2-SRU VSC Chemistry Prep Renovation Bid Set Drawings 20261113.pdf

PDF 8 MB Posted

Attached to
VSC Phase 1 Chem Lab Relocation & Renovation Project
Solicitation number
US.263094
Issued by
Butler County, Pennsylvania

About this file

Summary of Bid Set Drawings for VSC Chemistry Prep Renovation

This document comprises the bid set drawings for the Vincent Science Center Chemistry Prep Room Renovations project at Slippery Rock University, a State System of Higher Education institution located in Slippery Rock, Pennsylvania. The project involves selective demolition and renovation of two existing third-floor office spaces (Rooms 306 and 307) into a General Chemistry Prep Room (approximately 332 square feet) and an Autoclave Room (approximately 97 square feet), with a total work area of 440 square feet. The scope includes removal of existing partitions and finishes, installation of new partitions, doors, finishes, casework, and mechanical, plumbing, fire protection, and electrical renovations classified as Level 2 alterations. The project incorporates an existing fume hood being relocated from the Advanced Technology Science Hall Building and prepares for owner-furnished laboratory casework, sinks, and safety shower/eyewash units. A mandatory pre-bid conference with site visit is scheduled for November 24, 2026, at 11:00 AM at the Maintenance Center Conference Room, 100 Building & Grounds Road, Slippery Rock, Pennsylvania 16057. Electronic bids are due no later than 11:00 AM EST on December 10, 2026, through PennBid at https://pennbid.bonfirehub.com.

The project shall be executed by separate prime contractors under Pennsylvania statute, with the General Contractor designated as the lead prime contractor responsible for overall project coordination and management. Work is designed in accordance with the 2021 Pennsylvania Uniform Construction Code, the 2021 International Building Code (with exceptions), and applicable mechanical, plumbing, electrical, fire, and energy conservation codes. The existing three-story Vincent Science Center building (96,274 gross square feet) is Construction Type IIB with Business occupancy classification and includes automatic sprinkler systems and fire alarm systems throughout. The project specifications require compliance with 2009 ICC/ANSI A117.1 accessibility standards and include detailed architectural, structural, mechanical, plumbing, fire protection, and electrical drawings prepared by Crabtree, Rohrbaugh & Associates Architects and Baker Ingram & Associates (structural engineer). Shop drawings and product data submissions are required, and all work must be performed in coordination with existing building operations and the owner's occupied adjacent areas.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CRABTREE, ROHRBAUGH & ASSOCIATES - ARCHITECTS

MEP ENGINEER

STRUCTURAL

ENGINEER

www.cra-architects.com

401 EAST WINDING HILL ROAD

MECHANICSBURG PA 17055

Phone: (717) 458-0272

State System of Higher Education

Commonwealth of Pennsylvania Daniel Greenstein, Chancellor

Slippery Rock University

CAMPUS MAP

VICINITY MAP

VINCENT SCIENCE CENTER

CHEMISTRY PREP ROOM RENOVATIONS

SLIPPERY ROCK UNIVERSITY

CRA PROJECT No. 3896

NOVEMBER 13, 2026

Baker Ingram & Associates

1681 Crown Avenue

Suite 201

Lancaster, PA 17601

PHONE

WEB ADDRESS

Barton Associates, Inc.

400 Mosites Way

Suite 301

Pittsburgh, PA 15205

PHONE

WEB ADDRESS

BID SET

DRAWING LIST

SHEET

NUMBER SHEET NAME

GENERAL

CS.1 COVER SHEET

ARCHITECTURAL CODE COMPLIANCE

CC.1 CODE COMPLIANCE PLANS & INFORMATION

ARCHITECTURAL

A1.1 GENERAL CHEMISTRY PREP & AUTOCLAVE ROOMS

STRUCTURAL

S1.1 STRUCTURAL NOTES

S6.2 TYPICAL FRAMING DETAILS

MECHANICAL

M0.0 SYMBOLS, GENERAL NOTES, DETAILS, SCHEDULES &

SPECIFICATION - MECHANICAL

M1.3 THIRD FLOOR PLANS - MECHANICAL

M1.4 ROOF PLAN - MECHANICAL

PLUMBING

P0.0 SYMBOLS & GENERAL NOTES - PLUMBING

P1.2 SECOND FLOOR PLANS - PLUMBING

P1.3 THIRD FLOOR PLANS - PLUMBING

FIRE PROTECTION

F0.0 SYMBOLS & GENERAL NOTES - FIRE PROTECTION

F1.3 THIRD FLOOR PLANS - FIRE PROTECTION

ELECTRICAL

E0.0 SYMBOLS, GENERAL NOTES & SCHEDULES - ELECTRICAL

E0.1 SPECIFICATIONS - ELECTRICAL

E1.3 THIRD FLOOR PLANS - ELECTRICAL

E1.4 ROOF PLAN - ELECTRICAL

FOR REFERENCE ONLY;

WORK BEING PERFORMED BY OWNER,

REFER TO SUMMARY OF WORK

155' TO

TAL EXIT AC

C

ESS

TR

AVEL D

ISTAN

C

E

ETR

241 SF

CHEMISTRY PREP

1 - OL

97 SF

AUTOCLAVE

1 - OL

EXISTING

STAIRS

EXISTING

STAIRS

EXISTING

STAIRS

AREA OF WORK

440 SF

PROJECT DATA SUMMARY

AUTHORITY HAVING JURISDICTION: PA DEPARTMENT OF LABOR AND INDUSTRY

PROJECT DESCRIPTION/CLASSIFICATION OF WORK:

THIS PROJECT CONSISTS OF THE RENOVATION OF TWO EXISTING OFFICES INTO TWO NEW SUPPORT SPACES FOR THE CHEMISTRY DEPARTMENT ON THE THIRD FLOOR OF THE VINCENT SCIENCE CENTER BUILDING - A GENERAL CHEMISTRY PREP ROOM AND AUTOCLAVE ROOM. DEMOLITION OF EXISTING PARTITIONS AND FINISHES. INSTALLATION OF NEW PARTITIONS, FINISHES CASEWORK, EQUIPMENT, MECHANICAL, PLUMBING, FIRE PROTECTION, AND ELECTRICAL RENOVATIONS ARE INCLUDED. THE PROJECT REQUIRES LEVEL 2 ALTERATIONS TO THE WORK AREA.

APPLICABLE BUILDING CODES: PENNSYLVANIA UNIFORM CONSTRUCTION CODE (UCC)

2021 INTERNATIONAL BUILDING CODE (IBC) - EXCLUDING CHAPTERS 1, 11, & 30

2018 INTERNATIONAL BUILDING CODE (IBC) - CHAPTER 11 & APPENDIX E

2021 INTERNATIONAL EXISTING BUILDING CODE (IEBC) - CHAPTERS 5 - 8

2021 INTERNATIONAL ENERGY CONSERVATION CODE

2021 INTERNATIONAL FIRE CODE

2021 INTERNATIONAL MECHANICAL CODE

2021 INTERNATIONAL PLUMBING CODE

2020 NATIONAL ELECTRICAL CODE (NFPA 70-2020)

ACCESSIBILITY STANDARDS: 2009 ICC/ANSI A117.1 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES

2018 INTERNATIONAL BUILDING CODE

GENERAL BUILDING DATA: CONSTRUCTION TYPE CLASSIFICATION: IIB (EXISTING, NO CHANGE)

OCCUPANCY GROUP CLASSIFICATION: B - BUSINESS (EXISTING, NO CHANGE)

NUMBER OF FLOORS ABOVE GRADE: 3

BUILDING AREA SUMMARY:

FIRST FLOOR (EXISTING TO REMAIN) 33,710 SF

SECOND FLOOR (EXISTING TO REMAIN) 30,748 SF

THIRD FLOOR (EXISTING TO REMAIN) 31,375 SF

THIRD FLOOR (LEVEL 2 ALTERATION) 440 SF

TOTAL GROSS BUILDING AREA 96,274 SF

BUILDING HEIGHT: 38'-11", 3 STORIES (EXISTING, NO CHANGE)

BUILDING CODE INFORMATION: FACILITY: SLIPPERY ROCK UNIVERSITY

BUILDING: VINCENT SCIENCE CENTER

ADDRESS: 106 CENTRAL LOOP

CITY: SLIPPERY ROCK, PA

MUNICIPALITY: SLIPPERY ROCK TOWNSHIP

COUNTY: BUTLER

FIRE PROTECTION SYSTEMS: AUTOMATIC SPRINKLERS: YES, FULL THROUGHOUT - PER NFPA-13

FIRE ALARM SYSTEM: YES

FIRE EXTINGUISHERS: PER INTERNATIONAL FIRE CODE & NFPA-10

MAXIMUM TRAVEL DISTANCE TO EXTINGUISHERS:

CLASS 'A' HAZARDS: 75 FEET

CLASS 'B' HAZARDS: 30 OR 50 FEET

CLASS 'C' HAZARDS: BASED ON CLASS A OR B

CLASS 'D' HAZARDS: 75 FEET

FINISH FLOOR

T O

T O

P O

F H

A N

D

LE

4'

M A

X F

R O

M F

IN

IS

H F

LO

O

R

ELEVATION

WALL MOUNTED FIRE

EXTINGUISHER

WITHOUT CABINET

FIRE EXTINGUISHER

STUD WALL

(CMU WALL WHERE

OCCURS)

PLAN

FE

TYPE FE-1:

MULTIPURPOSE DRY-CHEMICAL TYPE, HOOK

HUNG EXTINGUISHER: UL-RATED 2A–10B:C, 5

LB. NOMINAL CAPACITY, WITH A SPECIALLY

FLUIDIZED AND SILICONIZED MONO

AMMONIUM PHOSPHATE-BASED DRY

CHEMICAL IN MANUFACTURER'S STANDARD

ENAMELED CONTAINER.

332 SF

GENERAL

CHEMISTRY

PREP ROOM

97 SF

AUTOCLAVE

ROOM

2'-2"

FE-1

ETR

FEC

SAFETY

SHOWER

CONTRACTOR L

AY-D

OW

N Z

ONE

DELI

VERIE

S

EXIS

TIN

G

LO

ADIN

G D

OCK /

CONTRACTOR

ENTRANCE

EXISTING ACCESSIBLE PATH

TO EXISTING

ACCESSIBLE

PARKING

EXIS

TIN

G A

CCESSIB

LE

P

ATH

CONTRACTOR L

AY-D

OW

N Z

ONE

KEEP O

PEN F

OR C

ONSTRUCTIO

N A

ND U

NIV

ERSIT

Y D

ELI

VERIE

S

− AREA OF WORK

PROJECT

PLOT SCALE:

FILENAME:

DATE:

01 MM-DD-YR DESCRIPTION OF CHANGESNAME

R E V I S I O N S

K E Y P L A N w w w .c ra -a rc h it e c ts

.c o m

ALL REPORTS, PLANS SPECIFICATIONS AND COMPUTER FILES RELATING TO THIS

PROJECT ARE THE PROPERTY OF CRABTREE, ROHRBAUGH & ASSOCIATES.

CRABTREE ROHRBAUGH & ASSOCIATES RETAINS ALL COMMON LAW, STATUTE AND

OTHER RESERVED RIGHTS INCLUDING THE COPYRIGHT THERETO. REPRODUCTION

OF THE MATERIAL HEREIN OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF

CRABTREE, ROHRBAUGH & ASSOCIATES VIOLATES THE COPYRIGHT LAWS OF THE

UNITED STATES AND WILL BE SUBJECT TO LEGAL PROSECUTION.

© CRABTREE, ROHRBAUGH & ASSOCIATES, INC 2025

C R

A B

T R

E E

R O

H R

B A

U G

H

A S

S O

C

IA

T E

S

A R

C H

IT

E

C T

S

C H

A R

LO

T

T E

S V

IL

LE

V

IR

G

IN

IA

E

A S

T W

IN

D

IN

G

H

IL

L R

O A

D

M E

C H

A N

IC

S

B U

R G

P

A

-4

-0

T O

W S

O N

M

A R

Y

LA

N D

W H

IT

E

S U

LP

H

U R

S P

R

IN

G S

W

E S

T V

IR

G

IN

IA

As indicated

CODE COMPLIANCE PLANS &

INFORMATION

NOVEMBER 13, 2026

CC.1

S L

IP

P

E R

Y R

O C

K U

N

IV

E R

S

IT

Y V

IN

C

E N

T S

C

IE

N C

E C

E N

T E

R

M

O R

R O

W W

A Y

S

L

IP

P E

R Y

R O

C K

P

A

BID SET

C H

E M

IS

T

R Y

P R

E P

R O

O M

R E

N O

V A

T

IO

N S

1/16" = 1'-0"CC.1

1 CODE COMPLIANCE PLAN - THIRD FLOOR

HE

CODE COMPLIANCE LEGEND

SITE ACCESSIBLE PATH

1 HOUR RATED FIRE BARRIER

2 HOUR RATED FIRE BARRIER

2 HOUR RATED FIRE WALL

ACCESSIBLE ENTRANCE

ACCESSIBLE MEANS OF EGRESS

HORIZONTAL EXIT

FIRE EXTINGUISHER LOCATIONS

EVACUATION ROUTE

RATED CEILING SYSTEM

1/2" = 1'-0"CC.1

3 FIRE EXTINGUISHER DETAILS

1/4" = 1'-0"CC.1

2 PARTIAL THIRD FLOOR CODE COMPLIANCE PLAN

3/64" = 1'-0"CC.1

4 SITE AND CONSTRUCTION LOGISTICS PLAN

F

GENERAL

CHEMISTRY

PREP ROOM

AUTOCLAVE

ROOM

A1.1

I4.1

A1.1

GENERAL

CHEMISTRY

PREP ROOM

AUTOCLAVE

ROOM

A1.1

A1.1 6

S3

S3

A1.1

ETR FEC

10'-4"

'-7

3'-4" 2'-3"

'-0

I4.1

I4.1 3I4.1

I4.1

A1.1

FUTURE

AUTOCLAVE

BY OWNER

NEW CEILING

SUSPENDED

HOOD BY HC

1'-4"

4"

M5

E X

T E

N T

O F

W P

(W A

LL P

R

O T

E C

T

IO

N

E X

T E

N T

O F

W P

W

A

LL

P R

O T

E C

T

IO

N

CASEWORK, SINK, FAUCETS

- PROVIDED & INSTALLED BY

CASEWORK VENDOR. PC, EC, & MC

TO MAKE FINAL CONNECTIONS

SAFETY SHOWER & EYEWASH UNIT

- PROVIDED BY CASEWORK

VENDOR, INSTALLED BY PC

RELOCATED

TACK BOARD

RELOCATED

MARKERBOARD

A1.1 8

FE-1

CASEWORK, SINK, & FAUCETS

- PROVIDED & INSTALLED BY OWNER. WALL

PREP & BLOCKING BY GC, ALL ROUGH-INS &

FINAL CONNECTIONS BY PC, EC, & MC.

ETR WINDOW STOOLS, TYP

EXISTING FUME HOOD, RELOCATED &

REINSTALLED BY OWNER FROM ATSH

BUILDING ROOM 303. ALL ROUGH-INS &

FINAL CONNECTIONS BY PC, EC, & MC.

CASEWORK, FLAMMABLE, & ACID CAB

- PROVIDED & INSTALLED BY OWNER. WALL

PREP & BLOCKING BY GC, ALL ROUGH-INS &

FINAL CONNECTIONS BY PC, EC, & MC.

GC TO MODIFY EXISTING HOOD SHROUD TO

ACCOMMODATE NEW CEILING HEIGHT

BASE AS

SCHEDULED

CASEWORK - PROVIDED &

INSTALLED BY OWNER. WALL

PREP & BLOCKING BY GC, ALL

ROUGH-INS & FINAL

CONNECTIONS BY PC, EC, & MC.

BASE AS SCHEDULED SAFETY SHOWER UNIT

- PROVIDED BY

OWNER, INSTALLED BY

GC. WALL PREP &

BLOCKING BY GC,

ROUGH-IN & FINAL

CONNECTIONS BY PC.

EXTENT OF WP

(WALL PROTECTION)

CASEWORK

- PROVIDED & INSTALLED BY

OWNER. WALL PREP &

BLOCKING BY GC, ALL

ROUGH-& FINAL

CONNECTIONS BY PC, EC,

&MC.

4'-0"

RELOCATED

TACK BOARD

FE

GC TO PROVIDE WOOD

BLOCKING AS REQUIRED

ETR GWB

BULKHEAD @

8'-6" AFF

ETR GWB

BULKHEAD @

10'-0" AFF

8' - 0"

8' - 8"

NEW CEILING

SUSPENDED

HOOD BY HC

MODIFY CEILING

AS REQUIRED TO

ACCOMMODATE

HOOD SHROUD

3B

1A

1A

4A

4B

5'-4" 4"

5A

5A

7A

8A 7A

3A 8A

4A

4B

7B

7B

D O O R T Y P E S

1. DOOR SPECIES, CUT, VENEER FLITCH MATCH AND STAIN TO MATCH EXISTING.

FINISH FLOOR

ELEVATION

N

6" * 10"

3'

8"

F

*GC TO VERIFY

NARROW LITE

DIMENSION TO MATCH

EXISTING SIDELITES

IN BUILDING.

SEE DOOR SCHEDULE

FOR DETAILS

FINISH FLOOR

ELEVATION

P E

R S

C H

E D

2" PER SCHED 2"

NEW LINTEL

TOOTH-IN NEW CMU

TO MATCH EXISTING

GLAZING (WHERE

OCCURS)

APPLIED STOP

(WHERE OCCURS)

EXISTING WALL

CONSTRUCTION

SEALANT AROUND

BOTH SIDES

5/ 8"

2"

8 3/4"

1 15/16"

1 15/16"

9/16"

EXISTING WALL

CONSTRUCTION

SEALANT AROUND

BOTH SIDES

RELOCATED EXIST

DOOR FRAME

9/16"

(3) METAL JAMB ANCHORS PER

SIDE, PROVIDE NON-SHRINK

GROUT, FILL AT EACH ANCHOR

SEALANT AROUND

BOTH SIDES

3/

4"

/1 6"

/1 6"

5/8"

2" EXISTING WALL

CONSTRUCTION

GLAZING

(WHERE

OCCURS)

APPLIED STOP

(WHERE OCCURS)

9/

INTERIOR STUD WALL TYPES

3 5/8" METAL STUDS

S3

5/8" GYPSUM WALL

BOARD (BOTH SIDES)

12" CMU

M5

3" MINERAL WOOL

INSULATION

'-3

'-9

EXIST WALL

AND WINDOW

CONSTRUCTION

TO REMAIN

CASEWORK

-PROVIDED BY

CASEWORK

VENDOR

7" COORDINATE W/

CASEWORK SUPPLIER

EPOXY

COUNTERTOP,

5" BACKSPLASH,

FAUCETS, &

INTEGRAL SINK

-PROVIDED BY

CASEWORK

VENDOR

1" 2'-5"

2X WOOD SUPPORT

BLOCKING AS REQ'D,

ANCHORED TO WALL

MASONRY

WALL ANCHOR

GROUT FILL

SEALANT AROUND

BOTH SIDES

CMU INFILL, SEE PLAN

RELOCATED EXIST

DOOR FRAME

9/

EQEQ

RELOCATED

MARKERBOARD

EXTENT OF WP (WALL

PROTECTION)

GC TO PROVIDE WOOD

BLOCKING AS REQUIRED

− AREA OF WORK

PROJECT

PLOT SCALE:

FILENAME:

DATE:

01 MM-DD-YR DESCRIPTION OF CHANGESNAME

R E V I S I O N S

K E Y P L A N w w w .c ra -a rc h it e c ts

.c o m

ALL REPORTS, PLANS SPECIFICATIONS AND COMPUTER FILES RELATING TO THIS

PROJECT ARE THE PROPERTY OF CRABTREE, ROHRBAUGH & ASSOCIATES.

CRABTREE ROHRBAUGH & ASSOCIATES RETAINS ALL COMMON LAW, STATUTE AND

OTHER RESERVED RIGHTS INCLUDING THE COPYRIGHT THERETO. REPRODUCTION

OF THE MATERIAL HEREIN OR SUBSTANTIAL USE WITHOUT WRITTEN PERMISSION OF

CRABTREE, ROHRBAUGH & ASSOCIATES VIOLATES THE COPYRIGHT LAWS OF THE

UNITED STATES AND WILL BE SUBJECT TO LEGAL PROSECUTION.

© CRABTREE, ROHRBAUGH & ASSOCIATES, INC 2025

C R

A B

T R

E E

R O

H R

B A

U G

H

A S

S O

C

IA

T E

S

A R

C H

IT

E

C T

S

C H

A R

LO

T

T E

S V

IL

LE

V

IR

G

IN

IA

E

A S

T W

IN

D

IN

G

H

IL

L R

O A

D

M E

C H

A N

IC

S

B U

-4

-0

T O

W S

O N

M

A R

Y

LA

N D

W H

IT

E

S U

LP

H

U R

S P

R

IN

G S

W

E S

T V

IR

G

IN

IA

As indicated

GENERAL CHEMISTRY PREP &

AUTOCLAVE ROOMS

NOVEMBER 13, 2026

A1.1

S L

IP

P

E R

Y R

O C

K U

N

IV

E R

S

IT

Y V

IN

C

E N

T S

C

IE

N C

E C

E N

T E

R

M

O R

R O

W W

A Y

S

L

IP

P E

R Y

R O

C K

P

A

BID SET

C H

E M

IS

T

R Y

P R

E P

R O

O M

R E

N O

V A

T

IO

N S

1/16" = 1'-0"A1.1

1 OVERALL THIRD FLOOR PLAN

1/4" = 1'-0"A1.1

3 GENERAL CHEMISTRY PREP & AUTOCLAVE PLAN

1/4" = 1'-0"A1.1

5 CHEM PREP - ELEV A

1/4" = 1'-0"A1.1

6 CHEM PREP - ELEV B

1/4" = 1'-0"A1.1

7 CHEM PREP - ELEV C

1/4" = 1'-0"A1.1

9 CHEM PREP - ELEV D

1/4" = 1'-0"A1.1

4 GENERAL CHEMISTRY PREP & AUTOCLAVE REFLECTED CEILING PLAN

1/4" = 1'-0"A1.1

2 GENERAL CHEMISTRY PREP & AUTOCLAVE DEMOLITION PLAN

ALTERATION LEGEND

TAG REMARK

1 - WALL

1A REMOVE EXISTING WALL & ALL ASSOCIATED COMPONENTS IN THEIR ENTIRETY. WHERE WALLS

CONTINUE BELOW THE EXISTING CONCRETE SLAB, REMOVE WALL TO MINIMUM DEPTH OF 8"

BELOW EXISTING FINISHED FLOOR ELEVATION PATCH AND PREPARE ADJACENT WALL, FLOOR &

CEILING SURFACES FOR NEW CONSTRUCTION / FINISHES AS SCHEDULED.

3 - DOOR

3A REMOVE EXISTING DOOR(S) AND/OR WINDOW, (SIDELITE) FRAME, WOOD TRIM, HARDWARE AND

ALL ASSOCIATED COMPONENTS IN THEIR ENTIRETY. PREPARE ADJACENT REMAINING WALL,

FLOOR & CEILING SURFACES FOR NEW CONSTRUCTION/INFILL & FINISHES AS SCHEDULED.

3B REMOVE AND REUSE EXISTING DOOR, FRAME, AND HARDWARE AS NOTED AT ADJACENT

CORRIDOR.

4 - FLOOR

4A REMOVE EXISTING BASE INCLUDING ALL ADHESIVES IN THEIR ENTIRETY. PATCH AND PREPARE

FLOOR AND WALL SUBSTRATES TO ACCOMMODATE NEW FINISHES AS SCHEDULED.

4B REMOVE EXISTING FLOOR FINISH AND RESIDUAL ADHESIVE IN THEIR ENTIRETY. PROVIDE

SELF-LEVELING UNDERLAYMENT AS REQUIRED. PREPARE SURFACE TO RECEIVE NEW FINISH AS

SCHEDULED.

5 - CEILING

5A REMOVE EXISTING CEILING SYSTEM IN ITS ENTIRETY, INCLUDING ALL FRAMING & SUSPENSION

COMPONENTS SO THE STRUCTURAL SYSTEM IS COMPLETELY EXPOSED. PATCH AND PREPARE

ADJACENT WALL SURFACES AS NEEDED TO ACCOMMODATE NEW CONSTRUCTION AND

FINISHES AS SCHEDULED.

7 - EQUIPMENT/CASEWORK

7A REMOVE EXISTING WALL MOUNTED COUNTERS AND ALL ASSOCIATED FASTENERS AND

COMPONENTS IN THEIR ENTIRETY. PREPARE ALL ADJACENT REMAINING SURFACES FOR NEW

CONSTRUCTION/FINISHES AS SCHEDULED.

7B <varies>

8 - MISCELLANEOUS

8A SALVAGE EXISTING SIGNAGE FOR REINSTALLATION, SEE NEW CONSTRUCTION PLANS.

DOOR SCHEDULE - THIRD FLOOR

OPENING

NUMBER

DOOR /

FRAME

UL

RATING

DOOR FRAME

HARDWARE

SET

SPECIAL

DETAIL REMARKS

DOOR

TYPE

DOOR

MATERIAL

GLAZING

TYPE

DIMENSIONS

FRAME

TYPE

FRAME

MATERIAL

DETAILS

WIDTH

HEIGHT THICKNESS HEAD JAMBLEAF 1 LEAF 2

306 -- F WD -- 3' - 0" 2' - 0" 7' - 2" 1 3/4" H1 HM 10 12

307 -- N WD -- 3' - 0" 7' - 2" 1 3/4" H1 HM 11 13 RELOCATED DOOR, FRAME, AND HARDWARE

NOTE: 1. CONCRETE MASONRY UNITS INDICATED ARE DIAGRAMATIC IN NATURE AND ARE NOT SPECIFIC TO ANY MANUFACTURER.

MASONRY CONTRACTOR SHALL INCORPORATE SHAPES AND OR CUT UNITS AS REQUIRED TO MEET DETAIL REQUIREMENTS.

2. LINTELS INDICATED TO BE COORDINATED WITH STRUCTURAL DRAWINGS.

H O L L O W M E T A L F R A M E D E T A I L S

NOTE: 1. ALL GLASS TO BE TEMPERED ADJACENT TO A DOOR WHERE THE NEAREST EXPOSED EDGE OF THE GLAZING IS WITHIN A 24 INCH ARC OR EITHER VERTICAL EDGE OF THE DOOR IN A CLOSED POSITION.

2. GLASS LITES GREATER THAN 9 SQUARE FEET WHERE THE BOTTOM EDGE IS WITHIN 18 INCHES OF THE

FINISHED FLOOR AND THE TOP EDGE EXTENDS ABOVE 36 INCHES AFF SHALL BE TEMPERED.

3. GLASS WHERE THE FINISHED FLOOR OR GRADE ON THE OPPOSING SIDE OF GLASS IS GREATER THAN 30

INCHES SHALL BE TEMPERED TO A HEIGHT OF 42 INCHES AFF.

4. ANY PORTION OF GLASS WITHIN CONSTRAINTS OF ABOVE REQUIREMENTS THE ENTIRE PANEL SHALL BE

TEMPERED.

H O L L O W M E T A L

F R A M E E L E V A T I O N S

H1

1 1/2" = 1'-0"A1.1

10 HM INTERIOR HEAD

1 1/2" = 1'-0"A1.1

11 HM INTERIOR HEAD

1 1/2" = 1'-0"A1.1

12 HM INTERIOR JAMB

ROOM FINISH SCHEDULE

NUMBER NAME

COLOR

SCHEME FLOOR BASE

WALLS

CEILING FINISH REMARKSWALL FINISH

WAINSCOT

FINISH HEIGHT

306 AUTOCLAVE ROOM VCT1 RB EPX1 -- -- ACT1 R1, R26

307 GENERAL CHEMISTRY PREP ROOM VCT1 RB EPX1/WP WP 4'-6" ACT1/EPX1 R1, R26

B A S E F I N I S H

C E I L I N G F I N I S H

W A L L F I N I S H

B A S E R E M A R K S

F L O O R R E M A R K S

C E I L I N G R E M A R K S

W A L L R E M A R K S

R1: SEE SPECIFICATIONS FOR ALTERNATE FINISHES

R2-R25: NOT USED

R26: SEE SPECIFICATIONS FOR ALTERNATE FINISHES.

R27-R50: NOT USED

R51-R75: NOT USED

R76-R100: NOT USED

G E N E R A L N O T E S

ROOM FINISH SCHEDULE LEGEND

F L OO R F I N I S H

VCT VINYL COMPOSITION TILE

RB RUBBER BASE

EPX EPOXY PAINT

FRP FIBERGLASS REINFORCED PLASTIC

WP WALL PROTECTION

ACT ACOUSTICAL CEILING TILE

EPX EPOXY PAINT

1. REFER TO SPECIFICATIONS FOR DETAILED

DESCRIPTION OF FINISH SYSTEM/TYPES.

2. REFER TO WALL TYPES FOR MASONRY LOCATIONS AND

DETAILS.

3. GYPSUM WALLBOARD BULKHEADS AND SOFFITS SHALL

BE PAINTED.

4. ALL HOLLOW METAL DOOR AND FRAMES IN PROJECT

AREA SHALL BE PAINTED.

5. ALL INTERIOR AND EXTERIOR FERROUS METAL SHALL

BE PAINTED INCLUDING LINTELS, RAILINGS, GRILLES

AND LOUVERS. (DOES NOT INCLUDE FACTORY OR PRE-

FINISHED ITEMS)

6. ETR = EXISTING TO REMAIN

7. EXIST = EXISTING

1/2" = 1'-0"A1.1

14 COUNTERTOP SECTION

1 1/2" = 1'-0"A1.1

13 HM INTERIOR JAMB

D1. DASHED LINES INDICATE EXISTING CONSTRUCTION TO BE REMOVED. PRIOR TO

BEGINNING SELECTIVE DEMOLITION, THE CONTRACTOR SHALL BE RESPONSIBLE

TO FIELD VERIFY ALL EXISTING CONDITIONS RELATED TO THE REQUIRED

SELECTIVE DEMOLITION AND AS REQUIRED FOR INSTALLATION OF ALL NEW

WORK SHOWN. WHERE DEMOLITION NOTES ARE GROUPED OVER MULTIPLE

ROOMS INDICATED WITH AN “X”, THE NOTES SHALL APPLY TO THE ENTIRE

GROUPING OF ROOMS.

D2. EXISTING CONDITIONS AS THEY APPEAR IN THESE CONTRACT DOCUMENTS MAY

DIFFER FROM ACTUAL CONDITIONS DUE TO WORK PERFORMED BY THE OWNER,

EITHER DIRECTLY OR UNDER SEPARATE CONTRACT SUBSEQUENT TO THE

ARCHITECT’S EXISTING CONDITIONS SURVEY. PRIOR TO SUBMITTING A BID, THE

BIDDER SHALL BE RESPONSIBLE TO VERIFY THE REQUIRED SCOPE OF THE

DEMOLITION WORK TO BE INCLUDED IN THEIR CONTRACT.

D3. THE SCOPE OF THE DEMOLITION WORK CONTAINED ON THE “D” SERIES

DRAWINGS SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO

PERFORM. CERTAIN WORK MAY BE SHOWN TO BE DEMOLISHED ON THESE

DRAWINGS (I.E. PLUMBING FIXTURES AND PIPING, ELECTRICAL DEVICES,

EQUIPMENT AND WIRING, MECHANICAL EQUIPMENT AND DUCTWORK, ETC.)

WHERE DEMOLITION OR SELECTIVE DEMOLITION BELONGS TO THOSE PRIME

CONTRACTORS. THESE ITEMS ARE SHOWN FOR COORDINATION PURPOSES,

HOWEVER PRIOR TO SUBMITTING A BID, GENERAL CONTRACTION BIDDERS SHALL

BE RESPONSIBLE TO REVIEW THE “ED”, “PD” AND “MD” SERIES DRAWINGS TO

CROSS COORDINATE THE ENTIRE EXTENT OF DEMOLITION REQUIRED TO

EXECUTE THE WORK. FURTHER, THE GENERAL CONTRACTOR, AS THE LEAD

PRIME CONTRACTOR, SHALL BE RESPONSIBLE TO COORDINATE WITH THE OTHER

AWARDED PRIME CONTRACTORS ON THE PROJECT ON ALL MATTERS

APPLICABLE TO THE REQUIRED DEMOLITION.

GENERAL DEMOLITION NOTES:

D4. REQUIRED DEMOLITION AND SELECTIVE DEMOLITION TO BE PERFORMED BY THE

GENERAL CONTRACTOR MAY BE SHOWN ON OTHER CONTRACT DRAWINGS, I.E.

STRUCTURAL DRAWINGS, FOOD SERVICE DRAWINGS, ETC. OTHER THEN THESE

“D” SERIES DRAWINGS. GENERAL CONTRACTION BIDDERS SHALL BE

RESPONSIBLE TO FULLY REVIEW ALL DRAWINGS, INCLUDING THE DEMOLITION

DRAWINGS ASSIGNED TO THE OTHER PRIME CONTRACT BIDDERS TO FULLY

UNDERSTAND THE PROJECT’S DEMOLITION REQUIREMENTS.

D5. THE OWNER RESERVES THE RIGHT TO REMOVE AND/OR SALVAGE ANY EXISTING

ITEMS AND MATERIALS THAT MAY BE SHOWN TO EXIST OR TO BE DEMOLISHED

ON THESE CONTRACT DOCUMENTS. BEFORE BEGINNING DEMOLITION AND

THROUGHOUT CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE TO

REVIEW WITH THE OWNER, ALL ITEMS SCHEDULED TO BE REMOVED OR

DEMOLISHED. ALL ITEMS DESIGNATED DURING THIS REVIEW TO REMAIN THE

OWNER'S PROPERTY SHALL BE CAREFULLY REMOVED, MAINTAINED IN GOOD

CONDITION AND TURNED OVER TO THE OWNER. ALL ITEMS DESIGNATED ON THE

CONTRACT DOCUMENTS TO BE SALVAGED, REUSED OR REINSTALLED AS PART

OF THE PROJECT SHALL BE MAINTAINED IN A REUSABLE CONDITION AND SHALL

BE STORED BY THE CONTRACTOR IN A CLEAN, DRY AND SECURE LOCATION

UNTIL REQUIRED FOR INSTALLATION. ALL REMAINING DEMOLITION DEBRIS AND

MATERIALS DEEMED BY THE CONTRACTOR TO BE GENERAL WASTE SHALL BE

PROPERLY DISPOSED OF OFF SITE AS REQUIRED BY APPLICABLE LAW.

D6. PRIOR TO SUBMITTING A BID, THE BIDDER SHALL BE RESPONSIBLE TO REVIEW

IN DETAIL THE WORK ASSIGNMENTS AND PROJECT REQUIREMENTS BY PRIME

CONTRACTOR INCLUDED IN DIVISION 1 SECTIONS “SUMMARY OF WORK”,

“CUTTING AND PATCHING” AND “CONSTRUCTION PROGRESS DOCUMENTATION”.

ALL QUESTIONS REGARDING THE INTENT OF THE PROJECT AND/OR WORK

ASSIGNMENTS SHALL BE DIRECTED TO THE ARCHITECT IN WRITING THROUGH

PRE-BID REQUEST FOR INFORMATION (RFI) TO BE CLARIFIED BY ADDENDUM.

UNLESS FORMALLY CLARIFIED OTHERWISE BY ADDENDUM, WORK

ASSIGNMENTS BY PRIME CONTRACT SHALL BE IN ACCORDANCE WITH

TRADITIONAL TRADE WORK ASSIGNMENTS.

D7. PRIOR TO SUBMITTING A BID, BIDDERS SHALL CLOSELY REVIEW THE

REQUIREMENTS OF THE INSTRUCTIONS AND SUPPLEMENTARY INSTRUCTIONS

TO BIDDERS. IN ACCORDANCE WITH THE SUPPLEMENTARY INSTRUCTIONS TO

BIDDERS, ARTICLE 2, SUBMITTING A BID REPRESENTS THAT THE BIDDER HAS A

COMPLETE UNDERSTANDING OF THE OWNER’S INTENDED SCOPE OF WORK AND

OF THE PROJECT’S FULL REQUIREMENTS, AND THAT ALL QUESTIONS THE

BIDDER MAY HAVE REGARDING THE SCOPE OF WORK HAVE BEEN SUBMITTED

TO THE ARCHITECT FOR CLARIFICATION BY ADDENDUM.

D8. PRIOR TO BEGINNING DEMOLITION OR SELECTIVE DEMOLITION OPERATIONS,

THE CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY THE LOCATIONS OF ALL

STRUCTURAL BEARING WALLS AND OTHER SUPPORTING STRUCTURAL

MEMBERS AND SHALL BE RESPONSIBLE TO PROVIDE ANY REQUIRED

TEMPORARY SHORING AND SUPPORT UNTIL THE NEW SUPPORTING

CONSTRUCTION IS FULLY INSTALLED.

GENERAL ALTERATION NOTES:

A.1 RESPONSIBILITY TO VERIFY FIELD DIMENSIONS

THE CONTRACTOR SHALL BE RESPONSIBLE TO FIELD VERIFY AND RECORD ALL

EXISTING BUILDING DIMENSIONS, CONDITIONS AND REQUIRED CLEARANCES

THAT EFFECT OR ARE RELATED TO NEW SCHEDULED WORK, INCLUDING

ALLOWANCES FOR NEW/FINAL SPECIFIED FINISHES. ALL DISCREPANCIES FROM

THE INFORMATION SHOWN ON THE CONTRACT DOCUMENTS SHALL BE DIRECTED

TO THE ARCHITECT IN WRITING THROUGH AN OFFICIAL WRITTEN REQUEST FOR

INFORMATION (RFI).

A2. PATCHING AND PREPARING EXISTING SURFACES - GENERAL

ALL EXISTING SURFACES AND FINISHES DISTURBED OR AFFECTED BY THE

SPECIFIED WORK SHALL BE PATCHED AND REPAIRED USING LIKE MATERIALS TO

ACHIEVE A UNIFORM COLOR, TEXTURE, PATTERN AND APPEARANCE TO THE

SURFACE BEING PATCHED. SURFACES SHALL BE PATCHED IN A WORKMANLIKE

MANNER TO BE AS SEAMLESS TO THE ADJACENT SURFACES AS IS REASONABLY

POSSIBLE.

A3. EXPOSED SURFACES THAT REMAIN EXPOSED IN THE FINAL WORK

UNLESS SPECIFICALLY NOTED OTHERWISE, WHERE EXISTING WALL, FLOOR OR

CEILING SURFACES ARE SCHEDULED AS PART OF THE WORK TO REMAIN

FINISHED SURFACES, THE CONTRACTOR SHALL BE RESPONSIBLE TO PATCH AND

PREPARE THESE SURFACES TO A SUITABLE, FINISHED CONDITION.

A4. EXISTING SURFACES SCHEDULED TO RECEIVE APPLIED FINISHES

WHERE AN EXISTING FLOOR, WALL OR CEILING SURFACE IS SCHEDULED AS PART

OF THE WORK TO RECEIVE A NEW APPLIED FINISH, THE SURFACE SHALL BE

PATCHED AND PREPARED AS A SUITABLE SUBSTRATE TO ACCEPT THE NEW

SPECIFIED FINISH INCLUDING, BUT NOT LIMITED TO, PATCHING ALL HOLES, VOIDS

AND OTHER SURFACE DAMAGE. FOR EXAMPLE, PAINTED WALL AND CEILING

SURFACES SHALL BE PATCHED AND PREPARED TO BE SMOOTH PRIOR TO

REPAINTING, AND FLOOR SLABS OR OTHER SUBSTRATES SHALL FLASH PATCHED

OR FLOATED AND PREPARED TO A SUITABLE CONDITION TO RECEIVE THE

SPECIFIED NEW FLOORING AND TO RECEIVE ALL APPLICABLE, SPECIFIED

MANUFACTURER’S WARRANTIES.

A5. PATCHING EXISTING CONCRETE FLOOR SLABS – MINIMUM STANDARDS

UNLESS SPECIFICALLY NOTED OTHERWISE, ALL PATCHES OF EXISTING

CONCRETE FLOOR SLABS SHALL BE ON 4-INCHES MINIMUM OF GRANULAR FILL

AND SHALL INCLUDE A VAPOR BARRIER BELOW THE SLAB. THE THICKNESS OF

CONCRETE SLAB PATCHES SHALL AT MINIMUM BE 4-INCHES THICK BUT WHERE

EXISTING SLABS ARE OF GREATER THICKNESS, THE PATCH SHALL MATCH THE

THICKNESS OF THE EXISTING CONCRETE SLAB. UNLESS SPECIFICALLY NOTED

OTHERWISE, ALL CONCRETE FLOOR SLAB PATCHES SHALL BE DOWELED INTO

THE EXISTING ADJACENT SLAB IN ACCORDANCE WITH THE GENERAL

REQUIREMENTS NOTED ON THE STRUCTURAL DRAWINGS.

A6. FLASH PATCHING AND PREPARING CONCRETE FLOOR PATCHES

FLASH PATCH OR FLOAT ALL PATCHED AND/OR INFILLED CONCRETE SLAB

SURFACES AS REQUIRED TO A SUITABLE CONDITION TO RECEIVE THE

SPECIFIED NEW FLOORING AND TO RECEIVE ALL APPLICABLE, SPECIFIED

MANUFACTURER’S WARRANTIES. BETWEEN NEW-TO-NEW, AND NEW-TO-

EXISTING FLOOR SURFACES, PATCHES SHALL EXTEND OUT TO A POINT TO

PROVIDE A SMOOTH, MINIMALLY APPARENT TRANSITION. REFER TO DIVISION 4

SECTION “HYDRAULIC CEMENT UNDERLAYMENT” AND TO THE DIVISION 9

FLOOR FINISHES SECTIONS FOR ADDITIONAL INFORMATION AND

REQUIREMENTS ON FLOOR PATCHING.

A7. FLASH PATCHING AT MIS-ALIGNED ADJACENT CONCRETE SLABS

WHERE WALLS THAT PENETRATE DOWN THROUGH AN EXISTING CONCRETE

FLOOR SLAB ARE DEMOLISHED AND THE CONCRETE SLAB ON BOTH SIDES OF

THE WALL IS NOT IN ALIGNMENT, AS PART OF THE INFILL PATCH, GRIND DOWN

OR FLASH PATCH UP THE MIS-ALIGNED SURFACES TO PROVIDE A SMOOTH,

MINIMALLY APPARENT TRANSITION.

A8. REQUIREMENT FOR BRIDGING CRACKS WITH NEW APPLIED FINISHES

WHERE NEW FLOOR FINISHES ARE APPLIED OVER PATCHES TO EXISTING

CONCRETE SLABS AND OTHER FLOOR SURFACES, PROVIDE MANUFACTURER

RECOMMENDED CLEAVAGE MEMBRANES OR SIMILAR MANUFACTURER

RECOMMENDED PRODUCTS SPECIFICALLY DESIGNED TO MINIMIZE CRACKING

OF THE NEW FINISHES OR TELEGRAPHING OF THE PATCHED JOINTS THROUGH

THE NEW FLOOR FINISHES. REFER TO THE DIVISION 9 FLOOR FINISHES

SECTIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

A9. CLOSING OPENINGS IN EXISTING WALLS

UNLESS SPECIFICALLY NOTED OTHERWISE, WHERE EXISTING WALL OPENINGS

ARE SPECIFIED TO BE CLOSED, USE MATERIALS AND FINISHES TO MATCH THE

ADJACENT EXISTING FINISHES. OPENINGS SHALL BE CLOSED AND PATCHED IN A

WORKMANLIKE MANNER TO BE AS SEAMLESS TO THE ADJACENT SURFACES AS

IS REASONABLY POSSIBLE. OPENINGS AT EXPOSED MASONRY WALLS (BRICK

AND CMU) SHALL BE PATCHED BY TOOTHING IN NEW MATCHING UNITS, USING

WHOLE UNITS, AND MATCHING THE EXISTING COURSING AND MASONRY BOND

PATTERN TO THE GREATEST EXTENT POSSIBLE. WHERE THE USE OF WHOLE

UNITS CANNOT BE ACCOMPLISHED, PRE-APPROVAL BY THE ARCHITECT IS

REQUIRED PRIOR TO EXECUTING THE PATCHWORK.

A10. FINISHING NEW OPENINGS THROUGH EXISTING WALLS

WHERE NEW OPENINGS ARE SPECIFIED TO BE CUT INTO EXISTING FINISHED

WALLS, THE OPENING’S EDGES SHALL BE FINISHED TO MATCH THE FINISH OF

THE PRIMARY WALL SURFACE UNLESS THE NEW CUT OPENING IS FULLY

CONCEALED AND OUT OF VIEW BY A FLANGE OR OTHER SIMILAR TRIM DEVICE.

THE EDGES OF OPENINGS CUT INTO EXISTING, EXPOSED OR FINISHED MASONRY

WALLS SHALL BE FINISHED BY TOOTHING IN WHOLE NEW “END BLOCKS” OR “END

BRICKS” INTO THE EXISTING COURSING AND MASONRY BOND PATTERN. THE USE

OF WITH CUT OR EXPOSED CORES IN EXPOSED WALL OPENINGS WILL NOT BE

ACCEPTABLE.

A11. VISIBLE OPENINGS THROUGH NEW MASONRY WALLS

WHERE OPENINGS ARE BEING CONSTRUCTED INTO NEW MASONRY WALLS (CMU

AND BRICK) WHERE THE OPENING WILL BE VISIBLE, INCLUDING WHERE BAR

JOISTS PASS THROUGH A MASONRY WALL, END BLOCKS SHALL BE USED ON ALL

EXPOSED ENDS OF THE OPENING. THE USE OF WITH CUT OR EXPOSED CORES IN

EXPOSED WALL OPENINGS WILL NOT BE ACCEPTABLE.

A12. NEW WALLS IN PLANE WITH EXISTING WALLS

UNLESS OTHERWISE NOTED, ALL MASONRY FOR NEW EXPOSED, PAINTED

MASONRY WALLS THAT ARE SHOWN TO BE CONSTRUCTED IN PLANE WITH

EXISTING MASONRY WALLS SHALL BE TOOTHED INTO THE EXISTING WALL

COURSING TO ACHIEVE A UNIFORM BOND PATTERN. WHERE NEW PAINTED

MASONRY WALL SURFACES ARE EXPOSED ON BOTH SIDES OF THE WALL, THE

NEW WALL SURFACES SHALL BE FLUSH WITH THE EXISTING WALL SURFACES ON

BOTH SIDES. THE CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY THE

EXISTING WALL THICKNESS AND MAY BE REQUIRED TO USE BACK-TO-BACK VS.

MONOLITHIC MASONRY UNITS TO ACHIEVE FLUSH ALIGNMENT ON BOTH SIDES.

A13. PATCHING SURFACES AT REMOVED EQUIPMENT AND DEVICES

WHERE EQUIPMENT OR DEVICES WHICH ARE MOUNTED TO EXISTING WALL,

FLOOR AND CEILING SURFACES ARE SCHEDULED TO BE DEMOLISHED, REMOVE

ALL COMPONENTS OF THE DEMOLISHED ITEM INCLUDING, BUT NOT LIMITED TO,

ALL FASTENERS AND ANCHORS, CLIPS, ETC. PATCH ALL EXISTING, REMAINING

SURFACES WITH APPROPRIATE PATCHING MATERIALS PRIOR TO APPLYING ANY

NEW SPECIFIED FINISHES. WHERE EQUIPMENT OR DEVICES ARE REMOVED FROM

EXISTING TO REMAIN CERAMIC TILE SURFACES, FILL ALL RESULTING HOLES IN

BOTH THE TILE AND IN THE GROUT JOINTS UP TO 1-INCH IN DIAMETER WITH A

COLORED EPOXY GROUT TO MATCH THE COLOR OF THE EXISTING TILE.

A14. PREPARING EXISTING PAINTED METAL SURFACES FOR REPAINTING

ALL EXISTING HOLLOW METAL DOORS AND FRAMES AND OTHER METAL

SURFACES SPECIFIED TO BE REPAINTED SHALL BE PROPERLY PREPARED IN

ACCORDANCE WITH THE APPROPRIATE SSPC PREPARATION METHOD. ALL

SCALE, RUST, DIRT AND LOOSE PAINT SHALL BE REMOVED AND THE ENTIRE

SURFACE SHALL BE SANDED TO BE SMOOTH PRIOR TO THE APPLICATION OF THE

NEW SPECIFIED FINISHES. THE CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY

THAT ALL NEW PAINT AND FINISH MATERIALS ARE COMPATIBLE WITH THE

EXISTING FINISHES TO ASSURE PROPER ADHESION.

A15. FINISH BLENDING REQUIREMENTS FOR PAINTING PATCHES IN EXISTING PAINTED

WALLS

WHERE PATCHING OF EXISTING PAINTED SURFACES OCCURS, THE PATCH SHALL

BE PRIMED AND SEALED AND PRELIMINARILY FINISH PAINTED AS REQUIRED SO

THAT THE AREA OF THE PATCH IS NON-APPARENT AND MATCHES THE TEXTURE

AND SHEEN OF THE EXISTING ADJACENT SURFACE. WHERE THE EXISTING

SURFACE IS NOT OTHERWISE SPECIFIED TO RECEIVE NEW PAINT, A FINAL FINISH

COAT SHALL BE APPLIED OVER THE ENTIRE UNBROKEN SURFACE CONTAINING

THE PATCH, I.E. TO THE NEAREST DOOR FRAME, INTERSECTING WALL OR OTHER

SEPARATING ITEM.

D9. UNLESS SPECIFICALLY SHOWN OTHERWISE, ALL WALLS AND OTHER

STRUCTURAL ELEMENTS SHOWN TO BE DEMOLISHED SHALL AT A MINIMUM, BE

DEMOLISHED FULLY DOWN TO THE TOP OF THE WALL’S OR ELEMENT’S

FOOTINGS. ALL EXTERIOR WALLS AND OTHER EXTERIOR STRUCTURAL

ELEMENTS SCHEDULED FOR DEMOLITION SHALL BE FULLY DEMOLISHED,

INCLUDING THEIR FOOTINGS. WHERE EXISTING FOOTINGS INTERFERE WITH

THE CONSTRUCTION OF NEW WORK, THE CONTRACTOR SHALL BE RESPONSIBLE

TO REMOVE THE EXISTING FOOTINGS AS PART OF THEIR BID.

D10. IN EXECUTING THE WORK, IF THE CONTRACTOR WOULD ENCOUNTER

ASBESTOS-CONTAINING OR SUSPECTED ASBESTOS CONTAINING MATERIALS

THAT ARE NOT IDENTIFIED OR ASSIGNED TO BE ABATED, THE CONTRACTOR

SHALL NOTIFY THE ARCHITECT IMMEDIATELY.

1/4" = 1'-0"A1.1

8 CHEM PREP - ELEV E

1. FOUNDATIONS HAVE BEEN DESIGNED IN ACCORDANCE WITH THE GEOTECHNICAL

ENGINEER'S REPORT PREPARED BY (NAME), (LOCATION).

2. SPREAD FOOTINGS SHALL BEAR ON UNDISTURBED SOIL OR COMPACTED STRUCTURAL

FILL HAVING A MINIMUM SAFE BEARING CAPACITY OF 2 KSF [PRESUMPTIVE].

3. THE BOTTOMS OF EXTERIOR FOOTINGS SHALL BE 36" [PRESUMPTIVE] MINIMUM BELOW

FINISH GRADE.

4. EDGES OF FOOTINGS SHALL NOT BE PLACED AT A GREATER THAN 1 (VERTICAL) TO 2

(HORIZONTAL) SLOPE WITH RESPECT TO ANY ADJACENT FOOTING OR EXCAVATION.

5. ADJACENT COLUMN FOOTINGS THAT ABUT SHALL BE SEPARATED BY A PAPER JOINT.

6. FOUNDATION CONCRETE SHALL BE NORMAL WEIGHT HAVING A MINIMUM 28 DAY DESIGN

COMPRESSIVE STRENGTH AS FOLLOWS:

SPREAD FOOTINGS 4000 PSI

WALLS & PIERS 4000 PSI

SLAB-ON-GRADE (INTERIOR) 3500 PSI

SLAB-ON-GRADE (EXTERIOR) 5000 PSI (0.40 W/C MAX. F3 EXPOSURE CLASS)

7. PROVIDE AIR-ENTRAINMENT IN ALL CONCRETE EXPOSED TO FREEZE-THAW CONDITIONS

DURING THE CONSTRUCTION PRIOR AND/OR IN THE COMPLETED STRUCTURE.

8. VERTICAL CRACK CONTROL/CONSTRUCTION JOINTS IN CONCRETE WALL SHALL BE

PROVIDED AT 25 FT. O/C MAX.

FOUNDATIONS

STRUCTURAL NOTES:

CONCRETE MASONRY

1. CONCRETE MASONRY CONSTRUCTION SHALL CONFORM TO ACI 530 AND 530.1.

2. MINIMUM COMPRESSIVE STRENGTH OF CONCRETE MASONRY, F'm SHALL BE 1500 PSI.

(MIN. NET AREA COMPRESSIVE STRENGTH OF UNIT = 2000 PSI.)

3. CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C90.

4. CONCRETE MASONRY REINFORCING SHALL BE DEFORMED BARS CONFORMING TO ASTM

A615, GRADE 60.

5. DEFORMED BAR ANCHORS (DBA) SHALL CONFORM TO ASTM A496,. DBA SHALL BE

WELDED BY AUTOMATIC EQUIPMENT.

6. GROUT SHALL CONFORM TO THE PROPORTIONAL REQUIREMENTS OF ASTM C476.

PROVIDE FINE AND COARSE GROUTS APPROPRIATE FOR THE SIZE OF VOID SPACE BEING

FILLED. GROUT SHALL HAVE A MINIMUM SLUMP OF 8 INCHES ACHIEVED THROUGH

SUFFICIENT WATER CONTENT . WATER REDUCING AND OTHER ADMIXTURES ARE NOT

PERMITTED IN GROUT.

7. GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 2000 PSI.

8. MORTAR SHALL CONFORM TO ASTM C270, TYPE M OR S, PCL OR MORTAR CEMENT.

THE USE OF MASONRY CEMENT IS NOT PERMITTED.

9. REINFORCING VOIDS, AND NON-REINFORCING VOIDS SPECIFIED TO BE GROUTED, IN

CONCRETE MASONRY SHALL BE FILLED SOLID WITH GROUT IN 5 FT. MAXIMUM LIFTS.

STOP POURS 1 1/2 INCHES BELOW THE BED JOINT TO FORM A KEY AT POUR JOINTS.

10. USE SQUARE ENDED BLOCK TO ENSURE REINFORCED VOIDS ALIGN VERTICALLY.

11. REINFORCED BARS SHALL BE TIED TO DOWELS AND HELD IN THE PROPER POSITION BY

MECHANICAL BAR POSITIONERS DESIGNED FOR THAT PURPOSE.

12. REINFORCING SHALL NOT BE PLUNGED INTO WET GROUT.

13. LAP UNCOATED, DEFORMED BARS 48 BAR DIAMETERS. INCREASE SPECIFIED LAP

LENGTHS 50% FOR EPOXY COATED BARS.

14. CONCRETE MASONRY SHALL BE LAID IN RUNNING BOND, UNO. PILASTERS SHALL BE

BONDED, UNO.

15. LOAD BEARING CMU SHALL HAVE FULL MORTAR BED JOINTS.

16. PROVIDE LADDER-TYPE HORIZONTAL JOINT REINFORCEMENT AS FOLLOWS:

TYPICAL: 16 IN. O/C MAX, UNO.

AT BELOW GRADE WALLS: PROVIDE AT 8" O/C

AT PARAPETS: PROVIDE AT 8" O/C

AT WALL OPENINGS: PROVIDE ADD'L REINF. NOT MORE THAN 8 IN.

ABOVE AND BELOW OPENING. TERMINATE 2

FT. BEYOND OPENING.

PROVIDE CONTINUITY AT INTERSECTIONS AND CORNERS USING PREFABRICATED T-

SHAPED AND L-SHAPED UNITS, AND LAP ALL CONSECUTIVE SECTIONS OF TRUSS TYPE

REINFORCING A MINIMUM OF 8 INCHES.

17. PROVIDE VERTICAL CONTROL JOINTS IN WALLS AT 24 FT. O/C MAX, U.N.O.

18. ALL CMU WALLS SHALL BE DOWELED TO SUPPORTING SLABS WITH MINIMUM #4@48

HOOKED DOWELS, UNO. ALL CMU WALLS SUPPORTED DIRECTLY ON STEEL MEMBERS

SHALL BE ANCHORED WITH 1/2" DIAMETER X 4" STUD ANCHORS AT 32" O/C, OR WITH #4

X 2'-0" DBA'S AT 48" O/C, UNO.

19. THE TOPS OF ALL NON-LOAD BEARING CMU WALL SHALL BE BRACED ACCORDING TO

SPECIFIC SECTIONS AND/OR TYPICAL DETAILS.

20. PROVIDE BOND BEAMS FOR WALL THICKNESS AND HEIGHTS AS FOLLOWS:

BOND BEAM UNITS SHALL BE OPEN CELL UNITS THAT PERMIT VERTICAL

REINFORCING TO PASS THROUGH.

6" CMU: UP TO 12 FT.: 1#5

UP TO 16 FT.: 1#6

8" CMU: UP TO 16 FT.: 2#5

UP TO 24 FT.: 2#6

10" & 12" CMU UP TO 12 FT.: 2#5

UP TO 24 FT.: 2#6

UP TO 32 FT.: 2#7

14" & 16" CMU UP TO 12 FT.: 3#5

UP TO 24 FT.: 3#6

UP TO 32 FT.: 3#7

SUBMITTALS

1. EXISTING CONDITIONS INDICATED ARE OBTAINED FROM AVAILABLE SOURCES (EXISTING

DRAWINGS, FIELD SURVEYS, ETC.) AND ARE NOT GUARANTEED TO BE TRUE AND EXACT.

CONTRACTOR(S) SHALL FIELD VERIFY EXISTING CONDITIONS AND NOTIFY THE ENGINEER OF

ANY DISCREPANCIES PRIOR TO PROCEEDING WITH THE AFFECTED PORTION OF THE WORK.

2. SEE ARCHITECTURAL DRAWINGS FOR EXTENT OF DEMOLITION OF EXISTING

CONSTRUCTION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE DEMOLITION

PROCEDURES AND SEQUENCE TO ENSURE STABILITY AND SAFETY DURING DEMOLITION.

THIS INCLUDES, BUT IS NOT LIMITED TO, THE ADDITION OF TEMPORARY SHORING AND

BRACING NECESSARY TO SUPPORT AND PREVENT DAMAGE TO REMAINING

CONSTRUCTION.

EXISTING CONDITIONS

GENERAL

MECHANICAL ROOFTOP EQPT CURBS, OPENINGS & ROOF ACCESS

1. PROVIDE FRAMING FOR ALL ROOFTOP EQUIPMENT CURBS AND OPENINGS, AND ROOF

ACCESS, IN NEW AND EXISTING CONSTRUCTION ACCORDING TO TYPICAL DETAILS, UNO.

2. COORDINATE SIZES AND LOCATIONS OF CURBS AND OPENINGS WITH MECHANICAL

DRAWINGS AND MECHANICAL CONTRACTOR AND ROOF ACCESS OPENINGS WITH

ARCHITECTURAL DRAWINGS. CURBS AND OPENINGS SHALL BE CENTERED BETWEEN

AND ACROSS NEW AND EXISTING ROOF MEMBERS.

3. ALL ROOF JOISTS AND TRUSSES (NEW AND EXISTING) SHALL BE REINFORCED FOR OFF-

PANEL POINTS LOADS ACCORDING TO TYPICAL DETAIL.

4. RE-USE EXISTING OPENINGS WHERE POSSIBLE.

TYPICAL DETAILS

MECHANICAL UNIT, DUCTWORK, AND PIPE SUPPORT FROM JOISTS

FOUNDATION SUBGRADE PREPARATION REQUIREMENTS

1. A GEOTECHNICAL ENGINEER, LICENSED IN THE JURISDICTION WHERE THE PROJECT IS

LOCATED, SHALL OBSERVE, REVIEW, AND APPROVE ALL WORK RELATED TO

EXCAVATION, BACKFILL, COMPACTION, SUBGRADE AND SUBBASE PREPARATION AND

MATERIAL SELECTION.

2. THE BUILDING SITE SHALL BE STRIPPED OF ANY TOPSOIL, ORGANIC MATTER,

VEGETATION, FILL MATERIALS, AND OTHERWISE UNSUITABLE OR SOFT SUBGRADE

MATERIALS.

3. UNSUITABLE MATERIALS SHALL BE EXCAVATED DOWN TO RESIDUAL SOIL ELEVATIONS.

4. SOIL BEARING ELEVATIONS SHALL BE VERIFIED BY THE GEOTECHNICAL ENGINEER PRIOR

TO BACKFILLING EXCAVATIONS OR CONSTRUCTING FOUNDATIONS.

5. WHERE ROCK IS ENCOUNTERED WITHIN 12 INCHES OF FOUNDATION BEARING

ELEVATION (SUBGRADE SHALL BE PROBED TO DETERMINE THIS), UNDERCUT ROCK BY

12 INCHES MIN. BELOW BEARING ELEVATION AND REPLACE WITH COMPACTED

STRUCTURAL FILL.

6. AT SLAB-ON-GRADE AREAS, FOLLOWING STRIPPING, THE SUBGRADES SHALL BE

PROOFROLLED WITH A LOADED TANDEM AXLE DUMP TRUCK OR TEN-TON ROLLER UNDER

OBSERVATION OF THE GEOTECHNICAL ENGINEER. AREAS WHICH EXHIBIT EXCESSIVE

PUMPING OR WEAVING, AS DETERMINED BY THE GEOTECHNICAL ENGINEER, SHALL BE

REMOVED AND REPLACED WITH NEW COMPACTED STRUCTURAL FILL.

7. COMPACTED FILL SHALL BE USED TO RAISE EXISTING GRADES TO THE PROPOSED NEW

ELEVATION WHERE REQUIRED.

8. UNDER-SLAB DRAINS, CONSISTING OF A 4 INCH WASHED GRAVEL OR CRUSHED STONE

DRAINAGE LAYER (CORRESPONDING TO PA DOT 2B), SHALL BE USED BENEATH THE

CONCRETE SLAB-ON-GRADE.

9. TB-# INDICATES TEST BORING NUMBER AND APPROXIMATE LOCATION.

[#.##'] INDICATES APPROXIMATE EXISTING SURFACE ELEVATION RELATIVE TO

DATUM

(#.##') INDICATES APPROXIMATE ELEVATION TO RESIDUAL SOIL ELEVATION,

RELATIVE TO DATUM, BELOW EXISTING FILL MATERIALS

<#.##'> INDICATES APPROXIMATE AUGER REFUSAL ELEVATION RELATIVE TO

DATUM.

INTERPOLATE RESIDUAL SOIL AND AUGER REFUSAL ELEVATIONS BETWEEN TEST

BORING LOCATIONS.

CONCRETE SLABS ON GRADE

1. GEOTECHNICAL ENGINEER SHALL OBSERVE AND APPROVE SUBGRADE BEFORE CONCRETE

PLACEMENT.

2. DO NOT PLACE CONCRETE SLABS ON FROZEN GROUND.

3. CONTROL JOINTS ARE REQUIRED IN CONCRETE SLABS-ON-GRADE. REFER TO PLANS AND

TYPICAL DETAILS FOR THE JOINT CONSTRUCTION, LOCATIONS, AND SPACING

REQUIREMENTS.

4. PROVIDE (2) #4 X 4'-0" LONG BARS DIAGONALLY AT ALL RE-ENTRANT CORNERS.

5. COORDINATE LOCATION AND DIMENSIONS OF RECESSED SLABS.

6. EXTERIOR CONDITIONS SHOULD USE A 5" SLAB DEPTH WITH 6x6 - W2.9xW2.9 WWF, UNO.

1. STRUCTURAL NOTES ARE NOT INTENDED TO REPLACE SPECIFICATIONS. SEE

SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. FOR INCONSISTENCIES STANDARD

PRACTICE, THE STRICTER REQUIREMENT SHALL APPLY, AND THE ENGINEER SHALL BE

NOTIFIED PRIOR TO PROCEEDING WITH THE AFFECTED PORTION OF THE WORK.

2. STRUCTURAL CONSTRUCTION DOCUMENTS SHALL BE USED WITH OTHER CONSTRUCTION

DOCUMENTS, INCLUDING ARCHITECTURAL, M/E/P, AND SITE DOCUMENTS. COORDINATE

WITH THESE DOCUMENTS FOR LOCATIONS AND DIMENSIONS OF OPENINGS, CHASES,

INSERTS, REGLETS, SLEEVES, DEPRESSIONS, ETC., NOT INDICATED ON THE STRUCTURAL

DOCUMENTS. ALL DIMENSIONS AND CONDITIONS, EXISTING OR NEW, SHALL BE FIELD

VERIFIED. THE ENGINEER SHALL BE NOTIFIED OF DISCREPANCIES PRIOR TO PROCEEDING

WITH THE AFFECTED PORTION OF WORK.

3. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AFTER THE BUILDING IS

COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION

PROCEDURES AND SEQUENCE TO ENSURE STABILITY AND SAFETY DURING

CONSTRUCTION. THIS INCLUDES, BUT IS NOT LIMITED TO, THE ADDITION OF SHEETING,

SHORING, TEMPORARY BRACING, GUYS, AND TIEDOWNS. THE CONTRACTOR SHALL

PROVIDE SHORING AND BRACING NECESSARY TO PROTECT EXISTING AND ADJACENT

STRUCTURES.

4. SECTIONS AND DETAILS SHOWN ON ANY STRUCTURAL DOCUMENTS SHALL BE

CONSIDERED TYPICAL FOR SIMILAR CONDITIONS THAT DO NOT HAVE A SPECIFIC SECTION

INDICATED, AND SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.

5. APPLICABLE FEDERAL, STATE AND MUNICIPAL REGULATIONS SHALL BE FOLLOWED,

INCLUDING THE FEDERAL DEPARTMENT OF LABOR OSHA.

6. THE CONTRACTOR IS RESPONSIBLE FOR LIMITING THE AMOUNT OF CONSTRUCTION LOAD

IMPOSED ON THE STRUCTURE. CONSTRUCTION LOADS SHALL NOT EXCEED THE

SPECIFIED DESIGN LIVE LOADS. CONCRETE SLABS AND TOPPINGS SHALL NOT BE

LOADED UNTIL THE CONCRETE HAS REACHED AT LEAST 75% OF THE SPECIFIED DESIGN

COMPRESSIVE STRENGTH.

7. THE CONTRACTOR'S CONSTRUCTION SEQUENCES SHALL ALLOW FOR THE EFFECTS OF

THERMAL MOVEMENTS DURING THE CONSTRUCTION PERIOD, PRIOR TO THE BUILDING

BEING ENCLOSED AND TEMPERATURE CONTROLLED. NEGATIVE EFFECTS OF SUCH

THERMAL MOVEMENTS, SUCH AS MATERIAL CRACKING, FROST HEAVE, ETC., SHALL BE

CORRECTED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.

8. IN THE ABSENCE OF SPECIFIC INSTRUCTIONS TO THE CONTRARY IN THE CONTRACT

DOCUMENTS, THE TRADE PRACTICES THAT ARE DEFINED IN ANY CODE OF STANDARD

PRACTICE SHALL GOVERN.

9. DO NOT SCALE DRAWINGS TO DETERMINE DIMENSIONS, LOCATIONS, OR SIZES OF ANY

ELEMENT.

1. TYPICAL DETAILS APPLY AT ALL APPROPRIATE LOCATIONS.

2. TYPICAL DETAILS ARE GENERALLY NOT CUT ON THE PLANS.

3. CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL TYPICAL DETAIL APPLICATIONS.

STRUCTURAL DESIGN CRITERIA

1. DESIGN LOADS ARE IN ACCORDANCE WITH THE 2021 EDITION OF THE INTERNATIONAL

BUILDING CODE (IBC) INCLUDING LOCAL CODES, WHERE APPLICABLE, AND THE

FOLLOWING STANDARDS REFERENCED IN IBC 2021:

ACI 318 - BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE

ACI 530 - BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES

ACI 530.1 - SPECIFICATIONS FOR MASONRY STRUCTURES

AISC 360 - SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS

ASCE 7 - MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES

2. IBC BUILDING RISK CATEGORY: III

3. LIVE LOADS ARE AS FOLLOWS. LIVE LOAD REDUCTIONS HAVE BEEN TAKEN WHERE

APPLICABLE, UNO.

ROOF LIVE LOAD 20 PSF

ASSEMBLY AREAS 100 PSF

CORRIDORS 100 PSF

LOBBIES 100 PSF

LABORATORIES 100 PSF

MECHANICAL ROOMS 150 PSF

STAIRS 100 PSF

CLASSROOMS 40 PSF

OFFICE 50 PSF (+15 PSF PARTITION)

4. SNOW LOADING IS BASED ON THE FOLLOWING. DRIFTING AND SLIDING SNOW LOADS

HAVE BEEN CONSIDERED WHERE APPROPRIATE:

RAIN ON SNOW SURCHARGE N/A (Pg > 20 PSF)

GROUND SNOW LOAD, Pg 30 PSF

FLAT ROOF SNOW LOAD 23.1 PSF

SNOW EXPOSURE FACTOR, Ce 1.0

SNOW THERMAL FACTOR, Ct 1.0

SNOW LOAD IMPORTANCE FACTOR, I 1.1

DESIGN SNOW LOAD 30 PSF

5. WIND LOADING IS BASED ON THE FOLLOWING:

BASIC WIND SPEED (3 SEC GUST) 116 MPH

EXPOSURE CATEGORY C

BUILDING CATEGORY: SIMPLE DIAPHRAGM, LOW-RISE, ENCLOSED, RIGID

INTERNAL PRESSURE COEFF. ±0.18

6. SEISMIC LOADING IS BASED ON THE FOLLOWING:

SEISMIC IMPORTANCE FACTOR 1.25

SEISMIC SITE CLASS D (PRESUMPTIVE)

SPECTRAL RESPONSE COEFF. (SS) 0.098g

SPECTRAL RESPONSE COEFF. (S1) 0.044g

SPECTRAL RESPONSE COEFF. (SDS) 0.104g SPECTRAL RESPONSE COEFF. (SD1) 0.07g

LONG PERIOD TRANSITION (TL) 12

SEISMIC DESIGN CATEGORY B

ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE

BASIC STRUCTURAL SYSTEM BEARING WALL & BUILDING FRAME

SEISMIC FORCE RESISTING SYSTEM STEEL SYSTEMS NOT SPECIFICALLY

DETAILED FOR SEISMIC

RESISTANCE (PRESUMPTIVE)

7. LATERAL EARTH PRESSURES ON RETAINING AND BASEMENT WALLS ARE BASED ON THE

FOLLOWING: [PRESUMPTIVE VALUES]

EQUIVALENT AT-REST FLUID PRESSURE (BASEMENT) 60 PSF

EQUIVALENT ACTIVE FLUID PRESSURE (CANTILEVERED) 45 PSF

EQUIVALENT PASSIVE FLUID PRESSURE 300 PSF

COEFFICIENT OF FRICTION 0.40

COHESION N/A

8. DESIGN REACTIONS AND SUPPORT DETAILS FOR ELEVATOR, ARCHITECTURAL,

MECHANICAL, ELECTRICAL AND PLUMBING EQUIPMENT ARE BASED UPON AVAILABLE

MANUFACTURER INFORMATION. SUPPORT CONDITIONS MAY NEED TO BE REVISED

BASED UPON ACTUAL SUPPLIED EQUIPMENT AND SUPPORT DETAILS

1. THE APPLICABLE CONTRACTOR SHALL SUBMIT THE FOLLOWING FOR APPROVAL:

CONCRETE MIX DESIGNS FOR EACH STRENGTH INDICATED

CONCRETE REINFORCING SHOP DRAWINGS, INCLUDING ELEVATIONS OF ALL WALLS

STRUCTURAL STEEL SHOP DRAWINGS & CONNECTION CALCS W/ P.E. SEAL

MASONRY REINFORCING SHOP DRAWINGS, INCLUDING ELEVATIONS OF ALL WALLS

MASONRY GROUT AND MORTAR MIX DESIGNS

PRODUCT DATA & MILL TEST FOR EACH APPLICABLE PRODUCT

METAL DECK SHOP DRAWINGS

CONCRETE REINFORCING

1. REINFORCED CONCRETE CONSTRUCTION SHALL CONFORM TO ACI 318.

2. CONCRETE REINFORCING SHALL CONFORM TO THE FOLLOWING DESIGNATIONS:

DEFORMED BARS ASTM A615, GRADE 60

DEFORMED BARS (WELDABLE) ASTM A706

WELDED WIRE FABRIC ASTM A1064

3. LAP DEFORMED BARS 40 DIA., U.N.O. PROVIDE CORNER AND L BARS AT CORNERS AND

INTERSECTIONS. REINFORCING INDICATED AS CONTINUOUS SHALL BE LAPPED. HOOKS

SHALL BE STANDARD HOOKS, U.N.0. LAP WELDED WIRE FABRIC SUCH THAT THE

OVERLAP OF THE OUTERMOST CROSS-WIRES OF EACH ADJOINING SHEET IS NOT LESS

THAN THE SPACING OF THE CROSS-WIRES PLUS TWO IN., U.N.0.

4. PROVIDE CONTINUOUS REINFORCEMENT WHEREVER POSSIBLE; SPLICE ONLY AS SHOWN

OR APPROVED. STAGGER SPLICES WHERE POSSIBLE. USE TENSION SPLICE CLASS "B"

U.N.O. DOWELS SHALL MATCH THE SIZE AND SPACING OF THE SPECIFIED

REINFORCEMENT AND SHALL BE LAPPED WITH TENSION SPLICES.

5. CONCRETE PROTECTION FOR REINFORCEMENT:

CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3 IN.

CONCRETE EXPOSED TO EARTH OR WEATHER:

#6 THROUGH #18 BARS 2 IN.

#5 BAR OR SMALLER 1½ IN.

CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND:

SLABS, WALLS, JOISTS:

#14 AND #18 BARS 1½"

#11 AND SMALLER ¾"

BEAMS, COLUMNS, PIERS: 1½"

6. REINFORCING FOR SLABS ON GRADE, WHERE NOT OTHERWISE SPECIFIED, SHALL BE AS

FOLLOWS:

REINFORCING BARS: SEE FOUNDATION AND TYPICAL DETAILS. AT SLAB

BLOCKOUT AND RE-ENTRANT CORNERS, PROVIDE 2#4 X

4'-0" DIAGONALS.

WIRE MESH: 6X6 W2.9XW2.9 WWF. REINFORCING SHALL BE

SUPPORTED PRIOR TO THE POUR AT MID-DEPTH OF SLAB.

SYNTHETIC FIBER: FIBRILLATED POLYPROPYLENE, IN ACCORDANCE WITH

MANUFACTURER'S RECOMMENDATIONS.

7. REINFORCING FOR CONCRETE TOPPING, WHERE NOT OTHERWISE SPECIFIED, SHALL BE AS

FOLLOWS:

REINFORCING BARS: SEE FRAMING AND TYPICAL DETAILS. AT OPENINGS AND

RE-ENTRANT CORNERS, PROVIDE 2#4 X 4'-0" DIAGONALS.

WIRE MESH: 6X6 W2.9XW2.9 WWF. REINFORCING SHALL BE

SUPPORTED 1" BELOW THE TOP OF SLAB PRIOR TO THE

POUR.

8. DETAILING OF CONCRETE REINFORCING AND ACCESSORIES SHALL CONFORM TO ACI

DETAILING MANUAL MNL-66, AND WITH ACI 315, MANUAL OF STANDARD PRACTICE FOR

DETAILING REINFORCING CONCRETE STRUCTURES.

STRUCTURAL STEEL

1. STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING DESIGNATIONS:

STRUCTURAL STEEL WF SHAPES ASTM A992

OTHER STRUCTURAL STEEL SHAPES ASTM A36, UNO

STEEL BARS, ANGLES AND PLATES ASTM A36, UNO

STIFF PLATES IN MOMENT CONNECTIONS ASTM A572, UNO

ROUND PIPE ASTMA53, TYPE E OR S

SQUARE & RECTANGULAR HSS ASTM A500, GRADE C

ROUND HSS ASTM A500, GRADE B

2. STRUCTURAL STEEL DESIGN IS AND SHALL BE BASED UPON AISC'S ASD METHOD.

3. BOLTS SHALL BE MINIMUM 3/4 IN. DIA. AND SHALL CONFORM TO THE FOLLOWING

DESIGNATIONS, UNO:

HIGH STRENGTH BOLTS ASTM F3125/A325 AND/OR A490

ANCHOR RODS ASTM F1554, GRADE 36 [55] [105]

4. BOLTED CONN SHALL CONFORM TO RCSC'S "SPECIFICATION FOR STRUCTURAL JOINTS

USING HIGH-STRENGTH BOLTS".

5. WELDING, WELDING ELECTRODES, AND FLUXES SHALL CONFORM TO AWS D1.1

"STRUCTURAL WELDING CODE - STEEL". ELECTRODES SHALL HAVE A MINIMUM TENSILE

STRENGTH OF 70 KSI.

6. GROUT UNDER STEEL COLUMNS OR POST BASEPLATES SHALL BE NON-METALLIC,

SHRINKAGE RESISTANT GROUT CONFORMING TO ASTM C1107 AND HAVING A MINIMUM

DESIGN COMPRESSIVE STRENGTH OF 5000 PSI. GROUT UNDER STEEL BEAM BEARING

PLATES IN CONCRETE OR MASONRY WALLS SHALL CONFORM TO ASTM C476.

7. HIGH STRENGTH BOLTED CONNECTIONS SHALL BE TIGHTENED TO THE SNUG-TIGHT

CONDITION, UNO.

8. HIGH STRENGTH BOLTS IN CONNECTIONS USED FOR KICKERS, BRACING MEMBERS OR

MOMENT CONNECTIONS THAT ARE FABRICATED WITH SLOTTED HOLES SHALL BE SLIP-

CRITICAL. IF STANDARD HOLES ARE USED, BOLTS SHALL BE FULLY PRE-TENSIONED.

9. MINIMUM CAPACITY OF BEAM SHEAR CONNECTIONS: DESIGN CONNECTIONS USING THE

"MAXIMUM TOTAL UNIFORM LOAD" TABLES IN THE AISC MANUAL. FOR NON-COMPOSITE

BEAMS THE CONNECTION CAPACITY SHALL BE AT LEAST 50% OF THE MAXIMUM

UNIFORM LOAD CAPACITY, UNO. FOR COMPOSITE BEAMS, THE CONNECTION CAPACITY

SHALL BE AT LEAST 80% OF THE MAXIMUM TOTAL UNIFORM LOAD, UNO. REACTIONS

NOTED ON DRAWINGS ARE BASED ON ASD.

10. PROVIDE FULL DEPTH CONNECTIONS AT ALL BEAM OR GIRDER TO COLUMN

CONNECTIONS.

11. PROVIDE COLUMN CAP PLATES AS FOLLOWS, UNO:

FOR DECK BEARING: 1/4" THICK (PROVIDE WHERE BEAMS DO

NOT FRAME INTO BOTH SIDES OF COLUMN)

FOR JOIST BEARING: 1/2" THICK AT K SERIES JOISTS

3/4" THICK AT LH & DLH JOISTS

1" THICK AT JOIST GIRDERS

FOR BEAM BEARING: SEE TYPICAL DETAILS, 3/4" MIN.

FOR WOOD TRUSSES BEARING: 1/2" THICK

FOR MOMENT CONNECTIONS: SEE TYPICAL DETAILS

PROVIDE COLUMN CAP PLATES AT ALL HSS COLUMNS

12. WEB STIFFENERS SHALL BE PROVIDED IN WF SHAPES AS FOLLOWS:

COLUMN WEBS: AT FULLY-DEVELOPED MOMENT CONNECTIONS. STIFFENERS SHALL BE

COMPLETE PENETRATION GROOVE WELDED, SAME THICKNESS AND GRADE AS BEAM

FLANGES. WHERE MOMENT CONNECTIONS OCCUR ON COLUMN FLANGES AND COLUMN

WEBS, STIFFENER THICKNESS SHALL EQUAL THE VECTOR SUMMATION OF THE

RESPECTIVE BEAM FLANGE THICKNESSES.

BEAM WEBS: WHERE BEAM BEARS ON COLUMN, SAME THICKNESS AND STRENGTH AS

COLUMN FLANGES.

BEAM WEBS: WHERE COLUMN BEARS ON BEAM, SAME THICKNESS AND STRENGTH AS

COLUMN FLANGES.

13. PRIOR TO DETAILING CONNECTIONS FOR STRUCTURAL STEEL, THE STEEL FABRICATOR

SHALL SUBMIT FOR APPROVAL REPRESENTATIVE DETAILS FOR EACH TYPE OF PROPOSED

STRUCTURAL CONNECTION. SUCH DETAILS SHALL INDICATE DESIGN CAPACITIES. AFTER

APPROVAL, THE CONNECTIONS SHALL BE INCORPORATED INTO THE SHOP DRAWINGS.

14. ALL EXTERIOR EXPOSED STRUCTURAL STEEL SHALL BE HOT-DIPPED GALVANIZED.

STEEL JOISTS AND JOIST GIRDERS

1. STEEL JOISTS, JOIST GIRDERS, AND BRIDGING SHALL CONFORM TO SJI'S STANDARD

SPECIFICATIONS" FOR K, KCS, VS, LH, DLH, AND SLH SERIES JOISTS AND SJI'S

"RECOMMENDED CODE OF STANDARD PRACTICE FOR STEEL JOISTS AND JOIST

GIRDERS".

2. PROVIDE AND ANCHOR BRIDGING LINES ACCORDING TO SJI SPECIFICATIONS. BRIDGING

INDICATED ON DRAWINGS IS SCHEMATIC, AND MAY NOT REFLECT THE SJI REQUIRED

MINIMUM NUMBER OF LINES.

3. JOIST AND JOIST GIRDER TO COLUMN CONNECTIONS SHALL HAVE BOTTOM CHORD

EXTENSIONS. BOTTOM CHORD EXTENSIONS SHALL HAVE POSITIVE ATTACHMENT TO

SUPPORT BY BOLTING OR BY WELDING. BOTTOM CHORD EXTENSIONS SHALL BE

CONNECTED ONLY AFTER ALL DEAD LOADS ARE APPLIED.

4. K-SERIES JOIST EXTENSIONS SHALL BE TYPE R-1, UNO.

5. PROVIDE JOIST CAMBER ACCORDING TO SJI SPECIFICATION, UNO.

6. REFER TO STRUCTURAL DESIGN CRITERIA FOR NET UPLIFT LOADING REQUIREMENTS FOR

ROOF JOISTS AND JOIST GIRDERS. PROVIDE ADDITIONAL WIND UPLIFT BRIDGING LINES

AT MEMBER ENDS.

7. MECH/ELEC/PLUMB CONFLICTS WITH JOIST BRIDGING: ALL HORIZONTAL & DIAGONAL

BRIDGING SHALL BE INSTALLED AND ANCHORED ACCORDING TO SJI REQUIREMENTS.

AFTER DECK IS INSTALLED, BRIDGING MAY BE RE-WORKED AS FOLLOWS TO

ACCOMMODATE INSTALLATION OF DUCTS, PIPING, CONDUIT, ETC.:

A. DIAGONAL BRIDGING MAY BE REPLACED WITH HORIZONTAL BRIDGING IN NON-

ADJACENT JOIST BAYS. DO NOT REMOVE DIAGONAL BRIDGING IN MORE THAN

ONE LOCATION AT A TIME BEFORE REINSTALLING HORIZONTAL BRIDGING.

B. HORIZONTAL BRIDGING MAY BE REMOVED ONLY IN NON-ADJACENT JOIST BAYS.

DIAGONAL BRIDGING MUST BE INSTALLED IN BOTH ADJACENT JOIST BAYS,

ALIGNED WITH THE LOCATIONS OF HORIZONTAL BRIDGING THAT IS TO BE

REMOVED. DO NOT REMOVE HORIZONTAL BRIDGING BEFORE INSTALLING NEW

DIAGONAL BRIDGING IN ADJACENT JOIST BAYS.

IF THE ABOVE LIMITATIONS CANNOT BE MET, THE JOIST MANUFACTURER SHALL BE

CONTACTED FOR DIRECTION.

1. METAL DECKING SHALL CONFORM TO THE FOLLOWING DESIGNATIONS:

ROOF DECK ASTM A653, GRADE 33

METAL DECK SHALL CONFORM TO AISI'S "SPECIFICATION FOR THE DESIGN OF COLD

FORMED STEEL STRUCTURAL MEMBERS", TO SDI'S "DESIGN MANUAL FOR FLOOR AND

ROOF DECKS", AND TO SDI'S. "MANUAL OF CONSTRUCTION WITH STEEL DECK".

2. WELDING SHALL CONFORM TO AWS D1.3 "STRUCTURAL WELDING CODE - SHEET STEEL"

3. PROVIDE WELDING WASHERS FOR DECK LIGHTER THAN 22 GAGE.

4. SPECIFIED ROOF DECK HAS BEEN DESIGNED TO BE CONTINUOUS OVER 3 SPANS

MINIMUM. FOR ONE OR TWO SPAN CONDITIONS, PROVIDE HEAVIER GAGE DECK AS

REQUIRED TO SUPPORT APPLICABLE LOADS.

5. FASTEN ROOF DECK PANELS TO SUPPORTING STEEL MEMBERS WITH 5/8" DIA PUDDLE

WELDS AT 12" O.C. (36/4 PATTERN), UNO. FASTEN TO PERIMETER STEEL MEMBERS AT

12" O.C., UNO. MECHANICAL FASTENING METHODS ARE PERMITTED IN LIEU OF

WELDING. CONTRACTOR SHALL PROVIDE SUBMITTAL TO INDICATE SPECIFIC FASTENING

SYSTEM AND DATA TO INDICATE THAT MECHANICAL FASTENERS MEET OR EXCEED THE

DIAPHRAGM CAPACITY ACHIEVED BY THE WELDING PATTERN DESCRIBED ABOVE, OR

OTHER SPECIFIC REQUIREMENTS INDICATED.

6. MECHANICALLY FASTEN ROOF DECK SIDE LAPS WITH SELF DRILLING NO. 10 SCREWS

AT MIDSPAN OR 36" (MAX) O.C., UNO.

METAL DECKINGIBC SPECIAL INSPECTIONS

1. STRUCTURAL TESTS AND SPECIAL INSPECTIONS ARE REQUIRED BY THE INTERNATIONAL

BUILDING CODE AND SHALL BE PERFORMED ON THIS PROJECT IN ACCORDANCE WITH

REQUIREMENTS OF IBC CHAPTER 17, "STRUCTURAL TESTS AND SPECIAL INSPECTIONS."

2. AS REQUIRED BY IBC, THE STRUCTURAL TESTS AND SPECIAL INSPECTIONS SHALL BE

PERFORMED BY AN INDEPENDENT, APPROVED AGENCY, EMPLOYED BY THE OWNER.

3. COPIES OF ALL REPORTS DOCUMENTING THE SPECIAL INSPECTIONS AND TESTS

PERFORMED BY THE INSPECTING AGENT SHALL BE SUBMITTED TO THE STRUCTURAL

ENGINEER OF RECORD (BAKER, INGRAM & ASSOCIATES).

4. SPECIAL INSPECTIONS SHALL INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING:

FABRICATOR INSPECTION: WHERE FABRICATION OF LOAD-BEARING MEMBERS AND

ASSEMBLIES (SUCH AS STRUCTURAL STEEL, LIGHT-GAGE STEEL TRUSSES, ETC.) IS

PERFORMED ON THE PREMISES OF A FABRICATOR'S SHOP, SPECIAL INSPECTION

SHALL BE PROVIDED TO VERIFY…

This is the start of the file's text. The full file is on GovTribe.