEREAFTER SPECIFIED.

SWITCHES SHALL BE OF THE HEAVY DUTY CLASS, SHALL BE UNDERWRITERS' LABORATORIES, INC. LISTED AND LABELED, HORSEPOWER RATED, CONFORMING TO FEDERAL SPECIFICATION WS-865C. SWITCHES SHALL GENERALLY HAVE NEMA 1

ENCLOSURE, UNLESS NOTED OTHERWISE.

FUSES 15 TO 100 AMPERE SHALL BE UL CLASS RK5, DUAL ELEMENT WITH A MINIMUM INTERRUPTING RATING OF 200,000 RMS

SYMMETRICAL AMPERES, BUSSMANN FUSETRON, MERSEN, TRI-ONIC, OR APPROVED EQUAL.

SAFETY SWITCH TYPE DISCONNECTS SHALL BE EATON, ABB, SCHNEIDER OR APPROVED EQUAL.

SAFETY SWITCHES SHALL BE OF THE HEAVY DUTY CLASS, SHALL BE UNDERWRITERS' LABORATORIES, INC. LISTED AND LABELED, HORSEPOWER RATED, CONFORMING TO FEDERAL SPECIFICATION W5-865C AND NEMA SPECIFICATION KSI-1969. SWITCHES SHALL

GENERALLY HAVE NEMA 1 ENCLOSURES UNLESS NOTED OTHERWISE.

ELECTRICAL SPECIFICATIONS

ELECTRICAL REQUIREMENTS FOR MECHANICAL AND PLUMBING EQUIPMENT

POWER WIRING:

ALL CONTROLLERS (STARTERS), ENCLOSED SWITCHES (DISCONNECT SWITCHES), AND VARIABLE FREQUENCY DRIVES (VFD'S), EXCEPT FACTORY MOUNTED CONTROLLERS AND VFD'S, FOR EQUIPMENT PROVIDED BY MECHANICAL CONTRACTOR SHALL BE FURNISHED BY MECHANICAL CONTRACTOR AND INSTALLED BY ELECTRICAL CONTRACTOR. FACTORY MOUNTED CONTROLLERS AND VFD'S ARE FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR. PROVIDE CONTROLLERS, ENCLOSED SWITCHES, AND VFD'S IN ACCORDANCE WITH ELECTRICAL SPECIFICATIONS.

ALL POWER WIRING, FOR MECHANICAL EQUIPMENT PROVIDED BY MECHANICAL CONTRACTOR, SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR TO THE POINT OF FINAL CONNECTION (FROM SOURCE TO CONTROLLERS, ENCLOSED SWITCHES, OR VFDS, AND TO EQUIPMENT, MOTOR, OR OTHER CONNECTION POINT). EXCEPT WHERE SPECIFICALLY INDICATED OTHERWISE, ALL POWER WIRING TO THE POINT OF FINAL CONNECTION, FOR EQUIPMENT PROVIDED UNDER BY MECHANICAL

CONTRACTOR, SHALL BE PROVIDED BY ELECTRICAL CONTRACTOR.

FINAL ELECTRICAL POWER CONNECTIONS TO ALL EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR. IN GENERAL, THE POINT OF FINAL CONNECTION SHALL BE THE TERMINAL HOUSING ON THE EQUIPMENT, MOTOR, OR AN INTEGRAL JUNCTION BOX ON THE EQUIPMENT ITEM. IF NO JUNCTION BOX IS FURNISHED, A JUNCTION BOX SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR. WIRE LEADS OF ADEQUATE LENGTH TO ENSURE A PROPER CONNECTION AT THE FINAL LOCATION SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR.

CONTROL WIRING:

ALL CONTROL WIRING (LINE VOLTAGE AND/OR LOW VOLTAGE) FOR MECHANICAL EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR. WIRING FROM POWER SOURCE TO ALL CONTROL PANELS, BAS CONTROL PANELS, CONTROLLERS, OPERATOR WORK STATIONS (PCS, PRINTERS, MONITORS, AND OTHER WORK STATION EQUIPMENT) AND OTHER CONTROL EQUIPMENT REQUIRED FOR A COMPLETE AND OPERABLE CONTROL SYSTEM SERVING MECHANICAL EQUIPMENT PROVIDED BY MECHANICAL CONTRACTOR SHALL BE FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR AND COORDINATED WITH ELECTRICAL CONTRACTOR. ALL WIRING FROM CONTROL PANELS TO CONTROL DEVICES FOR MECHANICAL EQUIPMENT PROVIDED BY MECHANICAL CONTRACTOR SHALL BE FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR.

ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRICAL CODE AND ELECTRICAL SPECIFICATIONS.

ALL CONTROL WIRING SHALL BE IN CONDUIT.

UNLESS OTHERWISE NOTED, ALL TEMPERATURE CONTROL DEVICES, INSTALLED PILOT DEVICES, AND ALL ASSOCIATED PILOT CONTROL EQUIPMENT FOR ALL EQUIPMENT PROVIDED BY MECHANICAL CONTRACTOR SHALL BE FURNISHED AND INSTALLED BY

MECHANICAL CONTRACTOR.

MANUAL MOTOR STARTERS

CLASS "A" MANUALLY-OPERATED MOTOR CONTROLLER WITH BI-METALLIC OR MELTING ALLOY THERMAL TYPE OVERLOAD RELAYS, NON-REVERSING TYPE.

FURNISH WITH TOGGLE OPERATOR AND MEANS FOR LOCKING IN THE "OFF" POSITION.

AutoCAD SHX Text I:\07510\0001\ENG\80-DRAWINGS\86-DESIGN\86E-ELECTRICAL\E-801.DWG 08/28/2026 13:55:06 ZACHARY ZDROJEWSKI

P-001

2.

4.

THIS PROJECT IS GOVERNED BY THE PENNSYLVANIA UNIFORM CONSTRUCTION CODES

INCLUDING, BUT NOT LIMITED TO:

1. 2021 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)

2021 INTERNATIONAL FUEL GAS CODE (IFGC)

2021 INTERNATIONAL BUILDING CODE (IBC)

CODE SUMMARY

3. 2021 INTERNATIONAL EXISTING BUILDING CODE (IEBC)

REVISION DESCRIPTION DATE

DRAWN

PROJ. MGR.

DESIGNED

CHECKED

DATE

M&C PROJ. #

REV

CONSTRUCTION DOCUMENTS

w w w .m ck im cr ee d.

co m

R ee ds da le S tre et

, S ui te

Ph on e:

(4

) 4

-9

0, F ax

2)

-8 bu rg h, P en ns yl va ni a

07510-0001

SR

U

- M

IH

A

LI

K T

H O

M

PS

O N

ST

A

D

IU

M W

A

TE

R H

EA

TE

R R

EP

LA

C

EM

EN

T

MEB

2026-08-28

PLUMBING SYMBOLS

HOSE BIBB

WALL HYDRANT

MEDICAL COMPRESSED AIR OUTLET

MEDICAL VACUUM OUTLET W/SLIDE

OXYGEN OUTLET

FIRE HYDRANT

MANHOLE

GAS VALVE BOX

WATE…

This is the start of the file's text. The full file is on GovTribe.