FAQ 1b NEW GENERATOR SET DATA 27nov2019.docx
DOCX document 26 KB Posted
- Attached to
- Purchase and Installation of one generator at the premises of the U. S. Embassy in Athens, Greece.
- Solicitation number
- 19GR1020Q0002
- Issued by
-
Department of State US Embassy Athens
About this file
This document outlines the requirements for a solicitation to purchase and install one generator at the U.S. Embassy in Athens, Greece. The U.S. Department of State will issue a solicitation on the Federal Business Opportunities website to acquire a single generator set that includes an indoor Caterpillar diesel-fueled packaged generator rated at 1200KW/1500kVA prime power output. The generator set must include an automatic voltage regulator, engine control module, formed steel base, seismic certification, vibration isolators, 800 gallon day tank with fuel return pump and alarms, engine coolant and lube oil, radiator, hospital grade silencer, dual electric starting system, batteries and charger, jacket water heater, and digital control panel. The control panel must provide generator and engine monitoring and protection functions along with control capabilities. The Government intends to award a firm fixed price contract to the lowest priced technically acceptable offeror and may make the award without discussions.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 19GR1020Q0002_Amendment_01.docx | DOCX document | |
| FAQ 1a EXISTING GENERATOR DATA 27nov2019.docx | DOCX document | |
| FAQ 1 Questions_And_Answers 27nov2019.docx | DOCX document | |
| 19GR1020Q0002.docx | DOCX document | |
| APPENDIX_B_EXISTING_GENERATOR_ENCLOSURE_DWG.pdf | ||
| APPENDIX_B_EXISTING_GENERATOR_AREA_LAYOUT.pdf | ||
| APPENDIX_A_Specification_263214_Engine_Generators.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERATOR SET – BILL OF MATERIAL
Two (2) New Indoor Caterpillar Diesel-Fueled Packaged Generator Set 3512 with Brushless Generator, 1200KW/1500kVA Prime Rated, , 0.8P.F., 400/230V, Three-Phase, 50 Hertz at 1500 RPM Each Generator Set to Include the following attachments and accessories:
· Automatic Voltage Regulator
· ADEM III Engine Control Module
· Formed Steel Base
· IBC Seismic Certified Package
· Seismic Rated Spring-Type Vibration Isolators
· 800 Gallon, 8-Hour Runtime at Full Load, Sub-base Day Tank. UL-142 Listed, Double-Walled Construction. Installed under generator set prior to shipment. 10 GPM Fuel Return Pump with Controls. Overfill Level and Low Level Alarms. (3) Spare 2" NPT Fittings in Tank and (1) Spare 2" NPT Fitting in Interstitial Area for Customer Supplied Fuel Monitoring System.
· 50/50% Coolant Mix and Lube Oil Installed
· 105 Degree C over 40 Degree Ambient Temperature Rise Rated Alternator
· Permanent Magnet Generator Excitation
· Anti-Condensation Space Heater
· Engine Mounted Radiator with Blower Fan. Rated for 50 degree C ambient cooling capability
· 12" Inlet/Outlet Hospital Grade Silencer. Exhaust system includes flex connection and Nuts/Bolts/Gasket Kits. Shipped loose for contractor installation
· Dual Electric Starting System, 24VDC
· (4) Batteries, 24VDC System, Lead Acid Type, to include Battery Rack and Cables
· Battery Charger, Auto-Equalize, 24VD, 20 Amp Output, 120 or 208-240VAC Single-Phase Input Is Required. Shipped Loose for Contractor Installation
· Jacket Water Heater, 9000W, 208-240VAC Single-Phase Input Is Required
· Shipped Loose Digital Generator control panel, Micro-processor controlled, EMCP 4.2, NFPA Compliant, NEMA 1 enclosure, generator mounted, to include the following:
· Generator Monitoring:
· Voltage (L-L, L-N); Current (Phase); Average Volt, Amp, Frequency; kW, kVAr, kVA (Average, Phase, %); Power Factor (Average, Phase); kW-hr, kVAr-hr (Total); Excitation Voltage and Current (with Optional CDVR); Generator Stator & Bearing temp. (with Optional Module) , Generator 'RUN' Relay, Common Alarm Volt Free Contacts
· Generator Protection:
· Generator Phase Sequence; Over/Under Voltage (27/59); Over/Under Frequency (81 O/U); Reverse Power (kW) (32); Reverse Reactive Power (kVAr) (32RV); Over-Current (50/51)
· Engine Monitoring:
· Coolant Temperature; Oil Pressure; Engine Speed (RPM); Battery Voltage; Run Hours; Crank Attempt & Successful Start Counter; Enhanced Engine Monitoring ( with Electronic Engines)
· Engine Protection:
· Control Switch Not in Auto (Alarm); High Coolant Temp. (Alarm & Shutdown); Low Coolant Temp. (Alarm); Low Coolant Level (Alarm & Shutdown); High Engine Oil Temp. (Alarm & Shutdown); Low, High and Weak Battery Voltage; Over-speed; Over-crank
· Control:
· Run / Auto / Stop Control; Speed & Voltage Adjust; Local & Remote Emergency Stop; Remote Start/Stop;
Cycle Crank
· Inputs & Outputs:
· Two Dedicated Digital Inputs; Six Programmable Digital Inputs; Six Programmable Form A Dry Contacts;
Two Programmable Form C Dry Contacts; Two Digital Outputs
· Communications:
· Primary & Accessory CAN Data Links; RS-485 Annunciator Data Link; Modbus RTU (RS-485 Half Duplex)
· Circuit Breakers o Main Breaker - Unit Mounted 3000A, 3 Pole, LSIG-P Electronic Trip