UTILITY BUILDING
UTILITY MEDIUM-VOLTAGE SERVICE IS RATED
15.16kV, 3Ø, 3W, UNGROUNDED WYE.
COORDINATE TERMINATION POINTS OF THE
FEEDER CONDUITS WITH THE LOCAL UTILITY
COMPANY TO PERMIT FINAL CONNECTIONS TO THE
UTILITY MEDIUM-VOLTAGE DISTRIBUTION SYSTEM
IN THE FUTURE.
100% RESISTIVE
LOAD BANK (PAD
MOUNTED)
520KW, 400V, 3PH,
3W, 50Hz
OUTDOOR EQUIPMENT
PARALLELING SWITCHGEAR
ROOM U105
FUTURE PAD-MOUNTED MEDIUM-
VOLTAGE SWITCHGEAR (15.16kV).
REFER TO DWG. CAP E2-112 FOR
LOCATION OF UTILITY DEMARCATION
SWITCHGEAR ROOM C223.
2500AF
2500AT
3P
INCOMING SERVICE #2
INCOMING SERVICE #1
INCOMING ELECTRICAL UTILITY DEMARCATION
SERVICE ROOM (IN SCAP)
METERING
CUBICLE
UTILITY
FEEDER
#1
UTILITY
FEEDER
#2
GENERATOR PLANT LINE UP
N+2 PRIME POWER CONFIGURATION
'CBLB'
1200AF
1000AT
3P ELEC
UTILITY BUILDING
GENERATOR ROOM U109
PLC POWER
SYSTEM
MASTER
CONTROLLER
PLC CONTROL WIRING
(TYPICAL)
SPD
TO POWER
MONITORING SYSTEM
4000A, (FULLY RATED BUS,) 400/230V, 3PH, 4-WIRE, 50Hz, 65kAIC
S P
A R
E
400AF
150AT
3P
SPD
NO
'GENSG', 4000A, (FULLY RATED BUS,) 400/230V, 3 PH, 50Hz, 65KAIC MINIMUM
MAIN DISTRIBUTION SWITCHBOARD "MDSGE" (E-BUS)
SPD
NO
PROVIDE GENERATOR
ANNUNCIATION WIRING
IN CONDUIT THROUGH
DUCTBANK TO NOB
100AF
30AT
3P
100AF
30AT
3P
100AF
30AT
3P
(PANEL MTD.)
SWITCHBOARD
CONSTRUCTION
SWITCHGEAR
CONSTRUCTION
SWITCHBOARD
CONSTRUCTION
SWITCHGEAR
CONSTRUCTION
ROOF OF UTL BLDG.
520KW/650KVA (MIN.)
PRIME RATED, 1500RPM,
400/230V, 50Hz DIESEL
GENERATOR
(TYP. OF 6 TOTAL)
4000AF
4000AT
4P ELEC
PSU1
NO
(FUTURE)
(FUTURE)
NC NC NC NC NC NC
GENERATOR #1 GENERATOR #2 GENERATOR #3 GENERATOR #4 GENERATOR #5 GENERATOR #6
A F
A T
,3 P
A F
A T
,3 P
A F
A T
,3 P
A F
A T
,3 P
A F
A T
,3 P
A F
A T
,3 P
'CBG1'
1200AF
1200AT
3P ELEC
'CBG2'
1200AF
1200AT
3P ELEC
'CBG3'
1200AF
1200AT
3P ELEC
'CBG4'
1200AF
1200AT
3P ELEC
'CBG5'
1200AF
1200AT
3P ELEC
'CBG6'
1200AF
1200AT
3P ELEC
NC
4000AF
4000AT
4P ELEC
LSIG
4000AF
4000AT
4P ELEC
NC
FUTURE SERVICE YARD
PROVIDE 11-103mm CONDUITS AND SPARE CONDUITS EXTENDED
TO MHE3A FOR FEEDERS FROM FUTURE MAIN OUTDOOR
SWITCHGEAR. REFER TO PACKAGE P1 DWG CMPD E1-101.
TO BE LOCATED EAST OF SCAP BUILDING
FOR FUTURE UTILITY SERVICE EQUIPMENT -
MEDIUM-VOLTAGE TRANSFORMER,
AUTOMATIC VOLTAGE REGULATOR,
AND LOW VOLTAGE MAIN SERVICE SWITCHGEAR.
PROVIDE 53mm CONDUITS EXTENDED UNDERGROUND TO MHE3A FOR
PLC CONTROL WIRING TO FUTURE MAIN SERVICE SWITCHGEAR IN
FUTURE SERVICE YARD - REFER TO PACKAGE P1 DWG. E1-101 & E1-301.
CMPD
MV
FEEDER
U10U9
G6G5G4G3G2G1
E8 U12U4E7 E6 U8E2E5 E4 E3 U7U5
LB
G
G
G
G
G
G
LSIG LSIG LSIG LSIG LSIG LSIG
LSIG LSIG LSIG LSIG LSIG LSIG LSIG
LSIG
NC
NC NC NC NC NC
PROVIDE CONTROL
WIRING IN CONDUIT TO
LOAD BANK CONTROL
PANEL IN UTL BLDG ROOM
U105
PSGE PSGU
C
LOAD BANK
M
LSIG
LSIG
CB2
4000AF
4000AT
4P ELEC
4000AF
4000AT
4P ELEC
PSU2
NO
LSIG
UTILITY BUILDING
MAIN DISTRIBUTION SWITCHGEAR 'MDSG'
IN ROOM U101
UTILITY BUILDING
C
LSIG
NC
TO NOB SWITCHBOARD
'NSWBDE' - REFER TO NOB
SINGLE LINE DIAGRAM -
DWG. NOB E4-601
400AF
70AT
3P
400AF
400AT
3P
LSIG
NO
S P
A R
E
400AF
225AT
3P
0A
F , 3
P S
P A
C E
O N
LY
0A
F , 3
P S
P A
C E
O N
LY
2500AF
2500AT
3P
U2
LSIG
NC
C
600AF
500AT
3P
U3
LSIG
NC
400AF
400AT
3P
LSIG
NC
600AF
500AT
3P
400AF
100AT
3P
S P
A R
E
400AF
400AT
3P
LSIG
NO
S P
A R
E
400AF
225AT
3P
0A
F , 3
P S
P A
C E
O N
LY
0A
F , 3
P S
P A
C E
O N
LY
4000A, (FULLY RATED BUS,) 400/230V, 3PH, 4-WIRE, 50Hz, 65kAIC
MAIN DISTRIBUTION SWITCHBOARD "MDSGU" (U-BUS)
POWER SYSTEM CONTROLLER SHALL CONTROL
SWITCHGEAR 'MDSG' ELECTRICALLY OPERATED CIRCUIT
BREAKERS
PROVIDE PRIMARY MEDIUM-VOLTAGE CONDUIT DUCTBANK AND ASSOCIATED
MANHOLES FROM UTILITY RIGHT-OF-WAY AT THE PROPERTY LINE TO THE SCAP
UTILITY DEMARCATION ROOM. TERMINATE IN TRENCH PROVIDED IN ROOM TO
SERVE THE FUTURE MEDIUM-VOLTAGE SWITCHGEAR.
PROVIDE MEDIUM-VOLTAGE CONDUIT DUCTBANK AND ASSOCIATED
MANHOLES FROM SCAP UTILITY DEMARCATION ROOM TO THE LOCATION
OF THE FUTURE UTILITY YARD - REFER TO PACKAGE P1 DWG CMPD E1-101.
2 2 2 2 2
2 2
2 2 2 2 2 2 22 2 2 2 2
2 2
SPD
CB1
NC
LSIG
CB3
NC
LSIG
4000AF
4000AT
4P ELEC
4000AF
4000AT
4P ELEC
TO LOAD BANK
CONTROL PANEL
M
PLC POWER
SYSTEM
MASTER
CONTROLLER
TO POWER
MONITORING SYSTEM
BUS FOR FUTURE FEEDER
CONDUCTORS FROM FUTURE
OUTDOOR SERVICE
SWITCHGEAR - TYPICAL FOR
PSU1
POWER SYSTEM CONTROLLER SHALL CONTROL
PARALLELING SWITCHGEAR 'GENSG' ELECTRICALLY
OPERATED CIRCUIT BREAKERS
FUTURE PLC
CONTROL WIRING
U6
400AF
100AT
3P
4000A BUS FROM LOAD SIDE OF
PSU2 TO LOAD SIDE OF PSGU.
TYPICAL FOR PSU1/PSGE.
F2500F150F70 F400 F500 F100 F100 F500
F30SPD
30A 3P
P/BD 'SC1E3'
P/BD 'SC1EU'
150A 3P
100A 3P
P/BD 'SC1E2'
P/BD 'SC1E1'
P/BD 'SC1ER'
30A 1P
TSS LOADS TSS LOADS
7 5
30A 1P
30A 3P
100A 3P
B
A
AA
A
F30TF30T
F100 F30
FROM P/BD 'N1EU2'
IN NOB. REFER TO
NOB SINGLE LINE
DIAGRAM - DWG
NOB E4-601.
FROM P/BD 'N1ER2'
IN NOB. REFER TO
NOB SINGLE LINE
DIAGRAM - DWG
NOB E4-601.
P/BD 'U1EU'
500A 3P
175A 3P
P/BD 'U1U1'
P/BD 'U1U2'
P/BD 'U1ER'
P/BD 'U1U3'
TSS REG.
LOADS
TSS UPS
LOADS
30A 1P
175A 3P
125A 3P
125A 3P
30A 1P
P/BD 'U1E1'
ESSENTIAL
POWER
70A 3P
REFER TO SINGLE LINE
DIAGRAM - DWG
UTL E7-601
B
A
A
P/BD 'U1U4'
100A 3P
100A 3P
DISTR. PANEL
POWER
DISTR.
POWER
DISTR.
GEN.
EQUIP
B
A
A
A
P/BD 'U1PV'
400A 3P
PV SYSTEM 5
B
UTILITY BLDG
REFER TO SINGLE LINE
DIAGRAM - DWG
CAP E2-601
SERVICE CAP
REFER TO SINGLE LINE
DIAGRAM - DWG
UTL E7-601
UTILITY BLDG
FROM P/BD 'N1ER2'
IN NOB. REFER TO
NOB SINGLE LINE
DIAGRAM - DWG
NOB E4-601.
FROM P/BD 'N1EU2'
IN NOB. REFER TO
NOB SINGLE LINE
DIAGRAM - DWG
NOB E4-601.
TO NOB SWITCHBOARD 'NSWBDU' - REFER TO
NOB SINGLE LINE DIAGRAM - DWG. NOB E4-601
F2500
60A 3P
P/BD 'M1U3'
400A 3P
60A 3P
P/BD 'M1U2'
P/BD 'M1U1'
7 5
60A 3P
60A 3P
B
AA
P/BD 'M1EU'P/BD 'M1ER'
TSS REG.
LOADS
TSS UPS
LOADS
30A 1P
30A 1P
A
A
FROM P/BD 'N1ER2'
IN NOB. REFER TO
NOB SINGLE LINE
DIAGRAM - DWG
NOB E4-601.
FROM P/BD 'N1EU2'
IN NOB. REFER TO
NOB SINGLE LINE
DIAGRAM - DWG
NOB E4-601.
REFER TO SINGLE LINE
DIAGRAM - DWG
MSGR E5-601
MSGR
P/BD 'R1U1'
P/BD 'WWTP'
POWER
DISTR.
100A 1P
100A 3P
A
B
500A 3P
100A 3P
P/BD 'W1U1'
P/BD 'W1U2' P/BD 'W1U3'
100A 3P
60A 3P
60A 3P
B
A
A
P/BD 'W1U4'
60A 3P
60A 3P
CARP.
SHOP
A
P/BD 'W1U5'
125A 3P
VEHICLE
MAINT.
A
POWER
DISTR.
POWER
DISTR.
ST
XFMR 'TPVW'
225kVA, Z=5.0%
TEMP. CLASS 150
400A 3P
400A 3P
P/BD 'W1PV'
B
WHE PV
SYSTEM
REFER TO SINGLE LINE
DIAGRAM - DWG
WHE E6-601
WHE BLDG
REFER TO SINGLE
LINE DIAGRAM -
DWG REC E8-601
REC BLDG
REFER TO PACK. P1
DWG CMPD E1-101
WWTP
POWER
DISTR.
P/BD 'W1EU'P/BD 'W1ER'
TSS REG.
LOADS
TSS UPS
LOADS
30A 1P
30A 1P
A
A
FROM P/BD 'N1ER2'
IN NOB. REFER TO
NOB SINGLE LINE
DIAGRAM - DWG
NOB E4-601.
FROM P/BD 'N1EU2'
IN NOB. REFER TO
NOB SINGLE LINE
DIAGRAM - DWG
NOB E4-601.
F30T F30T F30T F30T F30T F30T
F60 F60
XFMR'TPVU'
225kVA, Z=5.0%
TEMP. CLASS 150
F175 F125 F100
P/BD 'U1U5'
60A 3P
60A 3P
FUEL
SYSTEM
A
F60
P/BD 'U1U6'
100A 3P
100A 3P
WATER
EQUIP
A
F100
F400
F400
F100 F60 F60 F125 F400
F400
F4000 F4000
F1200 F1200 F1200 F1200 F1200 F1200F1000F
FUTURE MEDIUM-VOLTAGE COMPOUND TRANSFORMER TO BE PROVIDED AS A 2500kVA
TRANSFORMER EQUIPPED FOR THE PROVISION OF FANS PER SED SPECIFICATION SECTION
261200. PRESENT SHORT-CIRCUIT CALCULATIONS ARE BASED ON THE TRANSFORMER
HAVING 5.75% IMPEDANCE.
THE FUTURE AUTOMATIC VOLTAGE REGULATOR SIZE TO BE BASED ON THE MAIN COMPOUND
TRANSFORMER SIZE OF 2500kVA.
THE FUTURE OUTDOOR SERVICE SWITCHGEAR WILL BE A MAIN LUG ONLY TYPE, EQUIPPED
WITH TWO MAIN CIRCUIT BREAKERS. ONE BREAKER AND FEEDER WILL SERVE THE
COMPOUND ESSENTIAL LOADS AND THE OTHER BREAKER AND FEEDER WILL SERVE THE
COMPOUND UTILITY LOADS. BASED ON A 2500kVA TRANSFORMER, THE AIC RATING = 100kA.
U11
400AF
400AT
3P
LSIG
NC
F400
800A BUS
E1 U1
[60,569A]
REFER TO KEYNOTE-14. THE CALCULATED AVAILABLE FAULT
CURRENT LEVEL IS INDICATED BY [XXkA] AND IS BASED ON THE FUTURE UTILITY CONNECTION VIA A 2500kVA SERVICE
TRANSFORMER HAVING A 5.7% IMPEDANCE. EQUIPMENT AIC
RATINGS WILL BE BASED ON THESE AVAILABLE FAULT CURRENTS.
[60,531A]
[23,195A]
[9,200A]
[2,698A]
[2,609A] [1,673A]
[8,019A]
[42,168A] [2,083A]
[1,013A]
[6,153A]
[9,842A]
[9,457A] [9,100A] [6,149A] [4,403A]
[5,063A]
14 REFER TO KEYNOTE-14. THE CALCULATED AVAILABLE FAULT
CURRENT LEVEL IS INDICATED BY [XXkA] AND IS BASED ON THE FUTURE UTILITY CONNECTION VIA A 2500kVA SERVICE
TRANSFORMER HAVING A 5.7% IMPEDANCE. EQUIPMENT AIC
RATINGS WILL BE BASED ON THESE AVAILABLE FAULT CURRENTS.
F30SPD
400Y/230V
480Y/277V
480Y/277V
REFER TO CMPD
PV SYSTEM SINGLE
LINE DIAGRAM -
DWG CMPD E1-613
REFER TO CMPD
PV SYSTEM SINGLE
LINE DIAGRAM -
DWG CMPD E1-613
NEMA 4X
P/BD 'W1U6'
100A 3P
100A 3P
C.E.S. 5 A
F100
100A 3P
P/BD 'M2U1'
100A 3P
A
F100
400Y/230V
400A,3P
ENCLO.
C.B.
400A,3P
ENCLO.
C.B.
ALL 'GENSG' BREAKERS
SHALL BE 100% RATED.
[11,236A] [6,877A] [3,985A] [3,360A] [8,956A] [5,528A]
125A 3P
LSIG LSIG LSIG
FEEDER SCHEDULE
NO.
CONDUIT
FEEDER SIZE AND QUANTITY
NO.
COND.
FEEDER
MARK WIRE
SIZE COND.
GND.
SIZE
RATINGS
NOTES:
NO.
SETS
NEUT.
NO.
COND.
GND.
NO.
COND.
WIRE
SIZE
PH.
2500A (4-WIRE + GND)7 13 1 7 103mm
4 3 4 103mm 1200A (4-WIRE + GND)11
1000A (NOTE-1)3 3 3 103mm1-
2 3 2 103mm 450A (4-WIRE + GND)11
3 1 103mm 400A (4-WIRE + GND)111
3. FEEDER SIZE BASED ON CALCULATED VOLTAGE DROP.
3 1 53mm111 100A (4-WIRE + GND)
3 1 53mm111 60A (4-WIRE + GND)
1 1 27mm1 13 30A (4-WIRE + GND)
2. FEEDER SIZE BASED ON THE REQUIREMENT FOR A 200% RATED NEUTRAL.
4. FEEDERS BASED ON CONDUITS, 21mm(3/4"), 27mm(1"), 53mm(2"), 103mm(4").
(PER CONTRACTOR'S REQUEST TO STANDARDIZE ON CONDUIT SIZES FOR THIS PROJECT)
F1200
F2500
F1000F
F450
F400
F100
F60
F30
300mm2
185mm2
300mm2
120mm2
300mm2
50mm2
25mm2
6mm2
300mm2
185mm2
120mm2
300mm2
50mm2
25mm2
185mm2
95mm2
70mm2
35mm2
35mm2
10mm2
6mm2
6mm2
5. WIRING FOR AN INTEGRALLY-MOUNTED SPD UNIT WITHIN A PANELBOARD, SWITCHBOARD OR SWITCHGEAR.
1. THREE PHASE FEEDER (NO NEUTRAL INCLUDED).
3 1 53mm111 150A (4-WIRE + GND)F150 70mm2 70mm2 16mm2
3 1 103mm111 225A (4-WIRE + GND)F225 120mm2 120mm2 25mm2
F = THREE-PHASE FEEDER
N = 200% NEUTAL
S = SINGLE-PHASE FEEDER
GND. COND. = EQUIPMENT GND.
COND. (U.N.O.)
6mm2
3 1 53mm111 70A (4-WIRE + GND)F70 25mm2 25mm2 10mm2
1 1 21mm1 13 30A (NOTE-3)F30T 16mm2 16mm2 6mm2
F30SPD 1 - -1 13 30A (NOTE-5)6mm2 6mm2 6mm2
2 3 2 103mm 500A (4-WIRE + GND)11F500 150mm2 150mm2 35mm2
3 1 53mm111 175A (4-WIRE + GND)F175 70mm2 70mm2 16mm2
2 3 2 103mm 800A (4-WIRE + GND)11F800 300mm2 300mm2 70mm2
3 1 53mm111F125 50mm2 50mm2 16mm2 125A (4-WIRE + GND)
4000A (4-WIRE + GND)11 13 1 11 103mmF4000 300mm2 300mm2 300mm2
UNCLASSIFIED
A
CADD Plot Scale
CADD File Name:
Classification
H&A Project Number
OBO Project Number: Drawing Scale
Drawing Title
A/OBO/PE/PM A/OBO/PE/BDE
United States Department of StateUnited States Department of StateUnited States Department of StateUnited States Department of State
Washington, D.C.Washington, D.C.Washington, D.C.Washington, D.C.
WARNING:
Release For Construction:
Date
Drawn By
Checked By
This document is the property of the U.S. Government.
Further reproduction and/or distribution outside the contractor team is prohibited without the express written approval of:
U.S. Department of State
ATTN: RONETTE C MCBEAN
Washington, D.C. 20520.
OFFICE OF OVERSEAS BUILDINGS OPERATIONSOFFICE OF OVERSEAS BUILDINGS OPERATIONSOFFICE OF OVERSEAS BUILDINGS OPERATIONSOFFICE OF OVERSEAS BUILDINGS OPERATIONS
1:1
Sheet Number
B.L. Harbert International, L.L.C.
1031 London Drive Birmingham, Alabama 35211 Tel (205) 802-2900
Page Southerland Page, Inc.
1615 M Street NW, Suite 700 Washington, DC 20036 Tel (202) 909-4900
Cervantes & Associates, P.C.
4229 Lafayette Center Dr, Suite 1125 Chantilly, VA 20151 Tel: (703) 691-4114
Ehlert /Bryan, Inc.
1451 Dolley Madison Blvd, Suite 220 McLean, VA 22101 Tel: (703) 827-9552
Schnabel Engineering North, L.L.C.
46020 Manekin Plaza, Suite 110 Sterling, VA 20166 Tel: (703) 779-0773
NEW
Hankins and Anderson, Inc.
4880 Sadler Rd, Suite 300
Glen Allen, VA 23063 Tel. (804) 285-4171
Woods Peacock Engineering Consultants, Inc.
Halifax Office Park, Suite 420 5250 Cherokee Ave
Alexandria, VA 22312-2052 Tel: (703) 658-4400
Weidlinger Associates, Inc.
40 Wall Street, 19th Floor
New York, New York 10005 Tel: 212-367-2919
Rhodeside & Harwell 510 King Street, Suite 300 Alexandria, Virginia 22314
Tel: (703) 683-7447
9694.00
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
R
171 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
EMBASSY COMPOUND
FOR
N'DJAMENA, CHAD
S
T
S
T
07 APR 2015
SAQMMA-14-C-0055 AS NOTED
IF
C
A
P R
M
A Y
D E
L
IV
E R
Y T
O O
B O
P2 −
CERTIFICATION
P1B −
EARLY SITE
P1A − ROUGH
GRADING B
C
M
A Y
B C
F
E B
C D
−2
C D
−1
D
E C
IF
C
N
O V
C D
B C
S
E P
C D
N
O V
4/1/2015 1:16:48 AM
DGG
CVR
E1-612
COMPOUND SINGLE LINE
DIAGRAM
CMPD
NDJ−CMPD−E1−612− COMPOUND SINGLE LINE DIAGRAM.dwg
NOTES
1. REFER TO DWG. CMPD E1-001 FOR ABBREVIATIONS, LEGEND AND GENERAL NOTES.
2. THE COMPOUND PV SYSTEM DATA ACQUISITION SYSTEM SHALL BE INTEGRATED WITH
THE COMPOUND POWER MONITORING AND CONTROL SYSTEM. REFER TO DWG. CMPD
E1-615.
3. ALL SWITCHGEAR, SWITCHBOARDS AND PANELBOARDS SHALL BE EQUIPPED WITH
SPARE BREAKERS, SPACES FOR ADDITIONAL BREAKERS AND 20% SPARE CAPACITY PER
THE SPECIFICATIONS.
4. ALL PANELBOARDS SHALL BE EQUIPPED WITH BOLT-ON CIRCUIT BREAKERS ONLY.
5. PROVIDE CIRCUIT BREAKERS WITH MEANS TO PERMIT THE UTILIZATION OF LOCK-OUT,
TAG-OUT DEVICES IN ACCORDANCE WITH DIV. 26 SPECIFICATIONS.
KEYNOTES
1 PROVIDE 100% RATED CIRCUIT BREAKER.
2 PROVIDE CIRCUIT BREAKER WITH INTEGRAL CURRENT AND VOLTAGE METER WITH
DIGITAL DISPLAY. CIRCUIT BREAKER SHALL ALSO BE EQUIPPED WITH kWH
TRANSDUCER COMPATIBLE WITH THE POWER MONITORING AND CONTROL SYSTEM.
EQUIP CIRCUIT BREAKER WITH LOCAL MEANS OF DIRECTLY READING THE
TRANSDUCER MEASUREMENTS.
3 PROVIDE GENERATOR ANNUNCIATION WIRING TO REMOTE ANNUNCIATOR IN NOB
MSG POST 1.
4 PROVIDE GENERATOR ANNUNCIATION WIRING TO REMOTE ANNUNCIATOR IN NOB
SWITCHBOARD ROOM.
5 PROVIDE INTEGRAL SPD AND DISCONNECTING MEANS VIA A CIRCUIT BREAKER PER
SPECIFICATION SECTION 264315. SPD DESIGNATIONS SHALL BE "A = BRANCH PANEL
RATED - 120kA" , "B = DISTRIBUTION PANEL RATED - 160kA", "C = SERVICE ENTRANCE RATED - 240kA".
6 PROVIDE A MULTIFUNCTION DIGITAL METER WITH POWER QUALITY MONITORING
CAPABILITY.
7 GROUND THE ELECTRICAL SYSTEM IN ACCORDANCE WITH NEC 250.32(B)(1) FOR A
BUILDING SUPPLIED FROM A COMMON SERVICE. PANELBOARD SHALL BE PROVIDED
WITH SPD PROTECTION.
8 PROVIDE SWITCHGEAR/SWITCHBOARD WITH MAINTENANCE MODE ARC FLASH
REDUCTION SWITCHES PER SPECIFICATION SECTIONS 262315-2.2.V. AND 262413-2.1.O.
9 TERMINATE THE CONDUITS FOR THE FUTURE FEEDER FROM THE FUTURE MAIN
SERVICE SWITCHGEAR IN THE TRENCH BENEATH THE PARALLELING SWITCHGEAR
‘GENSG’. PROVIDE THE CIRCUIT BREAKER, METERING, ETC. FOR CONNECTION TO
THE FUTURE OUTDOOR MAIN SERVICE SWITCHGEAR FEEDER BREAKERS. TYPICAL
FOR PLC CONTROL AND POWER MONITORING WIRING.
10 PROVIDE LOAD BANK WITH INTEGRAL 1000A, 3P DISCONNECT SWITCH FOR LOAD
DISCONNECTION MEANS AT THE LOAD BANK. PROVIDE WIRING/CONDUIT BETWEEN
SWITCHGEAR POWER SYSTEM CONTROLLER AND THE LOAD BANK CONTROL PANEL.
11 PROVIDE COPPER MAIN BONDING JUMPER BUSSING BETWEEN THE NEUTRAL BUS
AND THE EQUIPMENT GROUNDING BUS, SIZED PER NEC 250.
12 COORDINATE THE BUS RATING OF THE PANELBOARD OR SWITCHBOARD AND THE
PLACEMENT OF THE FEEDER CIRCUIT BREAKER FOR THE FEEDER THAT IS
INTERCONNECTED TO THE PHOTOVOLTAIC SYSTEM PER THE REQUIREMENTS OF NEC
690.64 AND 705.12(D).
13 REFER TO COMPOUND MAIN EQUIPMENT GROUNDING DIAGRAM ON DWG.CMPD
E1-614.
14 THE AVAILABLE FAULT CURRENT LEVEL INDICATED IS BASED ON LOCAL ELECTRIC
UTILITY POWER VIA A 2500kVA TRANSFORMER WITH AN IMPEDANCE OF 5.7%.