Site Assessment and Recommendations

Concrete Potable Water Storage Tank and

Fire Water Storage Tanks

U.S. Embassy Suva, Fiji

Prepared for:

The United States Department of State Office of Overseas Building Operations

March 9, 2018

CMT

U.S. Embassy, Suva, Fiji

TABLE OF CONTENTS

Site Assessment and Recommendations Concrete Water Storage Tanks: Two Fire Usage Tanks and One Potable Water Tank section page

Project Abstract

• Cleaning Process

• Inspection Process

• Inspection Findings

2 Recommendations 4

Inspection Summary including tank drawings and photos

• Fire Tank 1

• Fire Tank 2

• Potable Tank 3

4 Drawing Key 24

Appendix

• CIM 1000 Trowel Grade

• CIM 61BG

• CIM 1061

• CIM Bonding Agent

• Application of CIM to Concrete

• Applying CIM within Confined Spaces

• Repair Detail Drawing

PROJECT ABSTRACT

Carolina Management Team was contracted by the U.S. Embassy in Suva, Fiji to assess and clean its concrete water storage tanks to determine recommendations for possible repairs and coating.

The Embassy’s water storage facilities consist of three concrete water storage tanks located in the basement of the compound. Two of the tanks are for the fire suppression system and one tank is for potable use. The two fire tanks and one potable water tank had not been drained, cleaned, or inspected since entering into service in 2011. The Embassy wants to use the fire tanks as a backup to the potable water tank when low flow conditions occur from the city water supply.

The fire storage tanks have a combined capacity of 188,000 liters and are interconnected. The potable water tank has a storage capacity of 12,000 liters. The internal walls of all tanks are coated with black CIM 1061. The access hatch, measuring 600mm x 800mm in size, is accessible via a fixed ladder and work platform.

The project team consisted of one inspector, one confined space attendant, and two technicians.

The project team conducted the cleaning, assessment, and super chlorination of the three water storage tanks at the Embassy from February 12, 2018 to February 17, 2018. The assessment of the two fire tanks and one potable tank was conducted by David Van Zee, Co-Owner of Carolina Management Team and a NACE Level 3 and SSPC Certified Coatings Inspector.

The purpose of this assessment was to inspect the structural integrity of the three tanks, as well as inspect the viability of the coatings on the three tanks.

Each of the three tanks was cleaned as well as inspected.

Cleaning Process

• 4,000 PSI water blaster was used with a 0 degree rotary nozzle to clean the film buildup on the tanks

• The specification requested that the tanks be cleaned by hand using no cleaning agents. Due to the nature of the film on the tanks, hand cleaning proved to be insufficient and special care was taken during the water blasting process, as not to damage the existing coatings

• Photos of the initial tank condition were taken upon arrival

PROJECT ABSTRACT

Inspection Process The assessment was a visual inspection with photos taken. In addition:

• Samples of delaminated coatings were taken

• Close inspection of the substrates was noted to determine the likely cause of failure

• The substrate surface profiles were compared to ICRI replica coupons and noted

• Defects of the coating system were noted on drawings

• Concrete was sounded with a hammer to determine if concrete delamination or hollow spots were present

This inspection was limited to nondestructive tests. It is possible that unknown conditions exist and that these conditions cannot be identified until removal of the coating system. It was not possible to determine the moisture vapor transmission rate because it would require destruction of the existing coating. Therefore, contingency measures should be considered prior to repairs being made to the coating system.

Other contingency measures that should be considered are ground water intrusion, insufficient (or too aggressive) substrate surface profile, exposed rebar, and poor concrete conditions. An additional assessment should be conducted after the coating defects are removed to address any conditions that do not meet the repair procedures specified in the latest version of the CIM IG-2 Instruction Guide Application of CIM to concrete. See attached Appendix.

Inspection Findings The visual inspections of the three tanks revealed that all tanks appear to be structurally sound. The visual inspections found the concrete to be sound, with no major cold joint separation cracks, and no exposed rebar or rebar rust staining. There are several coating defects in the lining system that have delaminated and could cause catastrophic failure to the fire suppression system.

Delaminated coating material could potentially get sucked into the fire pumps and clog the sprinkler heads.

All three tanks have delaminating coatings around the pipe penetrations that are below the water line. The steel fire pump suction pipe and diffuser are severely corroded around the nuts and bolts, and moderately corroded on the pipe and base plate. In the potable water tank, the effluent chlorine diffuser plate bolts are severely corroded and there is minor corrosion on the plate itself.

TANK 3

TANK

TANK

north w es t east south

RECOMMENDATIONS

Fire Water Tank 1 The failure of the coating system on various areas of the floor and walls creates the possibility that the delaminated coating could clog the sprinkler heads causing catastrophic failure to the fire suppression system. As result, we recommend:

• Removing the coating from the floor and from 1 foot above the wall, saw cut terminations, mechanically abrade 6” overlap to the existing coating, prime and coat per instruction guide CIM IG-2. Application of CIM to Concrete using CIM 1061 or CIM 1000 Trowel Grade

• Repairing any coating failures on walls and pipe penetrations by removing delaminated areas, saw cut terminations, mechanically abrade 6” overlap to the existing coating, prime and coat per instruction guide CIM IG-2. Application of CIM to Concrete using CIM 1000 Trowel Grade

• Preparing the fire tank effluent steel pipe aid diffuser plate per SSPC- SP11 “Hand/power tool clean to bare metal” with a 2-3 mil profile.

Applying 2 coats of NSF 61 Epoxy at 4-8 mils per coat

Fire Tank 2 The failure of the coating system on various areas of the walls creates the possibility that the delaminated coating could clog the sprinkler heads causing catastrophic failure to the fire suppression system. As result, we recommend:

• Repairing any coating failures on walls, floor, and pipe penetrations by removing delaminated areas, saw cut terminations, mechanically abrade 6” overlap to the existing coating, prime and coat per instruction guide CIM IG-2. Application of CIM to Concrete using CIM 1000 Trowel Grade

• Preparing the fire tank effluent steel pipe and diffuser plate per SSPC- SP11 “Hand/power tool clean to bare metal” with a 2-3 mil profile.

Applying 2 coats of NSF 61 Primer at 4-8 mils per coat

Potable Water Tank 3 We recommend that recoating of this tank is optional because the failure of the coating system on various areas of the floor and walls is not causing water quality issues and the tanks are not leaking. If a decision is made to repair the lining system, note the manufacturer’s two week cure time requirement for potable water service.

• Repairing any coating failures on walls, floor, and pipe penetrations by removing delaminated areas, saw cut terminations, mechanically abrade 6” overlap to the existing coating, prime and coat per instruction guide CIM IG-2. Application of CIM to Concrete using CIM 1000 Trowel Grade

• Preparing the fire tank effluent steel pipe and diffuser plate per SSPC- SP11 “Hand/power tool clean to bare metal” with a 2-3 mil profile.

Applying 2 coats of NSF 61 Primer at 4-8 mils per coat

INSPECTION SUMMARY

page drawing photos 540-571 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-12

Entry was made into this tank on Tuesday, February 13, 2018 and Wednesday, February 14, 2018. The tank was accessed through a manway entry approximately 3 meters up the side of the tank, measuring 600mm x 800mm. Upon entry, the tank had 254mm to 305mm of water at the bottom due to the drain line being located on the side of the tank. Draining the excess water from the bottom of the tank took approximately 2 hours using a trash pump.

Tank #1 was cleaned by water blasting using 4,000 PSI and a rotary nozzle. Most of the film build up was removed from the walls and ceiling, with the exception of areas with coating failure that would have been too destructive to clean. The floor of the tank had an inter-coat delamination between the two coats of CIM 1061. Through visual inspection, the most likely causes of this failure are a lack of film build (about 5-8 mils) and exceeding the maximum recoat window of 4 hours. The extent of the

TANK 1

Fire Water Tank – inspection summary page 1 of 7 failure exceeds 30% of the floor area, which leads us to recommend complete removal of the floor coatings. The pipe penetrations, patched areas, and area where the floor coating met the wall coating have delaminated. The cause of this failure was most likely due to the lack of required surface prep when the recoat window was exceeded, as well as lack of film build. Per the manufacturer’s instructions for CIM IG-2 (Instruction Guide Application of CIM to Concrete 5.9), recoating after missing the recoat window requires that the entire patched area be severely abraded and lap joints shall be a minimum of 6”. Other areas of delamination in the tank were caused by moisture “blisters” and lack of film build “pin holes.” Coating thickness should have been 60 mils. Other minor coating issues existed, such as coating runs on the walls and evidence of the coating dripping from the ceiling. Neither of these coating defects requires repair measures.

See drawings for location and type of coating defects.

U .S . Embassy, Suva, Fiji

INSPECTION SUMMARY

TANK 1

Fire Water Tank – inspection drawing page 2 of 7 west wall north wall north wall w es t w al l

’ 7

10”

22’ 5” east w all south wall

FLOOR

east wall south wall north wall w es t w al l w es t w al l east w all south wall

CEILING

ICRI CSP

�re pump

ICRI CSP ICRI CSP 4-6 on walls delamination to substrate di�user spot corrosion and pitting delamination to substrate split in corner abraded area but no recoat gaugeD EF

EF

OF RF

LI

IP

LI

EC

ED

ED

ABBREVIATION KEY

D Drain OF Over�ow LI Level Indicator RF Recirculating Fire IP In�uent Potable EC E�uent Chlorine ED E�uent Domestic EF E�uent Fire EQ Equalization

DRAWING KEY

inter-coat delamination joint delamination patch delamination blisters (size + frequency) delamination (substrate or topcoat) excessive runs pinhole in coating (size + frequency) ceiling drips

540 548 553

561 562

563 564

565541 delamination to substrate

1/2” - 1” x 50/sq ft depression

100/sq ft covering entire ceiling

4’ x 4’ patch delamination to topcoat coating well bonded to substrate missing bolt missing bolt

INSPECTION SUMMARY

west wall patch delamination joint delamination patch delamination missing bolt on ladder patch delamination

TANK 1

Fire Water Tank – photos page 3 of 7

INSPECTION SUMMARY

patch delamination joint delaminationdiffuser spot corrosion and pitting north wall pinhole delamination to substrate gauge

TANK 1

Fire Water Tank – photos page 4 of 7

INSPECTION SUMMARY

east wall pinhole delamination to substrate delamination to substrate blisters

TANK 1

Fire Water Tank – photos page 5 of 7 delamination to sub

INSPECTION SUMMARY

south wall abraded area pinholes and delamination delamination to topcoat abraded area

TANK 1

Fire Water Tank – photos page 6 of 7 split in corner

INSPECTION SUMMARY

delamination to topcoat ceiling drips depression on east wall

TANK 1

Fire Water Tank – photos page 7 of 7 delamination to topcoat

INSPECTION SUMMARY

TANK 2

Fire Water Tank – inspection summary page 1 of 7 page drawing photos 604-637 . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-18

Entry was made into this tank on Thursday, February 15, 2018. The tank was accessed through a manway entry approximately 3 meters up the side of the tank, measuring 600mm x 800mm. Upon entry, the tank had 254mm to 305mm of water at the bottom due to the drain line being located on the side of the tank.

Draining the excess water from the bottom of the tank took approximately 2 hours using a trash pump.

Tank #2 was cleaned by water blasting using 4,000 PSI and a rotary nozzle. Most of the film build up was removed from the walls and ceiling, with the exception of areas with coating failure that would have been too destructive to clean. The floor of the tank did not have inter-coat delamination as in Tank #1—therefore, removal of the floor coating in this tank is not necessary. The pipe penetrations, patched areas, and area where the floor coating met the wall coating have delaminated similarly to Tank #1.

INSPECTION SUMMARY

TANK 2

Fire Water Tank – inspection drawing page 2 of 7 west wall north wall north wall w es t w al l

’ 6

10”

’ 9

22’ 5” east w all south wall

FLOOR

east wall south wall north wall w es t w al l east w all south wall

CEILING

�re pump

ICRI CSP 2-6

D

EQ

OF topcoat to substrate drips from ceiling

RF

LI

IP

LI

EC

ED

EF

ABBREVIATION KEY

D Drain OF Over�ow LI Level Indicator RF Recirculating Fire IP In�uent Potable EC E�uent Chlorine ED E�uent Domestic EF E�uent Fire EQ Equalization

DRAWING KEY

inter-coat delamination joint delamination patch delamination blisters (size + frequency) delamination (substrate or topcoat) excessive runs pinhole in coating (size + frequency) ceiling drips

625 631

611 612 616

1/8” - 1/4” x 30/sq ft

100/sqft covering entire ceiling

1/4” - 3/4” 30/sq ft

1/4” - 3/4” 20/sq ft

1/4” - 3/8” 10/sq ft

�oor in better shape because little delamination thin

1/8” - 3/4” x 100/sq ft over entire �oor

INSPECTION SUMMARY

west wall delamination patch delamination patch delamination effluent fire patch delamination

TANK 2

Fire Water Tank – photos page 3 of 7

INSPECTION SUMMARY

patch delamination delamination patch delamination patch delamination patch delamination in corner north wall

Fire Water Tank – photos page 4 of 7

INSPECTION SUMMARY

patch delamination in corner east wall joint delamination blisters delamination blisters

Fire Water Tank – photos page 5 of 7

INSPECTION SUMMARY

delamination south wall blisters in corner severe delamination joint delamination patch delamination

628 631

629 632

630 633

Fire Water Tank – photos page 6 of 7

INSPECTION SUMMARY

joint delamination south-west corner blisters in corner ceiling blisters on floor close-up of ceiling drips

634 637

635 604

636 605

Fire Water Tank – photos page 7 of 7

INSPECTION SUMMARY

TANK3

Potable Water Tank – inspection summary page 1 of 5 page drawing photos 672-687 . . . . . . . . . . . . . . . . . . . . . . . . . . . 21-23

Entry was made into this tank on Saturday, February 17, 2018. The tank was accessed through a manway entry approximately 3 meters up the side of the tank, measuring 600mm x 800mm. Upon entry, the tank had 254mm to 305mm of water at the bottom due to the drain line being located on the side of the tank.

Draining the excess water from the bottom of the tank took approximately 20 minutes using a trash pump.

Tank #3 was cleaned by water blasting using 4,000 PSI and a rotary nozzle. Most of the film build up was removed from the walls and ceiling, with the exception of areas with coating failure that would have been too destructive to clean. Failure in this tank was limited to pipe penetrations and a few patched areas.

INSPECTION SUMMARY

TANK3

Potable Water Tank – inspection drawing page 2 of 5 west wall north wall south wall north wall w es t w al l

’ 6

3’

10’ 10” east w all south wall

FLOOR

east wall

EC

OFLI

IP

MS

ABBREVIATION KEY

D Drain OF Over�ow LI Level Indicator MS Main Suction IP In�uent Potable EC E�uent Chlorine ED E�uent Domestic ICC In�uent Chorine Circulator Return

DRAWING KEY

inter-coat delamination patch delamination blisters (size + frequency) excessive runs pinhole in coating (size + frequency) ceiling drips

681673

ED

ICC

LI

D north wall w es t w al l east w all south wall

CEILING

very thin coating

INSPECTION SUMMARY

runs in coating delamination on floor east wall west wall patch delamination diffuser

672 675

673 676

674 677

TANK 3

Potable Water Tank – photos page 3 of 5

INSPECTION SUMMARY

delamination pipe and diffuser pinhole drain excessive runs excessive runs

680 683

681 684

682 685

Potable Water Tank – photos page 4 of 5

INSPECTION SUMMARY

underside of diffuser ceiling drips

686 687

Potable Water Tank – photos page 5 of 5

DRAWING KEY

TYPE CAUSE REMEDY

inter-coat delamination

Missed recoat window and/or low film build causing the coating to disbond to a previous coat

• Remove disbonded area

• Saw cut terminations

• Severely abrade 6” overlap area

• Recoat per the manufacturer’s recommendations patch delamination

Missed recoat window and/or low film build causing the coating to disbond to the previous coat

• Remove disbonded area

• Saw cut terminations

• Severely abrade 6” overlap area

• Recoat per the manufacturer’s recommendations delamination of overlap joints

Missed recoat window with insufficient surface prep

• Remove disbonded area

• Saw cut terminations

• Severely abrade 6” overlap area

• Recoat per the manufacturer’s recommendations blistered area that has disbonded to the substrate (size + frequency)

Moisture in the concrete

• Remove disbonded area

• Saw cut terminations

• Severely abrade 6” overlap area

• Recoat per the manufacturer’s recommendations pinholes (size + frequency)

Insufficient film build or excessive off-gassing of the concrete

If pin holes have caused disbondment:

• Remove disbonded area

• Saw cut terminations

• Severely abrade 6” overlap area

• Recoat per the manufacturer’s recommendations If the pinholes have not caused disbondment:

• Patch the area per the manufacturer’s recommendations excessive runs Film build too high No repair is required ceiling drips Film build too high No repair is required

©CIM 11/06

DESCRIPTION CIM 1000 Trowel Grade is a tough, liquid applied, two component, chemical and corrosion resistant urethane elastomer coating, chemically thickened to allow trowel applications with minimum sag. CIM 1000 Trowel Grade can be used as a crack filler or for application to vertical surfaces and corner flashings. CIM 1000 Trowel Grade offers the same advan-tages as CIM 1000 and is approved for contact with potable water in accordance with ANSI/NSF 61. CIM 1000 Trowel Grade may be applied at thicknesses up to 250 mils on vertical surfaces.

ADVANTAGES CIM 1000 Trowel Grade offers exceptional waterproofing performance in a formulation modified to allow vertical or free form trowel application:

• ANSI/NSF 61 certified for potable water contact up to 180ºF.

• Forms a tough elastomeric coating able to bridge cracks and fill joints.

• Chemically thickened for application to vertical surfaces, cold joints, cant strips and cracks.

• Used for repairs or for forming flashings and seals around pipes and roof penetrations.

• Can be applied to complex tanks with multiple penetrations, sumps, and irregular shapes.

• Adheres to and bridges between common construction materials such as concrete, steel, glass, wood, and most coatings.

• Environmentally sound, complying with the toughest VOC standards.

• Can be repaired when damaged or when new penetrations are added.

• Excellent wear and abrasion service.

• UV stable.

SURFACE PREPARATION

GENERAL: Substrates must be clean and dry with no oils, grease or loose debris. CIM Bonding Agent is recommended on all non-porous substrates. Perform adhesion tests to confirm adequacy of surface preparation. See C.I.M. Industries’ specific substrate Instruction Guide for specific guidelines.

CONCRETE: ICRI-CSP 4-6 surface profile exposing aggregate. Concrete must exhibit minimum 3,000 psi compressive strength and be free of release agents and curing compounds. The substrate must be clean and dry (see CIM Instruction Guide IG-2), and free of contaminates.

STEEL: Minimum 3 mil profile.

Immersion service – SSPC-SP10 / NACE No. 2 Near White Blast.

Non-Immersion service – SSPC-SP6 / NACE No. 3 Commercial Blast.

Use CIM Bonding Agent for greater adhesion.

OTHER METALS: SSPC-SP1 solvent clean and abrasive blast to roughen and degloss the surface.

Use CIM Bonding Agent for greater adhesion.

GLASS: Thoroughly clean. CIM Bonding Agent must be used for increased adhesion. For immersion service roughen the surface.

WOOD: Substrate must be clean, dry and free of surface contamination.

PREVIOUS COATINGS CIM 1000 Trowel Grade may be applied over some existing coatings and linings and

AND LININGS: achieve acceptable performance. CIM Bonding Agent is recommended for greater adhesion.

Finished system results vary due to a variety of project specific factors, including the service conditions to which the system is exposed. Therefore, C.I.M. Industries does not accept responsibility for determining the suitability of an existing coating as a substrate for CIM products. Owner shall perform adhesion tests on any existing coating or lining to determine suitability.

EARTH: Use CIM Scrim.

COLOR CIM 1000 Trowel Grade is initially shiny black, turning dull over 3 to 6 months when exposed to direct sunlight. For a colored or reflecting surface finish, see C.I.M Industries’ Instruction Guide, “Topcoats” (IG–7) for further instructions.

SOLIDS BY VOLUME 89%

RECOMMENDED Recommended minimum thickness at all points of the coating is 60 wet mils. Higher

COVERAGE coverages may be specified, but extended time is required to insure proper solvent release prior to placing the liner in potable water service. Contact C.I.M. Industries for additional information.

VOC 88 g/l (0.74 lb./gal.). CIM 1000 Trowel Grade complies with the toughest VOC regulations.

CIM 1000 Trowel Grade

HIGH PERFORMANCE COATINGS AND LININGS

COATING PROFILE

C.I.M.

Industries Inc.

Abrasion Resistance–Wt. Loss, Taber Abraser CS–17 Wheel 1000 gr./1000 rev.

ASTM D4060 1.2 mg. Loss

Adhesion to Concrete (dry) Elcometer 350 psi

Deflection Temperature ASTM D648 below -60ºF

Density (Approx.)

Premix 7.9 lbs./gal.

Activator 10.1 lbs./gal.

Mixed & Cured 8.3 lbs./gal.

Elastomeric Waterproofing ASTM C836 exceeds all criteria ASTM C957 exceeds all criteria

Extension to Break

ASTM D412 300%

Flammability ASTM D2859 pass/combustible substrate UL790 Class A1

Hardness, Shore A

ASTM D2240 @ 77ºF 60

Jet Fuel Resistance FS SS-S-200D pass for joints

Liner Performance Crack Bridging

10 cycles @ -15ºF greater than 1/8” After heat aging greater than 1/4”

Liner Weight (60 mils wet film thickness) 31 lbs./100 sq. ft.

Mix Ratio Weight 6.1:1 Volume 7.7:1

Mullen Burst Strength ASTM D751, 50 mil 150 psi

Permeability to Water Vapor ASTM E96 Method E, 100ºF, 100 mil sheet 0.03 perms

Potable Water Service

ANSI/NSF 61

Approved to 180ºF

Recovery from 100% extension after 5 minutes 98% after 24 hours 100%

Salt Spray ASTM B117 pass 2000 hrs.

Service Temperature -60ºF to 220ºF

Softening Point, Ring & Ball

ASTM D36 >325ºF

Tear Strength ASTM D624 (Die C) 150 lbs./in.

Tensile Strength ASTM D412, 100 mil sheet 800 psi

Weathering ASTM D822 pass 5000 hrs.

CIM 1000 Trowel Grade

HIGH PERFORMANCE COATINGS AND LININGS

All information presented in this publication is believed to be accurate, but it is not to be construed as a guarantee of minimum performance. Test performance results are obtained in a controlled laboratory environment using procedures that may not represent actual operating environments.

TYPICAL PROPERTIES

C.I.M.

Industries Inc.

CHEMICAL RESISTANCE

CIM 1000 Trowel Grade is resistant to a broad range of acids and alkalis. Consult C.I.M. Industries for additional information regarding chemical resistance after reviewing CIM 1000 Chemical Resistance Chart.

THE INFORMATION PRESENTED IN THIS PUBLICATION IS SUBJECT TO CHANGE WITHOUT NOTICE.

CONTACT C.I.M. INDUSTRIES FOR CURRENT INFORMATION.

www.cimindustries.com

1Contact C.I.M. Industries for details regarding UL fire ratings

USE FOR PROFESSIONAL USE ONLY.

PRECAUTIONS Avoid contamination with water or moisture. Keep all pails and jugs tightly closed until ready for use. All equipment, air supplies, and application substrates must be ABSOLUTELY DRY.

Do not apply in wet weather or when rain is imminent or when the CIM 1000 Trowel Grade or the substrate may become wet within 4 hours after coating. Use caution when applying CIM 1000 Trowel Grade in confined spaces. See C.I.M. Industries’ Instruction Guide, “Applying CIM Within Confined Spaces” (IG–9).

TEMPERATURE Surface should be at least 50ºF (10ºC) and must be 5ºF (3ºC) above the dew point. DO

NOT APPLY WHEN THE SUBSTRATE OR AMBIENT TEMPERATURE IS RISING OR COATING

IS IN DIRECT SUNLIGHT. CIM 1000 Trowel Grade should be at least 60ºF (15ºC) when mixed and applied. CIM 1000 Trowel Grade may be preheated to facilitate application at low temperatures, but working time will be reduced. See C.I.M. Industries’ Instruction Guide “Applying CIM Membranes in Cold Weather” (IG–11).

EQUIPMENT CIM 1000 Trowel Grade is best applied with Trowel or brush. CIM 1000 Trowel Grade will not self level. CIM 1000 Trowel Grade may be sprayed with a properly configured plural component spray system. See C.I.M. Industries’ Instruction Guide, “Spray Application of CIM” (IG-12) or contact C.I.M. Industries for suggested equipment configuration.

POT LIFE Less than 20 minutes. Working time depends on temperature and method of application.

PRIMING Porous substrates such as wood and concrete may be primed with CIM 61BG Epoxy Primer to minimize outgassing. The recoat window for CIM 61BG Epoxy Primer shall be no longer than 48 hours. See CIM 61BG Epoxy Primer Coating Profile for additional information. Perform adhesion tests to confirm adequacy of adhesion to primer.

MIXING DO NOT THIN. DO NOT HAND MIX. Begin mixing each pail (4.0 gal.) of CIM 1000 Trowel Grade Premix using a power mixer (e.g. 1/2” drill and an eight inch mud mixer.) Do not draw air into the mix. While mixing, slowly add one jug (0.5 gal.) of CIM 1000 Activator to the pail and mix thoroughly for 3 FULL MINUTES. The proportions are pre-measured. DO NOT ESTIMATE. CIM Timers from C.I.M. Industries help eliminate mixing errors and increase productivity on the job. Do not use CIM Mixing Jigs when mixing CIM 1000 Trowel Grade.

See C.I.M. Industries’ Instruction Guide, “Mixing CIM Premix and Activator” (IG–8).

APPLICATION Apply CIM 1000 Trowel Grade directly to a clean and dry substrate. For thicker applications, mixed material should be allowed to build viscosity for several minutes before attempting to apply. See C.I.M. Industries’ specific substrate Instruction Guide for additional guidelines.

RECOATING CIM 1000 Trowel Grade may be recoated in 1 hour and must be recoated soon after the coating no longer comes off on polyethylene (typically within 4 hours of mixing.) If the coating has cured longer than this time, the surface must be severely abraded using surface grinder or other mechanical means, and be free of dust and debris. Use CIM Bonding Agent for better adhesion only when recoat window is missed. For immersion conditions, all coats shall be applied within four hours of each other, except at joint lines. For applications, such as cant strips and expansion joints, where adhesion of subsequent CIM coats is undesirable, allow 12 hours for CIM 1000 Trowel Grade to cure prior to recoating or, alternatively, use a bond breaker.

CURING TIME Before placing the coating into potable water service or similar applications, allow sufficient time for solvents to release from the coating. The required time for a 60 wet mil coating is two weeks at 60ºF (15ºC) and varies depending upon liner thickness and substrate temperature. Contact C.I.M. Industries for details. For many other applications, CIM 1000 Trowel Grade may be placed into service in 24 hours. Contact C.I.M. Industries for specific recommendations.

DISINFECTION CIM 1000 Trowel Grade coating must be washed, rinsed, and disinfected in accordance with C.I.M. Industries Instruction Guide “Decontamination or Washing Procedures for Potable Water Tank and Fish Pond Service” (IG–10).

CLEAN-UP Use mineral spirits for clean-up of uncured material. Cured material is very difficult to remove.

Soaking in solvent will soften the material and may assist in its removal.

CIM 1000 Trowel Grade

HIGH PERFORMANCE COATINGS AND LININGS

GENERAL APPLICATION INFORMATION

C.I.M.

Industries Inc.

CONTACT C.I.M. INDUSTRIES FOR SPECIFIC RECOMMENDATIONS AND INSTRUCTION GUIDES.

www.cimindustries.com

C.I.M.

Industries Inc.

23 Elm St., Peterborough, NH 03458 Tel: (800) 543-3458 (603) 924-9481 Fax: (603) 924-9482 Web site: www.cimindustries.com

WARNING Flammable. Use only in well ventilated areas. Do not store or use near open flame, sparks or hot surfaces. Keep tightly closed. Avoid contact with moisture or water.

Keep out of reach of children.

SAFETY INFORMATION This product contains petroleum asphalt, petroleum distillates, amine compounds and/or other chemical ingredients. Adequate health and safety precautions should be observed during the storage, handling, application and curing. Refer to C.I.M. Industries’ Material Safety Data Sheets for further details regarding the safe use of this product.

PACKAGING CIM 1000 Trowel Grade is available in mixed kits of 0.8 gallon and 4.5 gallons. Each unit consists of a container of premix and a smaller container of activator. Quantities have been premeasured to provide the proper mixing ratio, leaving sufficient room in the premix container to facilitate adequate mixing. Do not estimate proportions.

SHIPPING Premix Activator Weights

0.8 gallon kits 6.6 lbs. per can (26 lbs. per box of 4) 1 lb. per bottle (13 lbs. per carton of 12)

4.5 gallon units 36 lbs. per pail 5.5 lbs. per jug (33 lbs. per carton of 6)1

Properties Flash Point 101ºF > 250ºF

Shipping Name Coating Solution Not Regulated DOT Class Class 3, UN1139, PG III Not Regulated

STORAGE

Temperature 20ºF to 110ºF 70ºF to 95ºF Shelf Life 2 years 6 months

NFPA Class II Non Flammable

1 4.5 gallon units of CIM 1000 Trowel Grade use CIM 1000 Activator.

THE INFORMATION PRESENTED IN THIS PUBLICATION IS SUBJECT TO CHANGE WITHOUT NOTICE.

CONTACT C.I.M. INDUSTRIES FOR CURRENT INFORMATION.

FOR PROFESSIONAL USE ONLY.

www.cimindustries.com

WARRANTY & LIMITATION OF SELLER’S LIABILITY

C.I.M. Industries Inc. (C.I.M.) warrants that for a period of five (5) years from the date of shipment to the initial purchaser the products, when mixed in proper ratios for the proper length of time, (a) will not become brittle or crack and (b) will provide a water barrier. Due to application variables beyond C.I.M.’s control which may affect results, C.I.M. makes no warranty of any kind, expressed or implied, including that of merchantability, other than that the products conform to C.I.M.’s current quality control standards at time of manufacture. If breach of warranty is established, the buyer’s exclusive remedy shall be repayment of the purchase price of the non-conforming CIM membrane product or, at C.I.M.’s option, resupply of conforming product to replace the non-conforming product. The buyer expressly waives any claim to additional damages, including consequential damages.

CIM 1000 Trowel Grade

HIGH PERFORMANCE COATINGS AND LININGS

SHIPPING, STORAGE AND SAFETY DATA

C.I.M.

Industries Inc.

©CIM 07/10

OVERVIEW

DESCRIPTION CIM 61BG Epoxy Primer is a two component high solids epoxy coating formulated as a primer for porous and non-porous surfaces such as concrete and metal.

ADVANTAGES CIM 61BG Epoxy Primer can be used to prime a variety of surfaces.

•May be used as a primer for freshly blasted metal to prevent flash rust from occurring, prior to coating with CIM.

•May be used as a primer for properly prepared concrete to minimize the effects of outgassing.

•Approved for contact with potable water in accordance with ANSI/NSF 61.

SURFACE PREPARATION

GENERAL: Substrates must be clean and dry with no oils, grease or loose debris. Perform adhesion tests to confirm adequacy of surface preparation. See C.I.M. Industries’ specific substrate Instruction Guide for more information.

CONCRETE: ICRI-CSP 4-6 surface profile exposing aggregate. Concrete must exhibit minimum 3,000 psi compressive strength and be free of release agents and curing compounds.

The substrate must be clean and dry (see CIM Instruction Guide IG-2), and free of contaminates.

STEEL: Minimum 3 mil profile.

Immersion service – SSPC-SP10 / NACE No. 2 Near White Blast.

Non-Immersion service – SSPC-SP6 / NACE No. 3 Commercial Blast.

OTHER METALS: SSPC-SP1 solvent clean and abrasive blast to roughen and degloss the surface.

WOOD: Substrate must be clean, dry and free of surface contamination.

COLOR CIM 61BG Epoxy Resin is buff.

CIM 61BG Hardener is amber.

Mixed and Cured: beige.

MIXING RATIO 4 Parts Resin: 1 Part Hardener by Volume

SOLIDS BY VOLUME 80% mixed (1280 dry mil x sq. ft./gal.) (ASTM D 2697-7 days)

DENSITY CIM 61BG Resin approximately 13.39 Ibs./gal.

CIM 61BG Hardener approximately 8.17 Ibs./gal.

VOC (EPA 24) 170 g/l (1.41 lb./gal.)

CIM 61BG

EPOXY PRIMER

C.I.M.

Industries Inc.

A Chase Corporation Company

CIM 61BG

EPOXY PRIMER

GENERAL APPLICATION INFORMATION

FOR PROFESSIONAL USE ONLY.

PRECAUTIONS Mixing equipment and surfaces where material is applied must be ABSOLUTELY DRY. Do not apply in wet weather, when rain is imminent or when the surface may become wet before the coating is dry. Strictly observe mixing, induction times and substrate temperature requirements.

TEMPERATURE Throughout the curing period, the surface should be minimum 50ºF (10ºC) AND minimum 5ºF (3ºC) above the dew point. Contact C.I.M. Industries for lower temperature application.

EQUIPMENT Air Spray, Airless Spray, Brush, or Roller ( 3⁄8" or 1⁄2" synthetic nap).

Equipment Air Spray Airless

Graco Extreme Airless 45:1 or higher Air Hose 1⁄2" N/A Fluid Hose 1⁄2"

3⁄8" to 1⁄2"

Spray Gun XTR7 Tip E or D 0.021” to 0.027"

Atomizing Pressure up to 100 psi 1500 to 3000 psi

POT LIFE About 3.5 hours at 77ºF (25ºC).

MIXING Thoroughly mix each of the two components separately: CIM 61BG Epoxy Resin and CIM 61BG Hardener. DO NOT HAND MIX. Use a power mixer. Consistency should be uniform and smooth with no settled pigments remaining at the bottom.Add entire contents of each component and thoroughly mix until color and consistency are uniform. ALLOW A MINIMUM OF 15 MINUTES

INDUCTION TIME FOR MIXED PRIMER BEFORE APPLICATION.

The two components must be combined in proper ratios for this product to set up properly.

Failure to adequately mix each component separately to achieve a uniform dispersion or failure to blend to the proper volume proportion will result in a failure of the coating to perform adequately.

DO NOT THIN. Allow cold material to warm to room temperature before attempting to lower viscosity, warm mixed coating before applying. Do not heat containers above the materials flash point of 80ºF (27ºC).

APPLICATION

PRIMER: Apply CIM 61BG Epoxy Primer at a coverage rate of 5 to 10 wet mils per coat. When coating porous substrates apply primer when the substrate is in a temperature declining mode and not in direct sunlight. A uniform coating free of holidays or pinholes is necessary to minimize outgassing effects during the application of the CIM coating to porous surfaces such as concrete. Surfaces may require additional coats to achieve a pinhole free application.

THEORETICAL COVERAGE 320 sq. ft./gal. (about 5 wet mils). Irregular surfaces, waste, spillage, and application technique effect actual coverage.

C.I.M.

Industries Inc.

CONTACT C.I.M. INDUSTRIES FOR SPECIFIC RECOMMENDATIONS AND INSTRUCTION GUIDES.

www.cimindustries.com

CIM 61BG

EPOXY PRIMER

GENERAL APPLICATION INFORMATION (Continued)

C.I.M.

Industries Inc.

©CIM 07/10

CONTACT C.I.M. INDUSTRIES FOR SPECIFIC RECOMMENDATIONS AND INSTRUCTION GUIDES.

www.cimindustries.com

CIM COATING: Allow CIM 61BG Epoxy Primer to cure at least 12 hours at 70ºF (21ºC) to permit solvent loss.

Failure to allow sufficient time for solvent loss may result in the formation of solvent blisters or poor adhesion to CIM. Prior to CIM coating application, test for the presence of amine blush by testing the pH of the epoxy primed surface. The pH should be 7-8. If the pH is higher than 8, solvent wipe with methyl ethyl ketone until the pH is within the recommended range.

Application of CIM coating to epoxy primer with a high pH will result in poor adhesion. When applied to porous surfaces, CIM 61BG Epoxy Primer will greatly reduce the effects of outgassing, but it may not completely prevent the occurrence. CIM coatings and primer should be applied following C.I.M.’s published written instructions including application of the coating when substrate temperature is declining.

RECOATING Minimum/Maximum recoat is 12hrs/48hrs @ 70ºF.

Allow at least 12 hours between coats or applying a CIM coating or lining. If more than 48 hours has past since the application of CIM 61BG Epoxy Primer, or the CIM 61BG Epoxy Primer is otherwise contaminated use one of the following procedures:

1. Test surface for pH and check for contaminates. Solvent wipe with methyl ethyl ketone to clean surface and reapply CIM 61BG Primer if within 30 days.

2. Test surface for pH and check for contaminates. Solvent wipe with methyl ethyl ketone to clean surface. Abrade the existing CIM 61 BG Primer. Apply CIM Bonding Agent and apply CIM coating or lining. If the CIM 61BG Primer is damaged during abrading. An additional application of Primer may be necessary to insure a monolithic primer application.

CLEAN UP Clean all equipment immediately after use with xylene or MEK. Thoroughly flush spray equipment before coating has had a chance to set up.

SHIPPING, STORAGE AND SAFETY DATA

CIM 61BG

EPOXY PRIMER

WARNING Flammable. Use only in well ventilated areas. Do not store or use near open flame, sparks or hot surfaces. Keep tightly closed. Avoid contact with moisture or water.

SAFETY INFORMATION This product contains ingredients which are considered to be hazardous. Solvent exposure may cause dizziness, headache or nausea. Prolonged exposure may cause permanent brain or nervous system damage. Adequate health and safety precautions should be observed during storage, handling, application and clean-up. Refer to C.I.M.

Industries’ Material Safety Data Sheets for further details regarding the safe use of this product.

PACKAGING CIM 61BG Epoxy Primer is packaged in 1 gallon units consisting of 0.8 gallon of CIM 61BG Resin and 0.2 gallon of CIM 61BG Hardener and 5 gallon units consisting of 4 gallons of CIM 61BG Resin and 1 gallon of CIM 61BG Hardener. Proper volumes of each must be mixed thoroughly prior to application.

SHIPPING 61 BG Epoxy Resin 61 BG Epoxy Hardener Weights

5.0 gallon units 58 lbs/pail 47 lbs/box (4-1 gal cans)

1.0 gallon units 38 lbs/box (4-1 gal cans) 8 lbs/box (4-1 qt cans)

Properties Flash Point 80ºF (27ºC) 80ºF (27ºC) Shipping Name Coating Solution Corrosive Liquid, Flammable, n.o.s.

DOT Class Class 3, UN1139, PG III Class B, UN2920,PGII, (xylene, polyamines)

STORAGE

Temperature 40ºF to 110ºF (5ºC to 43ºC) 40ºF to 110ºF (5ºC to 43ºC) Shelf Life 2 years 2 Years NFPA Class IC Class IC

23 Elm St., Peterborough, NH 03458 Tel: (800) 543-3458 (603) 924-9481 Fax: (603) 924-9482 Web site: www.cimindustries.com

C.I.M.

Industries Inc.

WARRANTY & LIMITATION OF SELLER’S LIABILITY

C.I.M. Industries Inc. (C.I.M.) warrants only that CIM 61BG Epoxy Primer conforms to C.I.M.’s current quality control standards at the time of manufacture. Due to application variables beyond C.I.M.’s control which may affect results, C.I.M. makes no other warranty of any kind, expressed or implied, including that of merchantability. If breach of warranty is established, the buyer’s exclusive remedy shall be repayment of the purchase price of the non conforming CIM product or, at C.I.M.’s option, resupply of conforming product to replace the non-conforming product. The buyer expressly waives any claim to additional damages, including consequential damages.

THE INFORMATION PRESENTED IN THIS PUBLICATION IS SUBJECT TO CHANGE WITHOUT NOTICE.

CONTACT C.I.M. INDUSTRIES FOR CURRENT INFORMATION.

FOR PROFESSIONAL USE ONLY.

www.cimindustries.com

C.I.M.

Industries Inc.

A Chase Corporation Company

©CIM 7/10

DESCRIPTION CIM 1061 is a tough, abrasion, corrosion and chemical resistant, liquid applied coating specifically for use in water and wastewater applications including those which require ANSI/NSF 61 potable water certification. Typical applications for this two component elastomeric urethane coating include tank and reservoir liners, joint seals, tank repairs, and chemical containment.

ADVANTAGES CIM 1061 is one of the toughest coatings available, specifically formulated to meet the demanding needs of the water/wastewater industries:

•Ideal for coating concrete.

•ANSI/NSF 61 certified for potable water contact up to 180ºF.

•Tested to ANSI 118.10-199, “Standard Specification for Load Bearing, Bonded, Waterproof Membrane for Thin-Set Ceramic Tile and Dimension Stone Installation”.

•Forms a tough elastomeric coating able to bridge cracks and joints.

•Meets the most demanding health and safety requirements for drinking water, fish hatcheries, and food processing plants.

•Adheres to and bridges between common construction materials such as concrete, steel, glass, wood, and most coatings.

•Environmentally sound, complying with the toughest VOC standards.

•Can be repaired when damaged or when new tank penetrations are installed.

•Excellent wear and abrasion service.

•UV stable.

•Liquid, two-component urethane can be applied to complex tanks with multiple penetrations, and irregular shapes.

SURFACE PREPARATION

GENERAL: Substrates must be clean and dry with no oils, grease or loose debris. CIM Bonding Agent is recommended on all non-porous substrates. Perform adhesion tests to confirm adequacy of surface preparation. See C.I.M. Industries’ specific substrate Instruction Guide for specific guidelines.

CONCRETE: ICRI-CSP 4-6 concrete surface profile exposing aggregate. Concrete must exhibit minimum 3,000 psi compressive strength and be free of release agents and curing compounds. The substrate must be clean and dry (see CIM Instruction Guide IG-2), and free of contaminates.

STEEL: Minimum 3 mil profile.

Immersion service – SSPC-SP10 / NACE No. 2 Near White Blast.

Non-Immersion service – SSPC-SP6 / NACE No. 3 Commercial Blast.

Use CIM Bonding Agent for greater adhesion.

OTHER METALS: SSPC-SP1 solvent clean and abrasive blast to roughen and degloss the surface.

Use CIM Bonding Agent for greater adhesion.

GLASS: Thoroughly clean. CIM Bonding Agent must be used for increased adhesion. For immersion service roughen the surface.

WOOD: Substrate must be clean, dry and free of surface contamination.

PREVIOUS COATINGS CIM 1061 may be applied over some existing coatings and linings and achieve

AND LININGS: acceptable performance. CIM Bonding Agent is recommended for greater adhesion. Finished system results vary due to a variety of project specific factors, including the service conditions to which the system is exposed. Therefore, C.I.M. Industries does not accept responsibility for determining the suitability of an existing coating or lining as a substrate for CIM products. Owner shall perform adhesion tests on any existing coating or lining to determine suitability.

EARTH: Use CIM Scrim.

COLOR CIM 1061 is initially shiny black, turning dull over 3 to 6 months when exposed to direct sunlight. For a colored or reflecting surface finish, see C.I.M Industries’ Instruction Guide, “Topcoats” (IG–7) for further instructions.

SOLIDS BY VOLUME 88% (1416 dry mils x sq. ft./gal.)

VOC 90 g/l (0.75 lb./gal.). CIM 1061 complies with the toughest VOC regulations.

CIM 1061

HIGH PERFORMANCE COATINGS AND LININGS

OVERVIEW

CC..II..MM..

IInndduussttrriieess IInncc..

CHEMICAL RESISTANCE

CIM 1061 is resistant to a broad range of acids and alkalis. Consult C.I.M. Industries for additional information regarding chemical resistance after reviewing CIM 1061 Chemical Resistance Chart.

THE INFORMATION PRESENTED IN THIS PUBLICATION IS SUBJECT TO CHANGE WITHOUT NOTICE.

CONTACT C.I.M. INDUSTRIES FOR CURRENT INFORMATION.

www.cimindustries.com

Abrasion Resistance - Wt. Loss Taber Abraser CS-17 Wheel 1000 gr./1000 rev.

ASTM D4060 1.2 mg. Loss

Adhesion to concrete (dry) Elcometer 350 psi

Deflection Temperature ASTM D648 below -60ºF

Density (Approx.)

Premix 8.0 lbs./gal.

Activator 10.1 lbs./gal.

Mixed & Cured 8.3 lbs./gal.

Elastomeric Waterproofing ASTM C836 exceeds all criteria ASTM C957 exceeds all criteria

Extension to Break, ASTM D412 300%

Flooring and Shower Lining UPC/IBC ANSI 118.10 Pass

Green Roof Membrane/Root Barrier FLL, 2002 Pass

Hardness, Shore A

ASTM D2240 @ 77ºF 65

Liner Performance Crack Bridging

10 cycles @ -15ºF greater than 1/8” After heat aging greater than 1/4”

Liner Weight (60 mils wet film thickness) 31 lbs./100 sq. ft.

Mix Ratio Weight 6.2:1 Volume 7.8:1

Mullen Burst Strength, ASTM D751, 50 mil 150 psi

Permeability to Water Vapor ASTM E96 Method E, 100ºF, 100 mil sheet 0.03 perms

Potable Water Service ANSI/NSF 61 to 180ºF UL File Number - MH17445 WQA Certified

Recovery from 100% extension:

after 5 minutes 98% after 24 hours 100%

Service Temperature -60ºF to 220ºF

Softening Point, Ring & Ball

ASTM D36 >325ºF

Tear Strength ASTM D624 (Die C) 180 lbs./in.

Tensile Strength, ASTM D412, 100 mil sheet 1000 psi

Weathering ASTM D822 5000 hrs.

CIM 1061

HIGH PERFORMANCE COATINGS AND LININGS

All information presented in this publication is believed to be accurate, but it is not to be construed as a guarantee of minimum performance. Test performance results are obtained in a controlled laboratory environment using procedures that may not represent actual operating environments.

TYPICAL PROPERTIES

CC..II..MM..

IInndduussttrriieess IInncc..

FOR PROFESSIONAL USE ONLY.

PRECAUTIONS Avoid contamination with water or moisture. Keep all pails and jugs tightly closed until ready for use. All equipment, air supplies, and application substrates must be ABSOLUTELY DRY.

Do not apply in wet weather or when rain is imminent or when the CIM 1061 or the substrate may become wet within 4 hours after coating. Use caution when applying CIM 1061 in confined spaces. See C.I.M. Industries’ Instruction Guide, “Applying CIM Within Confined Spaces” (IG–9).

TEMPERATURE Surface should be at least 50ºF (10ºC) and must be 5ºF (3ºC) above the dew point. DO

NOT APPLY WHEN THE SUBSTRATE OR AMBIENT TEMPERATURE IS RISING OR COATING

IS IN DIRECT SUNLIGHT. CIM 1061 should be at least 60ºF (15ºC) when mixed and applied. CIM 1061 may be preheated to facilitate application at low temperatures, but working time will be reduced. See C.I.M. Industries’ Instruction Guide “Applying CIM Coatings in Cold Weather” (IG–11).

EQUIPMENT Spray equipment requires large diameter hose and air supplied mastic gun or plural component spray equipment. See “Spray Application of CIM” (IG–12) or contact C.I.M.

Industries for specific recommendations. Roller, squeegee, and trowel may also be used.

POT LIFE About 30 minutes. Working time depends on temperature and method of application.

Working time for spray applications will be significantly shorter.

PRIMING Porous substrates such as wood and concrete may be primed with CIM 61BG Epoxy Primer to minimize outgassing. The maximum recoat window for CIM 61BG Epoxy Primer is 48 hours.

See CIM 61BG Epoxy Primer Technical Data Sheet for additional information. Perform adhesion tests to confirm adequacy of adhesion to primer.

MIXING DO NOT THIN. DO NOT HAND MIX. Begin mixing each pail (4.4 gal.) of CIM 1061 Premix using a power mixer (e.g. 1/2” drill and an eight inch mud mixer). Do not draw air into the mix. While mixing, slowly add one jug (0.6 gal.) of CIM 1061 Activator to the pail and mix thoroughly for 3 FULL MINUTES. The proportions are premeasured; DO NOT ESTIMATE.

Mixing Jigs and Timers from C.I.M. Industries help eliminate mixing errors and increase productivity on the job. See C.I.M. Industries’ Instruction Guide, “Mixing CIM Premix and Activator” (IG–8).

APPLICATION Apply CIM 1061 directly to a clean and dry substrate. Vertical surfaces will require multiple coats. See C.I.M. Industries’ specific substrate Instruction Guide for additional guidelines.

RECOATING CIM 1061 may be recoated in 1 hour and must be recoated soon after the coating no longer comes off on polyethylene (typically within 4 hours of mixing). If the coating has cured longer than this time, the surface must be severely abraded using surface grinder or other mechanical means, and be free of dust and debris. Use CIM Bonding Agent for better adhesion. For immersion conditions, all coats shall be applied within four hours of each other, except at joint lines.

RECOMMENDED Recommended minimum thickness of the coating is 60 wet mils.

MINIMUM THICKNESS Additional thickness may be specified, but extended time is required to insure proper solvent release prior to placing the liner in service. Contact C.I.M. Industries for detailed cure time information. Refer to CIM 1061 Coverage Chart for coverage rates.

CURING TIME Before placing the coating into potable water service or similar applications, allow sufficient time for solvents to release from the coating. The required time for a 60 wet mil coating is two weeks at 60ºF (15ºC) and varies depending upon coating thickness and substrate temperature. For many other applications, CIM 1061 may be placed into service in 24 hours.

Contact C.I.M. Industries for specific recommendations.

DISINFECTION CIM 1061 coating must be washed, rinsed, and disinfected in accordance with C.I.M.

Industries Instruction Guide “Decontamination or Washing Procedures for Potable Water Tank and Fish Pond Service” (IG–10).

CLEAN-UP Use mineral spirits for clean-up of uncured material. Spray equipment must be flushed regularly during application to prevent material from setting up in the hose and pump. Cured material is very difficult to remove. Soaking in solvent will soften the material and may assist in its removal.

CIM 1061

HIGH PERFORMANCE COATINGS AND LININGS

GENERAL APPLICATION INFORMATION

CC..II..MM..

IInndduussttrriieess IInncc..

CONTACT C.I.M. INDUSTRIES FOR SPECIFIC RECOMMENDATIONS AND INSTRUCTION GUIDES.

www.cimindustries.com

©CIM 7/10

WARNING Flammable. Use only in well ventilated…