This document is a Questions and Answers (Q&A) bulletin for Solicitation No. 19CY6026Q0022, issued by the American Embassy Nicosia for West Office Structured Cabling.
The solicitation addresses six key technical clarifications regarding structured cabling requirements. The primary requirement specifies STP (shielded twisted pair) cabling with an exception allowing Panduit's Vari-MaTriX cable, which is technically U/UTP but provides equivalent EMI immunity without grounding-related STP failure risks. For European installations, cables must meet LSZH fire rating with minimum Cca EuroClass classification per EN 50575, with solid bare copper conductors (CCA conductors are prohibited). The specified part number for EMEA Panduit cables is QZYWCCB0001M{length}. The rack model is identified as Middle Atlantic Products SPN-44-36. Regarding fiber optic configurations, a 2×48-strand configuration for outside plant fiber runs may be approved upon submission of the complete proposed solution with compatible FC/APC splice and termination enclosures. Field-terminated cabling is not accepted; only modular pre-terminated connections are permitted to enable rapid self-install expansion and future hardware-only orders. The document includes technical specification sheets for Panduit's TX6A Category 6A U/UTP Vari-MaTriX cable and QuickNet Copper Cabling System ordering information with detailed part numbering guidance for EMEA procurement.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
American Embassy Nicosia West Office Structured Cabling
Solicitation No. 19CY6026Q0022 Questions &Answers No. 2
1. In the tender document under SECTION A – PRICING @ CLIN 0004 – BASE ITEM: DC Structured Cabling Materials – "A" Path (Top-of-Rack to End-of-Row, Primary) @ Specified Components (or approved equal) on page 10, it mentions:
• QEPBCCL…> Cat6A UTP Plenum Copper Trunk, Cassette-to-Cassette, Blue (6 connections per cassette) Copper rack-to-EoR runs
Where as in CLIN0004 & 0005, it mentions:
• Cat6A STP Plenum Copper Trunk or equal – copper racks to EoR "A", per Table 1 lengths (33 racks)
• What is the requirement:UTP or STP (unshielded or shielded?)
The requirement is STP for the structured cabling. Standard UTP is not allowed, with the sole exception of CLIN 08 (existing cabling).
However, we are opening the requirement to also accept Panduit's Vari-MaTriX cable (or approved vendor equal). While technically classified as U/UTP, its Vari-MaTriX tape suppresses alien crosstalk and provides EMI immunity comparable to shielded cable, without the grounding-related failure risks associated with improperly grounded STP.
Reference attachment 111707448.
2. In the tender document, cables are required to be plenum rated but these are not sold in
Europe, thus, can you please confirm the Euro class of the cables?
Requirement: LSZH with minimum Cca EuroClass fire rating (EN 50575).
(Note: "Cca" = fire rating, not Copper-Clad Aluminum. Conductors must remain solid bare copper — CCA conductors are not acceptable.)
3. (For the above 2 questions (2 & 3), are you may be asking for:
• Part number QULICCL0001Mxxx Copper QuickNet Trunk Assy, Category 6A, S/FTP Small Diameter LSZH International Gray Cable with Black Cassette to Black Cassette, Standard Packaging, xxx Meters
Or,
• Part number QELWCCL0001Mxxx Copper QuickNet Trunk Assy, Category 6A, U/FTP LSZH White Cable with Black Cassette to Black Cassette, Standard Packaging, xxx Meters)
See updated EMEA Panduit vendor attachment 110018042. Based on this document the part number is QZYWCCB0001M{length}.
4. What is the model of the rack?
Middle Atlantic Products model SPN-44-36.
5. Can a 2×48-strand configuration be used instead of the specified 4×24-strand configuration for the outside plant fibre runs?
The 2×48 configuration may be reviewed and approved once the Offeror submits the full proposed solution, including recommended compatible FC/APC splice/termination enclosures for that configuration.
6. Can field-terminated cabling be used instead of the modular pre-terminated option for the structured cabling?
No, only modular pre-terminated connections are accepted, to enable rapid self-install expansion in the future. We would place a hardware-only order in the future if a rack needs additional connectivity.
panduit.com
TX6A™ Category 6A U/UTP Copper Cable:
Vari-MaTriX High Density (HD) S P E C I F I C A T I O N S H E E T
SPECIFICATIONS
Category 6A/Class EA cable shall be constructed of 23 AWG copper conductors with foamed PE and HDPE insulation. The copper conductors shall be twisted in pairs and separated by a tape divider. All four pairs shall be surrounded by a Vari-MaTriX tape and a flame retardant jacket. The Vari-MaTriX tape shall minimize the cable diameter and suppress the effects of alien crosstalk while retaining U/UTP electromagnetic interference immunity. The small cable diameter shall maximize cable density such that existing pathways can be utilized when upgrading from Category 6 cabling.
TECHNICAL INFORMATION
Category 6A/ Class EA channel and component performance:
Certified channel performance in a 4-connector configuration up to 100m and exceeds the requirements of ANSI/TIA-568.2-E Category 6A and ISO 11801 Class EA Standards swept up to 650 MHz for supporting 10GBASE-T transmission over twisted-pair cabling systems as part of the TX6A U/UTP Copper Cabling System.
Certified component performance up to 100m and exceeds the ANSI/ TIA-568.2-E Category 6A and IEC 61156-5 Category 6A Standards for supporting 10GBASE-T transmission over twisted-pair cabling systems
Cable diameter: 6.3mm (0.248 in.) nominal
Insulation diameter: 1.04mm-1.22mm (0.041 in. - 0.048 in.)
Conductors/insulators: 23 AWG solid copper insulated with foamed PE and HDPE
Certification: ANATEL 02670-24-02371
Flame rating: IEC 60332-1, IEC 60332-3-22, IEC 60754, IEC 61034; EN 50575:
EuroClass Dca-s2,d2,a1
PoE compliant: Meets IEEE 802.3af, IEEE 802.3at and IEEE 802.3bt for PoE applications
Installation tension: 25 lbf (110 N) maximum
Cable jacket: LSZH
Cable weight: 13 kg/305m (29 lbs./1000 ft.)
Temperature rating: 0°C to 50°C (32°F to 122°F) during installation -20°C to 75°C (-4°F to 167°F) during operation
Packaging: 305m (1000 ft.) on a reel Package tested to ISTA procedure 1A
TX6A U/UTP Copper Cable with Vari-MaTriX HD Technology
LSZH: PUL6AHD04**-EG
**Colors: BU (Blue), WH (White), RD (Red), OR (Orange), YL (Yellow), GR (Green), VL (Violet), IG (International Gray), or BL (Black)
KEY FEATURES AND BENEFITS
Vari-MaTriX HD technology:
Best-in-class cable diameter delivers superior PSANEXT and PSAACRF suppression while retaining U/UTP EMI immunity
Superior headroom warranty:
Provides the highest worst-case margins above the industry standard for both electrical and alien crosstalk performance
High density cable design:
Improves fill capacity, cable management, reduces required bend radius and allows efficient use of pathways and spaces
Extended temperature range:
Allows operation in 75°C (167°F) ambient environment providing errorfree performance in high-density cabinets and large cable bundles running PoE+ or PoE++ applications
Highest density: All testing and headroom based on 48-port/1 RU panels
Descending length cable markings:
Easy identification of remaining cable to reduce installation time and cable scrap http://www.panduit.com panduit.com
TX6A™ Category 6A U/UTP Copper Cable: Vari-MaTriX High Density (HD) panduit.com/contact-us ©2025 Panduit Corp. ALL RIGHTS RESERVED. COSP680-WW-ENG 7/2025
ADDITIONAL SPECIFICATIONS
Mechanical Test
Ultimate breaking strength: > 90 lbf (400 N)
Minimum bend radius: 4 × cable diameter
Electrical Test
DC resistance < 9.38 Ohm per 100m (328 ft.)
DC resistance unbalance < 5%
Mutual capacitance < 5.6 nF per 100m (328 ft.) at 1 kHz
Capacitance unbalance < 160 pF per 100m (328 ft.) at 1 kHz
Characteristic impedance 100 Ohm +/-15% up to 100 MHz
Nominal velocity of propagation (NVP) 65% nominal
Operating voltage, maximum 80 V
ENGINEERING DRAWING
APPLICATIONS
The TX6A U/UTP Copper Cable with Vari-MaTriX HD Technology is a component of the TX6A Copper Cabling System. Interoperable and backward compatible, this end-to-end system provides design flexibility to protect network investments well into the future.
Key applications include:
| • | 10GBASE-T Ethernet |
| • | Data center I/O consolidation |
| • | Data center server virtualization |
| • | Consolidation of network interconnects |
| • | Back-bone aggregation |
| • | Parallel processing and high speed computing |
MaTriX Tape
Conductor Wire
Pair Separator
Conductor Insulator
Jacket http://www.panduit.com https://www.panduit.com/en/support/contact-us.html visit www.panduit.com
TM
The QuickNet™ Copper Cabling System provides a custom, pre-terminated cabling solution which meets unique requirements. Fast and simple to install, the system enables quick network deployment, increased reliability and lowest total cost of ownership as compared to field terminated installations. Engineered for maximum design flexibility and high rack density utilisation (up to 48 ports in one rack space), the system offers 100% factory tested pre-terminated cable assemblies in custom lengths and configurations. QuickNet™ Angled and Flat Patch Panels accept QuickNet™ Pre-Terminated Cassettes, Patch Panel Adapters, and blanks, which snap in and out, with one hand, for quick installation.
EMEA Product Bulletin
• Each QuickNet™ Cable Assembly is factory tested to electrical permanent link specifications
• TX6A™ 10Gig™ Copper Cabling Systems exceed requirements of ANSI/TIA-568-C.2, ISO 110801 Class EA Edition 2.1, and IEEE 802.3an standards for supporting 10GBASE-T requirements
• LSZH rated cables will be marked with the appropriate CPR Euroclass for the cable. Assemblies are not covered by CPR.
• Jack modules utiise patented Giga-TX™ Technology which optimises performance by maintaining cable pair geometry and eliminates conductor untwist
• Modular plugs meet all applicable ANSI/TIA-568-C.2 requirements and exceed IEC 60603-7 specifications
K e y F e a t u r e s B e n e f i t s Pre-terminated Controlled factory environment provides consistent network performance while reducing installation time and on-site waste as compared to field-terminated installations
100% factory tested Eliminates the time and cost associated with on-site testing and ensures verified performance (permanent link test data supplied with each cable assembly)
Wide range of cable types and performance levels
Category 6A UTP/FTP and Category 6 UTP performance levels available in Euroclass cable flame ratings
Wide range of termination configurations and custom lengths
Cable assemblies allow customization including pre-terminated cassettes, jack modules, modular plugs, and/or unterminated cable options to provide design flexibility for all installations in lengths from 3' to 90m
Modular design Pre-terminated cassettes snap in and out of QuickNet™ Patch Panels and include an integral release tab to ensure easy on-site moves, adds, and changes Patch panel adapter accepts Mini-Com™ Modules for UTP, fibre optic and audio/ visual applications
Standard and high-density solution QuickNet™ Patch Panels in angled and flat designs enable 24 and 48-ports in one rack unit for efficient rack space utilisation
Assembly identification Each cable assembly label includes part number, performance level, and serialized quality assurance number for future traceability
Integrated bonding and grounding Innovative shielded cassette and shielded jack design provides linear conductive path for proper bonding to QuickNet™ Shielded Metal Patch Panels
T e c h n i c a l I n f o r m a t i o n
QuickNet™ Copper Cabling System
QuickNet™ Cable Assembly Ordering Information for EMEA
1 – Q = QuickNet™
| 2 – | Performance Level | |
| C | = Category 6 UTP | |
| H | = Category 6A U/FTP Shielded | |
| Z | = Category 6A UTP Vari-MaTriX |
| 3 – | Flame Rating | |
| L | = Dca-s2-d2-a1 | |
| Y | = Cca-s1a-d1-a1 | |
| W | = B2ca-s1a-d1-a1 |
| 4 – | Cable Colour | |
| W | = White |
| 5 – | Termination End 1 | |
| C | = Cassette | |
| J | = Jack modules | |
| P | = Modular plugs |
| 6 – | Termination End 2 | |
| C | = Cassette | |
| J | = Jack modules | |
| P | = Modular plugs | |
| U | = Unterminated |
7 – Termination Colour Options Jack Module Colour Options B = Blue, L = Black, R = Red, W = White, Shielded Jack Modules, choose option L (all Shielded Jack Modules are Black) Modular Plug and Unterminated Colour Options X = No colour option available, End 1 and End 2 are plug and/or unterminated
8-11 – Serial Code 0001 No Variation
000B End 2 Unterminated with loose blue jacks and cassette
000Y End 2 Unterminated with loose black jacks and cassette
0013 End 2 Unterminated with loose red jacks and cassette
0017 End 2 Unterminated with loose white jacks and cassette
12 – Unit of Measure M = Metres
13, 14, 15 – Assembly Length** Metres = 003 to 090
Example: Q Z L W C C L 0 0 0 1 M 0 1 0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Copper QN Trunk, Cat6A, UTP VariMaTriX, LSZH, White Cable, End 1 Cassette, End 2 Cassette, Black Jacks, Standard Pkg, 10 Metres
Quality Assurance Label Loomed Cable QuickNet™
Pre-Terminated Cassette
Tak-Ty® Hook & Loop Strips visit www.panduit.com
Q u i c k N e t™ P a t c h P a n e l a n d A c c e s s o r i e s O r d e r i n g I n f o r m a t i o n
Part Number Part Description
No. of ˆ Rack
Spaces
Std.
Pkg.
Qty.
QAPP24BL Angled 24-port patch panel 1 1
QAPP48HDBL Angled 48-port high density patch panel 1 1
QAPP48HDVNSBL Angled 48-port high density patch panel with pre-printed vertical numbering on each port for switch applications 1 1
QPP24BL Flat 24-port patch panel 1 1
QPP48HDBL Flat 48-port high density patch panel 1 1
QPP48HDVNSBL Flat 48-port high density patch panel with pre-printed vertical numbering on each port for switch applications 1 1
QSP24BL Flat 24-port shielded all metal patch panel, for use with shielded QuickNet™ Pre-Terminated Cassettes and Shielded Jack Modules 1 1
QSP48HDBL Flat 48-port shielded all metal patch panel, for use with shielded QuickNet™ Pre-Terminated Cassettes and Shielded Jack Modules 1 1
QASP24BL Angled 24-port shielded all metal patch panel, for use with shielded QuickNet™ Pre-Terminated Cassettes and Shielded Jack Modules 1 1
QASP48HDBL Angled 48-port shielded all metal patch panel, for use with shielded QuickNet™ Pre-Terminated Cassettes and Shielded Jack Modules 1 1
QPPAB Patch panel adapter accepts all Mini-Com™ Modules for multimedia applications — 1
QPPBBL Patch panel blank reserves space for future use and promotes proper airflow and cooling — 1
QPPLC24 Label/label cover kit for 24-port QuickNet™ Patch Panels — 1
QPPRT Removal tool allows individual cables to be removed from plug pack without disruption of other network connections — 1
QPPLD6-X Lock-in device prevents unauthorized removal of cables from the plug pack — 10
QPPN6*** QuickNet™ Plug Pack individual housing accepts six RJ45 modular plugs — 1
QPPNR6S QuickNet™ Recessed Plug Pack individual housing accepts six RJ45 modular plugs — 1
^One rack space = 1.75" (44.45mm).
*All connectivity is wired T568B. Category 6 Enhanced Performance level utilses Panduit® TX6500™ Category 6 UTP Cable.
Permanent link test results shipped with each cable assembly.
**QuickNet™ Patch Panels also available in White (WH).
QuickNet™ Cable Assembly Ordering Information for EMEA
DISCLAIMER: THE INFORMATION CONTAINED HEREIN IS INTENDED AS A GUIDE FOR USE BY PERSONS HAVING TECHNICAL SKILL AT THEIR OWN DISCRETION AND RISK. BEFORE USING ANY PANDUIT PRODUCT, THE BUYER MUST DETERMINE THE SUITABILITY OF THE PRODUCT FOR HIS/HER INTENDED USE AND BUYER ASSUMES ALL RISK AND LIABILITY WHATSOEVER IN CONNECTION THEREWITH. PANDUIT DISCLAIMS ANDY LIABILITY ARISING FROM ANY
INFORMATION CONTAINED HEREIN OR FOR ABSENCE OF THE SAME.
WORLDWIDE SUBSIDIARIES AND SALES OFFICES
PANDUIT US/CANADA
Phone: 800.777.3300
PANDUIT EUROPE LTD.
London, UK Phone: 44.20.8601.7200
PANDUIT SINGAPORE PTE. LTD.
Republic of Singapore Phone: 65.6305.7575
PANDUIT JAPAN
Tokyo, Japan Phone: 81.3.6863.6000
PANDUIT LATIN AMERICA
Guadalajara, Mexico Phone: 52.33.3777.6000
PANDUIT AUSTRALIA PTY. LTD.
Victoria, Australia Phone: 61.3.9794.9020
For a copy of Panduit product warranties, log on to www.panduit.com/warranty
For more information Visit us at www.panduit.com
Contact Customer Service by email: cs@panduit.com or by phone: 800.777.3300
©2020 Panduit Corp.
ALL RIGHTS RESERVED.
COCB43--WW-UKE
5/2020
File details come from the government source that posted it. Updated .