2-Specifications For Generator.docx
DOCX document 19 KB Posted
- Solicitation number
- ITB-2026-Natural Gas Standby Generator Engine 60kW (New Only)
- Issued by
- Milwaukee County, Mattoon Village, Wisconsin
About this file
Summary
This specifications document pertains to a natural gas standby generator engine procurement for Timmerman Airport in Milwaukee, Wisconsin. The project requires a new 60kW generator unit meeting specific operational and technical requirements. The specifications establish detailed performance standards for the generator system, including requirements for fuel compatibility with natural gas, electrical output ratings, noise levels, control systems, and safety features. The document outlines technical parameters for engine performance, cooling systems, emissions compliance, and installation requirements to ensure the generator functions reliably as a backup power source for airport operations.
The specifications document includes requirements for generator construction materials, dimensional specifications, and certification standards. Bidders must provide equipment that complies with applicable local, state, and federal regulations, including environmental standards and electrical codes. The document specifies quality assurance requirements, warranty provisions, and performance testing protocols that must be met prior to final acceptance. Additional requirements address installation support, commissioning procedures, and documentation deliverables that vendors must provide with the equipment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1-Bid Prerequisite Requirements Generator Standby.docx | DOCX document | |
| 3-Milwaukee County Terms and Conditions.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERATOR SYSTEM SPECIFICATION SHEET Project Name: Timmerman Airport
GENERAL OVERVIEW This specification sheet outlines the requirements for a new, 60kW natural gas (NG) engine generator set and associated equipment for emergency standby power at Timmerman Airport The system provided must be Made in America.
1. PERFORMANCE METRICS & SYSTEM RATINGS
· Output Capacity: 60kW (Standby Rated at rated power factor)
· Load Factor: 85%
· Duty Rating: Emergency Standby Duty
· Voltage Requirements: 240VAC, 1-Phase, 4-Wire, 08 Power Factor
· Certifications: UL 2200, NFPA 110 (Level 1), EPA NSPS Certified
2. ENGINE SPECIFICATIONS
· Fuel Type: Natural Gas (NG)
· Operating Speed / Frequency: 1800 RPM / 60 Hz
· Governor: Electronic Isochronous Governor
· Filtration: Standard Duty Air, Fuel, and Oil Filters
· Mounting: Vibration Isolator Pads (shipped loose)
3. ALTERNATOR & COOLING SYSTEM
· Alternator Pitch: 2/3 Pitch
· Temperature Rise: 125°C Temperature Rise
· Voltage Regulation: Included
· Cooling System: Unit Mounted Radiator rated for 50°C / 122°F
4. ENCLOSURE & EXHAUST SYSTEM
· Type: Weather Protective / Sound Attenuated Enclosure
· Construction: Bolted construction, thermal insulation, galvanized angle mounting frame, plated hardware throughout Two coats of standard enamel finish
· Hardware: Stainless steel hardware; all latches must be stainless steel and padlocking
· Exhaust: Interior Mounted Critical Grade Muffler
5. CONTROL PANEL & ACCESSORIES
· Type: Digital Control Panel with Microprocessor-based controls
· Operation: Keypad Operation
· Metering & Displays: Digital AC Meters, Digital Engine Gauges, Running Time Meter, Low Fuel Level Display
· Switches/Controls: Voltage Adjusting, Three-Position Selector Switch, Cycle Crank
· Alarms/Relays: Pre-alarm Sender Kit, 4 Relay Board, Fuel Leak Detection
· Remote Annunciator: Remote Annunciator Panel compliant with NFPA 110 (remote to 4,000 feet) – shipped loose
6. ELECTRICAL COMPONENTS (BREAKERS, BATTERY & CHARGER)
· Circuit Breaker: One (1) 400A, 3-pole, 100% rated with LSI trip, mounted and wired in a NEMA 1 enclosure with standard lugs
· Battery System: Heavy Duty Lead Acid Battery with Rack and Cables
· Battery Charger: 12 Volt, 6 Amp
· Block Heater: 120V single-phase with isolation valves, mounted and wired
7. TRANSFER SWITCHES & CONNECTION CABINETS Automatic Transfer Switch (ATS) - Shipped Loose
· Rating: 400 Amp, 240VAC, 2-pole, 3-wire
· Type: Open Transition, NEMA 1 enclosure
· Features: Programmable engine exerciser
· (Note: An additional ATS adder is listed as 200 Amp, 480/277VAC, 3-pole, 4-wire, Open Transition, NEMA 1, programmable engine exerciser)
8. Manual Transfer Switch (MTS) / Connection Cabinet
· Rating: 400 Amp, 240VAC, 2-pole, 3-wire
· Type: Open Transition, NEMA 3R enclosure
· Breakers: Three (3) 400A 3P Molded Case Circuit Breakers (35kA 480Vac, 80% Rated) with Auxiliary Contacts Interlocked to prevent cross-connecting power sources
· Load Bank Camlock Section: 400A Rated Female Single Pole Camlock Receptacles (1x Brown, 1x Orange, 1x Yellow, 1x Green)
· Portable Generator Camlock Section: 400A Rated Male Single Pole Camlock Receptacles (1x Brown, 1x Orange)
9. WARRANTY
· Generator Set: Two (2) Year / 3000-Hour Factory Warranty
· Service Warranty: Sixty (60) days limitation period for defect claims on workmanship from the date the work is completed
· Parts/Materials Warranty: Passed through from the applicable manufacturer
10. SERVICES & LOGISTICS (START-UP & COMMISSIONING)
· Freight: One-way freight to job site or riggers yard included (Offloading by others)
· Flids: Initial filling of lube oil and a 50/50 water and anti-freeze mix included. (Note: Fuel and permits by others).
· Start-Up & Testing: On-site Factory Authorized Startup, Factory Certified Test & Reports, and two (2) hour resistive portable load bank test Performed during normal business hours (Mon-Fri, 7 AM-3:30 PM)
· Additional Services: Commissioning support, demonstration and training (same day as start-up), and provided O&M manuals