2_NIFC_415-MNT_Replace_DRAFT_DWGS_1.pdf
PDF 47 MB Posted
- Attached to
- NIFC Building 415 Replacement Industry Day Federal contract opportunity
- Solicitation number
- 140L0626R0003
About this file
This file is a set of draft construction drawings for the NIFC 415-Duane Graves Building Replacement project. The 47 MB PDF contains 155 sheets of detailed design documentation for Building 320-SGE, a new construction project located at the National Interagency Fire Center (NIFC) campus at 3833 Development Avenue, Boise, Idaho 83705. The project is identified as NIFC 415-Duane Graves Replacement and NIFC 320-SGE Construction, with project number 070117.024 and BLM project number 140L0624F0171. The drawings are dated 100% CD (Completed Development) phase as of September 30, 2025, and are marked "NOT FOR CONSTRUCTION," indicating they remain in draft status. The design was prepared by LBYD Federal, LLC (Idaho Falls, Idaho), with design by M. Anderson and A. Ricos.
The drawings encompass comprehensive design documentation across general, civil, landscape, structural, architectural, interiors, fire protection, plumbing, mechanical, and electrical disciplines. Civil work includes site demolition and utility demolition plans, overall site plans with coordinates, grading and drainage design with storm sewer profiles, and utility infrastructure (sanitary sewer, water, fire water, and irrigation systems). The project involves demolition of existing structures including a cabana, satellite pad, running path, and bollards, while retaining key elements like the guard house, security fence, and communications shelter. Site improvements include new asphalt and concrete paving, ABA-compliant parking (including van-accessible stalls), concrete sidewalks, bollards, parking bumpers, and landscaping. The design adheres to 2021 International Building Code (IBC), International Fire Code (IFC), and ADA accessibility standards, with occupancy classifications of Business (B), Moderate-Hazard Factory Industrial (F-1), and Storage (S-1, S-2), requiring fire sprinkler systems and mechanical ventilation throughout.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 3_NIFC_415-MNT_Replace_415-MNT_DEMO_DRAFT_SPECS_1.pdf | ||
| NIFC_PUBLIC_PARKING_Map_1.pdf | ||
| Industry_Day_Invite_1.pdf | ||
| 1_NIFC_415-MNT_Replace_DRAFT_SPECS_1.pdf | ||
| 4_NIFC_415-MNT_Replace_415-MNT_DEMO_DRAFT_DWGS_1.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STOPSTOP
BOLLARD
MCP
MCP
Vehicle Mail
DESIGNERS
ALWAYS THINK SAFETY
Project #
Sh ee t T itl e:
Date:
BLM Project #
U ni te d
St at es D ep ar tm en t o f t he In te rio r B ur ea u of L an d
M an ag em en t
D ra w n by
R ev is io ns
/1
5/
:2
AM
Q
:\L
BY
D Fe de ra l P ro je ct
F ile s\
-A ct ive P ro je ct s\
.0
Du an e G ra ve s Bu ild in g Rp l\0
Dr aw in gs
\C
AD
\0
7.
4G
-0
.d wg
A
B
C
D
2 3 4 5
Ap pr ov ed b y:
C he ck ed b y:
D es ig ne d by
Seal:
De sc rip tio n
Da te
Sheet of 155
09/30/2025
070117.024
140L0624F0171
NI
FC
-D
UA
NE
G
RA
VE
S
RE
PL
AC
EM
EN
T
NI
FC
-S
G E
CO
NS
TR
UC
TI
O
N
NA
TI
O
NA
L
IN
TE
RA
G
EN
CY
F
IR
E
CE
NT
ER
D
EV
EL
O
PM
EN
T
AV
E, B
O
IS
E, ID
0%
C D
- N O
T
FO
R
CO
NS
TR
UC
TI
O N
NO
T
FO
R C
O
NSTR
UCTI
O N
P
HASE
0%
C D
070117.024Project No.
LBYD FEDERAL, LLC
1425 Higham Street Idaho Falls, Idaho 83402 Phone (208) 528-8718
C copyright 2022 These drawings and design intent are the sole property of LBYD FEDERAL, LLC which may not be reproduced without written permission.
G-001
M . A
N D
ER
SE
N
A.
R
IC
O
SJ
BD
SJ
BD
C O
VE
R
S H
EE
T
VICINITY MAPREFERENCE MAP
PROJECT LOCATION
LATITUDE: 43.566443°
LONGITUDE: -116.208626°
3833 DEVELOPMENT AVE, BOISE, ID 83705
NATIONAL INTERAGENCY FIRE CENTER
NIFC 415-DUANE GRAVES REPLACEMENT
NIFC 320-SGE CONSTRUCTION
BOISE, IDAHO
PROJECT
LOCATION
NN
NIFC
CAMPUS
ALWAYS THINK SAFETY
Project #
Sh ee t T itl e:
Date:
BLM Project #
U ni te d
St at es D ep ar tm en t o f t he In te rio r B ur ea u of L an d
M an ag em en t
D ra w n by
R ev is io ns
/1
5/
:2
AM
Q
:\L
BY
D Fe de ra l P ro je ct
F ile s\
-A ct ive P ro je ct s\
.0
Du an e G ra ve s Bu ild in g Rp l\0
Dr aw in gs
\C
AD
\0
7.
4G
-0
.d wg
A
B
C
D
2 3 4 5
Ap pr ov ed b y:
C he ck ed b y:
D es ig ne d by
Seal:
De sc rip tio n
Da te
Sheet of 155
09/30/2025
070117.024
140L0624F0171
NI
FC
-D
UA
NE
G
RA
VE
S
RE
PL
AC
EM
EN
T
NI
FC
-S
G E
CO
NS
TR
UC
TI
O
N
NA
TI
O
NA
L
IN
TE
RA
G
EN
CY
F
IR
E
CE
NT
ER
D
EV
EL
O
PM
EN
T
AV
E, B
O
IS
E, ID
0%
C D
- N O
T
FO
R
CO
NS
TR
UC
TI
O N
NO
T
FO
R C
O
NSTR
UCTI
O N
P
HASE
0%
C D
070117.024Project No.
LBYD FEDERAL, LLC
1425 Higham Street Idaho Falls, Idaho 83402 Phone (208) 528-8718
C copyright 2022 These drawings and design intent are the sole property of LBYD FEDERAL, LLC which may not be reproduced without written permission.
G-002
M . A
N D
ER
SE
N
A.
R
IC
O
SJ
BD
SJ
BD
IN
D
EX
S
H
EE
T
DRAWING INDEX
SHEET
SUB
SHEET TITLE OF SHEET
GENERAL
1 G-001 COVER SHEET
2 G-002 INDEX SHEET
3 G-100 CODE REVIEW
4 G-101 FIRST FLOOR - LIFE SAFETY PLAN
5 G-103 SPACE UTILIZATION PLAN
6 G-104 FIRE STOPPING DETAILS
7 G-105 ACCESSIBILITY DIAGRAMS
8 G-106 ACCESSIBILITY DIAGRAMS
SURVEY
9 V-101 EXISTING SITE CONDITIONS
CIVIL
10 C-001 CIVIL LEGEND AND ABBREVIATIONS
11 C-002 CIVIL NOTES
12 CD101 OVERALL SITE DEMOLITION PLAN
13 CD102 OVERALL SITE UTILITY DEMOLITION PLAN
14 C-101 OVERALL SITE PLAN
15 C-102 OVERALL SITE COORDINATE PLAN
16 C-103 OVERALL SITE GRADING AND DRAINAGE PLAN
17 C-104 OVERALL SITE UTILITY PLAN
18 C-105 SITE UTILITY PROFILES
19 C-501 DETAILS
20 C-502 DETAILS
21 C-503 DETAILS
22 C-504 DETAILS
23 C-505 DETAILS
LANDSCAPE
24 LS001 NOTES AND SCHEDULE
25 LS101 PLANTING PLAN
26 LS102 IRRIGATION PLAN
27 LS501 LANDSCAPE DETAILS
STRUCTURAL
28 S-001 GENERAL NOTES
29 S-002 GENERAL NOTES CONT'D
30 S-003 SPECIAL INSPECTIONS
31 S-004 SPECIAL INSPECTIONS
32 S-005 ABBREVIATIONS AND SYMBOLS LEGEND
33 S-101 OVERALL FOUNDATION PLAN
34 S-102 PARTIAL FOUNDATION PLAN - BUILDING SOUTH
35 S-103 PARTIAL FOUNDATION PLAN - BUILDING NORTH
36 S-104 OVERALL ROOF PLAN
37 S-105 PARTIAL ROOF PLAN - BUILDING SOUTH
38 S-106 PARTIAL ROOF PLAN - BUILDING NORTH
39 S-301 FOUNDATION SECTIONS
40 S-302 FOUNDATION SECTIONS
41 S-311 FRAMING SECTIONS
42 S-312 FRAMING SECTIONS
43 S-501 TYPICAL DETAILS
44 S-502 TYPICAL DETAILS
45 S-503 TYPICAL DETAILS
46 S-504 TYPICAL DETAILS
47 S-505 TYPICAL DETAILS
48 S-506 TYPICAL DETAILS
49 S-701 COMPONENTS AND CLADDING
ARCHITECTURAL
50 A-001 LEGEND, NOTES, AND WALL TYPES
51 A-002 ASSEMBLIES
52 A-101 OVERALL FIRST FLOOR PLAN
53 A-101A FIRST FLOOR PLAN SOUTH
54 A-101B FIRST FLOOR PLAN NORTH
55 A-102 OVERALL LOWER ROOF PLAN
56 A-102A LOWER ROOF PLAN SOUTH
57 A-102B LOWER ROOF PLAN NORTH
58 A-103 OVERALL UPPER ROOF PLAN
59 A-103A UPPER ROOF PLAN SOUTH
60 A-103B UPPER ROOF PLAN NORTH
61 A-105 OVERALL REFLECTED CEILING PLAN
62 A-105A REFLECTED CEILING PLAN SOUTH
63 A-105B REFLECTED CEILING PLAN NORTH
64 A-201 EAST AND WEST ELEVATIONS
65 A-202 NORTH AND SOUTH ELEVATIONS
66 A-301 BUILDING CROSS SECTION
67 A-302 BUILDING LONGITUDINAL SECTIONS
68 A-310 WALL SECTIONS
69 A-311 WALL SECTIONS
70 A-401 ENLARGED PLANS AND INTERIOR ELEVATIONS - TYPICAL
71 A-402 ENLARGED PLANS AND INTERIOR ELEVATIONS - TYPICAL
72 A-403 ENLARGED PLANS AND INTERIOR ELEVATIONS - TYPICAL
73 A-404 ENLARGED STAIR PLANS, SECTIONS, AND DETAILS
74 A-501 ROOF AND WALL DETAILS
75 A-502 PLAN DETAILS
76 A-503 DOOR DETAILS
77 A-504 WINDOW DETAILS
78 A-506 CEILING AND ROOF DETAILS
79 A-601 DOOR SCHEDULES
80 A-602 DOOR HARDWARE AND ELEVATIONS
INTERIORS
81 IN-101 FIRST FLOOR FINISH PLAN
82 IN-501 INTERIOR DETAILS
83 IN-601 MATERIAL LIST
84 Q-101 EQUIPMENT PLAN AND SCHEDULE
FIRE PROTECTION
85 FP001 FIRE SPRINKLER SYSTEM SITE PLAN, NOTES, AND LEGEND
86 FP101A SOUTH FIRST FLOOR FIRE SPRINKLER SYSTEM PLAN
87 FP101B NORTH FIRST FLOOR FIRE SPRINKLER SYSTEM PLAN
88 FP301 FIRE SPRINKLER SYSTEM SECTIONS AND DETAILS
89 FP302 FIRE SPRINKLER SYSTEM FIRE RISER DETAILS
PLUMBING
90 P-001 PLUMBING LEGEND, NOTES AND ABBREVIATIONS
91 P-101 FIRST FLOOR - DOMESTIC PLUMBING PLAN
92 P-102 FIRST FLOOR - SANITARY PLUMBING PLAN
93 P-103 LOWER ROOF - SANITARY PLUMBING PLAN
94 P-104 FIRST FLOOR - COMPRESSED AIR PLAN
95 P-105 FIRST FLOOR - STORM DRAIN PLAN
96 P-106 UPPER ROOF - STORM DRAIN PLAN
97 P-401 ENLARGED DOMESTIC PLANS
98 P-402 ENLARGED SANITARY PLANS
99 P-501 PLUMBING DETAILS
100 P-502 PLUMBING DETAILS
101 P-503 PLUMBING DETAILS
102 P-504 PLUMBING DETAILS
103 P-601 PLUMBING SCHEDULES
104 P-901 DOMESTIC ISOMETRIC VIEW
105 P-902 SANITARY / VENT ISOMETRIC VIEW
106 P-903 STORM DRAIN ISOMETRIC VIEW
MECHANICAL
107 M-001 MECHANICAL LEGEND, NOTES AND ABBREVIATIONS
108 M-101 OVERALL FIRST FLOOR MECHANICAL PLAN
109 M-101A FIRST FLOOR MECHANICAL PLAN SOUTH
110 M-101B FIRST FLOOR MECHANICAL PLAN NORTH
111 M-102 ROOF MECHANICAL PLAN
112 M-103 SUB-FLOOR RADON MITIGATION PLAN
113 M-104 OVERALL FIRST FLOOR MECHANICAL PIPING PLAN
114 M-104A FIRST FLOOR MECHANICAL PIPING PLAN SOUTH
115 M-104B FIRST FLOOR MECHANICAL PIPING PLAN NORTH
116 M-301 MECHANICAL SECTIONS
117 M-401 MECHANICAL ENLARGED PLANS
118 M-402 MECHANICAL ENLARGED PLANS
119 M-403 MECHANICAL ENLARGED PLANS
120 M-501 HVAC DETAILS
121 M-502 HVAC DETAILS
122 M-503 HVAC DETAILS
123 M-504 HVAC DETAILS
124 M-505 HVAC DETAILS
125 M-506 HVAC DETAILS
126 M-601 MECHANICAL SCHEDULES
127 M-602 MECHANICAL SCHEDULES
128 M-603 MECHANICAL SCHEDULES
129 M-604 HVAC SYSTEM DIAGRAMS
130 M-605 HVAC SYSTEM DIAGRAMS
131 M-606 HVAC SYSTEM DIAGRAMS
ELECTRICAL
132 E-001 ELECTRICAL LEGEND, NOTES AND ABBREVIATIONS
133 ED101 PHASE 1 - UTILITY DEMOLITION SITE ELECTRICAL PLAN
134 ES101 PHASE 1 - SITE ELECTRICAL PLAN
135 E-101 FIRST FLOOR POWER PLAN
136 E-101A FIRST FLOOR POWER PLAN SOUTH
137 E-101B FIRST FLOOR POWER PLAN NORTH
138 E-102 ROOF POWER PLAN
139 E-103 FIRST FLOOR LIGHTING PLAN
140 E-103A FIRST FLOOR LIGHTING PLAN SOUTH
141 E-103B FIRST FLOOR LIGHTING PLAN NORTH
142 E-104 FIRST FLOOR TELECOMMUNICATIONS PLAN
143 E-104A FIRST FLOOR TELECOMMUNICATIONS PLAN SOUTH
144 E-104B FIRST FLOOR TELECOMMUNICATIONS PLAN NORTH
145 E-105 FIRST FLOOR FIRE ALARM PLAN
146 E-105A FIRST FLOOR FIRE ALARM PLAN SOUTH
147 E-105B FIRST FLOOR FIRE ALARM PLAN NORTH
148 E-106 FIRST FLOOR GROUNDING PLAN
149 E-401 ELECTRICAL ENLARGED PLANS
150 E-501 ELECTRICAL DETAILS
151 E-502 ELECTRICAL DETAILS
152 E-601 ELECTRICAL SCHEDULES
153 E-602 ELECTRICAL SCHEDULES
154 E-603 ELECTRICAL SCHEDULES
155 E-701 DIAGRAMS & SCHEDULES
GOVERNING CODES:
CODES ADOPTED BY THE BUREAU OF LAND MANAGEMENT:
2021 INTERNATIONAL BUILDING CODE (IBC)
2021 INTERNATIONAL FIRE CODE (IFC)
2021 INTERNATIONAL MECHANICAL CODE (IMC)
2021 INTERNATIONAL PLUMBING CODE (IPC)
2021 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
ASHRAE 90.1-2019
2022 NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS
2020 NFPA 70 NATIONAL ELECTRICAL CODE
2022 NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE
2021 NFPA 101 LIFE SAFETY CODE
2023 NFPA 780 STANDARD FOR THE INSTALLATION OF LIGHTNING PROTECTION
SYSTEMS
ABAAS ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS
2022 ASCE/SEI 7
2021 IBC ANALYSIS
OCCUPANCY CLASSIFICATION: B, F-1, S-1, S-2
304.1 BUSINESS GROUP B
306.2 MODERATE-HAZARD FACTORY INDUSTRIAL GROUP F-1
311.2 MODERATE-HAZARD STORAGE S-1
311.2.2 MOTOR VEHICLE REPAIR GARAGES SHALL COMPLY WITH SECTION 406.8
311.3 LOW-HAZARD STORAGE S-2
311.3.1 PUBLIC PARKING GARAGES SHALL COMPLY WITH SECTION 406.4 AND THE
ADDITIONAL REQUIREMENTS OF SECTION 406.6 FOR ENCLOSED PARKING GARAGES
FIRE SPRINKLER SYSTEM: PROVIDED
CONSTRUCTION TYPE: VB
406.1 ALL MOTOR-VEHICLE OCCUPANCIES SHALL COMPLY WITH SECTION 406.2. REPAIR
GARAGES SHALL ALSO COMPLY WITH SECTION 406.8.
406.2.9.1.1 CONNECTION OF A PARKING GARAGE WITH ANY ROOM IN WHICH THERE IS A FUEL-
FIRED APPLIANCE SHALL BE BY MEANS OF A VESTIBULE PROVIDING A TWO-DOORWAY
SEPARATION.
406.6.6.1 ENCLOSED VEHICLE PARKING GARAGES AND PORTIONS THEREOF THAT DO NOT
MEET THE DEFINITION OF OPEN PARKING GARAGES SHALL BE LIMITED TO THE ALLOWABLE
HEIGHTS AND AREAS SPECIFIED IN SECTIONS 504 AND 506 AS MODIFIED BY SECTION 507.
406.6.2 A MECHANICAL VENTILATION SYSTEM AND EXHAUST SYSTEM SHALL BE PROVIDED IN
ACCORDANCE WITH CHAPTERS 4 AND 5 OF THE INTERNATIONAL MECHANICAL CODE.
406.6.3 AN ENCLOSED PARKING GARAGE SHALL BE EQUIPPED WITH AN AUTOMATIC
SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.2.10.
406.8 REPAIR GARAGES SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE IFC AND
SECTION 406.2 AND 406.8.
406.8.1 REPAIR GARAGES SHALL BE MECHANICALLY VENTILATED IN ACCORDANCE WITH THE
INTERNATIONAL MECHANICAL CODE. THE VENTILATION SYSTEM SHALL BE CONTROLLED AT
THE ENTRANCE TO THE GARAGE.
406.8.3 A REPAIR GARAGE SHALL BE EQUIPPED WITH AN AUTOMATIC SPRINKLER SYSTEM IN
ACCORDANCE WITH SECTION 903.2.9.1
TABLE 504.3 ALLOWABLE BUILDING HEIGHT IN FEET ABOVE GRADE PLANE
FOR B, F, S OCCUPANCY, V-B, SPRINKLERED = 60 FEET
TABLE 504.4 ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE
FOR F-1, S-1 OCCUPANCY (MOST RESTRICTIVE), V-B, SPRINKLERED = 2 STORIES
ACTUAL = 1 STORY
TABLE 506.2 ALLOWABLE AREA FACTOR IN SQUARE FEET
FOR F-1 OCCUPANCY (MOST RESTRICTIVE), V-B, SPRINKLERED, 1 STORY = 34,000 SF
ACTUAL = 22,018 SF
508.3 NONSEPARATED OCCUPANCIES
508.3.2 THE ALLOWABLE BUILDING AREA, HEIGHT, AND NUMBER OF STORIES SHALL BE
BASED ON THE MOST RESTRICTIVE ALLOWANCES FOR THE OCCUPANCY GROUPS
UNDER CONSIDERATION FOR THE TYPE OF CONSTRUCTION OF THE BUILDING IN
ACCORDANCE WITH SECTION 503.1.
508.3.3 NO SEPARATION IS REQUIRED BETWEEN NONSEPARATED OCCUPANCIES.
TABLE 601 FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS
FOR TYPE VB, ALL EXCEPT NONBEARING EXTERIOR WALLS (SEE TABLE 705.5) = 0
HOURS
TABLE 705.5 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON
FIRE
SEPARATION DISTANCE FOR FIRE SEPARATION DISTANCE FOR B, S-1 OCCUPANCY, V-B:
X ≥ 10 FEET = 0 HOUR
TABLE 705.8 MAXIMUM AREA OF EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
DISTANCE AND DEGREE OF OPENING PROTECTION FOR UNPROTECTED, SPRINKLERED
OPENINGS (UP, S).
X ≥ 20 FEET = NO LIMIT
CODE REVIEW INFORMATION
IECC 2021 ANALYSIS
ADA COUNTY, IDAHO = ZONE 5B
C402.1.3 OPAQUE THERMAL ENVELOPE INSULATION COMPONENT MINIMUM REQUIREMENTS,
R-VALUE METHOD
ROOF
INSULATION ENTIRELY ABOVE ROOF DECK = R-30 CI
WALLS, ABOVE GRADE
MASS = R-11.4 CI
SLAB-ON-GRADE FLOORS
UNHEATED SLABS = R-15 FOR 24" BELOW
C402.1.4 OPAQUE THERMAL ENVELOPE ASSEMBLY MAXIMUM REQUIREMENTS, U-FACTOR
METHOD
OPAQUE DOORS
NONSWINGING DOOR = U-0.31
SWINGING DOOR = U-0.37
GARAGE DOOR <14% GLAZING = U-0.31
C402.4 BUILDING ENVELOPE FENESTRATION MAXIMUM U-FACTOR AND SHGC REQUIREMENTS
VERTICAL FENESTRATION
U-FACTOR
FIXED FENESTRATION = U-0.36
OPERABLE FENESTRATION = U-0.45
ENTRANCE DOORS = U-0.63
SHGC
PF < 0.2, FIXED = 0.38
PF < 0.2, OPERABLE = 0.33
SKYLIGHTS
U-FACTOR = U-0.50
SHGC = 0.40
TABLE 803.13 INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY OCCUPANCY
FOR GROUP B (MOST RESTRICTIVE), SPRINKLERED:
EXIT ENCLOSURES AND EXIT PASSAGEWAYS = B
CORRIDORS = C
ROOMS AND ENCLOSED SPACES = C
903.2.4 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT ALL
BUILDINGS CONTAINING A GROUP F-1 OCCUPANCY WHERE ONE OF THE FOLLOWING
CONDITIONS EXISTS:
1. A GROUP F-1 FIRE AREA EXCEEDS 12,000 SQUARE FEET.
903.2.9.1 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT ALL
BUILDINGS USED AS REPAIR GARAGES IN ACCORDANCE WITH SECTION 406, AS SHOWN:
2. BUILDINGS NOT MORE THAN ONE STORY ABOVE GRADE PLAN, WITH A FIRE AREA
CONTAINING A REPAIR GARAGE EXCEEDING 12,000 SQUARE FEET.
4. A GROUP S-1 FIRE AREA USED FOR THE REPAIR OF COMMERCIAL MOTOR VEHICLES
WHERE THE FIRE AREA EXCEEDS 5,000 SQUARE FEET.
903.2.10 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT BUILDINGS
CLASSIFIED AS PARKING GARAGES WHERE ANY OF THE FOLLOWING CONDITIONS EXISTS:
1. WHERE THE FIRE AREA OF THE ENCLOSED PARKING GARAGE IN ACCORDANCE WITH
SECTION 406.6 EXCEEDS 12,000 SQUARE FEET.
TABLE 1004.5 MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT
ACCESSORY STORAGE AREAS = 300 GROSS
ASSEMBLY WITHOUT FIXED SEATS, UNCONCENTRATED = 15 NET
BUSINESS AREAS = 150 GROSS
EXERCISE ROOMS = 50 GROSS
INDUSTRIAL AREAS = 100 GROSS
WAREHOUSES = 500 GROSS
1004.5.1 THE OCCUPANT LOAD IS PERMITTED TO BE INCREASED PROVIDED THAT ALL OTHER
REQUIREMENTS OF THE CODE ARE MET BASED ON SUCH MODIFIED NUMBER AND THE
OCCUPANT LOAD DOES NOT EXCEED ONE OCCUPANT PER 7 SQUARE FEET. HIGHER
OCCUPANT LOADS ARE USED FOR OPEN OFFICE AREAS WHERE THE ACTUAL SEAT COUNT IS
USED.
SEE PLAN ON G-101 FOR INDIVIDUAL ROOM OCCUPANCY COUNTS.
TOTAL OCCUPANCY COUNTS
ACCESSORY STORAGE AREAS = 32
ASSEMBLY WITHOUT FIXED SEATS, UNCONCENTRATED = 62
BUSINESS AREAS = 80
EXERCISE ROOMS = 37
INDUSTRIAL AREAS = 13
WAREHOUSES = 3
TOTAL OCCUPANT LOAD = 22
1005.3.2 OTHER EGRESS COMPONENTS - EXCEPTION 1
MEANS OF EGRESS CAPACITY FACTOR = 0.15 INCHES
TABLE 1006.2.1 SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY
B, F OCCUPANCY, MAXIMUM OCCUPANT LOAD = 49
MAXIMUM COMMON PATH OF EGRESS TRAVEL DISTANCE WITH SPRINKLER
SYSTEM = 100 FEET
S OCCUPANCY, MAXIMUM OCCUPANT LOAD = 29
MAXIMUM COMMON PATH OF EGRESS TRAVEL DISTANCE WITH SPRINKLER
SYSTEM = 100 FEET
TABLE 1017.2 EXIT ACCESS TRAVEL DISTANCE
B OCCUPANCY, WITH SPRINKLER SYSTEM = 300 FEET
F-1, S-1 OCCUPANCY, WITH SPRINKLER SYSTEM = 250 FEET
S-2 OCCUPANCY, WITH SPRINKLER SYSTEM = 400 FEET
1020.5 DEAD ENDS
EXCEPTION 2, IN GROUP B, F, AND S OCCUPANCIES, WHERE THE BUILDING IS EQUIPPED
THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
SECTION 903.3.1.1, THE LENGTH OF DEAD-END CORRIDORS SHALL NOT EXCEED 50
FEET.
TABLE 2902.1 MINIMUM NUMBER OF PLUMBING FIXTURES
B OCCUPANCY (MOST RESTRICTIVE), 175 OCCUPANTS, SEE G-101
WATER CLOSETS: 1 PER 25 FOR THE FIRST 50 AND 1 PER 50 THEREAFTER
REQUIRED: 6 GENDER NEUTRAL
PROVIDED: 8 GENDER NEUTRAL
LAVATORIES: 1 PER 40 FOR THE FIRST 80 AND 1 PER 80 THEREAFTER
REQUIRED: 4 GENDER NEUTRAL
PROVIDED: 8 GENDER NEUTRAL
DRINKING FOUNTAIN: 1 PER 100
REQUIRED: 2
PROVIDED: 2
SERVICE SINK:
REQUIRED: 1
PROVIDED: 1
2021 NFPA 101 ANALYSIS
OCCUPANCY: BUSINESS PER 6.1.11, INDUSTRIAL PER 6.1.12, STORAGE PER 6.1.13
CONSTRUCTION TYPE: V-000
STORIES: 1
SPRINKLER: PROVIDED
6.1.14.3 MIXED (NONSEPARATED) OCCUPANCIES
6.1.14.3.2 THE BUILDING SHALL COMPLY WITH THE MOST RESTRICTIVE REQUIREMENTS OF
THE OCCUPANCIES INVOLVED.
6.2.2.3 ORDINARY HAZARD CONTENTS. ORDINARY HAZARD CONTENTS SHALL BE
CLASSIFIED AS THOSE THAT ARE LIKELY TO BURN WITH MODERATE RAPIDITY OR TO GIVE
OFF A CONSIDERABLE VOLUME OF SMOKE.
CHAPTER 38, NEW BUSINESS OCCUPANCIES
38.2.5.2.1 COMMON PATH OF TRAVEL SHALL NOT EXCEED 100 FT.
38.2.5.3.1 DEAD-END CORRIDORS SHALL NOT EXCEED 50 FEET.
CHAPTER 40, INDUSTRIAL OCCUPANCIES
40.1.2.1.1 GENERAL INDUSTRIAL OCCUPANCY SHALL INCLUDE THE FOLLOWING:
(1) INDUSTRIAL OCCUPANCIES THAT CONDUCT ORDINARY- AND LOW-HAZARD
INDUSTRIAL OPERATIONS IN BUILDINGS OF CONVENTIONAL DESIGN THAT ARE USABLE
FOR VARIOUS TYPES OF INDUSTRIAL PROCESSES.
TABLE 40.2.6.1 TRAVEL DISTANCE SHALL NOT EXCEED 250 FEET.
CHAPTER 42, STORAGE OCCUPANCIES
42.8.1.2.1 WHERE BOTH PARKING AND REPAIR OPERATIONS ARE CONDUCTED IN THE SAME
BUILDING, THE ENTIRE BUILDING SHALL COMPLY WITH CHAPTER 40, EXCEPT AS MODIFIED
BY 42.8.1.2.2.
1 2 3 4 5
D
C
B
A
Sh ee t T itl e:
D es ig ne d by
D ra w n by
C he ck ed b y:
Ap pr ov ed b y:
R ev is io ns
U ni te d
St at es D ep ar tm en t o f t he In te rio r B ur ea u of L an d
M an ag em en t
BLM Project #
Project #
Date:
ALWAYS THINK SAFETY Sheet of
PHASE
NOT FOR C
ONSTRUCTIO
N
9/
/2
2:
:4
PM
U :\t yl er m or te ns on \D oc um en ts
R ev itL oc al
Te m p\
LB
YD
BL
M
_T O
_a rc h2
4_ ty le rm or te ns on
.rv t
C O
D E
R
EV
IE
W
M O
R
TE
N
SO
N
M
AU
N G
M O
R
TE
N
SO
N
G . T
H O
R
SO
N
N
IF
C
-D
U
AN
E G
R
AV
ES
R
EP
LA
C
EM
EN
T
N
IF
C
-S
G E
C O
N
ST
R U
C
TI
O N
D
EV
EL
O
PM
EN
T
AV
E, B
O
IS
E, ID
140L0624F0171
070117.024
9/30/2025
G-100
0%
C D
N
AT
IO
N
AL
IN
TE
R
AG
EN
C Y
FI
R
E C
EN
TE
R
3 155
0%
C D
De sc rip tio n
Da te
96 SF
OFFICE
Occupant Load : 1
96 SF
OFFICE
Occupant Load : 1
1613 SF
EXERCISE
Occupant Load : 37
96 SF
OFFICE
Occupant Load : 1
4481 SF
SHOP
Occupant Load : 15
699 SF
WOOD SHOP &
DELIVERY
Occupant Load : 8 478 SF
WELDING & DELIVERY
Occupant Load : 5
601 SF
SHOP & SECURE
STORAGE
Occupant Load : 2
100 SF
OFFICE
Occupant Load : 1
240 SF
MECH
Occupant Load : 1
105 SF
COMMS
Occupant Load : 1
174 SF
FIRE PUMP
Occupant Load : 1
61 SF
JAN
Occupant Load : 1
234 SF
BREAK ROOM
Occupant Load : 14
98 SF
OFFICE
Occupant Load : 1
98 SF
OFFICE
Occupant Load : 1
98 SF
OFFICE
Occupant Load : 1
1353 SF
CACHE
Occupant Load : 3
190 SF
SPECIAL
DEVICE
Occupant Load : 2
990 SF
UAV CACHE
Occupant Load : 4
741 SF
FLIGHT SIMULATORS
Occupant Load : 5
98 SF
MAINT.
Occupant Load : 1
64 SF
WELLNESS
Occupant Load : 1
47 SF
FOCUS
Occupant Load : 1
108 SF
OFFICE
Occupant Load : 1
478 SF
LARGE CONFERENCE
Occupant Load : 32
236 SF
MEDIUM CONFERENCE
Occupant Load : 16
108 SF
REFERENCE LIBRARY
Occupant Load : 1
33 SF
SECURE
CACHE
Occupant Load : 1
1533 SF
OPEN SUITE
Occupant Load : 12
2088 SF
OPEN SUITE
Occupant Load : 20
971 SF
OPEN SUITE
Occupant Load : 10
52 SF
ABA TOILET
Occupant Load : 1
52 SF
ABA TOILET
Occupant Load : 1
52 SF
ABA TOILET
Occupant Load : 1
84 SF
ABA SHOWER
Occupant Load : 1
84 SF
ABA SHOWER
Occupant Load : 1
84 SF
ABA SHOWER
Occupant Load : 1
84 SF
ABA SHOWER
Occupant Load : 1
33 SF
SECURE CACHE
Occupant Load : 1
53 SF
ABA TOILET
Occupant Load : 1
40 SF
DUST
Occupant Load : 1
42 SF
AIR
Occupant Load : 1
81 SF
VEST
Occupant Load : 1
42 SF
HALL
Occupant Load : 1
19 SF
SECURE CACHE
Occupant Load : 1
34 SF
COPY
1100A
Occupant Load : 1
87 SF
HALL
Occupant Load : 1
265 SF
HALL
Occupant Load : 2
86 SF
HALL
Occupant Load : 1
232 SF
HALL
Occupant Load : 2
10562 SF
'B' OCC
2628 SF
'S-2' OCC
1313 SF
'F' OCC
1673 SF
'S-1' OCC
4122 SF
'S-2' OCC
EXIT ACCESS TRAVEL DISTANCE = 96'-9"
COMMON PATH OF EGRESS TRAVEL = 73'-0"
EXIT ACCESS TRAVEL DISTANCE = 86'-5"
COMMON PATH OF EGRESS TRAVEL = 72'-2"
EX
IT
A C
C
ES
S
TR
AV
EL
D
IS
TA
N C
E
'-3
EX
IT
A C
C
ES
S
TR
TA
N C
E
'-1
EXIT ACCESS TRAVEL
DISTANCE = 162'-00"
EXIT ACCESS TRAVEL
DISTANCE = 177'-9"
406" 36
6"
36"
3.15"
36"
213.
0.45"
36"4 0.6"
36"8 1.05"
36"
3.15"
36"5 0.75"
36"
1.5"
36"
FEC
FE⚪
FE⚪
FEC△
FEC△
FEC
OCCUPANCY LEGEND
B
F
S-1
S-2
EX
IT
A C
C
ES
S
TR
TA
N C
E
'-1
0"
775 SF
'B' OCC
FE
FINISH FLOOR
TO
H
AN
D
LE
4'
0" M
AX
PORTABLE FIRE
EXTINGUISHER
Name Room_Occupancy_Class
150 SF
Occupant Load : Room_Occupant_Load
EXIT PATH
SPACE AREA
OCCUPANCY TAG:
OCCUPANT LOAD
1 HOUR FIRE BARRIER - SEAL
PERIMETER AND PENETRATIONS PER
DETAILS ON G-104
FIRE EXTINGUISHER CABINET AND
EXTINGUISHER - SEE SPECIFICATIONSFEC
SURFACE MOUNTED FIRE
EXTINGUISHER - SEE SPECIFICATIONS FE
M UL RATED FIRE DOOR AND FRAME WITH
RATING AS INDICATED - SEE SHEET A601
NOTE: SEE ELECTRICAL FOR ILLUMINATED EXIT SIGNS.
CODE PLAN LEGEND
ROOM / AREA NAME
ROOM / AREA NUMBER
1 2 3 4 5
D
C
B
A
Sh ee t T itl e:
D es ig ne d by
D ra w n by
C he ck ed b y:
Ap pr ov ed b y:
R ev is io ns
U ni te d
St at es D ep ar tm en t o f t he In te rio r B ur ea u of L an d
M an ag em en t
BLM Project #
Project #
Date:
ALWAYS THINK SAFETY Sheet of
PHASE
NOT FOR C
ONSTRUCTIO
N
9/
/2
2:
:5
PM
U :\t yl er m or te ns on \D oc um en ts
R ev itL oc al
Te m p\
LB
YD
BL
M
_T O
_a rc h2
4_ ty le rm or te ns on
.rv t
FI
R
ST
F
LO
O
R
LI
FE
S
AF
ET
Y
PL
AN
M O
R
TE
N
SO
N
M
AU
N G
M O
R
TE
N
SO
N
G . T
H O
R
SO
N
N
IF
C
-D
U
AN
E G
R
AV
ES
R
EP
LA
C
EM
EN
T
N
IF
C
-S
G E
C O
N
ST
R U
C
TI
O N
D
EV
EL
O
PM
EN
T
AV
E, B
O
IS
E, ID
140L0624F0171
070117.024
9/30/2025
G-101
0%
C D
N
AT
IO
N
AL
IN
TE
R
AG
EN
C Y
FI
R
E C
EN
TE
R
4 155
0%
C D
A1 FIRST FLOOR CODE PLAN
0 4' 8' 16' 24'
N
De sc rip tio n
96 SF
OFFICE
96 SF
OFFICE
1613 SF
EXERCISE
96 SF
OFFICE
4481 SF
SHOP
699 SF
WOOD SHOP &
DELIVERY
478 SF
WELDING &
DELIVERY
601 SF
SHOP & SECURE
STORAGE
100 SF
OFFICE
240 SF
MECH
105 SF
COMMS
174 SF
FIRE
PUMP
61 SF
JAN
234 SF
BREAK ROOM
98 SF
OFFICE
98 SF
OFFICE
98 SF
OFFICE
1353 SF
CACHE
190 SF
SPECIAL
DEVICE
990 SF
UAV CACHE
741 SF
FLIGHT
SIMULATORS
98 SF
MAINT.
64 SF
WELLNESS
47 SF
FOCUS
108 SF
OFFICE
478 SF
LARGE
CONFERENCE
236 SF
MEDIUM
CONFERENCE
108 SF
REFERENCE
LIBRARY
33 SF
SECURE
CACHE
1533 SF
OPEN SUITE
2088 SF
OPEN SUITE
971 SF
OPEN SUITE
52 SF
ABA
TOILET
52 SF
ABA
TOILET
52 SF
ABA
TOILET
84 SF
ABA SHOWER
84 SF
ABA SHOWER
84 SF
ABA SHOWER
84 SF
ABA SHOWER
33 SF
SECURE CACHE
140553 SF
ABA TOILET
105 SF
ROOF STAIR
40 SF
DUST
42 SF
AIR
81 SF
VEST
42 SF
HALL
19 SF
SECURE CACHE
34 SF
COPY
1100A
87 SF
HALL
265 SF
HALL
86 SF
HALL
232 SF
HALL
SPACE UTILIZATION LEGEND
EXEMPT
OFFICE
TARE
6,975 SF
904 SF
SPACE UTILIZATION CALCULATIONS
PER BLM IM NO 2023-046, NATIONAL INTERAGENCY FIRE CENTER (NIFC)
OFFICE FACILITIES SHALL USE 150 USF/PERSON AS THE STANDARD.
PER THE DOI-AAAP-0049 OFFICE SPACE UTILIZATION STANDARD, PORTIONS
OF THE BUILDING DOI-OWNED BUILDINGS DEDICATED TO OFFICE USE
COVERING RESTROOMS, MEP ROOMS, LOADING DOCS, EXIT STAIRCASES,
ELEVATOR SHAFTS, MEP SHAFTS, WALL THICKNESS, ETC. SHALL BE LIMITED
TO 60 GSF/PERSON
ALLOWABLE VS PROVIDED AREAS:
OFFICE SPACE
ALLOWABLE = 47 EMPLOYEES X 150 USF/P = 7,050 SF
PROVIDED = 6,975 SF
TARE
ALLOWABLE = 47 EMPLOYEES X 150 GSF/P = 1,820 SF
PROVIDED = 1,747 SF
TOTAL OFFICE / ADMIN AREA PROVIDED = 8,722 SF843 SFWALLS
1 2 3 4 5
D
C
B
A
Sh ee t T itl e:
D es ig ne d by
D ra w n by
C he ck ed b y:
Ap pr ov ed b y:
R ev is io ns
U ni te d
St at es D ep ar tm en t o f t he In te rio r B ur ea u of L an d
M an ag em en t
BLM Project #
Project #
Date:
ALWAYS THINK SAFETY Sheet of
PHASE
NOT FOR C
ONSTRUCTIO
N
9/
/2
2:
:2
PM
U :\t yl er m or te ns on \D oc um en ts
R ev itL oc al
Te m p\
LB
YD
BL
M
_T O
_a rc h2
4_ ty le rm or te ns on
.rv t
SP
AC
E U
TI
LI
ZA
TI
O N
P
LA
N
M O
R
TE
N
SO
N
M
AU
N G
M O
R
TE
N
SO
N
G . T
H O
R
SO
N
N
IF
C
-D
U
AN
E G
R
AV
ES
R
EP
LA
C
EM
EN
T
N
IF
C
-S
G E
C O
N
ST
R U
C
TI
O N
D
EV
EL
O
PM
EN
T
AV
E, B
O
IS
E, ID
140L0624F0171
070117.024
9/30/2025
G-103
0%
C D
N
AT
IO
N
AL
IN
TE
R
AG
EN
C Y
FI
R
E C
EN
TE
R
5 155
0%
C D
1 FIRST FLOOR SPACE UTILIZATION PLAN
0 4' 8' 16' 24'
N
De sc rip tio n
SYSTEM NO. C-AJ-3069
F RATING - 1 HR
T RATING - 1/2 HR
A
A
1A
1.
A.
2.
A.
3.
4.
FLOOR OR WALL ASSEMBLY
CONCRETE OR CMU
THROUGH PENETRANTS
CABLES
PACKING MATERIAL
FIRESTOP SEALANT
SECTION A-A
0' - 0 163/256" MIN
SYSTEM NO. WL 3065
F RATING - 1 HR & 2 HR (SEE ITEM 1)
T RATING - 0 HR & 3/4 HR (SEE ITEM 2)
L RATING AT AMBIENT - 15 CFM/SQ FT
L RATING AT 400 F - 8 CFM/SQ FT
A
A
1C
1A 1B
1. WALL ASSEMBLY
A. STUDS
B. BATTS AND BLANKETS
C. GYPSUM BOARD
2. THROUGH PENETRANTS
A. CABLES
3. METALLIC SLEEVE (OPTIONAL)
4. FIRESTOP SEALANT
SECTION A-A
ONE
HOUR
TWO
HOUR
1/2"
BEAD
1 HOUR 2 HOUR
FIRE AND/OR SMOKE
BARRIER - PROTECT ALL
OPENINGS/PENETRATIONS
3" LETTERS W/ 3/8" STROKE
STENCIL WALLS ABOVE CEILING
STENCIL WALLS WITHIN 5' OF ENDS AND AT 25' INTERVALS
0'
/1
" M
IN
SYSTEM NO. WL 1054
(FORMERLY SYSTEM NO. 605)
F RATING - 1 HR & 2 HR (SEE ITEMS 1 & 3)
T RATING - 0 HR
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT
A
A
2 3
1B
1A
SECTION A-A
1. WALL ASSEMBLY
A. STUDS
B. GYPSUM BOARD
2. THROUGH PENETRANTS
A. STEEL PIPE
B. CONDUIT
C. COPPER TUBING
3. FILL WITH FIRESTOP SEALANT
ONE
HOUR
TWO
HOUR
PARALLEL TO
METAL DECK
PERPENDICULAR
TO METAL DECK
1 HR. 2HR.
MINERAL WOOD BATT
INSULATION
COMPRESSED 50% TO
FILL VOID
METAL STUD
5/8" TYPE 'X'
GYP BD
DEFLECTION
TRACK
FIRESTOP
SPRAY - BOTH
SIDES
BOTTOM OF
METAL DECK
TOP OF METAL
DECK
MINERAL
WOOD BATT
INSULATION
COMPRESSED
50% TO FILL
VOID
5/8" TYPE 'X'
GYP BD METAL STUD
5/8" TYPE 'X' GYP BD
DEFLECTION
TRACK
FIRESTOP SPRAY -
BOTH SIDES
METAL DECK
1 HR. 2HR.
1 2 3 4 5
D
C
B
A
Sh ee t T itl e:
D es ig ne d by
D ra w n by
C he ck ed b y:
Ap pr ov ed b y:
R ev is io ns
U ni te d
St at es D ep ar tm en t o f t he In te rio r B ur ea u of L an d
M an ag em en t
BLM Project #
Project #
Date:
ALWAYS THINK SAFETY Sheet of
PHASE
NOT FOR C
ONSTRUCTIO
N
9/
/2
2:
:3
PM
U :\t yl er m or te ns on \D oc um en ts
R ev itL oc al
Te m p\
LB
YD
BL
M
_T O
_a rc h2
4_ ty le rm or te ns on
.rv t
FI
R
E
ST
O
PP
IN
G
D
ET
AI
LS
M O
R
TE
N
SO
N
M
AU
N G
M O
R
TE
N
SO
N
G .T
H O
R
SO
N
N
IF
C
-D
U
AN
E G
R
AV
ES
R
EP
LA
C
EM
EN
T
N
IF
C
-S
G E
C O
N
ST
R U
C
TI
O N
D
EV
EL
O
PM
EN
T
AV
E, B
O
IS
E, ID
140L0624F0171
070117.024
9/30/2025
G-104
0%
C D
N
AT
IO
N
AL
IN
TE
R
AG
EN
C Y
FI
R
E C
EN
TE
R
6 155
0%
C D
0 0.25' 0.5' 1' 1.5'
D1 CABLE BUNDLE THROUGH CMU WALL ASSEMBLY
C1 CABLE BUNDLE THROUGH GYP WALL ASSEMBLY
D2 FIRE BARRIER IDENTIFICATION STENCILS
B1 METALLIC PIPE WALL PENETRATION FIRE STOP
C2 TOP OF RATED WALL JOINT
De sc rip tio n
Da te
0 0.25' 0.5' 1' 1.5'
0 0.25' 0.5' 1' 1.5'
0 0.25' 0.5' 1' 1.5'
0 0.5' 1' 2'
1.
2.
3.
4.
5.
6.
CONTRACTOR IS RESPONSIBLE FOR VERIFYING
INSTALLATION IS IN COMPLIANCE WITH
ACCESSIBILITY STANDARDS.
NOTIFY ARCHITECT IF CONFLICTS ARE
DISCOVERED BETWEEN TYPICAL ACCESSIBILITY
DETAILS AND OTHER DETAILS SHOWN
ELSEWHERE.
INFORMATION ON THIS SHEET IS THE MINIMUM
REQUIRED TO PROVIDE ACCESSIBILITY AND DOES
NOT ADDRESS COMPLIANCE WITH OTHER CODES
OR STANDARDS. ALL INFORMATION SHOWN DOES
NOT NECESSARILY APPLY TO THIS PROJECT.
ALL DIMENSIONS SHOWN ARE TO THE FINISHED
FACE. CONTRACTOR TO MAKE ALLOWANCES FOR
THICKNESS OF FINISHES SPECIFIED.
A COPY OF THE ACCESSIBILITY STANDARDS IS
AVAILABLE FOR REFERENCE AT THE ARCHITECTS
OFFICE UPON REQUEST AS WELL AS ONLINE.
DOOR HARDWARE (& CLOSER) REQUIREMENTS
ARE LISTED IN ANSI A117.1 2017, SECTION 404.
MILLWORK HARDWARE REQUIREMENTS ARE
LISTED IN CHAPTER 9.
GENERAL NOTES
CARPET ON FLOOR SURFACE VERTICAL CHANGES IN LEVEL
OPENINGS IN FLOOR SURFACE
PREDOMINANT DIRECTION OF TRAVEL
LONG DIMENSION
PERPENDICULAR TO
DIRECTION OF
TRAVEL
M
AX1/
4"
1/2"
M
AX1/
2"
CIRCULAR
T-SHAPED - OPTION 3
MIN.
64"
M
IN
MIN.
12"
MIN.
40"
MIN.
12"
M
IN
67" M
IN.
T-SHAPED - OPTION 2
MIN.
64"
M
IN
MIN.
11"
MIN.
42"
MIN.
11"
M
IN
T-SHAPED - OPTION 1
MIN.
68"
M
IN
M
IN
MIN.
16"
MIN.
36"
MIN.
16"
M
IN
8"
8"
M
IN
M
IN
MAX OVERLAP
OF KNEE/TOE
CLEAR FLOOR SPACE (a) FORWARD APPROACH (b) PARALLEL APPROACH
(a) FORWARD APPROACH IN AN ALCOVE (b) PARALLEL APPROACH IN AN ALCOVE
M
IN
MIN.
52"
MIN.
52"
M
IN
M
IN
" X
MIN.
36"
MIN.
60"
M
IN
X
M
IN
MIN.
30"
(a) ELEVATION TOE CLEARANCE (b) PLAN TOE CLEARANCE
(a) ELEVATION KNEE CLEARANCE (b) PLAN KNEE CLEARANCE
9"
MAX.
6"
M
IN
9"
MIN.
11"
M
IN
M
IN
M
IN
25" MAX.
17" - 25"
MIN.
8"
LIMITS OF PROTRUDING OBJECTS
POST MOUNTED PROTRUDING OBJECTS
(a)
(b)
SIGN OR
OBSTRUCTION
4" MAX. 4" MAX.
X
0"
4" MAX. 4" MAX.
X
0"
4" MAX.4" MAX.
X > 12"
" M
AX
4" MAX.
X
X
X
X > 12"
UNLIMITED UNLIMITED
X ≤ 12"
UNLIMITED
(a) OBSTRUCTED
HIGH SIDE REACH
(b) OBSTRUCTED
HIGH FORWARD REACH
UNOBSTRUCTED
SIDE REACH
(b) OBSTRUCTED
HIGH SIDE REACH
UNOBSTRUCTED
FORWARD REACH
(a) OBSTRUCTED
HIGH FORWARD REACH
" M
AX
M
IN
10" MAX.
" M
AX
M
IN
" 48 " M
AX
MAX.
20"
> 20"-25" MAX.
" M
AX
" M
AX
" M
AX
10" MAX. < 10"-24" MAX.
" M
AX
" M
AX
" M
AX
42" MIN. 42" MIN.
180 DEGREE TURN
OPTION 2
" M
AX
43" MIN. 43" MIN.
X < 52"
180 DEGREE TURN
OPTION 3
X < 52"
" M
IN
36" MIN. 36" MIN.
180 DEGREE TURN
OPTION 1
X < 52"
CLEAR WIDTH OF AN ACCESSIBLE ROUTE
* 60"x60" PASSING SPACE EVERY 200 FEET.
MAX.
24"
MIN.
52"
MAX.
24"
M
IN
M
IN
M
IN
M
IN
CLEAR WIDTH AT 90 DEGREE TURN
OPTION 1
" M
IN
" M
IN
4"
40" MIN.
28" MIN.
36" MIN.
" M
IN
CLEAR WIDTH AT 90 DEGREE TURN
OPTION 2
36" MIN.
" M
IN
8" MIN.
CLEAR WIDTH AT 90 DEGREE TURN
OPTION 3
42" MIN.
" M
IN
CLEAR WIDTH AT 90 DEGREE TURN
OPTION 4
44" MIN.
" M
IN
AMBULATORY ACCESSIBLE COMPARTMENT
SIZE OF CLEARANCE
FOR WATER CLOSET
ACCESSIBLE WATER
CLOSET LOCATION
AMBULATORY
ACCESSIBLE WATER
CLOSET LOCATION
SWING-UP GRAB BARS
FOR WATER CLOSET
WALL-HUNG WATER
CLOSET - ADULT
FLOOR-MOUNTED WATER
CLOSET - ADULT
WHEELCHAIR ACCESSIBLE
COMPARTMENT DOORS
WHEELCHAIR ACCESSIBLE COMPARTMENT TOE CLEARANCE
(c) TOE CLEARANCE
PLAN
(a) ELEVATION ADULT (b) ELEVATION
CHILDREN
PARTITION PARTITION
ALTERNATE
DOOR
LOCATION
CL CL
CL
CL
NOTE:
WHERE THE COMBINED
TOTAL WATER CLOSET
COMPARTMENTS AND
URINALS PROVIDED IN A
TOILET ROOM OR BATHING
FACILITY IS SIX OR MORE, AT
LEAST ON AMBULATORY-
ACCESSIBLE WATER CLOSET
COMPARTMENT SHALL BE
PROVIDED IN ADDITION TO
THE WHEELCHAIR-
ACCESSIBLE COMPARTMENT.
" M
IN
60" MIN.
ADULT
16" - 18"
CHILDREN
12" - 18"
17" - 19"
15 3/4" 15 3/4"
MIN.
18"
MIN.
18"
60" MIN.
" M
IN
60" MIN.
" M
IN
4" MAX.
56" MIN.
" M
IN
8" MIN.
M
IN
9"
6" MIN.
M
IN
8" MIN.
8" M
IN
M
IN
" M
IN
17" - 19"
MIN.
35" - 37"
MIN.
32"
M
IN
42" MIN.
54" MIN.
1"
6"
39" - 41"
MAX.
12"
CL
MAX.
6"
MIN.
36"
42" MIN.
6"
SIDE-WALL GRAB BAR FOR
WATER CLOSET
REAR-WALL GRAB BAR FOR
WATER CLOSET
ACCESSIBLE WALL
HUNG URINAL HEIGHT
URINAL CLEAR FLOOR SPACE
M
AX
MIN.
52"
M
IN
MIN.
13 1/2"
1 2 3 4 5
D
C
B
A
Sh ee t T itl e:
D es ig ne d by
D ra w n by
C he ck ed b y:
Ap pr ov ed b y:
R ev is io ns
U ni te d
St at es D ep ar tm en t o f t he In te rio r B ur ea u of L an d
M an ag em en t
BLM Project #
Project #
Date:
ALWAYS THINK SAFETY Sheet of
PHASE
NOT FOR C
ONSTRUCTIO
N
9/
/2
2:
:3
PM
U :\t yl er m or te ns on \D oc um en ts
R ev itL oc al
Te m p\
LB
YD
BL
M
_T O
_a rc h2
4_ ty le rm or te ns on
.rv t
AC
C
ES
SI
BI
LI
TY
D
IA
G
R
AM
S
G . T
H O
R
SO
N
N
IF
C
-D
U
AN
E G
R
AV
ES
R
EP
LA
C
EM
EN
T
N
IF
C
-S
G E
C O
N
ST
R U
C
TI
O N
D
EV
EL
O
PM
EN
T
AV
E, B
O
IS
E, ID
140L0624F0171
070117.024
9/30/2025
G-105
0%
C D
N
AT
IO
N
AL
IN
TE
R
AG
EN
C Y
FI
R
E C
EN
TE
R
7 155
0%
C D
ANSI-2017 302 / 303 CHANGES IN LEVELS
D1
ANSI-2017 304 WHEEL CHAIR TURNING SPACE
D2
ANSI-2017 305 CLEAR FLOOR SPACE
D3
ANSI-2017 306 KNEE & TOE CLEARANCE
D4
ANSI-2017 307 PROTRUDING OBJECTS
B4
ANSI-2017 308 REACH RANGES
B1
ANSI-2017 403 WALKING SURFACES
B2
ANSI-2017 604 WATER CLOSETS AND
TOILET COMPARTMENTS
A1
ANSI-2017 605 URINALS
A4
De sc rip tio n
Da te
0 2' 4' 8' 0 2' 4' 8' 0 2' 4' 8' 0 1' 2' 4'
0 2' 4' 8' 0 2' 4' 8' 0 2' 4' 8'
0 2' 4' 8' 0 2' 4' 8'
LATCH APPROACH, PULL SIDE
FRONT APPROACH, PUSH SIDE
EXISTING BUILDING
HINGE APPROACH, PUSH SIDE
LATCH APPROACH, PUSH SIDE
FOLDING DOORHINGED DOOR SLIDING DOOR
DOORWAY
WITHOUT DOORS
* IF BOTH LATCH & CLOSER ARE PROVIDED
POCKET OR HINGE APPROACH STOP OR LATCH APPROACH
FRONT APPROACH
EXISTING BUILDING
SIDE APPROACH
(b) PUSH SIDE(a) PULL SIDE (c) PUSH SIDE, DOOR PROVIDED w/ BOTH
CLOSER AND LATCH
MANEUVERING CLEARANCE AT TWO DOORS IN A SERIES
(a) (b)
(c) THRESHOLD HEIGHT
MANEUVERING CLEARANCE AT RECESSED DOORS
MANEUVERING CLEARANCE AT DOORWAYS WITHOUT DOORS & MANUAL SLIDING / FOLDING DOORS
MANEUVERING CLEARANCE AT MANUAL SWINGING DOORS
CLEAR WIDTH OF DOORS
* IF BOTH LATCH & CLOSER ARE PROVIDED
* IF CLOSER IS PROVIDED * IF CLOSER IS PROVIDED
32" MIN.
32" MIN. 32" MIN. 36" MIN.
" M
IN
MIN.
12"
" M
IN
" M
IN
MIN.
22"
" M
IN
" M
IN
. MIN.
24"
" M
IN
" M
IN
MIN.
24"
X > 36" X > 36"
" M
IN
" M
IN
" M
IN
MIN.
22"
" M
IN
MIN.
24"
FO
R
W
AR
D A
PP
R
O
AC
H X
8"
, M U
ST
B
E
X
8"
" M
IN
FO
R
W
AR
D A
PP
R
O
AC
H X
8"
M
U
ST
B E
M
IN
60" MIN.
" M
IN
W
ID
TH
D
O O
R
" M
IN
W
ID
TH
D O
O R
60" MIN.
" M
AX
60" MIN.
W
ID
TH
D
O O
R
" M
IN
>2 4"
FRONT APPROACH, PULL SIDE
MIN.
18"
" M
IN
FRONT APPROACH, PUSH SIDE
* IF BOTH LATCH & CLOSER ARE PROVIDED
" M
IN
MIN.
12"
HINGE APPROACH, PULL SIDE
" M
IN
36" MIN.
HINGE APPROACH, PULL SIDE
" M
IN
42" MIN.
FRONT APPROACH
X > 36"
" M
IN
CL
CLCLCL
CL
CL
CLCL
CL
CL
" M
IN
CONTROL
WALL
36"
BACK
WALL
SEAT
WALL
52" MIN.
SIDE
WALL
BACK
WALL
SIDE
WALL M
IN
M
IN
60" MIN.
SIDE
WALL
BACK
WALL
SIDE
WALL
24"-36" 36" MIN.
60" MIN.
SIDE
WALL
CONTROL
WALL
18"
M
AX
4"
BACK
WALL
6" M
AX
6" MAX. 6" MAX.
6" M
AX
6"
6"
6" MAX.
6" M
AX
6" MAX.
SIDE
WALL
BACK WALL
SIDE
WALL
SIDE
WALL
SIDE
WALL
BACK WALL
SIDE
WALL
SIDE
WALL
BACK WALL
SIDE WALL
15" MAX.
" M
AX
" M
IN
27" MAX.
16" MIN.
" M
AX
CONTROL
WALL
FRONT WALL
NOTE: INSIDE FINISHED DIMENSIONS MEASURED AT
THE CENTER POINTS OF OPPOSED SIDES.
NOTE: INSIDE FINISHED DIMENSIONS MEASURED AT
THE CENTER POINTS OF OPPOSED SIDES.
NOTE: INSIDE FINISHED DIMENSIONS MEASURED AT
THE CENTER POINTS OF OPPOSED SIDES.
TRANSFER-TYPE SHOWER
COMPARTMENT SIZE AND CLEARANCE
STANDARD ROLL-IN-TYPE SHOWER
COMPARTMENT SIZE AND CLEARANCE
ALTERNATE ROLL-IN-TYPE SHOWER
COMPARTMENT SIZE AND CLEARANCE
GRAB BARS IN TRANSFER-TYPE
SHOWERS
GRAB BARS IN STANDARD ROLL-IN-TYPE SHOWERS
(a) WITHOUT SEAT (b) WITH SEAT
GRAB BARS IN ALTERNATE
ROLL-IN-TYPE SHOWERS
TRANSFER TYPE
ROLL-IN-TYPE SHOWERS
STANDARD ROLL-IN-TYPE SHOWER
CONTROL AND HANDSHOWER LOCATION
" M
IN
M
IN
INTERNATIONAL SYMBOL OF
ACCESS FOR HEARING LOSS
INTERNATIONAL SYMBOL OF
ACCESSIBILITY
VOLUME CONTROLLED
TELEPHONE
INTERNATIONAL TTY SYMBOL
LATCH SIDE
WOMEN MEN
ELECTRICAL
ROOM
MECHANICAL
ROOM
SPRINKLER
RISER ROOM
" A
.F .F
C L
" A
.F .F
C L
1 2 3 4 5
D
C
B
A
Sh ee t T itl e:
D es ig ne d by
D ra w n by
C he ck ed b y:
Ap pr ov ed b y:
R ev is io ns
U ni te d
St at es D ep ar tm en t o f t he In te rio r B ur ea u of L an d
M an ag em en t
BLM Project #
Project #
Date:
ALWAYS THINK SAFETY Sheet of
PHASE
NOT FOR C
ONSTRUCTIO
N
9/
/2
2:
:3
PM
U :\t yl er m or te ns on \D oc um en ts
R ev itL oc al
Te m p\
LB
YD
BL
M
_T O
_a rc h2
4_ ty le rm or te ns on
.rv t
AC
C
ES
SI
BI
LI
TY
D
IA
G
R
AM
S
M O
R
TE
N
SO
N
M
AU
N G
M O
R
TE
N
SO
N
G . T
H O
R
SO
N
N
IF
C
-D
U
AN
E G
R
AV
ES
R
EP
LA
C
EM
EN
T
N
IF
C
-S
G E
C O
N
ST
R U
C
TI
O N
D
EV
EL
O
PM
EN
T
AV
E, B
O
IS
E, ID
140L0624F0171
070117.024
9/30/2025
G-106
0%
C D
N
AT
IO
N
AL
IN
TE
R
AG
EN
C Y
FI
R
E C
EN
TE
R
8 155
0%
C D
ADA SIGNAGE
B4
ANSI-2017 404 DOORS & DOORWAYS
B1
ANSI-2017 608 SHOWER COMPARTMENTS
C3
ANSI-2017 703 TACTILE & VISUAL
B3
De sc rip tio n
Da te
0 2' 4' 8' 0 2' 4' 8' 0 2' 4' 8'
0 2' 4' 8'
SURVEY CONTROL
POINT #
NORTHING
693057.21
EASTING
2502903.81
ELEVATION
2861.27'
DESCRIPTION
BRC BM WFO SITE LS5082
TRENCH DRAIN
RIM: 2865.8±
INV: 2865.33 4" PVC (W)
CATCH BASIN
RIM: 2864.79
INV: UNKNOWN 4" PVC (E)
INV: 2862.20 12" CMP (S)
INV: 2862.34 12" CMP (W)
CATCH BASIN
RIM: 2864.33
INV: 2861.91 12" CMP (E)
INV: 2862.14 12" CMP (S)
INV: 2862.15 12" CMP (W)
SSMH RIM: 2865.18'
INV: 2854.77' 8" PVC (N)
INV: 2854.69' 8" PVC (W)
INV: 2854.72' 8" PVC (E)
SSMH RIM: 2865.18'
INV: 2853.23' 8" PVC (N)
INV: 2852.96' 8" PVC (W)
INV: 2853.03' 8" PVC (E)
CATCH BASIN
RIM: 2864.13
INV: 2862.29 8" PVC (S)
CATCH BASIN
RIM: 2862.58
ALWAYS THINK SAFETY
Project #
Sh ee t T itl e:
Date:
BLM Project #
U ni te d
St at es D ep ar tm en t o f t he In te rio r B ur ea u of L an d
M an ag em en t
D ra w n by
R ev is io ns
/1
5/
:2
AM
Q
:\L
BY
D Fe de ra l P ro je ct
F ile s\
-A ct ive P ro je ct s\
.0
Du an e G ra ve s Bu ild in g Rp l\0
Dr aw in gs
\C
AD
\0
7.
4V
-1
.d wg
A
B
C
D
2 3 4 5
Ap pr ov ed b y:
C he ck ed b y:
D es ig ne d by
Seal:
De sc rip tio n
Da te
Sheet of 155
09/30/2025
070117.024
140L0624F0171
NI
FC
-D
UA
NE
G
RA
VE
S
RE
PL
AC
EM
EN
T
NI
FC
-S
G E
CO
NS
TR
UC
TI
O
N
NA
TI
O
NA
L
IN
TE
RA
G
EN
CY
F
IR
E
CE
NT
ER
D
EV
EL
O
PM
EN
T
AV
E, B
O
IS
E, ID
0%
C D
- N O
T
FO
R
CO
NS
TR
UC
TI
O N
NO
T
FO
R C
O
NSTR
UCTI
O N
P
HASE
0%
C D
070117.024Project No.
LBYD FEDERAL, LLC
1425 Higham Street Idaho Falls, Idaho 83402 Phone (208) 528-8718
C copyright 2022 These drawings and design intent are the sole property of LBYD FEDERAL, LLC which may not be reproduced without written permission.
20' 40'0
V-101
M . A
N D
ER
SE
N
A.
R
IC
O
B.
P
U
FF
ER
B.
P
U
FF
ER
EX
IS
TI
N
G S
IT
E
C O
N D
IT
IO
N S
HORIZONTAL DATUM IS NAD 83 (NSRS2007), MODIFIED IDAHO
STATE PLANE COORDINATE SYSTEM (WEST ZONE 1103). ANY
BEARINGS SHOWN ARE AT GRID AZIMUTH. ANY DISTANCES
SHOWN REPRESENT GROUND DISTANCES.
MODIFIED IDAHO STATE PLANE COORDINATES,
REPRESENTING GROUND DISTANCES, WERE CALCULATED
BY USING A COMBINED FACTOR OF 1.0001799589 DERIVED
FROM THE ADA COUNTY GIS SYSTEM.
VERTICAL DATUM IS NORTH AMERICAN VERTICAL DATUM
1988 (NAVD88).
NGS BENCH MARK'S - (IDA 80 35, PID # OH0133) AND (T 86, PID
# OH0127) WERE USED TO CONTROL ELEVATION FOR THE
PROJECT.
THE CONTROL POINT FOR THE ENTIRE NIFC CAMPUS IS
SOUTH OF B115, NATIONAL WEATHER SERVICE BUILDING.
GENERAL SHEET NOTES
N
EXISTING SITE CONDITIONSA2
BLDG 300
JACK F. WILSON
BUILDING 415
MAINTENANCE
BUILDING 410A
INFORMATION SYSTEMS
TRASH
ENCLOSURE
RADIO
SHACK
GUARD
SHACK
CABANA
EXISTING TRANSFORMER ON
LARGE CONCRETE PAD AND
SURROUNDED BY BRICK WALL
Sh ee t T itl e:
Date:
BLM Project #
U ni te d
St at es D ep ar tm en t o f t he In te rio r B ur ea u of L an d
M an ag em en t
D ra w n by
R ev is io ns
/1
5/
:2
AM
Q
:\L
BY
D Fe de ra l P ro je ct
F ile s\
-A ct ive P ro je ct s\
.0
Du an e G ra ve s Bu ild in g Rp l\0
Dr aw in gs
\C
AD
\0
7.
4C
-0
.d wg
A
B
C
D
2 3 4 5
Ap pr ov ed b y:
C he ck ed b y:
D es ig ne d by
Seal:
De sc rip tio n
Da te
Sheet of 155
09/30/2025
070117.024
140L0624F0171
NI
FC
-D
UA
NE
G
RA
VE
S
RE
PL
AC
EM
EN
T
NI
FC
-S
G E
CO
NS
TR
UC
TI
O
N
NA
TI
O
NA
L
IN
TE
RA
G
EN
CY
F
IR
E
CE
NT
ER
D
EV
EL
O
PM
EN
T
AV
E, B
O
IS
E, ID
0%
C D
- N O
T
FO
R
CO
NS
TR
UC
TI
O N
NO
T
FO
R C
O
NSTR
UCTI
O N
P
HASE
0%
C D
070117.024Project No.
LBYD FEDERAL, LLC
1425 Higham Street Idaho Falls, Idaho 83402 Phone (208) 528-8718
C copyright 2022 These drawings and design intent are the sole property of LBYD FEDERAL, LLC which may not be reproduced without written permission.
C-001
M . A
N D
ER
SE
N
A.
R
IC
O
B.
P
U
FF
ER
B.
P
U
FF
ER
C
IV
IL
L
EG
EN
D A
N D
AB
BR
EV
IA
TI
O
N S
CONTROL POINT LOCATION
SS
W
FW
SANITARY SEWER
WATERMAIN
FIRE WATER
X CHAIN LINK FENCE
SD STORM DRAIN
4240 MAJOR CONTOURS
MINOR CONTOURS
JUNCTION BOX
GAS METER
SANITARY SEWER MANHOLE
SANITARY SEWER CLEANOUT
STORM DRAIN MANHOLE
TRANSFORMER
CATCH BASIN
LIGHT POLE
ELECTRICAL POWER POLE
FIRE HYDRANT
YARD HYDRANT
WATER METER
WATER VALVE
FIRE HYDRANT
BOLLARD
TREE
DOMESTIC WATER METER
ELECTRICAL METER
COMM MANHOLE
COMM PEDESTAL
UTILITY VAULT
PK NAIL
SURVEY MONUMENT
SIGN
WATER MANHOLE
ASPHALT 1" MILL AND OVERLAY
ASPHALT PAVEMENT
CONCRETE SIDEWALK
RUNNING PATH
TURF
CONCRETE PAVEMENT
BUILDING
NUMBER OF PARKING SPACES
LANDSCAPING
PROPOSEDEXISTING
SS
W
FW
X
SD
DY
H
OHP OVERHEAD POWEROHP
PS PRESSURE SEWER LINEPS
UGP UNDERGROUND POWERUGP
TC TELECOMMUNICATIONTC
WV
CO
DEMOLISH EXISTING FEATURES
LIMITS OF CONSTRUCTION
Ø DIAMETER
AB AGGREGATE BASE
ABDN ABANDONED
ABA ARCHITECTURAL BARRIERS ACT
AC ACRE, ASPHALT CONCRETE
ACP ASBESTOS CEMENT PIPE
ACM ASBESTOS CONTAINING MATERIAL
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
ALGN ALIGNMENT
ARV AIR RELEASE VALVE
ASB AGGREGATE SUBBASE
ASPH ASPHALT
BC BEGIN CURVE
BEG BEGIN
BFP BACK FLOW PREVENTER
BLDC BUILDING CORNER
BLDG BUILDING
BMP BEST MANAGEMENT PRACTICES
BOD BOTTOM OF DOCK
BOL BOLLARD
BSW BACK OF SIDEWALK
BVC BEGIN VERTICAL CURVE
BW FINISHED GRADE AT BOTTOM OF WALL
C CONCRETE OR CIVIL
CB CATCH BASIN
C&G CURB AND GUTTER
CG&S/W CURB, GUTTER & SIDEWALK
CI CAST IRON OR CURB INLET
CIP CAST IRON PIPE
CL CENTER LINE
CLR CLEAR
CMN COMMUNICATION
CMP CORRUGATED METAL PIPE
CO CLEAN OUT
CONC CONCRETE
CONST CONSTRUCTION OR CONSTRUCT
CONF CONFORM TO EXISTING
CR CONDENSATE RETURN
CU CUBIC
CY CUBIC YARD
D= DELTA (CURVE)
DCDA DOUBLE CHECK DETECTOR ASSEMBLY
DEMO DEMOLISH
DEPT DEPARTMENT
DET DETAIL
DI DROP INLET, DUCTILE IRON
DIA DIAMETER
DIP DUCTILE IRON PIPE
DOM DOMESTIC
DW DOMESTIC WATER
DWG DRAWING
E EASTING COORDINATE, ELECTRICAL
EC END CURVE
EG EXISTING GRADE
EL, ELEV ELEVATION
ELEC ELECTRICAL
EP EDGE OF PAVEMENT
EVA EMERGENCY VEHICLE ACCESS
EX (E) EXISTING
(F) FUTURE
FA FIRE ALARM
F/C, FC FACE OF CURB
FD FOUND
FDC FIRE DEPARTMENT CONNECTION
FF, FFE FINISH FLOOR ELEVATION
FG FINISH GRADE
FH FIRE HYDRANT
FL FLOW LINE, FLANGE
FOUND FOUNDATION
FS FINISHED SURFACE
FT FOOT, FEET
FW FIRE WATER
G GAS, GROUND ELEVATION
GB GRADE BREAK
GCS GROUND CONTROL STATION
GDT GROUND DATA TERMINAL
GI GALVANIZED IRON
GI GREASE INTERCEPTOR
GRD, G GROUND
GV GATE VALVE
HC HANDICAP
HCR HANDICAP ACCESSIBLE RAMP
HMA HOT MIX ASPHALT
HORIZ HORIZONTAL
HT HEIGHT
HP HIGH POINT
INV INVERT
INST INSTALL
IRR IRRIGATION
JP JOINT POLE
JT JOINT TRENCH
L LEFT
L= LENGTH (CURVE)
LF LINEAR FEET
LAT LATERAL
LIP LIP OF GUTTER
LP LIGHT POLE, LOW POINT
LPFH FIRE HYDRANT
LS LANDSCAPE
LSA LANDSCAPE ARCHITECT
MA MEDICAL AIR
MAX MAXIMUM
MEP MECHANICAL/ELECTRICAL/PLUMBING
MF MEDIA FILTER
MH MANHOLE
MIN MINIMUM
MPVC MIDPOINT OF VERTICAL CURVE
MON MONUMENT
N NORTHING COORDINATE
(N) NEW
NIC NOT IN CONTRACT
NO NUMBER
NTS NOT TO SCALE
OHE OVERHEAD ELECTRIC
O.R. OFFICIAL RECORDS
(P) PROPOSED
PA PAVEMENT ELEVATION
PB PULL BOX
PCC POINT OF COMPOUND CURVATURE
PE PLAIN END
PED PEDESTRIAN
PERF PERFORATED
PH POTHOLE
PID POINT ID
PIV POST INDICATOR VALVE
PLP PROPERTY LINE
PM PARKING METER
PMH POWER MANHOLE
POC POINT ON CURVE
POI POINT OF INTERSECTION
PP POWER POLE
PRC POINT OF REVERSE CURVATURE
PRUE PRIVATE UTILITY EASEMENT
PT POINT OF TANGENCY
PUE PUBLIC UTILITY EASEMENT
PVC POLYVINYL CHLORIDE PIPE
R RIGHT
R= RADIUS (CURVE)
RC RELATIVE COMPACTION
RCP REINFORCED CONCRETE PIPE
RIM RIM ELEVATION
RJ RESTRAINED JOINT
RP RADIUS POINT
RPBFP REDUCED PRESSURE BACKFLOW
PREVENTER
RPPA REDUCED PRESSURE PRINCIPLE
ASSEMBLY
RSC RECEIVING AND SUPPORT CENTER
R/W, ROW RIGHT OF WAY
S SOUTH, SLOPE
SB SEDIMENT BASIN
SD STORM DRAIN
SDCB STORM DRAIN CATCH BASIN
SDI STORM DRAIN INLET
SDMH STORM DRAIN MANHOLE
SDCO STORM DRAIN CLEANOUT
SF SILT FENCE
SG SUBGRADE
SHLDR SHOULDER
SHT SHEET
SL STREETLIGHT
SMH SIGNAL MANHOLE
SS SANITARY SEWER
SSCO SANITARY SEWER CLEANOUT
SSFM SANITARY SEWER FORCE MAIN
SSMH SANITARY SEWER MANHOLE
SSPS SANITARY SEWER PUMP STATION
STA STATION
STD STANDARD
S/W SIDEWALK
T TELEPHONE
TC TOP OF CURB
TD TRENCH DRAIN
TEL TELEPHONE
TEMP TEMPORARY
TFC TOP FACE OF CURB
TG TOP OF GRATE ELEVATION
THK THICK
TOD TOP OF DOCK
TOE TOE OF SLOPE
TRC TOP OF ROLLED CURB
TW, TOW TOP OF WALL
TS TOP OF SLAB
TYP TYPICAL
U.N.O UNLESS NOTED OTHERWISE
U/G UNDERGROUND
VC VERTICAL CURVE
W WEST, WATER
WM WATER METER
WV WATER VALVE
WWF WELDED WIRE FABRIC
W/ WITH
YDS YARDS
- ABBREVIATIONS -
CIVIL LEGEND (NOTE: NOT ALL SYMBOLS OR ABBREVIATIONS SHOWN ARE USED ON THESE DRAWINGS)
- GENERAL SYMBOLS -
SYMBOL DESCRIPTION
APPROXIMATE LIMITS OF
PROPOSED SITE IMPROVEMENTS
A1 C-101
SECTION
IDENTIFICATION
SHEET
IDENTIFICATION
A B-101
SECTION
IDENTIFICATION
SHEET
IDENTIFICATION
SECTION INDICATOR
DETAIL INDICATOR
[VIEW TITLE]A2 DRAWING AREA TITLE
NORTH ARROW
VIEW IDENTIFICATION
TOP OF CURB
BOTTOM OF CURB SPOT ELEVATION AT CURB
1.6% PROPOSED GRADE %
100 SPOT ELEVATION
M.E.± 105 SPOT ELEVATION TO
MATCH EXISTING
SYMBOL
- GRAPHIC SYMBOLS -
DESCRIPTION
N
LIGHTING CONDUIT BELOW GRADELTP
HANDHOLE
G NATURAL GAS
EP EDGE OF PAVEMENT
EG EDGE OF GRAVEL
PIRR IRRIGATION
IRRIGATION VAULT
PIRR
IRRIGATION HEAD
GRAVITY IRRIGATION PIPEGIRR
Sh ee t T itl e:
Date:
BLM Project #
U ni te d
St at es D ep ar tm en t o f t he In te rio r B ur ea u of L an d
M an ag em en t
D ra w n by
R ev is io ns
/1
5/
:2
AM
Q
:\L
BY
D Fe de ra l P ro je ct
F ile s\
-A ct ive P ro je ct s\
.0
Du an e G ra ve s Bu ild in g Rp l\0
Dr aw in gs
\C
AD
\0
7.
4C
-0
.d wg
A
B
C
D
2 3 4 5
Ap pr ov ed b y:
C he ck ed b y:
D es ig ne d by
Seal:
De sc rip tio n
Da te
Sheet of 155
09/30/2025
070117.024
140L0624F0171
NI
FC
-D
UA
NE
G
RA
VE
S
RE
PL
AC
EM
EN
T
NI
FC
-S
G E
CO
NS
TR
UC
TI
O
N
NA
TI
O
NA
L
IN
TE
RA
G
EN
CY
F
IR
E
CE
NT
ER
D
EV
EL
O
PM
EN
T
AV
E, B
O
IS
E, ID
0%
C D
- N O
T
FO
R
CO
NS
TR
UC
TI
O N
NO
T
FO
R C
O
NSTR
UCTI
O N
P
HASE
0%
C D
070117.024Project No.
LBYD FEDERAL, LLC
1425 Higham Street Idaho Falls, Idaho 83402 Phone (208) 528-8718
C copyright 2022 These drawings and design intent are the sole property of LBYD FEDERAL, LLC which may not be reproduced without written permission.
C-002
M . A
N D
ER
SE
N
A.
R
IC
O
B.
P
U
FF
ER
B.
P
U
FF
ER
C
IV
IL
N
O
TE
S
GENERAL NOTES
1. THE LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING UTILITIES BEFORE COMMENCING WORK. THE
CONTRACTOR AGREES TO BE FULLY RESPONSIBLE FOR ANY AND ALL DAMAGES WHICH MIGHT BE
OCCASIONED BY FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UNDERGROUND OR
OVERHEAD UTILITIES. CALL DIG-LINE AT 811 A MINIMUM OF 48 HOURS PRIOR TO EXCAVATING TO REQUEST LOCATIONS OF UNDERGROUND UTILITIES. UTILITY LOCATION AND VERIFICATION SHALL BE AN ONGOING PROCESS. WHERE CONFLICTING UTILITIES MAY BE PRESENT, THE CONTRACTOR
SHALL VERIFY LOCATION AHEAD OF TRENCHING OPERATIONS, AND IMMEDIATELY NOTIFY THE
GOVERNMENT OF ANY POTENTIAL CONFLICTS.
2. CONTRACTOR SHALL NOTIFY THE GOVERNMENT WHEN MATERIALS ARE ON SITE OR INSPECTION
OF THE WORK IS REQUIRED. NO WORK MAY BEGIN ON ANY PROJECT WITHOUT TWENTY-FOUR
(24) HOUR PRIOR NOTICE.
3. ALL MATERIAL FURNISHED ON OR FOR THE PROJECT MUST MEET THE MINIMUM REQUIREMENTS
OF THE GOVERNMENT.
4. WORK SUBJECT TO APPROVAL BY THE GOVERNMENT MUST BE APPROVED PRIOR TO (A)
BACKFILLING; (B) PLACING OF AGGREGATE BASE; AND (C) PLACING OF CONCRETE.
5. RETAIN AND PROTECT ALL FEATURES NOT DESIGNATED TO BE MODIFIED OR CONSTRUCTED.
6. ALL EXISTING FEATURES WHICH ARE BEING JOINED OR MATCHED IN CONNECTION WITH THIS
PROJECT, SHALL BE JOINED OR MATCHED IN A MANNER SATISFACTORY TO THE GOVERNMENT
INCLUDING NECESSARY SAW CUTTING, REMOVAL, REPLACEMENT, AND CAPPING.
7. SITE SHALL BE CLEANED AND RESTORED TO ORIGINAL OR BETTER CONDITION UPON
COMPLETION OF WORK.
8. THE CONTRACTOR SHALL REPAVE OR RE-GRAVEL TO EXISTING GRADE ANY EXISTING PAVED OR
GRAVELED STREETS DISTURBED DURING CONSTRUCTION.
9. CONTRACTOR SHALL ENSURE THAT ALL SIDEWALKS, RAMPS, ACCESSIBLE PARKING SPACES,
AND OTHER PEDESTRIAN ACCESS ITEMS COMPLY WITH THE ARCHITECTURAL BARRIERS ACT
(ABA) REQUIREMENTS.
10. TEMPORARY SHORING, BRACING, FORMING, SCAFFOLDING, ETC. ARE THE SOLE RESPONSIBILITY
OF THE CONTRACTOR AND HAVE NOT BEEN CONSIDERED BY THE DESIGNER.
11. ANY CHANGES OR DEVIATIONS MADE TO THE CIVIL PLANS, DETAILS, AND SPECIFICATIONS MUST
HAVE APPROVAL FROM THE GOVERNMENT IN WRITING PRIOR TO CONSTRUCTION.
EROSION AND SEDIMENT CONTROL NOTES
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL LOCAL, STATE, AND FEDERAL
PERMITS REQUIRED FOR STORM WATER MANAGEMENT AS A RESULT OF CONSTRUCTION
ACTIVITIES. THE CONTRACTOR SHALL PREPARE A STORM WATER POLLUTION PREVENTION PLAN
(SWPPP) FOR REVIEW BY THE GOVERNMENT. THE CONTRACTOR SHALL OBTAIN A COPY OF THE
U.S. ENVIRONMENTAL PROTECTION AGENCY'S (EPA) NATIONAL POLLUTANT DISCHARGE
ELIMINATION SYSTEM (NPDES) CONSTRUCTION GENERAL PERMIT (CGP) FOR STORM WATER
DISCHARGES ASSOCIATED WITH CONSTRUCTION ACTIVITY AND SUBMIT AND FILE A NOTICE OF
INTENT (NOI) AND NOTICE OF TERMINATION (NOT) AS REQUIRED BY THE EPA OR WITH THE LOCAL
IDAHO DEPARTMENT OF ENVIRONMENTAL QUALITY. THE CGP DOES NOT RELIEVE THE
CONTRACTOR FROM COMPLIANCE WITH OTHER REGULATIONS OR CONTRACT REQUIREMENTS
REGARDING STORM WATER POLLUTION PREVENTION INCLUDING BUT NOT LIMITED TO
PROTECTION OF SURFACE WATERS, PREVENTION OF TRACKED SOILS TO ADJACENT STREETS,
FUEL CONTAINMENT, SPILL CONTROL, ETC.
2. THE CONTRACTOR SHALL TAKE ALL NECESSARY ACTION, INCLUDING CONSTRUCTION AND
MAINTENANCE OF A VEHICLE TRACKING CONTROL FACILITY AT EACH CONSTRUCTION ENTRANCE, TO MINIMIZE DEPOSITING AND TRACKING OF MUD, DIRT, SAND, GRAVEL, ROCK, OR DEBRIS ON TO
THE PUBLIC RIGHT-OF-WAY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY CLEAN UP OF
THE PUBLIC RIGHTS-OF-WAY OR ADJACENT PRIVATE PROPERTY FROM ANY TRACKING OR
DEPOSITING OF MUD, DIRT, SAND, GRAVEL, ROCK, OR DEBRIS.
3. NO DEBRIS, DIRT, AGGREGATE, OR EXCAVATED MATERIALS OR CONSTRUCTION SUPPLIES, SHALL
BE PLACED ON THE PUBLIC RIGHT-OF-WAY UNLESS PERMITTED BY THE GOVERNMENT AGENCY,
OR OTHER CONTROLLING ENTITY. IN ADDITION, PUBLIC APPROACHES SHALL NOT BE REMOVED, BLOCKED, OR OTHERWISE RENDERED UNUSABLE BY CONSTRUCTION ACTIVITY, EQUIPMENT OR
MATERIALS, OR PORTABLE TOILETS, UNLESS A SAFE, USABLE ALTERNATE WALKWAY, WHICH
MEETS THE DESIGN STANDARDS, IS PLACED ON THE SAME SIDE OF THE RIGHT-OF-WAY BY THE
CONTRACTOR.
4. STAGING, PARKING AND SOIL STOCKPILE AREAS SHALL BE SHOWN ON THE SWPPP LISTED IN
EROSION AND SEDIMENT CONTROL NOTE 1. NO SOILS OR AGGREGATE STOCKPILES ARE
PERMITTED ON UNDISTURBED PORTIONS OF THE PROPERTY WITHOUT PRIOR APPROVAL OF THE
GOVERNMENT AND UNLESS EROSION CONTROL MEASURES ARE IN PLACE TO PREVENT
DEPOSITION OF THE OFF-SITE SEDIMENT.
5. CONTRACTOR SHALL MINIMIZE DISTURBANCE TO EXISTING NON-PAVED AREA CAUSED BY
VEHICLES AND EQUIPMENT. ALL DAMAGE TO EXISTING VEGETATION SHALL BE RESTORED TO THE
CONDITION THAT EXISTED PRIOR TO CONSTRUCTION OR BETTER.
6. CONTRACTOR SHALL COMPLY WITH ALL PERTINENT GOVERNMENT, FEDERAL, STATE AND LOCAL
AGENCIES WHICH HAVE JURISDICTION OVER DUST FOR THE CONTROL PROCEDURES AND
ADDITIVES USED IN DUST ABATEMENT. THE CONTRACTOR SHALL PREPARE AND MAINTAIN A DUST
CONTROL PLAN.
SURVEY NOTES:
1. EXISTING FEATURES: EXISTING ROADWAYS, UTILITIES, STRUCTURES, AND OTHER FEATURES ARE
SHOWN USING SURVEY PROVIDED BY JUB ENGINEERS, INC. AS PART OF THE TITLE I SERVICES
SURVEYED INFORMATION AND THE LOCATION, DEPTH AND ACCURACY OF SURFICIAL
INFORMATION SHALL BE FIELD VERIFIED. ADDITIONAL UNDERGROUND FEATURES MAY EXIST.
2. VERIFICATION: APPROXIMATE SIZE, CONDITION, LOCATION AND DEPTH OF EXISTING FEATURES
SHALL BE VERIFIED PRIOR TO CONSTRUCTION.
3. COORDINATES AND ELEVATIONS FOR THE PROJECT SITE ARE BASED ON A SITE SPECIFIC
SURVEY.
4. THE CONTRACTOR SHALL FIELD VERIFY AND PROTECT ALL BENCHMARKS AND OTHER
DIMENSIONS AND ELEVATIONS PRIOR TO COMMENCEMENT OF WORK. NOTIFY THE GOVERNMENT
OF ANY CONFLICTS.
CIVIL NOTES:
1. ALL EQUIPMENT SHALL BE CLEANED AND INSPECTED PRIOR TO USE ON THE PROJECT SO AS TO
PREVENT THE TRANSPORT AND SPREAD OF NOXIOUS WEEDS AS WELL AS TO PREVENT SPILLS
OR LEAKS OF EQUIPMENT FLUID.
2. SERVICE AND REFUEL EQUIPMENT IN DESIGNATED AREAS ONLY AS DIRECTED BY THE
GOVERNMENT.
3. CONTRACTOR SHALL NOT DISTURB AREAS OUTSIDE OF THE CONSTRUCTION LIMITS.
DISTURBANCES IN STAGING AREAS SHALL BE KEPT TO A MINIMUM, AND SHALL BE RESTORED TO
EXISTING CONDITIONS AFTER CONSTRUCTION ACTIVITIES.
4. STRIP AND STOCKPILE TOPSOIL/GRAVEL FOR REUSE AFTER COMPLETION OF CONSTRUCTION
ACTIVITIES.
5. CONTACT GOVERNMENT PRIOR TO INITIATION OF CONSTRUCTION ACTIVITIES FOR PLANT
REMOVAL, IF NECESSARY.
6. PROVIDE BEST MANAGEMENT PRACTICES FOR STORMWATER CONTROLS PRIOR TO AND DURING
CONSTRUCTION. THIS PLAN SHALL BE IN ACCORDANCE WITH ADA COUNTY, INCLUDING ALL
REQUIRED PERMITS AND APPROVALS, PRIOR TO CONSTRUCTION.
7. AT COMPLETION OF PROJECT STOCKPILE AREAS SHALL BE REMOVED AND RESTORED TO
EXISTING CONDITION UNLESS SPECIFIED OTHERWISE BY GOVERNMENT.
8. ALL AREAS DISTURBED DURING CONSTRUCTION SHALL BE REHABILITATED TO THE ORIGINAL
CONTOURS AND RESTORED TO THE ORIGINAL CONDITION TO THE GREATEST EXTENT POSSIBLE.
9. AT A MINIMUM, THE MATERIALS USED FOR A PUBLIC WATER SYSTEM MUST MEET IDAPA 58.01.08.
9.1. THE MINIMUM DEPTH OF PIPE COVER MUST BE 42".
9.2. POTABLE AND NON POTABLE UTILITY MAINS, LATERAL OR UNDOCUMENTED CONDUIT MUST
MAINTAIN HORIZONTAL AND VERTICAL SEPARATION REQUIREMENTS, IN ACCORDANCE WITH
THE MINIMUM REQUIREMENTS OUTLINED IN IDAPA 58.01.08.
9.3. OBTAINING APPLICABLE LICENSES, PERMITS, BONDS, OR OTHER REQUIRED ADMINISTRATIVE
REQUIREMENTS, SHALL BE AT THE CONTRACTOR'S EXPENSE.
10. ALL ROADWAYS SHALL BE CONSTRUCTED TO CONFORM WITH THE STATE OR LOCAL AUTHORITY
HAVING JURISDICTION. THIS INCLUDES ALL TESTING AND INSPECTION REQUIREMENTS TO
ENSURE THE ROADWAY WILL BE BUILT AND ACCEPTED BY THE LOCAL MOST AUTHORITY.
11. TRACE WIRE FOR ALL BURIED UTILITY MAINS SHALL BE PROVIDED OR APPROVED EQUAL.
CODE COMPLIANCE:
1. ALL WORK SHALL CONFORM TO THE FOLLOWING:
1.1. IDAPA 58.01.08 IDAHO RULES FOR PUBLIC DRINKING WATER SYSTEMS.
1.2. 2021 IBC (INTERNATIONAL BUILDING CODE).
REINFORCING STEEL NOTES:
1. ALL REINFORCING STEEL SHALL CONFORM TO ASTM A-615 GRADE 60 UNLESS SPECIFICALLY
NOTED OTHERWISE. ASTM A-615 GRADE 40 MAY BE USED FOR #3 BARS AT CONTRACTOR'S
OPTION UNLESS THE GRADE IS SPECIFICALLY NOTED OTHERWISE.
2. REINFORCING STEEL THAT IS TO BE WELDED SHALL CONFORM TO ASTM A-706, UNLESS
SPECIFICALLY NOTED OTHERWISE. OTHER GRADES, IF ALLOWED, SHALL HAVE A MAXIMUM
CARBON EQUIVALENT OF 0.55% PER ANSI/AWS D1.4-98 SECTION 1.3.4.2. WELDING ELECTRODES
SHALL BE LOW - HYDROGEN, AND SHALL BE E90XX FOR GRADE 60 REINFORCING STEEL, AND
E70XX FOR GRADE 40. WIRE MESH SHALL CONFORM TO ASTM A-185.
3. CONCRETE CLEAR COVERAGE TO REINFORCING STEEL SHALL CONFORM TO THE FOLLOWING
MINIMUMS, U.N.O.
A. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 3”
B. CONCRETE EXPOSED TO EARTH OR WEATHER:
1.1. #5 BARS AND SMALLER 1-1/2”
1.2. #6 BARS AND LARGER 2”
C. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND:
1.1. SLABS, WALLS, AND JOISTS
1.1.1. #11 BARS AND SMALLER 3/4”
1.1.2. #14 BARS AND LARGER 1-1/2”
1.2. COLUMNS AND BEAMS 1-1/2”
1.3. SHELLS, FOLDED PLATE MEMBERS:
1.3.1. #5 BARS AND…
This is the start of the file's text. The full file is on GovTribe.