2-Drawings.pdf
PDF 2 MB Posted
- Attached to
- Orangeville Manor - General Upgrades
- Solicitation number
- Not on record
- Issued by
- Columbia County, Pennsylvania
About this file
This is a set of architectural and structural drawings for building upgrades at Orangeville Manor, a property located at 210 Mill Street, Orangeville, PA 17859, prepared by Barry Isett & Associates, Inc. The project, identified as Job 1120724.000, consists of two primary components: the replacement of an existing access sidewalk, steps, and stairs to address damaged material and improve accessibility, and the construction of a new accessible automatic door to an existing building. The drawings, issued for bid on February 11, 2026, include a cover sheet, existing overall plan, enlarged exit plans for front and rear entrances, schedules, notes, and details, as well as foundation plans and specifications. Key project elements include the demolition of existing concrete landings, railings, entrance canopy, stairs, and associated foundations; the installation of new concrete landing and ramp systems with maximum slopes of 1:12 for the ramp and specifications for stair risers ranging from 4 to 7 inches; and the installation of a new hollow metal automatic swing door with sidelite glass. The contractor is required to verify all existing conditions and dimensions prior to commencing work, coordinate with the building owner regarding working hours and site logistics, and comply with the 2018 International Building Code and all applicable local, state, and federal codes. A pre-bid meeting is scheduled for February 17, 2026, at 10:00 AM on site, with sealed bids due February 27, 2026, at 10:00 AM through the PennBid Program.
The project is subject to Davis Bacon wage rates and requires bidders to submit a 10 percent bid bond and a 100 percent performance and payment bond. The contractor bears full responsibility for jobsite safety, construction sequencing, temporary bracing and shoring, and protection of existing finishes and structures. All shop drawings for structural elements, automatic door operators, stairs, railings, and concrete reinforcement must be submitted for engineer review prior to fabrication or installation, with a minimum two-week review period. The design of delegated elements, including metal stairs and railings, requires submission of sealed and stamped drawings and calculations from the contractor's registered engineer. Foundation design is based on a soil bearing capacity of 2,000 psf, and concrete mixes must meet specific exposure classifications and compressive strength requirements. Material and equipment specifications are detailed throughout the drawings, including requirements for non-shrink grout, reinforcing steel, welded wire fabric, and non-slip stair nosing. The contractor is responsible for obtaining all required permits, providing temporary sanitary facilities, securing the site, and coordinating with utility location services prior to excavation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1-Contract Documents and Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Drawings
JOB:
1120724.000
COPYRIGHT 2025
DRAWN:
SCALE:
AS NOTED
DATE:
02/11/2026
P MGR:
APPRD:
CHK
DSGN:
BU
IL
D
IN
G U
PG
R
AD
ES
O R
AN
G
EV
IL
LE
M
AN
O
R
M
IL
L
ST
O
R
AN
G
EV
IL
LE
, P A
R
EV
IS
IO
N S
D
AT
E
BY
SHEET:
Is su ed fo r B id
2/
/2
BUILDING UPGRADES
ORANGEVILLE MANOR
210 MILL STREET
ORANGEVILLE, PA 17859
PROJECT DESCRIPTION:
THIS PROJECT CONSISTS OF:
1. THE REPLACEMENT OF THE EXISTING ACCESS
SIDEWALK, STEP AND STAIRS TO REPLACE DAMAGED
MATERIAL AND INCREASE ACCESSIBILITY.
2. THE CONSTRUCTION OF NEW ACCESSIBLE AUTOMATIC
DOOR TO AN EXISTING BUILDING.
SITE MAP KEY MAP
Barry Isett & Associates, Inc.
Fox Ridge Professional Center
1170 Highway 315, Suite 3 Wilkes-Barre, PA 18702
570-285-8200 Contact: Corey McAndrew
AREA OF WORK
LIST OF DRAWINGS
SHEET SHEET TITLE
CURRENT
REVISION
DATE
CURRENT
REVISION
CS COVER SHEET
GA0.0 EXISTING OVERALL PLAN
GA1.0 ENLARGED EXISTING / DEMOLITION PLAN
GA2.0 ENLARGED EXIT PLANS
GA3.0 SCHEDULES, NOTES, AND DETAILS
S1.0 FOUNDATION PLAN, NOTES, AND DETAILS
S2.0 FOUNDATION NOTES, SCHEDULES AND
DETAILS
APPLICABLE CODES GENERAL NOTES
GENERAL NOTES
1. THE CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIALS UNLESS NOTED OTHER WISE TO COMPLETE THE WORK.
2. ALL WORK WILL BE SUBJECT TO THE APPROVAL OF THE BUILDING OWNER AND PRIME DESIGN PROFESSIONAL.
3. ALL WORK IS TO BE COORDINATED WITH THE BUILDING OWNER, INCLUDING WORKING HOURS, DUMPSTER LOCATIONS, LOADING AREAS, ETC.
4. ALL WORK SHOWN ON THESE DRAWINGS HAS BEEN DESIGNED IN ACCORDANCE WITH THE REQUIREMENTS OF THE "2018 INTERNATIONAL BUILDING CODE"
5. CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE LOCAL, STATE AND FEDERAL CODES AND ORDINANCES.
6. MECHANICAL AND ELECTRICAL SYSTEMS SHALL COMPLY WITH ALL APPLICABLE LOCAL, STATE AND FEDERAL CODES AND ORDINANCES.
7. CONTRACTOR SHALL BE COMPLETELY FAMILIARIZED WITH ALL CONTRACT DOCUMENTS. BY SUBMITTING A COST PROPOSAL TO COMPLETE THE WORK, THE CONTRACTOR REPRESENTS THAT THEY HAVE VISITED THE SITE AND ARE FAMILIAR WITH THE
CONDITIONS UNDER WHICH THE WORK WILL BE PERFORMED.
8. WORK NOT INDICATED ON A PART OF THE DRAWINGS BUT REASONABLY IMPLIED TO BE SIMILAR TO THAT SHOWN AT CORRESPONDING PLACES SHALL BE REPEATED.
9. JOBSITE SAFETY AND CONSTRUCTION PROCEDURES ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR. REVIEW OF THE CONSTRUCTION BY THE DESIGN PROFESSIONAL IS FOR GENERAL CONFORMANCE WITH DESIGN ASPECTS ONLY, NOT TO REVIEW THE CONTRACTOR'S PROVISIONS FOR JOBSITE SAFETY. LACK OF COMMENT ON THE PART OF THE DESIGN PROFESSIONAL WITH REGARD TO JOBSITE SAFETY IS NOT TO BE INTERPRETED AS APPROVAL OF JOBSITE SAFETY PRACTICES.
10. THE CONTRACTOR SHALL COORDINATE OPENINGS, SLEEVES, CONCRETE HOUSEKEEPING PADS, INSERTS, AND DEPRESSIONS SHOWN ON THE PRIME PROFESSIONAL, MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTION DRAWINGS.
11. ALL COSTS OF INVESTIGATION AND/OR REDESIGN DUE TO CONTRACTOR IMPROPER INSTALLATION OF ELEMENTS OR OTHER ITEMS NOT IN CONFORMANCE WITH THE CONTRACT DOCUMENTS SHALL BE AT THE CONTRACTOR'S EXPENSE.
12. ALL DRAWINGS SHALL BE USED IN CONJUNCTION WITH EACH OTHER. IF THERE IS A DISCREPANCY BETWEEN DRAWINGS AND SPECIFICATIONS, IT IS THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE PRIME PROFESSIONAL PRIOR TO PERFORMING THE WORK.
IN THE CASE OF A CONFLICT, THE MORE STRINGENT IN COST OR QUALITY SHALL APPLY.
13. THE CONTRACTOR SHALL VERIFY ALL EXISTING BUILDING INFORMATION SHOWN (DIMENSIONS, EXISTING CONDITIONS, ELEVATIONS, ETC.) AND NOTIFY THE PRIME PROFESSIONAL OF ANY DISCREPANCIES PRIOR TO FABRICATION OR INSTALLATION OF ANY COMPONENTS. FAILURE TO NOTIFY PRIME PROFESSIONAL OF UNSATISFACTORY CONDITIONS CONSTITUTES ACCEPTANCE OF UNSATISFACTORY CONDITIONS.
14. IF THE EXISTING FIELD CONDITIONS DO NOT PERMIT THE INSTALLATION OF THE WORK IN ACCORDANCE WITH THE DETAILS SHOWN, THE CONTRACTOR SHALL NOTIFY THE PRIME PROFESSIONAL IMMEDIATELY AND PROVIDE A SKETCH OF THE CONDITION WITH THE PROPOSED MODIFICATION OF THE DETAILS SHOWN ON THE CONTRACT DOCUMENTS. DO NOT COMMENCE WORK UNTIL CONDITION IS RESOLVED AND MODIFICATION IS APPROVED BY THE PRIME PROFESSIONAL.
15. SHOP DRAWINGS FOR ALL MATERIALS ARE TO BE SUBMITTED TO THE PRIME DESIGN PROFESSIONAL FOR REVIEW PRIOR TO THE START OF FABRICATION OR COMMENCEMENT OF WORK. REVIEW PERIOD SHALL BE A MINIMUM OF TWO (2) WEEKS.
16. REPRODUCTION OF ANY PORTION OF THE CONTRACT DRAWINGS FOR RESUBMITTAL AS SHOP DRAWINGS IS PROHIBITED. SHOP DRAWINGS PRODUCED IN SUCH A MANNER WILL BE REJECTED AND RETURNED.
17. SHOP DRAWINGS SUBMITTED FOR REVIEW SHALL CONSIST OF THREE (3) SETS OF PRINTS. ONLY ONE (1) MARKED UP SET WITH THE COMMENTS WILL BE RETURNED TO THE CONTRACTOR.
18. SHOP DRAWINGS SHALL BEAR THE CONTRACTOR'S STAMP OF APPROVAL WHICH SHALL CONSTITUTE CERTIFICATION THAT THE CONTRACTOR HAS VERIFIED ALL CONSTRUCTION CRITERIA, MATERIALS, AND SIMILAR DATA AND HAS CHECKED EACH DRAWING FOR
COMPLETENESS, COORDINATION, AND COMPLIANCE WITH THE CONTRACT DOCUMENTS.
19. THE DRAWINGS HAVE BEEN PRODUCED ENTIRELY ON A CADD SYSTEM. ANY OTHER LETTERING, LINES OR SYMBOLS, OTHER THAN PROFESSIONAL STAMPS AND SIGNATURES, HAVE BEEN MADE WITHOUT THE AUTHORIZATION OF BIA AND ARE NOT VALID.
20. ALL MATERIALS SHALL BE STORED TO PROTECT THEM FROM EXPOSURE TO THE ELEMENTS, IN ACCORDANCE WITH MANUFACTURERS WRITTEN INSTRUCTIONS.
21. DEBRIS, WASTE OR OTHER UNUSED CONSTRUCTION MATERIALS SHALL NOT BE PERMITTED TO ACCUMULATE. EACH TRADE IS RESPONSIBLE FOR THE REMOVAL AND DISPOSAL OF THEIR RESPECTIVE DEBRIS. LOCATION OF DUMPSTERS IS TO BE APPROVED BY
THE BUILDING OWNER.
22. UPON COMPLETION OF THE WORK, THE GENERAL CONTRACTOR IS RESPONSIBLE FOR LEAVING THE SITE IN "BROOM-CLEAN" CONDITION.
23. GENERAL CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF ALL FINISHES TO REMAIN, INCLUDING COMMON CORRIDORS, LOBBIES, STAIRS, LANDSCAPING, ELEVATOR CABS, ETC.
24. GENERAL CONTRACTOR SHALL PROVIDE AN ESTIMATED CONSTRUCTION WORK SCHEDULE. SCHEDULE SHALL BE UPDATED AS REQUIRED DUE TO CHANGES IN THE PROGRESS OF WORK AND UPON THE REQUEST OF THE BUILDING OWNER AND/OR PRIME DESIGN
PROFESSIONAL.
25. CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE THE FOLLOWING SANITARY FACILITIES: TEMPORARY TOILETS, WASH FACILITIES, AND DRINKING WATER FOR USE OF CONSTRUCTION PERSONNEL. COMPLY WITH AUTHORITIES HAVING JURISDICTION FOR TYPE, NUMBER, LOCATION, OPERATION, AND MAINTENANCE OF FIXTURES AND FACILITIES.
26. CONTRACTOR SHALL BE RESPONSIBLE TO SECURE ALL PERMITS REQUIRED BY AUTHORITIES HAVING JURISDICTION.
THIS PROJECT IS DESIGNED AND SHALL BE BUILT TO COMPLY
WITH THE FOLLOWING CODES LISTED BELOW:
INTERNATIONAL BUILDING CODE 2018
CHAPTER 11 & APPENDIX E 2018
INTERNATIONAL EXISTING BUILDING CODE 2018
ALTERATION - LEVEL 2
INTERNATIONAL MECHANICAL CODE 2018
INTERNATIONAL PLUMBING CODE 2018
NATIONAL FIRE PREVENTION CODE 2016/2017/2018
NATIONAL ELECTRIC CODE 2017
ICC / ANSI A 117.1-7 2017
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH
ALL APPLICABLE CODES OF THE AUTHORITY HAVING JURISDICTION
AND MUST NOTIFY THE PROJECT ENGINEER OF ANY
DISCREPANCIES INDICATED BY THESE DOCUMENTS FOUND PRIOR
TO OR DURING CONSTRUCTION. NOTIFICATION MUST BE GIVEN TO
THE ENGINEER PRIOR TO PROCEEDING WITH CONSTRUCTION.
A.F.F. Above Finish Floor BCX Bottom Chord Extension B.O.F. Bottom of Footing B.S. Brick Shelf Elevation (plans) B.S. Both Sides (sections) CANT. Cantilever CJ Control Joints CL Center Line CMU Concrete Masonry Units CONT. Continuous DIA. Diameter DBA Deformed Bar Anchor E.E. Each End E.F. Each Face E.S. Each Side E.W. Each Way EXIST Existing F.F. Finish Floor F.S. Flat Strap GA Gage GALV Galvanized HORIZ Horizontal HSS Hollow Structural Section L Angle
ABBREVIATION LIST
LG Long LLH Long Leg Horizontal LLV Long Leg Vertical LSH Long Side Horizontal LSV Long Side Vertical N.T.S. Not To Scale o.c. On Center PL Plate REINF. Reinforcing REM. To Remain S.F. Step Footing STIFF PL Stiffener Plate T.B.R. To Be Removed T&B Top and Bottom T.F. Top of Footing T.O.S. Top of Steel T.O.W. Top of Wall T.P. Top of Pier TYP Typical U.N.O. Unless Noted Otherwise VERT. Vertical V.I.F. Verify In Field WWF Welded Wire Fabric XE Extended End - Type R
C O
VE
R
S H
EE
T
CS
M
IL
L
ST
RE
ET
AutoCAD SHX Text FILENAME: \\biaces.com\Work\Projects\2024\1120724.000_Orangeville_Manor\WORK_PRODUCT\STRUC\2.0_Revit-Dwg\1120724000_Orangeville-Manor_GA.dwg - February 10, 2026 8:09 AM
AutoCAD SHX Text CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS FOR THE ENTIRE PROJECT BEFORE PROCEEDING WITH THE WORK.
AutoCAD SHX Text CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS FOR THE ENTIRE PROJECT BEFORE PROCEEDING WITH THE WORK.
VESTIBULE
VESTIBULE
JOB:
1120724.000
COPYRIGHT 2025
DRAWN:
SCALE:
AS NOTED
DATE:
02/11/2026
P MGR:
APPRD:
CHK
DSGN:
BU
IL
D
IN
G U
PG
R
AD
ES
O R
AN
G
EV
IL
LE
M
AN
O
R
M
IL
L
ST
O
R
AN
G
EV
IL
LE
, P A
R
EV
IS
IO
N S
D
AT
E
BY
SHEET:
Is su ed fo r B id
2/
/2
EX
IS
TI
N
G O
VE
R
AL
L
PL
AN
GA0.0
EXISTING OVERALL PLAN
SCALE: 1/8"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
GA1.0
AutoCAD SHX Text
AutoCAD SHX Text
GA2.0
AutoCAD SHX Text
AutoCAD SHX Text
GA1.0
AutoCAD SHX Text
AutoCAD SHX Text
GA2.0
AutoCAD SHX Text
AutoCAD SHX Text S1.0
AutoCAD SHX Text
AutoCAD SHX Text S1.0
AutoCAD SHX Text FILENAME: \\biaces.com\Work\Projects\2024\1120724.000_Orangeville_Manor\WORK_PRODUCT\STRUC\2.0_Revit-Dwg\1120724000_Orangeville-Manor_GA.dwg - February 10, 2026 8:09 AM
AutoCAD SHX Text CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS FOR THE ENTIRE PROJECT BEFORE PROCEEDING WITH THE WORK.
AutoCAD SHX Text
GA0.0
F.
F.
:1
'-3
0'-
0"
101'-4"+/-
107'-0"+/-
3'
-7
EXIST CONC
PAD TO REMAIN
EXIST CONC PAD
TO REMAIN
EXIST CONC PAD
AND HEATING FUEL
TANK TO REMAIN
VESTIBULE
F.F.: 100'-0"
99'-0 1/2"+/- 99'-7 1/2"+/-
JOB:
1120724.000
COPYRIGHT 2025
DRAWN:
SCALE:
AS NOTED
DATE:
02/11/2026
P MGR:
APPRD:
CHK
DSGN:
BU
IL
D
IN
G U
PG
R
AD
ES
O R
AN
G
EV
IL
LE
M
AN
O
R
M
IL
L
ST
O
R
AN
G
EV
IL
LE
, P A
R
EV
IS
IO
N S
D
AT
E
BY
SHEET:
Is su ed fo r B id
2/
/2
EN
LA
R G
ED
E
XI
ST
IN
G
D
EM
O
LI
TI
O N
P
LA
N
GA1.0
ENLARGED FRONT EXIT PLAN
SCALE: 1/4"=1'-0"
1.
2.
3.
4.
5.
6.
NOTES:
DENOTES ITEMS TO BE REMOVED
(T.B.R.) DENOTES ITEMS TO BE REMOVED
(T.B.R.R.) DENOTES ITEMS TO BE REMOVED AND REPLACED.
(REM.) DENOTES ITEMS TO REMAIN.
(REP.) DENOTES ITEMS TO BE REPLACED.
(REL.) DENOTES ITEMES TO BE RELOCATED.
ENLARGED REAR EXIT PLAN
SCALE: 1/4"=1'-0"
1.
2.
3.
4.
5.
6.
NOTES:
DENOTES ITEMS TO BE REMOVED
(T.B.R.) DENOTES ITEMS TO BE REMOVED
(T.B.R.R.) DENOTES ITEMS TO BE REMOVED AND REPLACED.
(REM.) DENOTES ITEMS TO REMAIN.
(REP.) DENOTES ITEMS TO BE REPLACED.
(REL.) DENOTES ITEMES TO BE RELOCATED.
DEMOLITION KEYED NOTES
MARK NOTE
EXIST DOOR, THRESHOLD, AND FRAME (T.B.R.). REMOVE ALL ANCHORS, NAILS,
SCREWS AND PREPARE OPENING FOR NEW DOOR FRAME
EXIST CONCRETE LANDING, RAILING, AND ENTRANCE CANOPY (T.B.R.). PATCH
AND REPAIR EXISTING AS NEEDED.
EXIST PLANTERS AND STONE EDGING TO BE REMOVED IN THEIR ENTIRETY.
REMOVE EXIST WOOD SIGN AND TURN OVER TO OWNER. REMOVE
ASSOCIATED WOOD POSTS AND FOUNDATIONS IN THEIR ENTIRETY.
REMOVE EXIST FLAG POLE, ASSOCIATED POST AND FOUNDATION IN THEIR
ENTIRETY.
EXISTING ASPHALT TO BE SAW CUT ARE REMOVED AS REQUIRED TO INSTALL
NEW LANDING, RAMP AND STAIR UNIT. COORDINATE EXTENT WITH NEW PLAN
AND ACCOUNT FOR WORKING SPACE FOR NEW FOOTINGS AND FOUNDATIONS.
NOTE: SAW CUT AREA SHALL BE STRAIGHT CUTS WITH 90 DEGREE CORNERS
TO PROVIDE A CLEAN TRANSITION POINT FROM ASPHALT PATCH TO EXISTING
ASPHALT.
FIELD CONDITION: IT MAYBE NECESSARY TO REMOVE EXISTING STONE SILL
FROM DOOR OPENING BASED ON EXISTING CONDITIONS AFTER DEMOLITION.
IF THIS SILL IS LOOSE IN ANY MANOR IT MUST BE REMOVE AND AREA
PREPARED FOR NEW CONCRETE INFILL.
EXIST STAIRS, LANDINGS, AND RAILING TO BE REMOVED IN THEIR ENTIRETY.
EXIST FOOTINGS, PIERS, AND PADS TO BE REMOVED IN THEIR ENTIRETY.
D1
1.
2.
3.
4.
5.
6.
DEMOLITION NOTES:
DEMOLITION PLANS & KEYNOTES ARE FOR THE CONTRACTOR'S CONVENIENCE
ONLY. THE CONTRACTOR SHALL REMOVE ALL MATERIALS THAT ARE NOT REQUIRED
IN THE FINISH WORK. ALL PATCH MATERIALS SHALL MATCH EXISTING TYPE, PLANE,
& FINISH UNLESS OTHERWISE NOTED.
CONTRACTOR SHALL REPAIR WALLS & FLOORS TO MATCH EXISTING MATERIALS
WHERE OTHER MATERIALS ARE REMOVED. I.E. INTERSECTIONS OF WALLS, FLOORS,
ETC. IF CONDITIONS ARE EXPOSED IN THE FINAL WORK.
ALL USEABLE EXISTING REMOVED CONSTRUCTION SHALL BE RETURNED TO THE
OWNER. OWNER SHALL DETERMINE USEABLE CONSTRUCTION.
ALL UNUSABLE REMOVED CONSTRUCTION SHALL BE REMOVED FROM THE SITE.
IN ACCORDANCE TO STATE LAW, THE CONTRACTOR SHALL BE REQUIRED TO CALL
PA ONE-CALL FOR UTILITY MARK-OUT IN ADVANCE OF ANY UTILITY EXCAVATION.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ENGAGING A THIRD-PARTY UTILITY
LOCATION TO IDENTIFY ALL PRIVATE UTILITIES.
D1
D2
D3D3
D2
D3
D8
D4
D4
D5
D6
D9
D9
D9
D9
D5
D7
D6D6
D7
D8
D9
AutoCAD SHX Text FILENAME: \\biaces.com\Work\Projects\2024\1120724.000_Orangeville_Manor\WORK_PRODUCT\STRUC\2.0_Revit-Dwg\1120724000_Orangeville-Manor_GA.dwg - February 10, 2026 8:09 AM
AutoCAD SHX Text CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS FOR THE ENTIRE PROJECT BEFORE PROCEEDING WITH THE WORK.
AutoCAD SHX Text
AutoCAD SHX Text
GA1.0
AutoCAD SHX Text
GA1.0
UP
LA
N
D
IN
G
4' -9
/2
T R
EA
D
S
1"
1' -1
1" 5'
-0
1' -2
6'-9 1/2"
1'-0"
11 TREADS @ 11" =10'-1" 4'-9 1/2"
LANDING
4'-0"
4'-9 1/2"
4' -0
4' -9
/2
5'-0"
LANDING
1' -0
VESTIBULE
F.
F.
:1
'-3
100' 0"+/-
' 0
/2
VESTIBULE
SURFACE
MOUNT BA
SL
O
PE
1:
M
AX
CLEAR FLOOR
SPACE (TYP)
C
JC
J
F.F.: 100'-0"
9'-0"
LANDING SEE NOTE E
11'-6"+/-
RAMP - SEE NOTE D
SLOPE 1:12 MAX
5' -1
0"
MIN 5' DIA CLEAR
FLOOR SPACE
SEE TYPICAL
NEW-TO-EXISTING
SLAB DETAIL
' 0
/2
CONTRACTOR TO
SHAPE CONCRETE
EDGE TO MATCH
EXIST PAVEMENT
99' 0 1/2"+/-
' 0
/2
5'-11"
LANDING SEE NOTE F
11" 5'-0"
5' -0
"3' -6
SL
O
PE
1:
M
AX
100' 0"
CC
(1) TREAD @ 11"
(2) RISERS @ 5-3/4" +/-
SEE NOTE E
DASHED LINE
INDICATES
APPROXIMATE
LOCATION OF NEW TO
EXISTING ASPHALT
JOINT - SEE NOTE G
1'-3"
DOOR HEADER / OPERATOR DETAIL
SCALE: 1 1/2"=1'-0"
INSTALL DOUBLE 2x8 BLOCKING IN
EACH STUD CAVITY FOR LENGTH
OF DOOR OPERATOR / HEADER
FOR ATTACHMENT OF OPERATOR
REMOVE AND REPLACE
WALL FINISH AS NEEDED
TO INSTALL BLOCKING
REMOVE AND REINSTALL
CEILING GRID AND TILES
AS NEEDED TO INSTALL
BLOCKING
CONTRACTOR TO PROVIDE
BLOCKING, AS REQUIRED, FOR
INSTALLATION. REFER TO
MANUFACTURERS WRITTEN
INSTALLATION INSTRUCTIONS.
EXTENDED OPERATOR
ARM MAYBE NEEDED DUE
TO JAMB DEPTH-
CONFIRM WITH FIELD
CONDITIONS
PATCH EXTERIOR FINISH
ON FACE OF WALL AND
JAMB BACK TO NEW FRAME
AS NEEDED
NEW HOLLOW METAL
FRAME - FLUSH WITH
EXTERIOR SURFACE
EXIST WALL
CONSTRUCTION
CONT. BACKER ROD AND
SEALANT AROUND
PERIMETER OF FRAME,
BOTH SIDES
PATCH INTERIOR GYPSUM
BOARD ON INTERIOR FACE
OF WALL AND JAMB BACK TO
DOOR FRAME. FINISH EDGE
OF GYP. BD WITH J-TRIM
TYPE 1
TYPE 1
DOOR TYPES
FRAME TYPE
SEE
SCHEDULE
SE
E
SC
H
ED
U
LE
7' -0
" R .O
(V
.I.
F.
2"
5'-4" R.O.2" 2"
A: 18 GAUGE, INSULATED
DOOR, MIN U=0.37
A: 14 GAUGE, HOLLOW
METAL FRAME WELDED
B: 16 GAUGE, HOLLOW
METAL FRAME KNOCK
DOWN
C: 16 GAUGE, HOLLOW
METAL FRAME WELDED
D: 14 GAUGE, HOLLOW
METAL FARM, KNOCK
DOWN
SCALE: 3/4" = 1'-0"
Door and Frame Details
1" INSULATED LOW E w/
ARGON CLEAR,
TEMPERED GLASS
SCALE: 3/4" = 1'-0"
Jamb Detail
1/ 2"
FR
AM
E
SE
TB
AC
K
PATCH EXTERIOR STUCCO
FINISH ON FACE OF WALL
AND JAMB BACK TO NEW
FRAME AS NEEDED
NEW HOLLOW METAL
FRAME - FLUSH WITH
EXTERIOR SURFACE
CONT. BACKER ROD AND
SEALANT AROUND
PERIMETER OF FRAME,
BOTH SIDES
PATCH INTERIOR GYPSUM
BOARD ON INTERIOR FACE
OF WALL AND JAMB BACK TO
DOOR FRAME. FINISH EDGE
OF GYP. BD WITH J-TRIM
EXIST WALL
CONSTRUCTION
JOB:
1120724.000
COPYRIGHT 2025
DRAWN:
SCALE:
AS NOTED
DATE:
02/11/2026
P MGR:
APPRD:
CHK
DSGN:
BU
IL
D
IN
G U
PG
R
AD
ES
O R
AN
G
EV
IL
LE
M
AN
O
R
M
IL
L
ST
O
R
AN
G
EV
IL
LE
, P A
R
EV
IS
IO
N S
D
AT
E
BY
SHEET:
Is su ed fo r B id
2/
/2
EN
LA
R G
ED
E
XI
T
PL
AN
S
GA2.0
ENLARGED FRONT EXIT PLAN
SCALE: 1/4"=1'-0"
ENLARGED REAR EXIT PLAN
SCALE: 1/4"=1'-0"
PROPOSED DOOR KEYED NOTES
MARK NOTE
- NEW HOLLOW METAL DOOR AND SIDELITE FRAME SIZED TO EXISTING ROUGH
OPENING. V.I.F. EXACT DIMENSIONS.
- AFTER DEMOLITION, INSPECT EXISTING JAMB FRAMING. NEW 2x WOOD JAMB
BLOCKING MAY BE REQUIRED DUE TO ROT OR DAMAGE AFTER DEMOLITION.
SOLID OPENING FRAMING MUST BE PROVIDED TO ANCHOR NEW FRAME.
- HOLLOW METAL FRAME TO BE INSTALLED TO FACE OF ROUGH OPENING
BLOCKING. SHIM AS REQUIRED. PROVIDE APPROPRIATE FRAME ANCHORS- (4)
ANCHORS PER JAMB VERTICALLY. PROVIDE BACKER ROD AND SEALANT
AROUND PERIMETER OF FRAME BOTH SIDES.
- COORDINATE WITH AUTOMATIC DOOR OPENER PROVIDER FOR NECESSARY
WIRING FOR POWER AND ACTUATORS.
- SIDELITE GLASS TO BE 1" THICK INSULATED, LOW E WITH ARGON, CLEAR
TEMPERED GLASS.
- HOLLOW METAL FRAME AND DOOR TO BE FACTORY PRIMED AND FIELD
PAINTED TWO COATS. COLOR SELECTED BY OWNER.
- SET FRAME 1/2" +/- IN FROM OUTSIDE FACE OF WALL.
P1
NOTE:
PROVIDE NEW 20A 1 POLE CIRCUIT FOR
AUTOMATIC DOOR POWER IN EXISTING
SERVICE CLOSET WITH 2#12, 1#12G, IN 3/4"
CONDUIT. PULL WIRE TO ABOVE CEILING
AND DOWN WALL TO OPERATOR
LOCATION, COORDINATE EXACT LOCATION
WITH INSTALLER. COORDINATE ALL
WIRING REQUIREMENTS WITH
MANUFACTURER.
ENTRANCE KEYED NOTES
MARK NOTE
DASHED LINE INDICATES OVERHEAD WALL MOUNTED STANLEY ACCESS TECHNOLOGIES,
M-FORCE AUTOMATIC SWING DOOR OPENER. COORD WITH GENERAL DETAILS ON THE
DRAWING, FIELD CONDITIONS AND STANLEY SPECIFIC INSTALLATION INSTRUCTIONS
FOR A FULL AND COMPLETE INSTALLATION. COORDINATE WITH E.C. FOR POWER
DELIVERY TO OPERATOR. OPERATORS WILL BE USING WIRELESS TRANSMITTER.
NOTE: EXTENDED OPERATOR ARM MAYBE NEEDED DUE TO JAMB DEPTH - CONFIRM
WITH FIELD CONDITIONS
BEA, 4.5 INCH ROUND PUSH PLATES. CONNECTED TO BEA'S LINE OF WIRELESS
TRANSMITTERS. 10PBR451. INTERIOR SURFACE MOUNTED BOX. REMOVE AND REPLACE
INTERIOR WALL FINISH AS NEEDED TO INSTALL BLOCKING FOR ACTUATOR BOX.
PATCH INTERIOR WALL SURFACES ALL AS REQUIRED AFTER INSTALLATION OF
BLOCKING, PROVING A SMOOTH SPACKLED TRANSITION FROM NEW TO EXISTING
SURFACES. PRIME ALL NEW MATERIAL. PAINT WITH TWO FINISH COATS ALL WALL
AREAS AFFECTED BY THIS SCOPE OF WORK FULL HEIGHT AND TO THE NEAREST BREAK
IN THE WALL OR CORNER.
LANDING AND RAMP TO BE 4" CONCRETE SLAB WITH WWF REINFORCING. LANDING TO
BE FLAT WITH MAXIMUM CROSS SLOPE AWAY FROM THE BUILDING OF 1:48, RAMP TO BE
MAXIMUM SLOPE OF 1:12 AND MAXIMUM CROSS SLOPE AWAY FROM THE BUILDING OF
1:48.
- CONTRACTOR TO PROVIDE TRANSIT SURVEYED ELEVATION VERIFICATION TO CONFIRM
RAMP LENGTH OF 11'-6" TO MAINTAIN MAXIMUM SLOPE OF 1:12. NOTE: BOTTOM LANDING
SURFACE TO BE FLUSH WITH ADJACENT ASPHALT.
- LANDING AND RAMP SURFACE TO HAVE TOOLED EDGES AND BROOM FINISH RUNNING
PERPENDICULAR TO THE BUILDING WALL.
- JOINT AT BUILDING TO BE 1/2" COMPRESSIBLE FILLER WITH EXTERIOR CAULKING AT
TOP.
STAIR RISERS AND TREADS TO BE CONCRETE FORMED AND REINFORCED.
- PITCH 1:48 MAXIMUM FOR DRAINAGE
- BROOM FINISH
- PROVIDE ECOGLO S2-N30 NON-SLIP CAST IN PLACE STAIR NOSING S2150 - YELLOW
(BASIS OF DESIGN)
- CONTRACTOR TO PROVIDE TRANSIT SURVEYED ELEVATION VERIFICATION TO CONFIRM
TOTAL RISE OF 11-1/2". MIN-MAX RISER HEIGHTS ARE 4" TO 7".
- JOINT AT BUILDING TO BE 1/2" COMPRESSIBLE FILLER WITH EXTERIOR CAULKING AT
TOP.
RAMP BOTTOM LANDING TO BE 4" CONCRETE SLAB WITH WWF REINFORCING. LANDING
TO HAVE MAXIMUM CROSS SLOPE IN EACH DIRECTION OF 1:48.
-CONTRACTOR TO PROVIDE TRANSIT SURVEYED ELEVATION VERIFICATION TO CONFIRM
EXISTING SLOPES AND ELEVATIONS. NOTE: BOTTOM LANDING SURFACE TO BE FLUSH
WITH ADJACENT ASPHALT.
- NEW LANDING SURFACE TO HAVE TOOLED EDGES AND BROOM FINISH RUNNING
PERPENDICULAR TO THE BUILDING WALL.
- JOINT AT BUILDING TO BE 1/2" COMPRESSIBLE FILLER WITH EXTERIOR CAULKING AT
TOP.
PATCH AROUND NEW LANDINGS, STAIR AND RAMP WITH FULL DEPTH ASPHALT. PROVIDE
LEVEL TRANSITION FROM NEW TO EXISTING- SEAL THIS JOINT
A
B
C
P1
Door and Frame Schedule
No.
Door Data
Fire Rating
Frame Data
RemarksType Material Finish Glass Size
Type Material Finish Details
Width Height Thickness Jamb
100 1 HM PAINT 1" INSUL 3'-0" 7'-0" (V.I.F.) 1 3/4" - 1C HM PAINT A -
NEW STAIR KEYED NOTES
MARK NOTE
STAIR LANDING TO BE ANCHORED TO BUILDING WALL WITH CONTINUOUS C12x20.5
CHANNEL
LANDING SUPPORT POST TO BE 4x4x1/2" TUBE STEEL. SEE TYPICAL SONOTUBE DETAIL.
POSTS TO BE PRIMED AND PAINTED.
CHANNEL STRINGERS TO BE SUPPORTED ON TURN DOWN STRUCTURAL SLAB. BASE
PLATE OR BOLTED CONNECTION TO SLAB IS ACCEPTABLE.
4" THICK SLAB ON GRADE LANDING WITH WWF REINFORCING WITH INTEGRAL TURN
DOWN FOUNDATION FOR STAIR. SLOPE SLAB 1:48 FROM STAIR AND PROVIDE TOOLED
EDGES BROOMED FINISH. TOP OF SLAB TO BE 1" HIGHER THAN SURROUND GRADE.
NEW TOP SOIL AND SEEDING TO BE FLUSH WITH TOP OF SLAB AND SLOPE AWAY TO
PROVIDE POSITIVE DRAINAGE FROM PAD
ENTIRE AREA TO RECEIVE 4" OF NEW TOP SOIL AND SEEDING UPON COMPLETION OF
ALL CONSTRUCTION. TOP SOIL THICKNESS ALONG BUILDING TO BE SLIGHTLY HIGHER
TO PROMOTE POSITIVE SURFACE DRAINAGE AWAY FROM BUILDING.
NEW STAIR NOTES
GENERAL NOTE: CONTRACTOR TO PROVIDE TRANSIT SURVEYED ELEVATION
VERIFICATION TO CONFIRM TOTAL RISE FROM EXISTING SECOND FLOOR
ELEVATION DOWN TO PROPOSED GRADE LANDING PAD. NOTE: TOP OF BOTTOM
LANDING PAD TO BE 1" ABOVE EXISTING GRADE. RISER HEIGHTS MAY NEED TO BE
ADJUSTED SLIGHTLY BASED ON FIELD VERIFICATION.
GENERAL NOTE: STAIR LAYOUT PROVIDED AS A GENERAL GUIDE TO MEET DESIGN
AND IBC CODE REQUIREMENTS. FINAL STAIR DETAILING, MEMBER SIZING,
CONNECTIONS TO BE A DELEGATED DESIGN TO A STAIR FABRICATOR. THIS
SUB-CONTRACTOR TO PROVIDE SIGNED AND SEALED SHOP DRAWING IF
REQUIRED BY THE AUTHORITY HAVING JURISDICTION.
GENERAL NOTE: GENERAL DESIGN STANDARDS: TREADS AND LANDINGS TO BE
OPEN SERRATED MIN. 1" THICK, STEEL PLATE RISERS, C-CHANNEL FRAMING,
GUARD AND HANDRAILS TO BE 1-1/2" DIAMETER STEEL. ALL STEEL, INCLUDING
SUPPORT POSTS, TO BE PRIMED AND FINISHES WITH TWO COATS OF PAINT.
D
E
F
G
12 RISERS @ 6 5/8"+/-
R
IS
ER
S
/8
AutoCAD SHX Text FILENAME: \\biaces.com\Work\Projects\2024\1120724.000_Orangeville_Manor\WORK_PRODUCT\STRUC\2.0_Revit-Dwg\1120724000_Orangeville-Manor_GA.dwg - February 10, 2026 8:09 AM
AutoCAD SHX Text CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS FOR THE ENTIRE PROJECT BEFORE PROCEEDING WITH THE WORK.
AutoCAD SHX Text
AutoCAD SHX Text
GA2.0
AutoCAD SHX Text
GA2.0
SEE NOTE #4
NOTE: REFER TO PENNDOT DETAIL RC-67M, (LATEST EDITION)
ASPHALT
PAVEMENT
SURFACE. SEE
RESTORATION
DETAIL, IF
REQUIRED
JOINT SEAL
MATERIAL
M
AT
C H
EX
IS
T
NOTES:
1. CLASS A CONCRETE
2. MAXIMUM WATER CEMENT RATIO 0.45
3. 6% AIR ENTRAINMENT, ± 1.5%
4. CONCRETE WALK SHALL HAVE A 2% MAX.
CROSS SLOPE, UNLESS NOTED OTHERWISE.
5. TOOL ALL EDGES.
6. MATCH EXISTING SIDEWALK FINISH.
CONCRETE SIDEWALK DETAIL
SCALE: N.T.S.
6" 2B STONE
SUBBASE
COMPACTED
SUBGRADE
4" CONC
SEE PLAN FOR WIDTH
CONSTRUCTION JOINT
NOTE: CONTRACTOR'S
OPTION
FOR TYPE OF JOINT
TYPICAL CRACK CONTROL JOINTS
T T
T
SCALE: 3/4"=1'-0"
PREMOLDED
KEYED JOINT
SAWED CONTROL JOINT
1'-6"1'-6"
TOOL OR SAW CUT - 1/3 DEPTH
(SAW WITHIN 24 HRS.
OF PLACING CONCRETE)
STOP REINFORCING
6" FROM JOINT
T/
T/
NEW
CONCRETE
SLAB
~8"Ø x 18" LONG SMOOTH DOWELS @ 24" o.c. EPOXY
INTO EXISTING SLAB AND
GREASE INTO NEW
CONCRETE POUR
TYPICAL NEW-TO-EXISTING
SLAB DETAIL (U.N.O.)
NOTE: DOWELS ARE NOT REQUIRED IF BOTH SLABS
BEAR 4" (MIN.) ON A FOUNDATION WALL
~0" Ø HOLE
SCALE: N.T.S.
EXIST.
CONCRETE
SLAB
SAWCUT EXISTING SLAB
PROVIDE BONDING AGENT
(SIKADUR 32, HI-MOD OR
APPROVED EQUAL) TO BOND
OLD CONCRETE TO NEW
0'-9"
RAILING ALONG RAMP EDGE
4'-0" 1'-0"
MIN
1:12
MAX SLOPE
NOTES:
1. LANDING REQUIRED WHEN RAMP REACHES 30" HIGH.
2. SEE PLAN FOR RAMP WIDTH.
3. THE CLEAR WIDTH OF A RAMP BETWEEN HANDRAILS SHALL BE 36" MINIMUM.
LANDING
LANDING
5'-0" MIN
5'-0" MIN
NOT REQ'D
IF RETURN
TO WALL
1 1/2" O.D.
NOMINAL PIPE
SIZE
TYPICAL RAMP HANDRAIL DETAIL
SCALE: 1/2"=1'-0"
4" M
AX
NEW FRONT EXIT RAMP
TYPICAL STAIR HANDRAIL DETAIL
SCALE: N.T.S.
3~8"3~
7" M
AX
1 1/2" O.D. NOMINAL
PIPE SIZE
1'-0"
MIN
11" MIN11" MIN*
NOTE:
*11" MIN OR HORIZONTAL DISTANCE
EQUAL TO ONE TREAD DEPTH
BEYOND BOTTOM TREAD NOSING
6"∅ SPHERE SHALL
NOT PASS
NEW FRONT EXIT STAIR AND RAMP
HANDRAIL EMBEDMENT DETAIL
SCALE: 3"=1'-0"
NOTES:
1. POSTS SHALL BE LOCATED 3 1/2" CLEAR FROM
EDGE OF SLAB. REFER TO TYPICAL STAIR
HANDRAIL DETAIL.
1 1/2" O.D. NOMINAL PIPE
SIZE HANDRAIL POST
NON-SHRINK
GROUT POCKET
EDGE OF CONCRETE
1/ 4"
5"
3"
3 1/2"
1/
2"
" M
AX
5'-0"
1' -9
1 1/2" O.D.
NOMINAL PIPE
SIZE (TYP)
21"Ø SPHERE SHALL
NOT PASS BETWEEN
BARS
GUARDRAIL DETAIL
SCALE: 3/4"=1'-0"
4"
NEW FRONT EXIT STAIR AND RAMP
6"∅ SPHERE SHALL
NOT PASS
4"∅ SPHERE SHALL
NOT PASS
BETWEEN BARS
NOTE:
*11" MIN OR HORIZONTAL DISTANCE
EQUAL TO ONE TREAD DEPTH BEYOND
BOTTOM TREAD NOSING
ELEVATION
SECTION
1'-0"
MIN.
1/2"
2' -1
0"3' -6
7" M
AX
11" 11"
" M
IN
1 1/2"
1 1/4" - 2"
1/
2"
3 1/2"
SCALE: 3/4" = 1'-0"
TYPICAL STAIR GUARDRAIL w/ HANDRAIL DETAIL
NEW REAR EXIT STAIR
1 1/2" O.D.
NOMINAL
PIPE SIZE
SEE PLAN FOR
HANDRAIL
LOCATION
REQUIREMENTS
4"
1/2"
5'-0"
3' -6
1 1/2"
1-1/4" - 2"
4"∅ SPHERE SHALL
NOT PASS
BETWEEN BARS
SCALE: 3/4" = 1'-0"
TYPICAL GUARD DETAIL w/ HANDRAIL
NEW REAR EXIT STAIR
JOB:
1120724.000
COPYRIGHT 2025
DRAWN:
SCALE:
AS NOTED
DATE:
02/11/2026
P MGR:
APPRD:
CHK
DSGN:
BU
IL
D
IN
G U
PG
R
AD
ES
O R
AN
G
EV
IL
LE
M
AN
O
R
M
IL
L
ST
O
R
AN
G
EV
IL
LE
, P A
R
EV
IS
IO
N S
D
AT
E
BY
SHEET:
Is su ed fo r B id
2/
/2
SC
H
ED
U
LE
S, N O
TE
S, A N
D D
ET
AI
LS
GA3.0
AutoCAD SHX Text FILENAME: \\biaces.com\Work\Projects\2024\1120724.000_Orangeville_Manor\WORK_PRODUCT\STRUC\2.0_Revit-Dwg\1120724000_Orangeville-Manor_GA.dwg - February 10, 2026 8:09 AM
AutoCAD SHX Text CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS FOR THE ENTIRE PROJECT BEFORE PROCEEDING WITH THE WORK.
AutoCAD SHX Text
6" TOPSOIL, FURNISHED AND PLACED
AutoCAD SHX Text
SEED AREA AND APPLY STRAW MULCH
AutoCAD SHX Text
LAWN RESTORATION N.T.S.
AutoCAD SHX Text
UNCOMPACTED SUBGRADE
AutoCAD SHX Text NOTES: 1. REFER TO SEEDING SCHEDULE FOR INFORMATION. REFER TO SEEDING SCHEDULE FOR INFORMATION. 2. BENEATH TREES, PROVIDE A 3 FT DIAMETER AREA OF DOUBLE SHREDDED BENEATH TREES, PROVIDE A 3 FT DIAMETER AREA OF DOUBLE SHREDDED HARDWOOD MULCH, 4 INCH DEPTH. CONFIRM MULCH COLOR WITH OWNER.
AutoCAD SHX Text
AUGUST 15 - OCTOBER 15
AutoCAD SHX Text
SEEDING DATES: MARCH 15 - MAY 15
AutoCAD SHX Text
(AUGUST 16 TO NOVEMBER 1)
AutoCAD SHX Text
(MARCH 15 TO JUNE 15)
AutoCAD SHX Text
ANNUAL RYEGRASS
AutoCAD SHX Text ANNUAL RYEGRASS or
AutoCAD SHX Text %%uSPECIES
AutoCAD SHX Text
SPRING OATS
AutoCAD SHX Text
WINTER RYE
AutoCAD SHX Text %%uPERMANENT COVER FOR STABILIZATION
AutoCAD SHX Text
AT 1,000 LB PER ACRE.
AutoCAD SHX Text
PERMANENT: ALL DISTURBED AREAS TO BE PREPARED AND SEEDED
AutoCAD SHX Text
OF AGRICULTURAL LIMESTONE AND 10-20-20 FERTILIZER
AutoCAD SHX Text
TESTS ARE NOT AVAILABLE, APPLY SIX TONS PER ACRE
AutoCAD SHX Text
TEST) INTO THE TOP 6" OF TOPSOIL. IF SOIL
AutoCAD SHX Text
SITE PREPARATION: INCORPORATE LIME AND FERTILIZER (RATE BASED ON SOIL
AutoCAD SHX Text
RATE FOLLOWING FINAL GRADING:
AutoCAD SHX Text %%uSEASON
AutoCAD SHX Text
SUMMER
AutoCAD SHX Text
SPRING
AutoCAD SHX Text
FALL
AutoCAD SHX Text
(JUNE 16 TO AUGUST 15)
AutoCAD SHX Text %%uRATE (LB./ACRE)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text %%uTEMPORARY COVER FOR EROSION CONTROL
AutoCAD SHX Text %%uSEEDING SCHEDULE
AutoCAD SHX Text
WITH THE FOLLOWING SPECIES AT THE NOTED SEEDING
AutoCAD SHX Text ANNUAL RYEGRASS or
AutoCAD SHX Text
AutoCAD SHX Text
TALL FESCUE
AutoCAD SHX Text
WINTER RYE
AutoCAD SHX Text
FINE FESCUE
AutoCAD SHX Text
%%USUGGESTED VARIETIES
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ARCOOSTOOK OR BALBO TYPE
AutoCAD SHX Text
RELIANT II, SR3100, DISCOVERY, OSPREY
AutoCAD SHX Text Houndog V, Montauk, Marksman, and Apache II
AutoCAD SHX Text TURF-TYPE PERENNIAL RYEGRASS (LOLIUM PERENNE) and
AutoCAD SHX Text KENTUCKY BLUEGRASS (POA PRATENSIS) and
AutoCAD SHX Text %%uSEED SPECIES BY SITE
AutoCAD SHX Text FINE (RED or CHEWING) FESCUE (FESTUCA RUBA RUBA/COMMUTATA)
AutoCAD SHX Text 2.5
AutoCAD SHX Text
AutoCAD SHX Text 1.5
AutoCAD SHX Text
%%URATE (LB./1000 SF)
AutoCAD SHX Text
LAWNS
AutoCAD SHX Text
KENTUCKY BLUEGRASS
AutoCAD SHX Text
AutoCAD SHX Text
SR 2109, NORTH STAR, BLACKSBURG, BRILLIANT
AutoCAD SHX Text
* ALL SEED TO BE MIN. 98% PURE LIVE SEED.
AutoCAD SHX Text INITIAL PROTECTION: APPLY TEMPORARY SEEDING WHEN PERMANENT SEEDING IS DELAYED OR OUT OF PLANTING SEASON.
AutoCAD SHX Text MULCHING: APPLY THREE TONS PER ACRE OF STRAW TO ACHIEVE A LOOSE LAYER 3/4-1" DEEP. USE JUTE MATTING RATHER THAN STRAW ON STEEP SLOPES. APPLY CELLULOSE FIBER TACKIFIER OVER STRAW MULCH AT A RATE OF 800-1000 LBS. PER ACRE. HYDROMULCHING IS ACCEPTABLE WHEN BLOWING OF STRAW IS A CONCERN.
AutoCAD SHX Text SPECIFICATION: THE FOLLOWING SPECIFICATION SHALL BE USED FOR THIS PROJECT UNLESS OTHERWISE NOTED. Penn State College of Agriculture Sciences, EROSION CONTROL AND CONSERVATION PLANTINGS ON NONCROPLAND by Peter Landschoot, 1997 or as revised.
AutoCAD SHX Text METHOD: APPLY SEED USING DRILL FITTED WITH A DEPTH BAND AND PACKER WHEEL. PLANT GRASS SEEDS AT 0.25 TO 0.5 INCHES DEEP. WHEAT, RYE AND OATS MAYBE PLANTED 1 TO 1.5 INCHES DEEP. BROADCAST SEEDING PERMITTED WITH IMMEDIATE MULCH COVER. HYDROSEEDING OF PERMANENT SEEDING IS NOT PERMITTED.
AutoCAD SHX Text
METHOD: APPLY SEED USING SURFACE BROADCASTING OR HYDROSEEDING.
AutoCAD SHX Text MULCHING: APPLY THREE TONS PER ACRE OF STRAW TO ACHIEVE A LOOSE LAYER 3/4-1" DEEP. USE JUTE MATTING RATHER THAN STRAW ON STEEP SLOPES. APPLY CELLULOSE FIBER TACKIFIER OVER STRAW MULCH AT A RATE OF 800-1000 LBS. PER ACRE. HYDROMULCHING IS ACCEPTABLE WHEN BLOWING OF STRAW IS A CONCERN.
AutoCAD SHX Text BEFORE PLACING TOPSOIL, PREPARE SUBGRADE TO A DEPTH 6" BELOW FINAL GRADE. SCARIFY SUBGRADE WITH DEEP TINE PLOW. SCREEN TOPSOIL AND UNIFORMLY BLEND IN 20-25% BY VOLUME LEAF MOULD OR PROCESSED MUSHROOM SUBSTRATE. SPREAD AMENDED/SCREENED TOPSOIL OVER SUBGRADE TO OBTAIN FINISHED GRADE. COMPACT SURFACE TO 80-85% COMPACTION. DO NOT OVER COMPACT.
AutoCAD SHX Text
AT 500 LB PER ACRE.
AutoCAD SHX Text
OF AGRICULTURAL LIMESTONE AND 10-10-10 FERTILIZER
AutoCAD SHX Text
TESTS ARE NOT AVAILABLE, APPLY ONE TON PER ACRE
AutoCAD SHX Text
TEST) INTO THE TOP 4-6" OF TOPSOIL. IF SOIL
AutoCAD SHX Text
SITE PREPARATION: INCORPORATE LIME AND FERTILIZER (RATE BASED ON SOIL
AutoCAD SHX Text SIDEWALK NOTES: : 1. ALL SIDEWALK ARE TO BE CONCRETE CONSTRUCTION, UNLESS ALL SIDEWALK ARE TO BE CONCRETE CONSTRUCTION, UNLESS OTHERWISE INDICATED. 2. CONTRACTION JOINTS SHALL BE UNIFORMLY SPACED AT 5 FOOT CONTRACTION JOINTS SHALL BE UNIFORMLY SPACED AT 5 FOOT INTERVALS, APPROXIMATELY " WIDE, AND AT LEAST 1 INCH DEEP. 18" WIDE, AND AT LEAST 1 INCH DEEP. 3. PLACE " PREMOLDED, EXPANSION JOINT MATERIAL FOR THE FULL PLACE " PREMOLDED, EXPANSION JOINT MATERIAL FOR THE FULL 12" PREMOLDED, EXPANSION JOINT MATERIAL FOR THE FULL DEPTH OF THE SIDEWALK, OPPOSITE EXPANSION JOINTS IN ADJACENT CURB, BETWEEN THE SIDEWALK AND THE CURB, AND BETWEEN THE SIDEWALK AND RIGID STRUCTURES. PLACE ONE EXPANSION JOINT FOR EVERY 20 FEET OF SIDEWALK. 4. SEAL JOINTS IN ACCORDANCE WITH THE RELEVANT SECTION OF SEAL JOINTS IN ACCORDANCE WITH THE RELEVANT SECTION OF PENNDOT PUBLICATION 408, AS LAST REVISED. 5. SIDEWALKS SHALL RECEIVE A STANDARD BROOM FINISH. SIDEWALKS SHALL RECEIVE A STANDARD BROOM FINISH. 6. SIDEWALK CROSS SLOPE SHALL NOT EXCEED 2.00%, UNLESS SIDEWALK CROSS SLOPE SHALL NOT EXCEED 2.00%, UNLESS EXISTING CONDITIONS DICTATE OTHERWISE OR APPROVED BY THE ENGINEER. 7. CONTRACTION JOINTS SHALL BE A 3/8" WIDE SAWCUT.CONTRACTION JOINTS SHALL BE A 3/8" WIDE SAWCUT.
AutoCAD SHX Text
EXISTING PAVEMENT
AutoCAD SHX Text
PROPOSED PAVEMENT
AutoCAD SHX Text 2'-0"
AutoCAD SHX Text 2'-0"
AutoCAD SHX Text
REMOVE BIT. PAVING
AutoCAD SHX Text
SAWCUT EXISTING PAVEMENT
AutoCAD SHX Text
6" WIDE CLBM-1 PAVEMENT SEAL
PAVEMENT SAWCUT SECTION N.T.S.
VESTIBULE
VESTIBULE
F.
F.
:1
'-3
FROST WALL SEE
"TYPICAL FROST WALL
DETAIL"
16" SONOTUBE (TYP)
- SEE "TYPICAL
SONOTUBE DETAIL"
FROST WALL SEE
"TYPICAL STAIR
STRINGER ATTACHMENT
TO SLAB ON GRADE"
100' 0"+/-
VESTIBULE
#4 @ 12" o.c.
#4 @ 12" o.c.
#4 NOSING
BAR (TYP)
Typical Section Thru Concrete Stairs Typical Slab to Wall Connections
#4 @ 12" o.c.
TYPICAL
FROST
WALL
#4 @ 12" o.c.
BOTH SIDES
(3) #5
1' -0
2'-6"
1" CLR
ALL SIDES
9" 1'-0" 9"
VA
R
IE
S
SE
E
AR
C
H . D
W G
S.
3'
-6 " M
IN
SEE ARCH. DWGS.
6"
SCALE: 3/4" = 1'-0"
VERTICAL
BARS
CONCRETE
WALL
BENT
BARS
CONCRETE
SLAB ON
GRADE
SCALE: 3/4" = 1'-0"
1.
2.
NOTES:
CONTINUOUS BARS SHALL HAVE 3" MINIMUM COVER
ON ALL SIDES.
BENT BARS SHALL BE THE SAME SIZE AND SPACING
AS FOUNDATION WALL VERTICAL REINFORCING.
BENT
BARS (B)
CONT.
BARS
D
EP
TH
WIDTH
SCALE: 3/4" = 1'-0"
Wall Footing Schedule at Concrete Foundation Walls
W10-6
1.
2.
3.
4.
5.
NOTES:
ALL REINFORCING BARS SHALL HAVE 2" MINIMUM COVER ON ALL SIDES. 8" WALLS
SHALL HAVE ONLY ONE LAYER OF REINFORCING CENTERED IN THE WALL
BENT BARS SHALL BE THE SAME SIZE AND SPACING AS FOUNDATION WALL
VERTICAL REINFORCING.
FOR WALL WITH SHELF - 'Z' BARS SIZE AND SPACING SHALL MATCH (V) BARS.
FOR WALLS BACKING VENEER INSTALL DOVETAIL SLOTS @ 24" o.c. HORIZONTALLY AND METAL TIES @ 16" o.c. VERTICALLY
COORDINATE SHELF LOCATIONS AND ELEVATIONS WITH ARCHITECTURAL
DRAWINGS
BENT
BARS (B)
VERT.
BARS (V)
HORIZ.
BARS (H)
WIDTH DOWELS @ MASONRY
WALLS - SIZE AND
SPACING TO MATCH
MASONRY WALL VERTICAL
REINFORCING
'Z' BARS
VERT.
BARS (V)
HORIZ.
BARS (H)
WALL AT SHELF
'X' 'Y'
'X' - WIDTH OF CONC. STEM
'Y' - WIDTH OF CONC. BRICK SHELF
SCALE: 3/4" = 1'-0"
Concrete Foundation Wall Schedule
JOB:
1120724.000
COPYRIGHT 2025
DRAWN:
SCALE:
AS NOTED
DATE:
02/11/2026
P MGR:
APPRD:
CHK
DSGN:
BU
IL
D
IN
G U
PG
R
AD
ES
O R
AN
G
EV
IL
LE
M
AN
O
R
M
IL
L
ST
O
R
AN
G
EV
IL
LE
, P A
R
EV
IS
IO
N S
D
AT
E
BY
SHEET:
Is su ed fo r B id
2/
/2
FO
U
N D
AT
IO
N P
LA
N
, N O
TE
S, A N
D D
ET
AI
LS
S1.0
ENLARGED REAR EXIT FOUNDATION PLAN
SCALE: 1/4"=1'-0"
ENLARGED FRONT EXIT FOUNDATION PLAN
SCALE: 1/4"=1'-0"
Schedule - Wall Footing
MARK DEPTH WIDTH REINFORCING
WF1230 1'-0" 2'-6" (3) #5 CONT.
Schedule - Concrete Foundation Wall
MARK WIDTH REINFORCING
W8 8" #4 @ 12" o.c. (V) #4 @ 12" o.c. (H)
Foundation Wall Size Marker W**
Foundation Wall Footing Size Marker WF****
Foundation Symbol Legend
W8
WF1230
CONTROL JOINT NOTE:
SLAB-ON-GRADE CONTROL JOINT SPACING AND LOCATIONS SHALL BE
COORDINATED WITH ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS. A PLAN LAYOUT SHALL BE SUBMITTED TO THE
ARCHITECT FOR REVIEW PRIOR TO CONSTRUCTION.
Floor Schedule - Foundation Plan
TYPE
SLAB
REINFORCING FINISH FLOOR
5" Concrete 44-W4.0xW4.0 SEE GA PLANS
NOTES:
1. SEE CHART BELOW FOR FINISH FLOOR ELEVATION AND SLAB CONSTRUCTION
NOTES:
1. SEE CHART BELOW FOR FINISH FLOOR ELEVATION AND SLAB CONSTRUCTION
Floor Schedule - Foundation Plan
TYPE
SLAB
REINFORCING FINISH FLOOR
5" Concrete 44-W4.0xW4.0 SEE GA PLANS
AutoCAD SHX Text A
AutoCAD SHX Text S1.0
AutoCAD SHX Text B
AutoCAD SHX Text S1.0
AutoCAD SHX Text FILENAME: \\biaces.com\work\Projects\2024\1120724.000_Orangeville_Manor\WORK_PRODUCT\STRUC\2.0_Revit-Dwg\1120724000_Orangeville-Manor_GA.dwg - February 10, 2026 3:53 PM
AutoCAD SHX Text CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS FOR THE ENTIRE PROJECT BEFORE PROCEEDING WITH THE WORK.
AutoCAD SHX Text
AutoCAD SHX Text S1.0
AutoCAD SHX Text
AutoCAD SHX Text S1.0
AutoCAD SHX Text A
AutoCAD SHX Text S1.0
AutoCAD SHX Text B
AutoCAD SHX Text S1.0
AutoCAD SHX Text B
S1.0
(2) #5
3' -6
M
IN
8"
1'-0"
SCALE: 3/4" = 1'-0"
Typical Frost Wall
5"
NEW TOPSOIL
SLOPED AWAY FROM
LANDING SLAB
WRAP MESH
AROUND #4
NOSING BAR
6" WELL
COMPACTED
STONE BASE
SCALE: 3/4" = 1'-0"
Typical Sonotube Detail
6" 4'
-0
4x4x1/2" STEEL POST -
BY DELEGATED
DESIGN ENGINEER
BASE PLATE AND
ANCHOR RODS BY
DELEGATED DESIGN
ENGINEER
16" DIA CONC
SONOTUBE POST
FOUNDATION
(6) #5 VERT BARS EQ
SPACED AROUND
PERIMETER w/ 3" MIN
COVERAGE AND #4
TIES @ 12" o.c. VERT
SCALE: 3/4" = 1'-0"
Typical Stair Stringer Attachment to Slab on Grade
STAIR STRINGER
(SEE ARCH. DWGS)
CONCRETE SLAB
ON GRADE
1/4 0 1'-0"
CLIP L3x3x1/4 x 4" LONG w/ 1/2" DIA.
EXP. BOLTS
SEE TYPICAL
FROST WALL
DETAIL
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
FOUNDATIONS AND BACKFILL
SOIL BEARING CAPACITY OF 2,000 PSF WAS UTILIZED IN THE DESIGN OF THE
FOUNDATION SYSTEM.
SLAB ON GRADE DESIGN BASED ON MODULUS OF SUBGRADE REACTION OF
PCI.
PLACE EXTERIOR FOOTINGS AND FROST WALLS EXPOSED TO WEATHER AT LEAST
42" BELOW THE ADJACENT OUTSIDE FINISHED GRADE TO PROTECT FROM FROST
DAMAGE.
THE OWNER SHALL ENGAGE THE SERVICES OF A REGISTERED PROFESSIONAL
GEOTECHNICAL ENGINEER TO MONITOR AND INSPECT ALL EARTH WORK AND TO
PERFORM THE SPECIAL INSPECTIONS REQUIRED BY THE SCHEDULE OF SPECIAL
INSPECTIONS. THE GEOTECHNICAL ENGINEER SHALL SUPERVISE THE PLACING OF
THE COMPACTED FILL AND ALL THE MATERIALS AND EQUIPMENT USED FOR THIS
PURPOSE. THE GEOTECHNICAL ENGINEER SHALL CERTIFY, BY SEAL AND
SIGNATURE, THAT THE EARTH-WORK IS IN ACCORDANCE WITH THE GEOTECHNICAL
REPORT, PLANS AND SPECIFICATIONS.
THE SUB-FLOOR MATERIALS SHALL CONSIST OF AT LEAST FOUR TO SIX INCHES OF
GRAVEL OR CRUSHED STONE. THE SUB-FLOOR MATERIALS SHALL BE COMPACTED
BY AT LEAST FOUR COVERAGES OF A HEAVY-DUTY VIBRATORY ROLLER OR UNTIL
NO FURTHER COMPACTION IS OBSERVED. SEE THE DRAWINGS AND
SPECIFICATIONS FOR THE VAPOR BARRIER SIZE, TYPE AND LOCATION.
PRIOR TO CONCRETE PLACEMENT THE FOUNDATION BOTTOM SHALL BE
COMPACTED USING A WALK BEHIND VIBRATORY ROLLER OR GAS-POWERED
TAMPER.
IF SOIL OF THE BEARING CAPACITY NOTED ABOVE IS NOT ENCOUNTERED AT THE
ELEVATIONS SHOWN ON PLAN, UNSUITABLE SOILS SHALL BE REMOVED AND
REPLACED WITH STRUCTURAL FILL IN ACCORDANCE WITH THE GEOTECHNICAL
ENGINEER'S DIRECTION.
IF BEDROCK IS ENCOUNTERED AT OR ABOVE FOUNDATION SUBGRADE ELEVATION,
THE BEDROCK SURFACE SHALL BE OVER EXCAVATED A MINIMUM OF SIX INCHES
AND BACKFILLED WITH CRUSHED STONE TO THE SUBGRADE ELEVATION.
THE GEOTECHNICAL ENGINEER SHALL APPROVE SAMPLES OF ALL CONTRACTOR
PROPOSED COMPACTED FILL MATERIAL. IMPORTED STRUCTURAL FILL SHALL BE
FREE OF ORGANIC MATTER, ASH, CINDERS AND DEMOLITION DEBRIS.
CONTROL OF MOISTURE FOR PLACING FILL WILL BE BASED ON THE RESULTS OF
ASTM D-1557 MODIFIED PROCTOR TESTS.
ALL COMPACTED FILL SHALL HAVE A DENSITY OF AT LEAST 98% OF MAXIMUM DRY
DENSITY AS DETERMINED BY THE ASTM D-1557 MODIFIED PROCTOR TEST. PLACING
OF FILL WITH MOISTURE CONTENT OUTSIDE THE LIMITS FOR PROPER COMPACTION
SHALL NOT BE PERMITTED.
THE EXISTING SUBGRADE IN ALL FILL AND CUT AREAS SHALL BE COMPACTED TO A
FIRM, STABLE CONDITION AS DETERMINED BY THE GEOTECHNICAL ENGINEER,
PRIOR TO PLACEMENT OF FILLS AND EXCAVATION FOR FOOTINGS.
FILL MATERIAL SHALL BE PLACED IN LOOSE LIFTS NOT EXCEEDING 8" IN THICKNESS
AND SHALL BE MIXED, SPREAD, AND PLACED IN SUCH A WAY AS TO PRODUCE A
UNIFORM THICKNESS OF MATERIAL AFTER PLACING.
EACH LAYER OF FILL MATERIAL SHALL BE COMPACTED ON ALL PORTIONS OF THE
SURFACE OF EACH LIFT OF FILL BY RUBBER TIRE ROLLERS, SHEEP'S FOOT
ROLLERS, VIBRATORY ROLLERS, ETC. AS NECESSARY TO ATTAIN THE MAXIMUM DRY
DENSITY NOTED ABOVE AND AS APPROVED BY THE GEOTECHNICAL ENGINEER.
WHENEVER IN PLACE DENSITIES ARE FOUND TO BE BELOW LIMITS ACCEPTABLE TO
THE GEOTECHNICAL ENGINEER, ADDITIONAL ROLLING TO PRODUCE THE SPECIFIED
DENSITIES SHALL BE REQUIRED.
PLACING OF FILL WHEN FREE WATER IS STANDING ON THE EXISTING SURFACE
SHALL NOT BE PERMITTED.
PLACING OF FILL IN A FROZEN CONDITION OR ON TOP OF FROZEN MATERIAL SHALL
NOT BE PERMITTED.
SUBGRADE SUITABILITY SHALL BE VERIFIED BY GEOTECHNICAL ENGINEER WITHIN
24 HOURS PRIOR TO PLACING CONCRETE FOUNDATIONS AND CONCRETE SLABS ON
GRADE TO CONFIRM THAT NO DETERIORATION HAS OCCURRED SUBSEQUENT TO
TESTING PERFORMED AT TIME OF FILL PLACEMENT. UNSUITABLE CONDITIONS
SHALL BE CORRECTED PER GEOTECHNICAL ENGINEER'S RECOMMENDATION.
EXCAVATIONS SHOULD BE BACKFILLED OR HAVE CONCRETE PLACED AS SOON AS
POSSIBLE DURING CONSTRUCTION TO MINIMIZE ADVERSE AFFECTS TO SUBGRADE
CONDITIONS. GRADING DEPRESSIONS SHOULD BE AVOIDED.
WATER SHALL BE PREVENTED FROM ENTERING OPEN EXCAVATIONS. ANY
ACCUMULATED WATER SHALL BE REMOVED AS SOON AS POSSIBLE. IT IS
RECOMMENDED THAT CONCRETE BE PLACED THE SAME DAY THE EXCAVATION IS
MADE.
THE CONTRACTOR SHALL PROVIDE FOR DEWATERING AS REQUIRED DURING
EXCAVATION AND CONSTRUCTION.
CONCRETE MIX DESIGN CRITERIA
FOOTINGS AND
FOUNDATION WALLS
EXPOSURE
CLASS
F1,S0,W0,C1
MAX. w/c
RATIO
0.55 c
3,500
AIR
CONTENT
5%
CEMENT
TYPE
I or II
F3,S0,W0,C2 0.40
REBAR LAP SPLICE LENGTHS
BAR LOCATION
VERT. & HORIZ. WALL BARS
FOOTING TOP BARS
FOOTING BOTTOM BARS
BAR SIZE
#3 ld ls ldh
20" 25" 8"
15" 19" 8"
#4 ld ls ldh
25" 33" 10"
19" 25" 10"
#5 ld ls ldh
32" 41" 12"
24" 31" 12"
20" 25" 8" 25" 33" 10" 32" 41" 12"
VERT. & HORIZ. WALL BARS
FOOTING TOP BARS
FOOTING BOTTOM BARS
#6 ld ls ldh
38" 50" 15"
29" 38" 15"
#7 ld ls ldh
55" 71" 17"
42" 54" 17"
#8 ld ls ldh
62" 81" 19"
47" 62" 19"
38" 50" 15" 55" 71" 17" 62" 81" 19"
BAR SIZE
CONTRACTOR NOTE
CONCRETE WALL SHALL BE IN PLACE A MINIMUM OF 14 DAYS
BEFORE BACKFILLING. AT CONTRACTOR'S OPTION, BACKFILL MAY
BE PLACED AGAINST WALL THAT HAS BEEN TEMPORARILY SHORED;
HOWEVER, CONTRACTOR SHALL BE RESPONSIBLE FOR CORRECTING
ANY MOVEMENT OF WALL DUE TO BACKFILLING.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
CONCRETE
ALL WORK SHALL CONFORM TO THE "SPECIFICATIONS FOR STRUCTURAL
CONCRETE" (AMERICAN CONCRETE INSTITUTE, ACI 301) AND THE "BUILDING CODE
REQUIREMENTS FOR REINFORCED CONCRETE" (ACI 318), LATEST EDITIONS, UNLESS
NOTED OTHERWISE IN THE DRAWINGS OR PROJECT SPECIFICATIONS.
CONSTRUCTION TOLERANCES SHALL CONFORM TO THE "SPECIFICATION FOR
TOLERANCES FOR CONCRETE CONSTRUCTION AND MATERIALS" (ACI 117), LATEST
EDITION.
SHOP DRAWINGS SHALL BE PREPARED IN ACCORDANCE WITH THE " GUIDE TO
PRESENTING REINFORCING STEEL DESIGN DETAILS " (ACI 315) AND THE "ACI
DETAILING MANUAL" (SP-066), LATEST EDITIONS.
CONCRETE MATERIALS SHALL BE PROVIDED IN ACCORDANCE WITH THE
FOLLOWING SPECIFICATIONS:
PORTLAND CEMENT ASTM C150
HYDRAULIC CEMENT ASTM C1157
FLY ASH AND NATURAL POZZOLAN ASTM C618
SLAG CEMENT ASTM C989
SILICA FUME ASTM C1240
NORMAL WEIGHT AGGREGATE ASTM C33
LIGHTWEIGHT AGGREGATE ASTM C330
MIXING WATER ASTM C1602
ADMIXTURES
WATER REDUCTION AND SETTING TIME MODIFICATION ASTM C494
PRODUCING FLOWING CONCRETE ASTM C107
AIR ENTRAINMENT ASTM C260
INHIBITING CHLORIDE-INDUCED CORROSION ASTM C1582
REINFORCING MATERIALS:
REINFORCING BARS PLAIN-STEEL ASTM A615, GRADE 60, DEFORMED
REINFORCING BARS LOW-ALLOY-STEEL ASTM A706, DEFORMED
(WELDABLE)
REINFORCING BARS EPOXY-COATED ASTM A775
WELDED WIRE FABRIC ASTM A1064
EPOXY-COATED WELDED WIRE FABRIC ASTM A884, CLASS A COATING
REINFORCING SHALL COMPLY WITH ACI FOR FABRICATING, PLACING, AND
SUPPORTING REINFORCEMENT, AND THE FOLLOWING:
BAR SPLICE LOCATIONS SHALL CONFORM TO ACI 318
HORIZONTAL REINFORCING BARS IN WALLS AND FOOTINGS SHALL BE
CONTINUOUS AROUND CORNERS.
UNLESS DETAILED CALCULATIONS ARE PROVIDED, REINFORCING BARS
DEVELOPMENT LENGTHS, EMBEDMENT DEPTHS AND LAP SPLICE DISTANCES
FOR f'c = 4000psi, NORMAL-WEIGHT CONCRETE, SHALL BE PER BELOW
EMBEDDED AND MISCELLANEOUS STEEL SHALL COMPLY WITH ASTM A36.
CONTINUOUS WALL OR FOOTING PLACEMENT SHALL NOT EXCEED 60 FEET
BETWEEN CONSTRUCTION JOINTS.
ALL EXPOSED CONCRETE CORNERS SHALL BE CHAMFERED 3/4" AT 45 DEGREES
UNLESS NOTED OTHERWISE.
SHALLOW INTERIOR FOUNDATIONS AND SLABS ON GRADE ARE NOT DESIGNED FOR
OR INTENDED TO BE EXPOSED TO FREEZE/THAW CYCLING OR RESIST FROST
HEAVE FORCES. GENERAL CONTRACTOR TO COORDINATE CONSTRUCTION AND
PROVIDE INTERIOR FOOTINGS BELOW FROST PENETRATION AS REQUIRED FOR
WINTER CONSTRUCTION.
PROVIDE CONSTRUCTION / CONTROL JOINT INSTALLATION PLAN AND PLACEMENT
SEQUENCE PLAN SUBMITTALS FOR REVIEW OF STRUCTURAL ENGINEER OF
RECORD PRIOR TO PLACING CONCRETE.
PROVIDE WALL AND SLAB THRU-SLEEVE PLAN SUBMITTALS FOR REVIEW OF
STRUCTURAL ENGINEER OF RECORD PRIOR TO PLACING CONCRETE.
CORE-DRILLING CONCRETE WALLS, SLABS, BEAMS OR COLUMNS WITHOUT
REINFORCING LOCATION SCANS AND PRIOR APPROVAL OF STRUCTURAL ENGINEER
OF RECORD SHALL NOT BE PERMITTED.
CONDUITS AND PIPES SHALL NOT BE EMBEDDED IN ELEVATED CONCRETE SLABS
SUPPORTED BY METAL DECK OR CONCRETE SLABS ON GRADE.
FIBER REINFORCED CONCRETE SHALL COMPLY WITH "GUIDE TO DESIGN WITH
FIBER-REINFORCED CONCRETE" (ACI 544.4), LATEST EDITION. DESIGN
CALCULATIONS SHALL BE SUBMITTED AS PER THE SHOP DRAWING NOTES AND
SPECIFICATIONS.
NON-SHRINK GROUT SHALL CONFORM TO ASTM C1107 AND ACHIEVE A MINIMUM 28
DAY COMPRESSIVE STRENGTH OF 8,000 psi.
STRUCTURAL ADHESIVES SHALL ONLY BE USED WITH PRIOR PERMISSION OF THE
STRUCTURAL ENGINEER OF RECORD OR AS SHOWN ON CONSTRUCTION
DOCUMENTS. THE BASIS OF DESIGN FOR ADHESIVES IS HY-200 BY "HILTI" OR SET BY
"SIMPSON" - THE USE OF ANY OTHER STRUCTURAL ADHESIVES SHALL BE SUBJECT
TO REVIEW BY THE EOR PRIOR TO INSTALLATION.
MINIMUM WIRE WELDED FABRIC REQUIREMENTS FOR SLABS:
3-1/2" FLOOR SLAB ON METAL DECK 66-W2.9xW2.9 5" FLOOR SLAB ON METAL DECK 66-W2.9xW2.9 4" FLOOR SLAB ON GRADE 66-W2.9xW2.9 5" FLOOR SLAB ON GRADE 44-W4.0xW4.0
COLD-WEATHER CONCRETE PLACEMENT SHALL COMPLY WITH THE PROVISIONS OF
ACI 306R. THE USE OF CALCIUM CHLORIDE, SALT, AND OTHER MATERIALS
CONTAINING ANTI- FREEZE AGENTS OR CHEMICAL ACCELERATORS SHALL NOT
BE PERMITTED UNLESS ACCEPTED IN THE MIX DESIGN.
HOT-WEATHER CONCRETE PLACEMENT SHALL COMPLY WITH THE PROVISIONS OF
ACI 305.
MINIMUM CONCRETE CLEAR COVER SHALL BE PROVIDED FOR REINFORCEMENT
PER ACI AND THE FOLLOWING:
CONCRETE CAST AGAINST EARTH & PERMANENTLY 3"
EXPOSED
CONCRETE EXPOSED TO EARTH OR WEATHER
#6 & LARGER 2"
#5 & SMALLER 1-1/2"
CONCRETE NOT EXPOSED TO WEATHER OR GROUND
SLABS, WALLS, AND JOINTS 3/4"
BEAMS AND COLUMNS 1-1/2"
NOTE:
VALUES ABOVE ARE FOR NORMAL WEIGHT CONCRETE ONLY.
ld = MINIMUM TENSION DEVELOPMENT LENGTH ldh = MINIMUM 90 DEGREE HOOKED BAR DEVELOPMENT LENGTH ls = MINIMUM LENGTH OF LAP SPLICES IN TENSION
MIN. f'
EXTERIOR SLABS 5,000 6% I or II
1.
2.
a.
b.
c.
d.
e.
f.
g.
h.
3.
a.
SHOP DRAWINGS
DUPLICATION/PHOTOCOPYING OF THESE STRUCTURAL DRAWINGS SHALL NOT BE
PERMITTED FOR SHOP DRAWINGS. THIS INCLUDES PARTIAL AND/OR COMPLETE
DUPLICATION OF PLAN SHEETS AS BACKGROUNDS FOR SHOP DRAWINGS. ALL
SECTIONS INCLUDED IN THESE CONTRACT DRAWINGS MAY NOT BE
DUPLICATED/PHOTOCOPIED ON ANY SHOP DRAWINGS.
ORIGINAL SHOP DRAWINGS SHALL BE SUBMITTED FOR THE ARCHITECT/ENGINEER
REVIEW FOR THE FOLLOWING ITEMS AND AS PER THE SPECIFICATIONS:
CONCRETE AND MASONRY REINFORCING
SLAB ON GRADE CONTROL JOINT LAYOUT
CONCRETE MIX DESIGNS
FOUNDATIONS
RETAINING WALLS
ELEVATED SLABS
SLAB ON GRADE LISTING FIBER MESH REINFORCEMENT & DOSAGE RATE
MASONRY CERTIFICATIONS AND GROUT DESIGN
STEEL JOIST AND DECKING
STRUCTURAL STEEL
LIGHT GAGE METAL FRAMING
PRECAST CONCRETE
CONTRACTOR SHALL SUBMIT, FOR REVIEW, DRAWINGS AND CALCULATIONS FOR
ALL PERFORMANCE ASSEMBLIES IDENTIFIED IN THE GENERAL NOTES AND SPECIFIC
MATERIAL NOTES AS WELL AS LISTED BELOW: THE DESIGN OF THESE ASSEMBLIES
IS THE RESPONSIBILITY OF THE CONTRACTOR'S ENGINEER REGISTERED IN THE
PROJECT'S JURISDICTION. ALL SUBMITTALS SHALL BEAR THIS ENGINEER'S SEAL
AND SIGNATURE. REVIEW SHALL BE FOR GENERAL CONFORMANCE WITH THE
PROJECT REQUIREMENTS AS INDICATED ON THE DRAWINGS AND IN THE GENERAL
NOTES.
METAL STAIRS AND METAL RAILINGS: DESIGNS SHALL TAKE INTO ACCOUNT
ALL VERTICAL AND LATERAL LOADS REQUIRED BY APPLICABLE BUILDING
CODES. WHERE HEADERS OR OTHER TYPES OF STRUCTURAL MEMBERS
HAVE BEEN DESIGNATED BY THE STRUCTURAL ENGINEER OF RECORD TO
SUPPORT THE STAIRS, THE CONNECTIONS FROM THE STAIRS SHALL BE
DESIGNED SO THAT NO ECCENTRIC OR TORSIONAL FORCES ARE INDUCED
IN THESE STRUCTURAL MEMBERS. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR FURNISHING AND INSTALLING HARDWARE AS REQUIRED
BY THE STAIR DESIGN.
1.
2.
3.
4.
5.
6.
a.
b.
c.
d.
e.
f.
7.
8.
9.
GENERAL NOTES
THE CONTRACTOR IS ADVISED THAT ALL PLANS, DIMENSIONS, AND DETAILS DEPICT
FIELD CONDITION AS SHOWN. MINOR VARIATIONS ARE TO BE EXPECTED AND ANY
DEVIATIONS FROM THE CONTRACT DOCUMENTS SHALL BE APPROVED BY THE
ARCHITECT IN WRITING PRIOR TO PROCEEDING.
THE CONTRACTOR SHALL FIELD CHECK AND VERIFY ALL DIMENSIONS AND
ELEVATIONS OF EXISTING WORK PRIOR TO FABRICATION OF ANY NEW MATERIALS.
IF THE EXISTING FIELD CONDITIONS DO NOT PERMIT THE INSTALLATION OF THE
WORK IN ACCORDANCE WITH THE DETAILS SHOWN, THE CONTRACTOR SHALL
NOTIFY THE ENGINEER IMMEDIATELY AND PROVIDE A SKETCH OF THE CONDITION
WITH THEIR PROPOSED MODIFICATION OF THE DETAILS GIVEN ON THE CONTRACT
DOCUMENTS. DO NOT COMMENCE WORK UNTIL CONDITION IS RESOLVED AND
MODIFICATION IS APPROVED BY THE ENGINEER.
IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE THE LOCATION OF
UTILITIES IN THE IMMEDIATE VICINITY OF CONSTRUCTION SO AS TO PREVENT
DAMAGE TO THEM. SHOULD DAMAGE TO SUCH UTILITIES OCCUR, THE CONTRACTOR
SHALL BE REQUIRED TO REPAIR SUCH DAMAGE AT THEIR OWN EXPENSE AND TO
THE SATISFACTION OF THE OWNER.
SHOP DRAWINGS FOR ALL STRUCTURAL ELEMENTS SHOWN ON THE CONTRACT
DOCUMENTS MUST BE SUBMITTED BY THE GENERAL CONTRACTOR AND REVIEWED
BY THE ENGINEER. IF THE CONTRACTOR OR OWNER FAILS TO OBTAIN ENGINEER'S
REVIEW OF THE SHOP DRAWINGS, THE ENGINEER WILL NOT BE RESPONSIBLE FOR
THE STRUCTURAL CERTIFICATION AND DESIGN OF THE PROJECT. SHOP DRAWINGS
ARE REVIEWED BY THE ENGINEER AS A CONVENIENCE TO THE GENERAL
CONTRACTOR AND ARE NOT A CONTRACT DOCUMENT.
LOADS GREATER THAN THE DESIGN LIVE LOADS SHALL NOT BE PLACED ON THE
STRUCTURE. A CONCRETE STRUCTURE MAY NOT SUPPORT IT'S DESIGN LIVE LOAD
FOR 28 DAYS. CONTRACTOR SHALL SUPPORT ADJACENT STRUCTURES, UTILITIES,
AND EXCAVATIONS AS REQUIRED. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS
FOR ALL TEMPORARY FORM WORK, SHEETING, SHORING AND UNDERPINNING
SEALED BY A PROFESSIONAL ENGINEER AS A PART OF THE CONTRACTOR'S WORK.
THE CONTRACTOR SHALL CONSULT THE ARCHITECTURAL, MECHANICAL, AND
ELECTRICAL DRAWINGS FOR THE QUANTITY, LOCATION, AND DIMENSION OF HOLES
THROUGH FLOOR AND ROOF: CHASES, INSERTS, OPENINGS, SLEEVES, WASHERS,
DRIPS, REVEALS, DEPRESSIONS AND OTHER PROJECT REQUIREMENTS. REFER TO
ARCHITECTURAL DRAWINGS FOR THE FOLLOWING INFORMATION:
LOCATION AND THICKNESS OF MASONRY PARTITIONS
FULL EXTENT OF MASONRY INFILL AREAS
LOCATION AND THICKNESS OF STUD PARTITIONS
LOCATION AND SIZE OF WINDOWS, DOORS AND WALL OPENINGS
STAIRS, FLOOR AND WALL FINISHES
DETAIL DIMENSIONS AND SECTION DETAILS AS REQUIRED
THIS STRUCTURE HAS BEEN DESIGNED TO BE SELF-SUPPORTING AND STABLE
AFTER THE CONSTRUCTION OF THE BUILDING IS TO BE COMPLETED. THE STABILITY
OF THE STRUCTURE PRIOR TO COMPLETION IS SOLELY THE RESPONSIBILITY OF
THE CONTRACTOR. THIS RESPONSIBILITY EXTENDS TO ALL RELATED ASPECTS OF
THE CONSTRUCTION ACTIVITY INCLUDING, BUT NOT LIMITED TO, ERECTION
METHODS, ERECTION SEQUENCE, TEMPORARY BRACING, FORMS, SHORING, USE OF
EQUIPMENT AND SIMILAR CONSTRUCTION PROCEDURES.
THE CONTRACTOR SHALL BE RESPONSIBLE TO DETERMINE ALLOWABLE
CONSTRUCTION LOADS AND TO PROVIDE DESIGN AND CONSTRUCTION OF
FALSEWORK, FORMWORK, STAGING, BRACING, SHEETING, SHORING, AND
UNDERPINNING AS NECESSARY TO PREVENT ANY LATERAL OR VERTICAL
MOVEMENTS TO, AND TO INSURE THE STRUCTURAL INTEGRITY OF EXISTING
BUILDINGS, STREETS, AND ANY EXISTING UTILITY LINES.
BRACING, SHEETING, SHORING, ETC., REQUIRED TO INSURE THE STRUCTURAL
INTEGRITY OF THE EXISTING BUILDINGS OR NEW CONSTRUCTION, SIDEWALKS,
UTILITIES ETC., SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER ENGAGED BY
THE CONTRACTOR. DETAILED SIGNED AND SEALED SHOP DRAWINGS SHALL BE
PREPARED INDICATING ALL WORK TO BE PERFORMED. SUBMIT THE SHOP
DRAWINGS IN ACCORDANCE WITH THE CONTRACT REQUIREMENTS.
b. COLUMNS, BASE PLATES & ANCHOR RODS: DESIGN SHALL TAKE INTO ACCOUNT
ALL VERTICAL AND LATERAL LOADS REQUIRED BY APPLICABLE BUILDING CODES
TO SUPPORT THE DELEGATED DESIGN STAIR.
JOB:
1120724.000
COPYRIGHT 2025
DRAWN:
SCALE:
AS NOTED
DATE:
02/11/2026
P MGR:
APPRD:
CHK
DSGN:
BU
IL
D
IN
G U
PG
R
AD
ES
O R
AN
G
EV
IL
LE
M
AN
O
R
M
IL
L
ST
O
R
AN
G
EV
IL
LE
, P A
R
EV
IS
IO
N S
D
AT
E
BY
SHEET:
Is su ed fo r B id
2/
/2
FO
U
N D
AT
IO
N N
O
TE
S, S
C H
ED
U
LE
S, A N
D D
ET
AI
LS
S2.0
DESIGN LOADS:
DESIGN FLOOR LIVE LOADS
FLOOR 15 PSF
a.
b.
c.
d.
ADDITIONAL NOTES:
THE CONTRACTOR IS CAUTIONED AS TO NOT STORE ANY
CONSTRUCTION MATERIALS OR UNDERTAKE ANY CONSTRUCTION
OPERATION WILL EXCEED THE DESIGN LIVE LOAD CAPACITIES NOTED.
THE STRUCTURE HAS BEEN DESIGNED FOR THE DEAD AND LIVE
LOADS INDICATED ABOVE,…