19710-VMS HVAC COMPLETE SET 4.10.26.pdf
PDF 4 MB Posted
- Attached to
- IFB # VMS-02-202526 VIRGINIA MIDDLE SCHOOL HVAC
- Solicitation number
- IFB-117905
- Issued by
- Bristol City, Virginia
About this file
This is a comprehensive construction document set for the Virginia Middle School HVAC Replacement project in Bristol, Virginia Public Schools. The project consists of the installation of new HVAC mechanical equipment, including replacement of existing fan coils and unit ventilators with direct replacement equipment, replacement of chilled water and hot water pumps with the addition of a redundant chilled water pump, insulation of air-cooled chiller piping connections, installation of an electric heater in the boiler room, addition of a mini-split system to the library server room, and replacement of the kitchen make-up air unit and exhaust fan with direct replacement equipment. The project is designed in accordance with the 2021 Virginia Uniform Statewide Building Code, 2021 Virginia Construction Code, 2021 Virginia Energy Conservation Code, 2020 NFPA 70 National Electrical Code, and ADA accessibility standards. The school building, originally constructed circa 1914 with additions in 1994 and 1995, is classified as Use Group E (Educational) Type V construction. The project does not modify existing building heights, areas, occupant loads, occupancy type, or plumbing fixture counts.
The mechanical scope of work includes multiple fan coil units (FC-001 through FC-B203), unit ventilators (UV-001 through UV-B114), circulating water pumps (CWP-1, CWP-2, HWP-1, HWP-2), air handling units (AC-1), exhaust fans (KEF-1), make-up air units (KSF-1), and a ductless mini-split heat pump system (HP-1 with indoor unit IDU-1) specified with Trane and Greenheck equipment. The electrical work includes new disconnects, variable frequency drives, control wiring connections, circuit breaker modifications in existing panels, and a 480-volt 225-ampere service upgrade to accommodate the new loads. The project documents indicate available electrical service capacity of 640 amperes with existing demand loads of 508 amperes, and new HVAC loads totaling 95.8 amperes, leaving 36.2 amperes of remaining capacity. All work must comply with manufacturer recommendations, include proper ductwork insulation per SMACNA standards, condensate drainage with proper trapping, and system balancing by AABC or NEBB certified contractors. The contractor is responsible for obtaining permits, coordinating with all trades, verifying field conditions prior to construction, and providing a five-year warranty on air conditioning compressors and one-year service guarantees on all new controls and equipment.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT DESCRIPTION:
THE PROJECT CONSIST OF THE INSTALLATION OF NEW HVAC MECHANICAL EQUIPMENT.
CODES & REGULATIONS
2021 VIRGINIA UNIFORM STATEWIDE BUILDING CODE (VUSBC); EFFECTIVE JANUARY 18,
2024.
2021 VIRGINIA CONSTRUCTION CODE (VCC), PART I OF THE VIRGINIA UNIFORM
STATEWIDE BUILDING CODE (VUSBC); EFFECTIVE JANUARY 18, 2024.
2021 VIRGINIA CONSTRUCTION CODE (VCC), PART II OF THE VIRGINIA UNIFORM
STATEWIDE BUILDING CODE (VUSBC); EFFECTIVE JANUARY 18, 2024 - USING THE WORK
AREA METHOD: LEVEL-1 ALTERATIONS.
2021 VIRGINIA ENERGY CONSERVATION CODE (2021 VECC).
ACCESSIBILITY: ADA90-TITLE-II.
ICC/ANSI A117.1-2017 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
2021 VIRGINIA MECHANICAL CODE
2021 VIRGINIA PLUMBING CODE
2020 NFPA 70 NATIONAL ELECTRICAL CODE
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN (ADAAG)
2021 VIRGINIA STATEWIDE FIRE PREVENTION CODE
2021 VIRGINIA BUILDING AND FIRE CODE RELATED REGULATIONS
ALL NEW WORK TO COMPLY WITH THE ADA STANDARDS FOR ACCESSIBLE DESIGN (2010
EDITION).
EXISTING CONSTRUCTION SHALL BE MAINTAINED IN COMPLIANCE WITH THE CODE IN
EFFECT AT THE TIME OF CONSTRUCTION.
VIRGINIA MIDDLE SCHOOL: CONSTRUCTED CIRCA: 1914, 1994, 1995.
PROJECT DOES NOT MODIFY THE EXISTING BUILDINGS' HEIGHTS.
PROJECT DOES NOT MODIFY THE EXISTING BUILDINGS' AREAS.
PROJECT DOES NOT MODIFY THE EXISTING BUILDINGS' OCCUPANT LOADS, OCCUPANCY
TYPE/ USE GROUP.
PROJECT DOES NOT REDUCE THE PLUMBING FIXTURE COUNTS.
CODE DATA
BUILDING PURPOSE / OCCUPANCY: EDUCATIONAL (EXISTING)
USE GROUP CLASSIFICATION: USE GROUP E (EXISTING)
CONSTRUCTION TYPE: TYPE V (EXISTING) (ASSUMED)
BRISTOL VIRGINIA PUBLIC SCHOOLS
PREPARED FOR
KENTUCKY
TENNESSEE
NORTH CAROLINA
VIRGINIA
WEST
VIRGINIA
WASHINGTON
D.C.
NASHVILLE
FRANKFORT
CHARLESTON
RICHMOND
RALEIGHKNOXVILLE
CHATTANOOGA
ASHEVILLE
CHARLOTTE
ROANOKE
BLUEFIELD
TAZEWELL
ABINGDON
BRISTOL
DUFFIELD
HARLAN
NORTON
RICHLANDS
GRUNDY
PRINCETON
LEXINGTON
N
PROJECT LOCATION
PROJECT LOCATION
FOR MECHANICAL ONLY
Sheet No.
Seal
Designed
Drawn
Checked
Date
Project No.
D a te /T im e
F il e
N a m e
VICINITY MAP LOCATION MAPEST. 1956
100 Fifth Street
Suite 400
Bristol, TN 37620
P: (423) 989-9491, F: (423) 989-9010 www.T-L.com
H V
A C
R E
P
LA
C E
M E
N T
/1
/2
:4
:4
A M se rv e r-b ri st o l\ b ri st o l\ p ro je ct s\
-V
M S
H V
A C
\0
A R
C H
IT
E
C T
U R
A L\
D ra w in g s\
C o n st ru ct io n
D ra w in g s\
B a se F il e s\
-V M
S H
V A
C .r v t
G001
T
IT
LE
S
H E
E T
B R
IS
T
O L
V
IR
G
IN
IA
P
U B
LI
C
S C
H O
O
LS
V
IR
G
IN
IA
M
ID
D
LE
S
C H
O O
L
APRIL 10, 2026
PROJECT NO. : 19710
APRIL 10, 2026
ISSUED FOR BIDS
19710
KS
EL
EL
BRISTOL VIRGINIA PUBLIC SCHOOLS
VIRGINIA MIDDLE SCHOOL
HVAC REPLACEMENT
BRISTOL, VA
SHEET INDEX
SHEET NAME SHEET NUMBER
GENERAL
TITLE SHEET G001
STRUCTURAL
GENERAL NOTES, PARTIAL SECOND LEVEL FRAMING PLAN, AND SECTIONS S100
MECHANICAL
MECHANICAL NOTES, SPECIFICATIONS & LEGEND M001
MECHANICAL SCHEDULES & DETAILS M002
MECHANICAL DETAILS M003
GROUND FLOOR HVAC DEMO PLAN MD100
FIRST FLOOR-NORTH WING HVAC DEMO PLAN MD101
FIRST FLOOR-SOUTH WING HVAC DEMO PLAN MD102
SECOND FLOOR-NORTH WING HVAC DEMO PLAN MD103
SECOND FLOOR-SOUTH WING HVAC DEMO PLAN MD104
GROUND FLOOR NEW HVAC WORK PLAN M100
FIRST FLOOR-NORTH WING HVAC NEW WORK PLAN M101
FIRST FLOOR-SOUTH WING HVAC NEW WORK PLAN M102
SECOND FLOOR-NORTH WING HVAC NEW WORK PLAN M103
SECOND FLOOR-SOUTH WING HVAC NEW WORK PLAN M104
ELECTRICAL
GENERAL NOTES, LEGEND, AND ABBREVIATIONS E001
ELECTRICAL PLAN -GROUND FLOOR E100
ELECTRICAL PLAN -FIRST FLOOR NORTH WING E101
ELECTRICAL PLAN -FIRST FLOOR SOUTH WING E102
ELECTRICAL PLAN -SECOND FLOOR NORTH WING E103
ELECTRICAL PLAN -SECOND FLOOR SOUTH WING E104
SCHEDULES E701
SCHEDULES E702
N o
D a te
P u rp o s e o f D o c u m e n t Is s u e
FOR STRUCTURAL ONLY FOR ELECTRICAL ONLY
'-5
INSTALL SIMPSON LU28 W/ #9x1 1/2" SD
CONNECTOR SCREWS, 8 SCREWS IN SUPPORTING
MEMBER, 6 SCREWS IN SUPPORTED MEMBER
INSTALL SIMPSON LU210R-18 W/ #9x1 1/2" SD
CONNECTOR SCREWS, 10 SCREWS IN SUPPORTING
MEMBER, 6 SCREWS IN SUPPORTED MEMBER
INSTALL SIMPSON LU28 W/ #9x1 1/2" SD
CONNECTOR SCREWS, 8 SCREWS IN SUPPORTING
MEMBER, 6 SCREWS IN SUPPORTED MEMBER
EXST 2x8
EXST 2x10 ROUGH
CUT @ 16" OC, TYP
EXST BRG WALL
EXST BRG WALLAC-1
4"
'-6
S100S100
EXTEND HSS A MINIMUM OF 1'-0"
BEYOND END OF AC-1. HSS SHALL
EXTEND AT LEAST TO ADJACENT
EXST FLOOR JOIST PAST UNIT.
HSS6x4x1/4 ASTM
A500 GR C
EXST PLYWOOD
SHEATHING
AC-1
EXST 2x10
ROUGH CUT
GENERAL
1. THE CONTRACTOR SHALL REFER TO DRAWINGS OF OTHER TRADES AND VENDOR DRAWINGS FOR EMBEDDED ITEMS
AND RECESSES NOT SHOWN ON THE STRUCTURAL DRAWINGS.
2. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS OF EXISTING CONSTRUCTION WHICH AFFECT NEW
CONSTRUCTION AND REPORT VARIATIONS TO THE ENGINEER PRIOR TO SUBMISSION OF SHOP DRAWINGS.
3. THE CONTRACTOR SHALL VERIFY ALL SIZES AND LOCATIONS OF ALL MECHANICAL AND ELECTRICAL OPENINGS AND
EQUIPMENT PADS WITH THE MECHANICAL AND ELECTRICAL EQUIPMENT DETAILS AND SHOP DRAWINGS. IT SHALL
BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ALL OPENINGS AND SLEEVES FOR THE PROPER
DISTRIBUTION OF ALL UTILITY LINES THROUGHOUT THE BUILDING.
4. THE CONTRACTOR SHALL PROVIDE ADEQUATE BRACING FOR THE STRUCTURE SO THAT IT WILL BE STABLE DURING
ALL STAGES OF CONSTRUCTION. THE STRUCTURE AND FOUNDATIONS ARE DESIGNED FOR A COMPLETED
CONDITION ONLY AND, THEREFORE, REQUIRE ADDITIONAL SUPPORT TO MAINTAIN STABILITY BEFORE
COMPLETION.
RENOVATION AND EXISTING STRUCTURES
1. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS, ETC., NECESSARY FOR THE PROPER
CONSTRUCTION AND ALIGNMENT OF THE NEW PORTIONS OF THE STRUCTURE TO THE EXISTING STRUCTURE. THE
CONTRACTOR SHALL VERIFY ALL MEASUREMENTS NECESSARY FOR PROPER FABRICATION AND ERECTION OF ALL
STRUCTURAL MEMBERS.
2. BEFORE PROCEEDING WITH ANY WORK WITHIN OR ADJACENT TO THE EXISTING STRUCTURE, THE CONTRACTOR
SHALL BECOME FAMILIAR WITH EXISTING CONDITIONS. DURING THE PROCESS OF CONSTRUCTION, IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO MAINTAIN THE INTEGRITY OF THE EXISTING STRUCTURE WHERE THE EXISTING
STRUCTURE IS MODIFIED TO ACCOMMODATE NEW CONSTRUCTION AND TO PROTECT FROM DAMAGE THOSE
PORTIONS OF THE EXISTING STRUCTURE, WHICH ARE TO REMAIN.
3. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER OF ANY EXISTING CONDITIONS THAT DIFFER FROM
THOSE INDICATED ON THE DRAWINGS.
4. ANY DAMAGE TO THE EXISTING STRUCTURE FROM NEW CONSTRUCTION SHALL BE REPAIRED BY THE CONTRACTOR
AT NO COST TO THE OWNER.
Sheet No.
Seal
Designed
Drawn
Checked
Date
Project No.
D a te /T im e
F il e
N a m e
/1
/2
:0
:4
P
M R
P ro je ct s\
V ir g in ia
M id d le
S ch o o l H V
A C
\0
E N
G
IN
E E
R
IN
G \S
T R
U C
T \D ra w in g s\ D
W G
\1
V ir g in ia
M id d le
S ch o o l- S tr u ct u ra l v
.r v t
S100
G E
N E
R A
L N
O T
E S
P
A R
T
IA
L S
E C
O N
D L
E V
E L
F R
A M
IN
G
P
LA
N
A N
D
S E
C T
IO
N
S
B R
IS
T
O L
V
IR
G
IN
IA
P
U B
LI
C
S C
H O
O
LS
V
IR
G
IN
IA
M
ID
D
LE
S
C H
O O
L H
V A
C R
E P
LA
C
E M
E N
T
19710
04/10/2026
MLT
TOW
KAA
SCALE: 1/2" = 1'-0"
1' 2'0 4'
PLAN NORTH
1/2" = 1'-0"
PARTIAL SECOND FLOOR FRAMING PLAN
SCALE: 3/4" = 1'-0"S100 S100
1 SECTION
SCALE: 3/4" = 1'-0"
8" 1'-4"0 2'-8"
NORTH WING
SOUTH WING
KEY PLAN
NTS
N o
D a te
P u rp o s e o f D o c u m e n t Is s u
= SMOKE/FIRE DAMPER
DAMPERS IN HORIZONTAL DUCT
DAMPERS IN VERTICAL DUCT
= SMOKE DAMPER
SIDEWALL GRILLE
RETURN, TRANSFER GRILLE
SUPPLY DIFFUSER
EXHAUST GRILLE
GRILLE IDENTIFICATION
AND CFM RATING
LOUVER WITH
POINT OF DEMOLITION
POINT OF CONNECTION
NEW TO EXISTING
or MANUAL BALANCING DAMPER
SQUARE TO ROUND TRANSITION
BIRD SCREEN
THERMOSTAT
TAKE-OFF WITH SPIN-IN
FITTING
VERTICAL RISE
IN RETURN/EXHAUST DUCT
FULL RADIUS ELBOW
VERTICAL RISE
IN SUPPLY DUCT
SPIN-IN TAKE-OFF IN
BOTTOM OF DUCT
TURNING VANES
SQUARE TURN WITH
DOUBLE THICKNESS
H.V.A.C. LEGEND AND SYMBOLS
SUPPLY, EXHAUST,
RETURN DUCT
BRANCH TAKE-OFF
= FIRE DAMPER
12x8
12x8
12x8 x8
12x8
~ 6"∅
12x8
8x8
12x8
OR
OR
OR
OR
OR
OR
OR
OR
OR
OR
VERTICAL DROP
IN SUPPLY DUCT
~ ~OR
OR ~ ~
VERTICAL DROP
IN RETURN/EXHAUST DUCT
T
1. GENERAL
A. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY TO INSTALL ALL AIR CONDITIONING, HEATING AND VENTILATING WORK INDICATED ON THE DRAWINGS, SPECIFIED HEREIN, AND
IN ACCORDANCE WITH ALL CITY, STATE, AND NATIONAL CODES.
B. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED PERMITS, FEES, AND INSPECTIONS. COORDINATE WITH ALL OTHER TRADES, APPLICABLE SPECS, DRAWINGS, AND OWNER'S DIRECTIONS.
C. THE MECHANICAL DRAWINGS ARE GENERALLY DIAGRAMMATIC. DO NOT SCALE THE DRAWINGS FOR EXACT SIZE OR LOCATIONS.
D. PRODUCTS SHALL BE NEW AND FIRST LINE QUALITY, OF GRADE AND TYPE SHOWN ON PLANS AND SPECIFIED, OR EQUALS AS APPROVED BY THE DESIGNER IN WRITING. ALL PRODUCTS SHALL BE IN CURRENT
PRODUCTION WITH NO NOTICE OF BEING DISCONTINUED OR DRASTICALLY CHANGED FROM CURRENT PRODUCTION.
E. MECHANICAL EQUIPMENT AND ACCESSORIES SHALL BE INSTALLED IN A NEAT WORKMANLIKE MANNER. UNSIGHTLY INSTALLATIONS SHALL BE REMOVED OR REWORKED AT NO EXPENSE TO THE OWNER.
F. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING A BID AND PRIOR TO CONSTRUCTION.
G. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL COORDINATION WITH THESE DRAWINGS.
H. COORDINATE ALL PENETRATIONS OF FLOOR SLABS, ROOF AND WALLS WITH STRUCTURAL DRAWINGS.
I. SEAL ALL WALL, ROOF AND FLOOR PENETRATIONS BY MECHANICAL AND ELECTRICAL SERVICE AIRTIGHT.
J. EXISTING CONDITIONS SHOWN HEREIN WERE TAKEN FROM SITE OBSERVATIONS, ORIGINAL DESIGN DRAWINGS AND AS-BUILT DOCUMENTATION WHERE AVAILABLE; ANY DISCREPANCIES BETWEEN THE PLANS AND
ACTUAL FIELD CONDITIONS SHALL BE REPORTED TO THE ARCHITECT / ENGINEER.
K. HVAC CONTRACTOR SHALL REPLACE THE EQUIPMENT FILTERS AT THE TIME OF POSSESSION OF THE PROJECT BY THE OWNER, USING ONLY NEW FILTERS OF THE PROPER SIZE AND TYPE.
L. HVAC CONTRACTOR SHALL REPAIR, REPLACE, OR REPAINT TO MATCH EXISTING SURFACES DAMAGED DURING INSTALLATION OF THE MECHANICAL SYSTEM.
M. EQUIPMENT AND MATERIALS SUBMITTED AS ALTERNATES TO THE SPECIFIED DATA MUST BE CLEARLY MARKED AS TO THE DIFFERENCES IN SUBMITTED VERSUS SPECIFIED. FAILURE TO CLEARLY MARK THE SUBMITTALS
AS SUCH IS GROUNDS FOR REJECTION. SUBMITTALS NOT CLEARLY MARKED AS BEING ALTERNATE TO THE SPECIFIED DATA CAN BE ASSUMED TO MEET ALL SPECIFIED REQUIREMENTS AND THE PROVIDER IS
RESPONSIBLE TO PROVIDE AS SUCH.
2. DEMOLITION
A. THE CONTRACTOR SHALL REMOVE EXISTING HVAC EQUIPMENT, ALL ASSOCIATED ACCESSORIES AND MATERIALS AS SHOWN AND TURN OVER TO THE OWNER OR REMOVE FROM THE SITE LEGALLY IF SO DIRECTED BY
THE OWNER.
B. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY EXISTING CONDITIONS BEFORE DEMOLITION WORK BEGINS. REPORT ANY DISCREPANCIES BETWEEN THE PLANS AND ACTUAL FIELD CONDITIONS TO THE
ARCHITECT / ENGINEER PRIOR TO THE COMMENCEMENT OF DEMOLITION WORK.
C. DEMOLITION WORK SHALL BE PHASED TO ACCOMPLISH REPLACEMENT WITH MINIMUM AMOUNT OF DOWNTIME. SCHEDULE NEW AND DEMOLITION WORK IN ADVANCE WITH THE OWNER.
3. EQUIPMENT
A. THE MECHANICAL SYSTEM(S) SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
B. ALL EQUIPMENT SHALL BE U.L. LISTED.
C. CONTRACTOR SHALL VERIFY ELECTRICAL VOLTAGE, LOADS ETC. WITH ELECTRICAL TRADE, OR EXISTING CONDITIONS, PRIOR TO ORDERING EQUIPMENT.
D. EQUIPMENT SELECTIONS SHOWN ON THE DRAWINGS ARE THE BASIS OF DESIGN. ACTUAL INSTALLED EQUIPMENT AND DIFFERENT MANUFACTURERS MAY DIFFER FROM THAT SHOWN. EQUIPMENT TYPE, PHYSICAL
SIZE, CLEARANCES, WEIGHT, CAPACITIES AND PERFORMANCE CHARACTERISTICS SHALL BE GOVERNING FACTORS IN SUBMITTING SUBSTITUTIONS FOR REVIEW AND APPROVAL. COORDINATE EQUIPMENT ELECTRICAL
REQUIREMENTS WITH THE ELECTRICAL DRAWINGS.
E. EQUIPMENT SHALL OPERATE QUIETLY. THE OPERATION OF THE EQUIPMENT SHALL CAUSE NO PERCEPTIVE VIBRATION OR OBJECTIONABLE NOISE IN ANY PORTION OF THE BUILDING OR STRUCTURE.
F. DO NOT BLOCK COIL PULL OR SERVICE SPACE ON EQUIPMENT WITH PIPING, DUCTWORK, ETC. (FLANGE OR REMOVABLE SECTION MAY BE USED IN SOME INSTANCES WHERE TIGHT CLEARANCE EXIST).
G. DO NOT BLOCK FILTER REMOVAL ON EQUIPMENT WITH PIPING, DUCTWORK, ETC. DEMONSTRATE FILTER REMOVAL TO OWNER'S REPRESENTATIVE FOR EACH UNIT AS PART OF TRAINING.
H. PROVIDE STARTERS, INTERNAL PROTECTION, OR OTHER DEVICES INDICATED ON DRAWINGS. COORDINATE VOLTAGE, PHASE, AMPERAGE, AND OTHER REQUIREMENTS WITH ELECTRICAL DRAWINGS. UNLESS OTHERWISE
NOTED, SERVICE DISCONNECTS SHALL BE PROVIDED BY MECHANICAL CONTRACTOR AND INSTALLED BY ELECTRICAL CONTRACTOR.
I. RECIRCULATING AIR SYSTEMS ABOVE 2,000 CFM SHALL HAVE A DUCT MOUNTED SMOKE DETECTOR IN THE RETURN AIR STREAM PRIOR TO ANY EXHAUSTING FROM THE BUILDING OR MIXING WITH FRESH AIR MAKE-
UP.
J. PROVIDE LOW AMBIENT CONTROL TO 0 DEGREE FAHRENHEIT FOR ALL REFRIGERANT EQUIPMENT.
K. PROVIDE SUCTION LINE ACCUMULATOR FOR REFRIGERANT LINES OVER 70 EQUIVALENT LINEAL FEET (MAX LENGTH 120 FEET). VERIFY WITH MANUFACTURER.
L. FURNISH A FIVE-YEAR WARRANTY ON AIR CONDITIONING COMPRESSOR UNIT AND PROVIDE A ONE-YEAR SERVICE AND GUARANTEE ON ALL NEW CONTROLS AND EQUIPMENT. CONTRACTOR SHALL REPLACE ANY
DEFECT IN MATERIAL OR WORKMASHIP FOR (1) ONE YEAR FROM DATE OF ACCEPTANCE. DATE OF ACCEPTANCE IS DATE CERTIFIED BY ARCHITECT / ENGINEER THAT CONTRACT HAS BEEN SATISFACTORILY COMPLETED
IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
MECHANICAL NOTES & SPECIFICATIONS
4. AIR DISTRIBUTION
A. FRESH AIR INTAKES SHALL NOT BE LOCATED CLOSER THAN 10 FEET FROM ANY EXHAUST OR OUTLET VENT.
B. EVERY EFFORT HAS BEEN MADE TO ALLOW A FREE PATH OF RETURN AIRFLOW TO THE PROPER HVAC UNIT FOR THE CEILING RETURN PLENUM SYSTEM. IF UNEXPECTED FIELD CONDITIONS ARE FOUND TO PROHIBIT
THE AIR RETURN PATH THE CONTRACTOR SHALL REPORT THE ISSUE TO THE ARCHITECT / ENGINEER.
C. DUCTWORK:
a. DUCTWORK SHALL BE GALVANIZED SHEET METAL, UNLESS OTHERWISE NOTED, AND INSTALLED ACCORDING TO SMACNA STANDARDS.
b. PROVIDE FLEXIBLE CONNECTORS BETWEEN DUCTWORK AND ALL EQUIPMENT / FANS.
c. ALL ROUND DUCTWORK ELBOWS SHALL BE RADIUS TYPE WITH CENTERLINE RADIUS EQUAL TO 1.5 X DIAMETER. RECTANGULAR DUCT ELBOWS SHALL BE RADIUS TYPE WITH CENTERLINE RADIUS EQUAL TO
1.5 X WIDTH WHERE INSTALLATION PERMITS. SQUARE THROATED ELBOWS WITH SINGLE WALL TURNING VANES SHALL BE USED WHERE RADIUS TYPE RECTANGULAR DUCT ELBOWS CAN NOT BE
PRACTICALLY INSTALLED. FABRICATE AND INSTALL PER SMACNA STANDARDS.
d. INSTALL BALANCING DAMPERS AT ALL BRANCH DUCT TAKE-OFFS.
e. DUCTWORK DIMENSIONS GIVEN ARE INSIDE CLEAR.
f. CONTRACTOR SHALL VERIFY CLEARANCE REQUIREMENTS AND INDICATED ROUTING OF DUCTWORK PRIOR TO FABRICATION AS RISES AND DROPS MAY BE NECESSARY DUE TO THE TRUSS FRAMING
SYSTEM.
g. VARIATION OF DUCT CONFIGURATION OR SIZES OTHER THAN THOSE OF EQUIVALENT OR LOWER LOSS COEFFICIENT IS NOT PERMITTED EXCEPT BY WRITTEN PERMISSION. SIZE ROUND DUCTS INSTALLED IN
PLACE OF RECTANGULAR DUCTS IN ACCORDANCE WITH ASHRAE TABLE OF EQUIVALENT RECTANGULAR AND ROUND DUCTS.
h. ALL EXPOSED DUCTWORK AND ACCESSORIES SHALL BE FURNISHED WITH A PAINTABLE FINISH.
i. COORDINATE MOUNTING HEIGHT OF EXPOSED DUCTWORK WITH LIGHTING.
j. WHERE DUCTWORK CAN BE SEEN THRU GRILLES, PAINT DUCT WITH FLAT BLACK ENAMEL PAINT.
k. ALL SUPPLY, RETURN AND OUTSIDE AIR DUCTWORK SHALL BE EXTERNALLY INSULATED UNLESS OTHERWISE NOTED. INSULATE DUCT SYSTEM WITH 2.2 INCH, 3/4 LB DENSITY, FOIL FACED FIBERGLASS
INSULATION WITH VAPOR BARRIER ON THE OUTSIDE. INSTALL PER SMACNA STANDARDS. INSULATED FLEX DUCT SHALL HAVE A MINIMUM R-6 INSULATION VALUE. (EXCEPTION: DUCT LOCATED OUTSIDE
THE BUILDING INSULATION LAYER SHALL BE 2 INCH, 3 LB DENSITY AND FLEX DUCT TO BE R-8).
l. EXHAUST DUCT SHALL NOT BE INSULATED, UNLESS OTHERWISE NOTED.
m. EXPOSED SPIRAL DUCT SHALL NOT BE INSULATED, UNLESS OTHERWISE NOTED.
n. ALL TRANSFER AIR DUCT SHALL BE LINED WITH ½” ACOUSTICAL LINER UNLESS OTHERWISE NOTED ON THE PLANS.
o. EXTERIOR DUCTWORK SHALL BE EXTERNALLY INSULATED WITH 2”, 3 LB DENSITY FOIL FACED FIBERGLASS INSULATION WITH ALUMINUM JACKET SEALED WEATHER TIGHT. TOP SURFACE SHALL BE TAPERED
TO PREVENT WATER POOLING ON THE DUCTWORK.
p. CONTRACTOR SHALL PROVIDE CERTIFIED AIR SYSTEM BALANCE. BALANCING CONTRACTOR SHALL BE AABC OR NEBB CERTIFIED. PROVIDE REPORT TO ENGINEER/ARCHITECT.
D. KITCHEN HOOD EXHAUST DUCT:
1. MUST BE CONSTRUCTED OF 16 GA. CARBON STEEL OR 18 GA. STAINLESS STEEL. ALL SEAMS, JOINTS AND PENETRATIONS MUST HAVE LIQUID TIGHT CONTINUOUS EXTERNAL WELDS.
2. DUCT MUST HAVE 18” CLEARANCE FROM ANY COMBUSTIBLE MATERIALS. EXCEPTION: THE DUCT IS WRAPPED WITH FIREMASTER DUCTWRAP (OR APPROVED EQUAL) PER MANUFACTURERS
RECOMMENDATION.
3. AN ACCESS DOOR LARGE ENOUGH TO PERMIT CLEANING MUST BE PROVIDED AT EACH CHANGE IN DIRECTION OF THE DUCT.
4. DUCT MUST BE SIZED TO PRODUCE NO LESS THAN 1,500 (500, NEW NFPA) FEET PER MINUTE OF VELOCITY.
E. AIR DEVICES:
1. REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATION OF GRILLES, REGISTERS AND DIFFUSERS.
2. COORDINATE GRILLE, REGISTER AND DIFFUSER LOCATIONS WITH THE LIGHTING AND CEILING GRID LAYOUT.
3. PROVIDE ALL DIFFUSERS IN THE SAME SPACE WITH THE SAME FULL-FACE SIZE USING THE LARGEST SIZE.
4. DUCT MOUNTED REGISTERS SHALL BE MOUNTED IN A COLLAR WITH SUFFICIENT LENGTH TO PREVENT DAMPERS FROM OBSTRUCTING AIR FLOW. COLLARS TO BE OVERSIZED FOR REVERSE FLANGE
REGISTER MOUNTING.
5. PROVIDE COMPANION OPPOSED BLADE VOLUME DAMPERS WITH ALL DIFFUSERS MOUNTED IN DRYWALL.
5. PIPING
A. ALL CONDENSATE DRAIN LINES SHALL BE SCHEDULE 40 DWV-PVC PIPE AND FULL SIZE, OR LARGER, OF EQUIPMENT DRAIN. TRAP AND VENT AT EQUIPMENT. ROUTE TO THE NEAREST FLOOR DRAIN OR AS DIRECTED
ON THE DRAWINGS. MAINTAIN A MIN. 2" AIR GAP FROM DRAIN DISCHARGE TO DRAIN TOP.
B. REFRIGERANT PIPE INSULATION SHALL BE FLEXIBLE, CLOSED CELL ELASTOMERIC PIPE INSULATION. INSULATION MATERIAL SHALL BE CLOSED CELL STRUCTURE TO PREVENT MOISTURE FROM WIKING AND SHALL
HAVE A FLAME SPREAD INDEX OF LESS THAN 25 AND A SMOKE DEVELOPED INDEX OF LESS THAN 50 AS TESTED PER ASTM E 84. INSULATION THICKNESS TO BE ¾”.
C. HYDRONIC CHILLED WATER AND HOT WATER PIPING 2-1/2” OR LESS SHALL BE COPPER TYPE-L. PIPING 3” OR LARGER SHALL BE BLACK STEEL. PIPING SHALL BE INSULATED ACCORDING TO THE ENERGY CODE, UNLESS OTHERWISE NOTED.
D. INSTALL HEAT TAPE TO ALL WATER CONTAINING PIPE SUBJECT TO FREEZING. (OR MINIMUM WATT DENSITY OF 8 WATTS PER LINEAR FOOT FOR PIPE AND 16 WATTS PER LINEAR FOOT FOR VALVES AND FITTINGS.
COVER HEAT CABLE WITH A MINIMUM OF 2” INSULATION. COVER INSULATION WITH A WEATHERPROOF OUTER JACKET.
E. PROVIDE CHROME-PLATED ESCUTCHEONS AT ALL EXPOSED PIPE PENETRATIONS THROUGH WALLS.
F. THE CONTRACTOR SHALL PROVIDE A CERTIFIED HYDRONIC SYSTEM BALANCE. BALANCING CONTRACTOR SHALL BE AABC OR NEBB CERTIFIED. PROVIDE REPORT TO ENGINEER/ARCHITECT.
G. ANY EXPOSED, HORIZONTAL, INSULATED PIPE LOWER THAN 8'-0" AFF SHALL RECEIVE METAL JACKET TO PROTECT INSULATION.
6. CONTROLS
A. PROVIDE CONTROLS REQUIRED TO OPERATE EQUIPMENT AND AS INDICATED ON DRAWINGS. WIRE AND CONNECT AS REQUIRED.
B. PROVIDE 7-DAY PROGRAMMABLE THERMOSTAT; LOCATE AS SHOWN ON PLANS. THERMOSTATS SHALL BE WALL MOUNTED AT 5'-6" AFF. INSTALL AT 4'-0" AFF WHERE REQUIRED AND/OR AS DIRECTED TO MEET
HANDICAP ACCESSIBILITY.
C. CONTROLS SHALL BE INSTALLED IN ACCORDANCE WITH THE CONTROL MANUFACTURER'S SUGGESTIONS AND RECOMMENDATIONS. CONTROL WIRING AND CONTROL WIRING CONNECTIONS TO HVAC EQUIPMENT
SHALL BE BY THE MECHANICAL CONTRACTOR. ALL EXPOSED CONTROL WIRING THAT MAY BE SUBJECTED TO PHYSICAL DAMAGE SHALL BE ROUTED IN CONDUIT.
SCOPE OF WORK:
1) REPLACEMENT OF THE EXISTING FAN COILS AND UNIT VENTILATORS WITH DIRECT REPLACEMENT EQUIPMENT.
2) REPLACEMENT OF THE CHILLED WATER AND HOT WATER PUMPS AND THE ADD A REDUNDANT CHILLED WATER PUMP.
3) INSULATE THE AIR COOLED CHILLER PIPING CONNECTIONS.
4) ADD AN ELECTRIC HEATER TO THE BOILER ROOM.
5) ADD A MINI-SPLIT TO THE LIBRARY SERVER ROOM.
6) REPLACEMENT OF THE KITCHEN MAKE-UP AIR UNIT AND EXHAUST FAN WITH DIRECT REPLACEMENT EQUIPMENT.
Sheet No.
Designed
Drawn
Checked
Date
Project No.
D a te /T im e
F il e
N a m e
/9 /2
:3
:3
P M
C
U se rs \j o h n n y ca rr
\D o cu m e n ts \1
V ir g in ia M id d le S ch o o l M e ch
R jc a rr
Z
LX
X Q
.r v t
M001
M E
C H
A N
IC
A
L N
O T
E S
S
P E
C
IF
IC
A
T
IO
N S
L
E G
E N
D
B R
IS
T
O L
V
IR
G
IN
IA
P
U B
LI
C
S C
H O
O
LS
V
IR
G
IN
IA
M
ID
D
LE
S
C H
O O
L H
V A
C R
E P
LA
C
E M
E N
T
19710
04/10/2026
JRC
LRF
LRF
IS
S
U E
D F
O R
R E
V
IE
W
N o
D a te
R e v is io n s
FOUR-PIPE FAN COIL UNIT SCHEDULE
MARK TYPE CFM
MIN.
O.A. CFM
MANUFACTURER AND MODEL NO. VOLT/PHE.S.P.
FC-001 TRANE MODEL FCCB060 HORIZ. CONCEALED 600 60 0.2 115/1
MCA
3.88
MOCP
CAPACITY
MBH
22.57
GPM
P.D.
(FT. HD)
3.34
EWT/LWT
(DEG F)
190/144.91
SENS MBH
14.3
TOTAL MBH
GPM
2.04
P.D.
(FT. HD)
3.95
EWB/LWB
(DEG F)
67/57.45
WEIGHT
(LBS.)
HOT WATER HEATING (PREHEAT) CHILLED WATER COOLING
CAPACITY
FC-002 TRANE MODEL FCCB080 HORIZ. CONCEALED 800 200 0.2 115/1 3.88 15 27.82 1 4.06 190/134.39 18.89 23.7 3.5 5.34 67/57.59 147
FC-003 TRANE MODEL FCCB030 HORIZ. CONCEALED 300 60 0.2 115/1 2.75 15 11.51 0.65 1.02 190/154.63 7.06 9 1.56 3.55 67/57.45 81
FC-004 HORIZ. CONCEALED 1000 - 0.2 115/1 6.08 15 34.95 1 5.64 190/120.09 21.27 23 2.85 2.43 67/59.83 200
FC-005 HORIZ. CONCEALED 600 100 0.2 115/1 3.88 15 22.57 1 3.34 190/144.91 14.3 18 2.04 3.95 67/57.45 139
FC-A101 HORIZ. CONCEALED 600 60 0.2 115/1 3.88 15 22.57 1 3.34 190/144.91 14.3 18 2.04 3.95 67/57.45 139
FC-A102 HORIZ. CONCEALED 600 - 0.2 115/1 3.88 15 22.57 1 3.34 190/144.91 14.3 18 2.04 3.95 67/57.45 139
FC-A103 HORIZ. CONCEALED 600 100 0.2 115/1 3.88 15 22.57 1 3.34 190/144.91 14.3 18 2.04 3.95 67/57.45 139
FC-A104 VERTICAL CABINET 800 - 0.0 115/1 4.19 15 28.99 1.15 5.17 190/139.62 15.38 17.72 3.5 4.29 67/60.12 165
FC-A105
FC-A106 HORIZ. CONCEALED 1000 - 0.2 115/1 6.08 15 34.95 1 5.64 190/120.09 21.27 23 2.85 2.43 67/59.83 200
FC-A107
FC-B101 HORIZ. CONCEALED 200 - 0.2 115/1 2.75 15 7.56 0.27 0.22 190/134.02 4.5 5.5 0.86 1.24 67/58.32 81
FC-B102 -
FC-B103 HORIZ. CONCEALED 400 60 0.2 115/1 2.75 15 15.42 0.8 1.74 190/151.5 8.39 8.9 0.96 1.7 67/60.08 109
FC-B104 60 -
FC-B105 HORIZ. CONCEALED 400 - 0.2 115/1 2.75 15 15.42 0.8 1.74 190/151.5 8.39 8.9 0.96 1.7 67/60.08 109
FC-B106 HORIZ. CONCEALED 300 50 0.2 115/1 2.75 15 11.51 0.65 1.02 190/154.63 7.06 9 1.56 3.55 67/57.45 81
FC-B107 HORIZ. CONCEALED 600 - 0.2 115/1 3.88 15 22.57 1 3.34 190/144.91 14.3 18 2.04 3.95 67/57.45 139
FC-A201 HORIZ. CONCEALED 600 60 0.4 115/1 3.88 15 22.57 1 3.34 190/144.91 14.3 18 2.04 3.95 67/57.45 139
FC-A202 HORIZ. CONCEALED 600 - 0.4 115/1 3.88 15 22.57 1 3.34 190/144.91 14.3 18 2.04 3.95 67/57.45 139
FC-A203 HORIZ. CONCEALED 1200 300 0.2 115/1 6.08 15 37.55 1.05 6.16 190/118.47 25.14 27 3.26 3.15 67/60 200
FC-A204
FC-A205 HORIZ. CONCEALED 400 50 0.2 115/1 2.75 15 15.42 0.8 1.74 190/151.5 8.39 8.9 0.96 1.7 67/60.08 109
FC-A206 HORIZ. CONCEALED 800 80 0.2 115/1 3.88 15 27.82 1 4.06 190/134.39 18.89 23.7 3.5 5.34 67/57.59 147
FC-B201 HORIZ. CONCEALED 600 100 0.2 115/1 3.88 15 22.57 1 3.34 190/144.91 14.3 18 2.04 3.95 67/57.45 139
FC-B202
FC-B203
TRANE MODEL FCCB100
TRANE MODEL FCCB060
TRANE MODEL FCCB060
TRANE MODEL FCCB060
TRANE MODEL FCCB060
TRANE MODEL FCBB080
TRANE MODEL FCCB100
TRANE MODEL FCCB020
TRANE MODEL FCCB040
TRANE MODEL FCCB040
TRANE MODEL FCCB030
TRANE MODEL FCCB060
TRANE MODEL FCCB060
TRANE MODEL FCCB060
TRANE MODEL FCCB120
TRANE MODEL FCCB040
TRANE MODEL FCCB080
TRANE MODEL FCCB060
200HORIZ. CONCEALED 1000 - 0.2 115/1 6.08 15TRANE MODEL FCCB100
HORIZ. CONCEALED 200 0.2 115/1 2.75 15
HORIZ. CONCEALED 400 0.2 115/1 2.75 15
TRANE MODEL FCCB020
TRANE MODEL FCCB040
HORIZ. CONCEALED 600 100 0.2 115/1 3.88 15TRANE MODEL FCCB060
HORIZ. CONCEALED 600 100 0.2 115/1 3.88 15TRANE MODEL FCCB060
200HORIZ. CONCEALED 1200 300 0.2 115/1 6.08 15TRANE MODEL FCCB120
34.95 1 5.64 190/120.09 21.27 2.85 2.43 67/59.8323
7.56 0.27 0.22 190/134.02 4.5 5.5 0.86 1.24 67/58.32
15.42 0.8 1.74 190/151.5 8.39 8.9 0.96 1.7 67/60.08
37.55 1.05 6.16 190/118.47 27 3.26 3.15 67/6025.14
22.57 1 3.34 14.3 18 2.04 3.95 67/57.45
22.57 1 3.34 14.3 18 2.04 3.95 67/57.45
190/144.91
190/144.91
EDB/LDB
(DEG F)
70/104.69
70/102.06
70/105.39
70/102.23
70/104.95
70/104.69
70/104.69
70/104.69
70/103.41
70/102.23
70/104.86
70/105.55
70/105.39
0/104.69
70/104.69
70/104.69
70/98.85
70/105.55
70/102.06
70/104.69
EDB/LDB
(DEG F)
80/58.14
80/58.33
80/58.42
80/60.48
80/58.14
80/58.14
80/58.14
80/58.14
80/62.37
80/60.48
80/59.38
80/60.76
80/58.42
80/58.14
80/58.14
80/58.14
80/60.78
80/60.76
80/58.33
80/58.14
FAN COIL NOTES
1. DISCONNECT TO BE PROVIDED AND INSTALLED BY ELECTRICAL
2. ECM FAN MOTOR
3. COPPER COIL AND ALUMINUM FINS
4. NON-CORRISIVE DRAIN PAN WITH CONDENSATE OVERFLOW SENSOR
5. 1" MERV 8 FILTER
6. PROVIDE NEW 7-DAY PROGRAMMABLE AUTO-CHANGEOVER SPACE THERMOSTAT
7. PROVIDE NEW 2-WAY MODULATING CONTROL VALVES AND BALANCING VALVES
8. CONNECT TO EXISTING DUCTWORK
9. CONNECT TO EXISTING BAS
10. FIELD VERIFY LEFT / RIGHT HAND COIL CONNECTIONS WITH EXISTING PIPING
PRIOR TO ORDER
11. OUTSIDE AIR RATES ARE BASED ON EXISTING DRAWINGS.
12. PROVIDE LOCKABLE THERMOSTAT COVER FOR UNITS IN THE CORRIDOR.
EWT/LWT
(DEG F)
45/62.58
45/55.09
45/61.11
45/56.53
45/62.58
45/63.51
45/58.5
45/62.58
45/61.11
45/62.58
45/62.58
45/62.58
45/58.5
45/62.58
45/56.53
70/102.23 80/60.48 45/61.11
45/63.51
45/57.74
45/62.58
70/104.86 80/59.38 45/57.74
70/105.55 80/60.76 45/63.51
70/105.55 80/60.76 45/63.51
70/104.69 80/58.14 45/62.58
70/104.69 80/58.14 45/62.58
45/62.58
45/61.51
70/98.85 80/60.78 45/61.51
VERTICAL CABINET 800 - 0.0 115/1 4.19 15 28.99 1.15 5.17 190/139.62 15.38 17.72 3.5 4.29 67/60.12 165TRANE MODEL FCBB080 70/103.41 80/62.37 45/55.09
CIRCULATING WATER PUMP SCHEDULE
GPMMARK HP HEAD (FT.) EFF.% TYPEMANUFACTURER AND MODEL NO.
RPM @
DUTY POINT
VOLTS/PH
CWP-1 B&G SERIES E-1510 MODEL 5EB 660 30 105 76.5 1770 END SUCTION
CWP-2
HWP-1 B&G SERIES E-1510 MODEL 3EB 237 15 87.1 70.2 1588 END SUCTION 460-3
HWP-2
B&G SERIES E-1510 MODEL 5EB 660 30 105 76.5 1770 END SUCTION
1. CWP-1&2 TO HAVE B&G SUCTION DIFFUSER PLUS MODEL GG-3X AND B&G TRIPLE DUTY VALVE MODEL 3DS-6B
2. HWP-1&2 TO HAVE B&G SUCTION DIFFUSER PLUS MODEL EE-3X AND B&G TRIPLE DUTY VALVE MODEL 3DS-4B
3. MOUNT TO NEW CONCRETE PADS
4. CONNECT TO EXISTING PIPING
5. PROVIDE NEW COMBINATION DISCONNECT/VFD'S.
6. CONNECT TO EXISTING CONTROLS
WEIGHT IN LBS.
685460-3
460-3
B&G SERIES E-1510 MODEL 3EB 237 15 87.1 70.2 1588 END SUCTION 460-3 450
AIR HANDLING UNIT SCHEDULE
FILTERS
WPDGPMLWTEWTAPD
F.V.
MAX
TCLATEAT
COOLING COIL (CHILLED WTR.)
MBH
LAT
DEG. F
APD
CFM ESPDESIGN HP
VOLTS
PREHEAT COIL (HOT WATER)
EAT
DEG. F
MANUFACTURER AND MODEL NO. MAX F.V.
FT/MIN
2" PLEATED MERV 820.8770.9956.23450.71151640055.72870.148516477.8292.4540460-3100.758400TRANE MODEL UCCAG17AC-1 2185
WEIGHT
(LBS.)GPM
FLA
2" PLEATED MERV 816.7181.0455451.102590406.6353.31800.137590361.7584.7550460-3150.59600TRANE MODEL UCCAG17HV-1 2392.632.521
2" PLEATED MERV 811.4787.3855450.848560438.4555.05800.125560432.9985.0250460-37-1/20.611400TRANE MODEL UCCAG21HV-2 2639.937.511
AC-1 NOTES
1. DISCONNECT TO BE PROVIDED AND INSTALLED BY ELECTRICAL
2. FAN MOTOR VFD
3. COPPER COIL AND ALUMINUM FINS
4. NON-CORRISIVE DRAIN PAN WITH CONDENSATE OVERFLOW SENSOR
5. 2" MERV 8 FILTER
6. PROVIDE NEW 7-DAY PROGRAMMABLE AUTO-CHANGEOVER SPACE
THERMOSTAT. PROVIDE LOCKABLE COVER.
7. PROVIDE NEW 3-WAY MODULATING CONTROL VALVES AND BALANCING VALVES
8. CONNECT TO EXISTING DUCTWORK
9. CONNECT TO EXISTING BAS
10. FIELD VERIFY LEFT / RIGHT HAND COIL CONNECTIONS WITH EXISTING PIPING
PRIOR TO ORDER
11. CONFIRM MECHANICAL ROOM DOOR OPENING PRIOR TO ORDER AND
INSTALLATION.
HV NOTES
1. DISCONNECT TO BE PROVIDED AND INSTALLED BY ELECTRICAL
2. FAN MOTOR VFD
3. COPPER COIL AND ALUMINUM FINS
4. NON-CORROSIVE DRAIN PAN WITH CONDENSATE OVERFLOW SENSOR
5. 2" MERV 8 FILTER
6. PROVIDE NEW 7-DAY PROGRAMMABLE AUTO-CHANGEOVER SPACE THERMOSTAT. PROVIDE
LOCKABLE COVER.
7. PROVIDE NEW 3-WAY MODULATING CONTROL VALVES AND BALANCING VALVES
8. CONNECT TO EXISTING DUCTWORK
9. CONNECT TO EXISTING BAS
10. FIELD VERIFY LEFT / RIGHT HAND COIL CONNECTIONS WITH EXISTING PIPING PRIOR TO
ORDER
11. SEE STRUCTURAL DRAWINGS FOR HANGING UNIT FROM GYM STRUCTURE.
SC
289.99
282.46
313.47
EXHAUST FAN SCHEDULE
CONTROLLOCATIONSONES
RPM
TYPE
HPWG
CFMMARK
SP.
MANUFACTURER AND MODEL NO.
FAN
MOTOR
VOLTS
GREENHECK MODEL CUBE-300-30 7255 1.1 3 460/3 UPBLAST 698 16 KITCHEN ON/OFFKEF-1
1. DISCONNECT PROVIDED BY MECHANICAL AND INSTALLED BY ELECTRICAL
2. INTERLOCK WITH EXISTING KITCHEN HOOD
3. PROVIDE CURB ADAPTER
4. BIRDSCREEN AND BACKDRAFT DAMPER
(LBS.)
WEIGHT
MAKE-UP AIR UNIT SCHEDULE
MARK
CFM
AIRFLOW
KSF-1
(IN)
ESP
0.25
HEATING CAPACITY
(MBH) ENT LVG GAS HEAT
AIR TEMP (DEG. F)
SUPPLY FAN
HP RPM
ELECTRICAL DATA
VOLTAGE MCA FUSE
MAX
LBS.
WEIGHT
11.4 460/35080 421
INPUT
NAT GAS
MBH
GROSS HEAT
CAPACITY
387.3 822 1725 5.1 15 1154
MANUFACTURER &
MODEL NUMBER
GREENHECK MODEL DGX-P116-H22-MF
1. DISCONNECT PROVIDED BY MECHANICAL AND INSTALLED BY ELECTRICAL
2. INTERLOCK WITH EXISTING KITCHEN HOOD. ONLY OPERATE WHEN HOOD IS ON
3. PROVIDE CURB ADAPTER
4. PROVIDE NEW UNIT CONTROLLER AND CONNECT TO EXISTING CONTROLS
5. PROVIDE FACTORY SUPPLIED RECEPTACLE WITH OUTDOOR COVER
6. CONNECT TO EXISTING GAS PIPING
FOUR-PIPE UNIT VENTILATOR SCHEDULE
MARK TYPE CFM O.A. CFMMANUFACTURER AND MODEL NO. VOLT/PHE.S.P.
UV-001 TRANE MODEL HUVC150 HORIZONTAL
MCA MOCP CAPACITY
MBH
GPM
P.D.
(FT. HD)
EWT/LWT
(DEG F) SENS MBH TOTAL MBH
GPM
P.D.
(FT. HD)
EWB/LWB
(DEG F)
WEIGHT
(LBS.)
HOT WATER HEATING (PREHEAT) CHILLED WATER COOLING
CAPACITY
UV-002
UV-003 TRANE MODEL HUVC125 HORIZONTAL 1200 300 0.15 277/1 6.56 15 70.3 1.5 0.23 190/96.17 28.3 38.6 9.63 10.71 67/56.83 435
UV-004
UV-005
UV-006 TRANE MODEL HUVC150 HORIZONTAL
UV-007
UV-008
UV-009
UV-010
UV-A101 TRANE MODEL HUVC125 HORIZONTAL 1200 300 0.15 277/1 6.56 15 70.3 1.5 0.23 190/96.17 28.3 38.6 9.63 10.71 67/56.83 435
UV-A102 TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.86 32.51 48.4 10 8.53 67/55.92 470
UV-A103 TRANE MODEL HUVC125 HORIZONTAL 1200 250 0.15 277/1 6.56 15 69.11 1.5 0.23 190/97.76 28.3 38.6 9.63 10.71 67/56.83 435
UV-A104
UV-A105 TRANE MODEL HUVC150 HORIZONTAL 1404 - 0.15 277/1 6.56 15 68.22 1.5 0.26 190/98.95 32.89 44.6 10 12.97 67/56.98 500
UV-A106 TRANE MODEL HUVC150 HORIZONTAL 1404 300 0.15 277/1 6.56 15 74.69 1.5 0.26 190/90.29 32.89 44.6 10 12.97 67/56.98 500
UV-A107
UV-A108 TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.88 32.51 48.4 10 8.53 67/55.92 470
UV-A109
UV-A110
UV-A111 TRANE MODEL VUVE075 VERTICAL 750 150 0.0 277/1 2 15 30.47 1.6 1.03 180/142.66 13.63 19.58 4 2.49 67/57.27 320
UV-B101
UV-B102 TRANE MODEL HUVC125 HORIZONTAL 1200 300 0.15 277/1 6.56 15 70.3 1.5 0.23 190/96.17 28.3 38.6 9.63 10.71 67/56.83 435
UV-B103
UV-B104 TRANE MODEL HUVC150 HORIZONTAL 1404 300 0.15 277/1 6.56 15 74.69 1.5 0.26 190/90.29 32.89 44.6 10 12.97 67/56.98 500
UV-B105
UV-B106 TRANE MODEL HUVC150 HORIZONTAL 1404 200 0.15 277/1 6.56 15 74.47 1.5 0.26 190/93.26 32.89 44.6 10 12.97 67/56.98 500
UV-B107 TRANE MODEL HUVC125 HORIZONTAL 1200 250 0.15 277/1 6.56 15 68.81 1.5 0.23 190/98.16 28.3 38.6 9.63 10.71 67/56.83 435
UV-B108
UV-B109 TRANE MODEL HUVC100 HORIZONTAL 953 200 0.15 277/1 6.56 15 46.86 1 0.1 190/96.18 21.46 30 7.42 5.82 67/57.07 375
UV-B110
UV-B111 TRANE MODEL HUVC200 HORIZONTAL 1621 750 0.15 277/1 6.56 15 102.64 2.1 0.48 190/92.13 42.06 62 14.12 12.93 67/54.65 600
UV-B112
UV-B113 TRANE MODEL VUVE150 VERTICAL 1500 750 0.0 277/1 4 15 86.32 3.5 6.98 180/131.31 32.51 48.4 10 8.53 67/55.92 470
UV-B114
UV-A201 TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.88 32.51 48.4 10 8.53 67/55.92 470
UV-A202
UV-A203
UV-A204
UV-A205 TRANE MODEL VUVE125 VERTICAL 1250 200 0.0 277/1 4 15 41.48 1.6 1.8 180/129.33 22.68 34.14 8 6.2 67/55.75 450
UV-A206 TRANE MODEL VUVE100 VERTICAL 1000 200 0.0 277/1 2 15 38.23 1.6 1.53 180/133.22 22.5 32.26 6 4.06 67/55.57 405
UV-A207 TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.88 32.51 48.4 10 8.53 67/55.92 470
UV-A208
UV-A209
UV-A210
UV-A211
UV-A212
UV-B201 TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.88 32.51 48.4 10 8.53 67/55.92 470
UV-B202
UV-B203
UV-B204
TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.88 32.51 48.4 10 8.53 67/55.92 470
TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.88 32.51 48.4 10 8.53 67/55.92 470
TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.88 32.51 48.4 10 8.53 67/55.92 470
TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.88 32.51 48.4 10 8.53 67/55.92 470
TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.88 32.51 48.4 10 8.53 67/55.92 470
TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.88 32.51 48.4 10 8.53 67/55.92 470
TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.88 32.51 48.4 10 8.53 67/55.92 470
TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.88 32.51 48.4 10 8.53 67/55.92 470
TRANE MODEL VUVE150 VERTICAL 1500 750 0.0 277/1 4 15 86.32 3.5 6.98 180/131.31 32.51 48.4 10 8.53 67/55.92 470
TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.88 32.51 48.4 10 8.53 67/55.92 470
TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.88 32.51 48.4 10 8.53 67/55.92 470
TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.88 32.51 48.4 10 8.53 67/55.92 470
TRANE MODEL HUVC150 HORIZONTAL
TRANE MODEL HUVC125 HORIZONTAL 1200 300 0.15 277/1 6.56 70.3 1.5 0.23 190/96.17 28.3 38.6 9.63 10.71 67/56.83 435
TRANE MODEL HUVC150 HORIZONTAL
TRANE MODEL HUVC150 HORIZONTAL
TRANE MODEL HUVC150 HORIZONTAL
TRANE MODEL HUVC150 HORIZONTAL
TRANE MODEL HUVC125 HORIZONTAL 1200 250 0.15 277/1 6.56 69.11 1.5 0.23 190/97.76 28.3 38.6 9.63 10.71 67/56.83 435
TRANE MODEL HUVC150 HORIZONTAL 1404 300 0.15 277/1 6.56 74.69 1.5 0.26 190/90.26 32.89 44.6 10 12.97 67/56.98 500
TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.88 32.51 48.4 10 8.53 67/55.92 470
TRANE MODEL VUVE150 VERTICAL 1500 300 0.0 277/1 4 15 52.21 1.5 1.89 180/111.88 32.51 48.4 10 8.53 67/55.92 470
TRANE MODEL VUVE075 VERTICAL 750 150 0.0 277/1 2 15 30.47 1.6 1.03 180/142.66 13.63 19.58 4 2.49 67/57.27 320
TRANE MODEL HUVC125 HORIZONTAL 1200 300 0.15 277/1 6.56 70.3 1.5 0.23 190/96.17 28.3 38.6 9.63 10.71 67/56.83 435
TRANE MODEL HUVC150 HORIZONTAL 1404 300 0.15 277/1 6.56 74.69 1.5 0.26 190/90.29 32.89 44.6 10 12.97 67/56.98 500
TRANE MODEL HUVC125 HORIZONTAL 1200 250 0.15 277/1 6.56 68.81 1.5 0.23 190/98.16 28.3 38.6 9.63 10.71 67/56.83 435
TRANE MODEL HUVC100 HORIZONTAL 953 200 0.15 277/1 6.56 46.86 1 0.1 190/96.18 21.46 30 7.42 5.82 67/57.07 375
TRANE MODEL HUVC200 HORIZONTAL 1621 750 0.15 277/1 6.56 102.64 2.1 0.48 190/92.13 42.06 62 14.12 12.93 67/54.65 600
TRANE MODEL HUVC125 HORIZONTAL 1200 300 0.15 277/1 6.56 70.3 1.5 0.23 190/96.17 28.3 38.6 9.63 10.71 67/56.83 43515
HORIZONTAL 1404 300 0.15 277/1 6.56 15 74.69 1.5 0.26 190/90.26 32.89 44.6 10 12.97 67/56.98 500
HORIZONTAL 1404 300 0.15 277/1 6.56 15 74.69 1.5 0.26 190/90.26 32.89 44.6 10 12.97 67/56.98 500
HORIZONTAL 1404 300 0.15 277/1 6.56 15 74.69 1.5 0.26 190/90.26 32.89 44.6 10 12.97 67/56.98 500
HORIZONTAL 1404 300 0.15 277/1 6.56 15 74.69 1.5 0.26 190/90.26 32.89 44.6 10 12.97 67/56.98 500
HORIZONTAL 1404 300 0.15 277/1 6.56 15 74.69 1.5 0.26 190/90.26 32.89 44.6 10 12.97 67/56.98 500
HORIZONTAL 1404 300 0.15 277/1 6.56 15 74.69 1.5 0.26 190/90.26 32.89 44.6 10 12.97 67/56.98 500
HORIZONTAL 1404 300 0.15 277/1 6.56 15 74.69 1.5 0.26 190/90.26 32.89 44.6 10 12.97 67/56.98 500
EDB/LDB
(DEG F)
EDB/LDB
(DEG F)
55/109.03 80/59.42
55/109.03 80/59.42
58/92.22 80/58.89
57.4/110.52 80/59.42
70/114.79 80/59.57
58/107.04 80/59.57
58/92.22 80/58.89
58/101.92 80/60.54
55/109.03 80/59.42
58/107.04 80/59.57
62.2/109.79 80/59.57
58/110.89 80/59.42
58/103.33 80/59.58
47.5/105.88 80/55.98
40/96.58 80/58.89
58/92.22 80/58.89
58/97.07 80/58.84
58/96.63 80/57.47
58/92.22 80/58.89
58/92.22 80/58.89
EWT/LWT
(DEG F)
45/52.99
45/52.99
45/54.9
45/52.99
45/53.89
45/53.89
45/54.9
45/55.09
45/25.99
45/53.89
45/53.89
45/52.99
45/53.06
45/53.75
45/54.9
45/54.9
45/53.77
45/56.02
45/54.4
45/54.9
58/92.22 80/58.89 45/54.9
58/92.22 80/58.89 45/54.9
58/92.22 80/58.89 45/54.9
40/96.58 80/58.89 45/54.9
58/92.22 80/58.89 45/54.4
58/92.22 80/58.89 45/54.4
58/92.22 80/58.89 45/54.4
58/92.22 80/58.89 45/54.4
58/92.22 80/58.89 45/54.4
58/92.22 80/58.89 45/54.9
58/92.22 80/58.89 45/54.9
58/92.22 80/58.89 45/54.9
47.5/105.88 80/55.98 45/53.75
58/103.33 80/59.58 45/53.06
58/110.89 80/59.42 45/52.99
58/107.04 80/59.57 45/53.89
55/109.03 80/59.42 45/25.99
58/101.92 80/60.54 45/55.09
58/107.04 80/59.57 45/53.89
58/92.22 80/58.89 45/54.9
58/92.22 80/58.89 45/54.9
57.4/110.52 80/59.42 45/52.99
58/107.04
58/107.04
58/107.04
58/107.04
58/107.04
58/107.04
58/107.04
45/53.89
45/53.89
45/53.89
45/53.89
45/53.89
45/53.89
45/53.89
80/59.57
80/59.57
80/59.57
80/59.57
80/59.57
80/59.57
80/59.57
55/109.03 80/59.42 45/52.99
55/109.03 80/59.42 45/52.99
ELECTRIC UNIT HEATER SCHEDULE
AGENCY
RATING
MARK KWMANUFACTURER AND MODEL NO.
MARKEL P3P5105CA1N ETL-CUS 5.0EH-1
BTU
17100
VOLT/PH
480/3
AMP
6.18
CONTROL
VOLTAGE
TEMP
RISE
AIR
THROW
CFM
MOUNTING
HEIGHT
VERTICAL
9'-0"
WEIGHT
(IN LBS)
Sheet No.
Designed
Drawn
Checked
Date
Project No.
D a te /T im e
F il e
N a m e
/9 /2
:3
:3
P M
C
U se rs \j o h n n y ca rr
\D o cu m e n ts \1
V ir g in ia M id d le S ch o o l M e ch
R jc a rr
Z
LX
X Q
.r v t
M002
M E
C H
A N
IC
A
L S
C H
E D
U
LE
S
B R
IS
T
O L
V
IR
G
IN
IA
P
U B
LI
C
S C
H O
O
LS
V
IR
G
IN
IA
M
ID
D
LE
S
C H
O O
L H
V A
C R
E P
LA
C
E M
E N
T
19710
04/10/2026
JRC
LRF
LRF
IS
S
U E
D F
O R
R E
V
IE
W
UV NOTES
1. DISCONNECT TO BE PROVIDED AND INSTALLED BY ELECTRICAL
2. ECM FAN MOTOR AND VARIABLE SPEED CONTROL
3. COPPER COIL AND ALUMINUM FINS
4. NON-CORRISIVE DRAIN PAN WITH CONDENSATE OVERFLOW SENSOR
5. 1" MERV 8 FILTER
6. PROVIDE NEW 7-DAY PROGRAMMABLE AUTO-CHANGEOVER SPACE THERMOSTAT
7. PROVIDE NEW 2-WAY MODULATING CONTROL VALVES AND BALANCING VALVES
8. CONNECT TO EXISTING DUCTWORK
9. CONNECT TO EXISTING BAS
10. FIELD VERIFY LEFT / RIGHT HAND COIL CONNECTIONS WITH EXISTING PIPING PRIOR TO ORDER
11. BOTTOM OF CEILING HUNG UNITS ARE TO BE FLUSH WITH CEILING
12. RETURN AIR GRILLE BOTTOM, FRONT DUCTED DISCHARGE, FIELD VERIFY OUTSIDE AIR CONNECTION
IS TOP OR END OF UNIT PRIOR TO ORDERING.
13. OUTSIDE AIR RATES ARE BASED ON EXISTING DRAWINGS.
14. PROVIDE LOCKABLE THERMOSTAT COVER FOR UNITS IN THE CAFETERIA.
1. FINAL DESIGN AND LAYOUT TO BE FIELD VERIFIED AND UPDATED WITH APPROPRIATE RISE, DROPS, AND LENGTHS FOR REFRIGERANT ROUTING.
2. PROVIDE DISCONNECT SIZED AND FUSED/NONFUSED PER MANUFACTURER'S NAMEPLATE REQUIREMENTS. DISCONNECT PROVIDED BY
MECHANICAL AND INSTALLED BY ELECTRICAL.
3. INDOOR UNITS RECEIVE POWER FROM OUTDOOR UNITS THROUGH FIELD-SUPPLIED INTERCONNECTED WIRING.
4. PROVIDE ROOF PAD AND WIND BAFFLES FOR OUTDOOR UNIT.
5. PROVIDE CONDENSATE PUMPS FOR INDOOR UNITS.
6. PROVIDE WITH REMOTE CONTROLLER AND INTERFACE.
7. REFRIGERANT SHALL BE R454B.
DUCTLESS MINI SPLIT SCHEDULE
MANUFACTURER AND MODEL NO.
IDU-1
MARK
MITSUBISHI MSZ-GX12NL
TOTAL
CFM
COOLING
CAPACITY (MBH)
SENSIBLE
10.92
DB
ENTERING AIR
WB
LEAVING AIR
DB
CAPACITY
(MBH) DB
ENTERING AIR
LEAVING AIR
DB
ELECTRICAL
VOLT/PH
HEATING @ 17 DEG. F
WEIGHT IN
LBS
57.3 7.6 86 SEE NOTE 3 30
HP-1
MARK MANUFACTURER AND MODEL NO.
MITSUBISHI MUZ-GX12NLHZ
NOMINAL
COOLING
12 MBH
ELECTRICAL
VOLT/PH MCA MOCP
HEAT PUMP UNIT SCHEDULE
208/230-1 16 20
WEIGHT IN
LBS
N o
D a te
R e v is io n s1. HANG FROM CEILING STRUCTURE. INCLUDE FACTORY MOUNTING KIT.
2. SET THERMOSTAT TO 50 DEG. F
3. DISCONNECT PROVIDED BY MECHANICAL AND INSTALLED BY ELECTRICAL.
CONTROL ACCESS PANEL
REFRIGERANT
LIQUID LINE
BACK-SEATED REFRIGERANT
CONNECTION (TYPICAL)
VALVE (TYPICAL)
REFRIGERANT GAUGE
HANDLE FOR MOVING
SLEEPER PADS
CONTROLPOWER
CONDUIT CONDUIT
FAN GUARD
CONDENSING COIL
MOISTURE INDICATOR
LINE WITH INSULATION
REFRIGERANT SUCTION
SIGHT GLASS WITH
(PROVIDE LOCKING CAPS ON REFRIGERANT SERVICE VALVES)
BALANCING VALVE
LOW PRESSURE
DROP UNION
2-WAY CONTROL VALVE
1/2" AIR VENT
P&T FITTING
1/2" DRAIN
COIL
SHUTOFF VALVE
BALANCING VALVE
3-WAY CONTROL VALVE
1/2" AIR VENT
P&T FITTING
1/2" DRAIN
COIL
LOW PRESSURE
DROP UNION
SHUTOFF VALVE
COMB. STOP, SILENT
TRIPLE DUTY VALVE.
CHECK & BALANCING.
W/ GAUGE COCK &
FLEXIBLE CONNECTION OR
COMPOUND PRESS. GAUGE
VICTAULIC FLEX CPLG, TYP.
SUCTION DIFFUSER
W/ REMOVABLE
BUTTERFLY VALVE
STRAINER
SPILL INTO
FLR. DRAIN.
SNUBBER.
PAD WITH CHAMFERED EDGES
SPRING ISOLATOR
3" HOUSEKEEPING
COUPLING GUARD
NEW PAD
CONNECT TO
EXISTING PIPING
CONNECT TO
EXISTING PIPING
U-BOLT
WITH WASHER
INSULATION
SUCTION LINE
6"X4"X1/2"-12" LONG
ANCHORED TO STRUCTURE
WITH 1/2"X3-1/2"
EXPANSION BOLTS
WALL
U-BOLT
WITH WASHER
ANCHOR TO STRUCTURE
WITH 1/2"X1-1/2" BOLT
WALL
16 GAUGE
GALV. SLEEVE
SUCTION LINE
INSULATION
AROUND OPENING
SEAL ALL
2"X2"X3/16"
BRASS SLEEVE AROUND PIPE.
LIQUID LINE SIMILAR WITH FELT LINED
NOTE:
TYPE "A" VANES
TYPE "B" VANES
RADIUS "F" = 2" RADIUS "G" = 1"
RADIUS "F" = 4-1/2" RADIUS "G" = 2-1/4"
PROVIDE 1 STAY FOR DUCTS 12"
TO 120" WIDE AND 2 STAYS AT 1/3
POINTS FOR 120" AND ABOVE
"G"
DOF ELBOW 45°C
"D" AND "D" UP TO 24"
VANES PRE-ASSEMBLED ON
RUNNERS IN ALL CASES
AIR FLOW
TYPE "B" VANES
TYPE "A" VANES
"D" AND "D" OVER 24"
L
E = 1"C = 1/4"
A = 3-1/4" A = 1-1/2"
C = 1/2"
D
C
E = 2-1/4" B = 9" B = 5"
C
NEEL VANE
OF VANES 50°L
GALVANIZED SHEET METAL VANES
AND PLATES SAME GAUGE AS DUCT
WELD VANES TO PLATE OR ATTACH
WITH ANGLE BRACKETS RIV.
B A
RADIUS
RADIUS "F"
E
E E
C
NOTE: INSULATE DRAIN LINES FROM UNIT FULL LENGTH.
CEILING
FAN COIL UNIT
(SEE SCHEDULE)
AUXILIARY DRAIN PAN
SPRING AND FIBERGLASS
VIBRATION ISOLATORS
FULL SIZE CONDENSATE
DRAIN FROM UNIT
PITCH
SUPPLY AIR
FLEXIBLE CONNECTION
THREADED ROD HANGER
FLOAT SWITCH
CONTACTS TO STOP
WIRE TO COMPRESSOR
ARE MADE
WHEN CONTACTSDRAIN FROM PAN
CAP 3/4" CONDENSATE
AIR
RETURN
OUTSIDE AIR
(IF APPLICABLE)
P-TRAP
SEE COIL CONNECTION DETAIL
CONNECT NEW UNIT TO EXIST. DUCTWORK
HANGERS
(BY OTHERS)
CONNECT TO
EXISTING OUTSIDE
AIR DUCT
EXISTING SUPPLY
AIR DUCT
RETURN
UNIT VENTILATOR
CEILING
CONNECT TO
EXIST PIPING
BOTTOM OF UNIT TO BE
FLUSH WITH CEILING
EXISTING
INTAKE
LOUVER
CHILLED WATER
SUPPLY & RETURN
HOT WATER
SUPPLY & RETURN ~
HEATING COIL
COOLING COIL
FAN
FILTER
RUBBER IN-SHEAR
VIBRATION ISOLATORS
FLOOR
AIR
OUTSIDE
WALL
AIR
RETURN
AIR
SUPPLY
CONNECT NEW UV
TO EXISTING OA
Sheet No.
Designed
Drawn
Checked
Date
Project No.
D a te /T im e
F il e
N a m e
/9 /2
:3
:4
P M
C
U se rs \j o h n n y ca rr
\D o cu m e n ts \1
V ir g in ia M id d le S ch o o l M e ch
R jc a rr
Z
LX
X Q
.r v t
M003
M E
C H
A N
IC
A
L D
E T
A
IL
S
B R
IS
T
O L
V
IR
G
IN
IA
P
U B
LI
C
S C
H O
O
LS
V
IR
G
IN
IA
M
ID
D
LE
S
C H
O O
L H
V A
C R
E P
LA
C
E M
E N
T
19710
04/10/2026
JRC
LRF
LRF
IS
S
U E
D F
O R
R E
V
IE
W
AIR COOLED CONDENSING UNIT DETAIL
CHILLED/HOT WATER COIL PIPING DIAGRAM
(2-WAY VALVE)
CHILLED/HOT WATER COIL PIPING DIAGRAM
(3-WAY VALVE) BASE MOUNTED PUMP DETAILREFRIGERANT PIPE SUPPORTS AT WALL
SQUARE ELBOW DETAIL
N o
D a te
R e v is io n s
HORIZONTAL 4-PIPE FAN COIL INSTALLATION DETAIL
HORIZONTAL 4-PIPE UNIT VENTILATOR
INSTALLATION DETAIL
VERTICAL 4-PIPE UNIT VENTILATOR
INSTALLATION DETAIL
EXIST.
FC-001
EXIST.
CUH-001
EXIST.
CUH-002
EXIST.
FC-005
EXIST.
FC-004
EXIST.
FC-003
EXIST.
FC-002
EXIST.
UH-001
20x8 SA26x8 RA
22x8 OA 32x8 SA x8 R
A x6
S A x8 S
A 22x8 RA
32x8 SA22x8 OA 3 x8 S
A
22x8 OA x8 S
A
22x8 OA
20x8 RA x1
S A x1
S A
20x8 RA x8 S
A
22x8 OA x8 O
A x8
S A
36x8 SA 22x8 OA
1-1/4" CWS & CWR
1" HWS & HWR
1-1/4" CWS & CWR
1" HWS & HWR
1" CWS & CWR
3/4" HWS & HWR
1-1/4" CWS
& CWR
1-1/4" CWS
& CWR
1" HWS
& HWR
1" HWS
& HWR
1" HWS
& HWR
1-1/4" CWS
& CWR
3/4" CWS
& CWR
3/4" HWS
& HWR
1" CWS & CWR
3/4" HWS & HWR
1-1/4" CWS & CWR
1" HWS & HWR 1-1/4" CWS & CWR
1" HWS & HWR
1" CWS & CWR
1" HWS & HWR
1-1/4" CWS & CWR
1" HWS & HWR
1" HWS
& HWR
1-1/4" CWS
& CWR
EXIST.
UV-010
EXIST.
UV-009
EXIST.
UV-008
EXIST.
UV-006
EXIST.
UV-007
EXIST.
UV-003 EXIST.
UV-002
EXIST.
UV001
EXIST.
UV-004
EXIST.
UV-005
1" CWS & CWR
1" HWS & HWR
T T T
T
T T T T T
T
TTTTT
x8 S
A
22x8 OA
36x8 SA 22x8 OA
24x8 SA 22x8 RA
CLASS
TEACHER WORK
CLASS
CRAWL SPACE
COMPUTER
Room
Room
G.T.
CORRIDOR
CLASS
CLASS
CLASS
REMED.
Room
SPEC. ED.
CLASS
CLASS
CLASS
CLASS
Room
CLASS
B.T.
Room
BASEMENT
Room
MECH.
Room
TECH. LAB
Room
Room
Room
Room
JAN. STORAGE
Room
J.C.
TOILET
008A
TOILET
008B
SUPPLY
Room
Sheet No.
Designed
Drawn
Checked
Date
Project No.
D a te /T im e
F il e
N a m e
/9 /2
:3
:4
P M
C
U se rs \j o h n n y ca rr
\D o cu m e n ts \1
V ir g in ia M id d le S ch o o l M e ch
R jc a rr
Z
LX
X Q
.r v t
MD100
G R
O U
N D
F
LO
O R
H V
A C
D E
M O
P
LA
N
B R
IS
T
O L
V
IR
G
IN
IA
P
U B
LI
C
S C
H O
O
LS
V
IR
G
IN
IA
M
ID
D
LE
S
C H
O O
L H
V A
C R
E P
LA
C
E M
E N
T
19710
04/10/2026
JRC
LRF
LRF
IS
S
U E
D F
O R
R E
V
IE
W
SCALE: 1/8" = 1'-0"
4' 8'0 16'
PLAN NORTH
1/8" = 1'-0"
GROUND FLOOR HVAC DEMO PLAN
NORTH WING
SOUTH WING
KEY PLAN
NTS
DEMOLITION KEYED NOTES:
1 DISCONNECT EXISTING PIPING, CONDENSATE AND DUCTWORK AND REMOVE EXISTING UNIT VENTILATORS.
2 DISCONNECT EXISTING PIPING, CONDENSATE AND DUCTWORK AND REMOVE EXISTING FAN COILS.
3 EXIST UNIT HEATERS TO REMAIN.
1 1 1 1
N o
D a te
R e v is io n s
GENERAL DEMO NOTES:
1. AREAS WITH NO UNITS SHOWN ARE OUT OF SCOPE.
2. EXISTING DUCTWORK INCLUDING OUTSIDE AIR CONNECTIONS SHALL REMAIN IN PLACE.
3. EXISTING PIPING EXCEPT CONTROL VALVES AND BALANCING VALVES SHALL REMAIN IN PLACE.
4. DEMOLISH EXISTING UV AND FC THERMOSTATS.
3 3
UPUPUP
CUH-B109
EXIST.
FC-B106
EXIST.
FC-B105
EXIST.
CUH-B101
EXIST.
CUH-B102
EXIST.
UH-B101
EXIST.
FC-B107
EXIST.
UV-B113
EXIST.
UV-B114
EXIST.
CUH-B103
EXIST.
CUH-B104
EXIST.
CUH-B105
EXIST.
CUH-B106
EXIST.
CUH-B108
EXIST.
CUH-B101
EXIST.
FC-B101
EXIST.
FC-B102
1" CWS & CWR
3/4" HWS & HWR
" HWS & HWR
1-1/4" CWS & CWR
1-1/4" CWS & CWR
" HWS & HWR
1" CWS & CWR
3/4" HWS & HWR
1-1/4" CWS & CWR
1" HWS & HWR
1" HWS
& HWR
1-1/4" CWS
& CWR1" HWS
& HWR
1-1/4" CWS
& CWR
1" HWS
& HWR
3/4" CWS & CWR
3/4" HWS & HWR
3/4" CWS & CWR
3/4" HWS & HWR
3/4" CWS & CWR
3/4" HWS & HWR 3/4" CWS & CWR
3/4" HWS & HWR
3/4" CWS & CWR
3/4" HWS & HWR
3/4" CWS & CWR
3/4" HWS & HWR
1" HWS
& HWR
1-1/4" CWS
& CWR
1" HWS & HWR
1" CWS
& CWR
1" HWS & HWR
1" CWS
& CWR1" HWS
& HWR
1-1/4" CWS
& CWR
1" HWS
& HWR
1-1/4" CWS
& CWR
10x6 SA 14x10 RA x6 S
A x6
R A
22x8 OA
30x10 OA 30x10 OA18x8 SA 18x8 SA x8 S
A x1
O
A x1
O A x8 S
A 24x6 SA
78x10 SA
78x10 SA
36x8 SA x6 S
A
24x10 RA
24x10 RA 16x6 SA
18x8 RA 22x8 SA
18x10 RA14x6 SA
78x10 OA
78x10 OA
EXIST.
FC-B103
EXIST.
FC-B104
EXIST.
UV-B109
EXIST.
UV-B108
EXIST.
UV-B107
EXIST.
UV-B110
EXIST.
UV-B106
EXIST.
UV-B111
EXIST.
UV-B112
EXIST.
UV-B102
EXIST.
UV-B103
EXIST.
UV-B104
EXIST.
UV-B105
EXIST.
UV-B101
24x8 RA
T
T T
T
T
T
T
T
T
T
T
T
T
GIRLS LOCKER
STORAGE
SUPP.
STORAGE
TOILET
JAN.
CORRIDOR
136A
P.E. STOR
SPEC. ED.
LOBBY/CORRIDOR
COMPUTER
CLASS
STORAGE
HEALTH CLASS
HEALTH CLASS
PRACTICE
PRACTICE
PRACTICE
146 OFFICE
BAND
INSTR. STOR.
149VEST.
CORRIDOR
154 CHORUS
OFFICE
LIBRARY
STORAGE
VEST.
G.T.
JANITOR
B.T.
DINING
ELEC.
141A
CONCESS.
Sheet No.
Designed
Drawn
Checked
Date
Project No.
D a te /T im e
F il e
N a m e
/9 /2
:3
:4
P M
C
U se rs \j o h n n y ca rr
\D o cu m e n ts \1
V ir g in ia M id d le S ch o o l M e ch
R jc a rr
Z
LX
X Q
.r v t
MD101
F
IR
S T
F
LO
O R
-N O
R T
H W
IN
G
H V
A C
D E
M O
P
LA
N
B R
IS
T
O L
V
IR
G
IN
IA
P
U B
LI
C
S C
H O
O
LS
V
IR
G
IN
IA
M
ID
D
LE
S
C H
O O
L H
V A
C R
E P
LA
C
E M
E N
T
19710
04/10/2026
JRC
LRF
LRF
IS
S
U E
D F
O R
R E
V
IE
W
SCALE: 1/8" = 1'-0"
4' 8'0 16'
PLAN NORTH
1/8" = 1'-0"
FIRST FLOOR-NORTH WING HVAC DEMO PLAN
NORTH WING
SOUTH WING
KEY PLAN
NTS
DEMOLITION KEYED NOTES:
1 DISCONNECT EXISTING PIPING, CONDENSATE AND DUCTWORK AND REMOVE EXISTING UNIT VENTILATORS.
2 DISCONNECT EXISTING PIPING, CONDENSATE AND DUCTWORK AND REMOVE EXISTING FAN COILS.
3 EXIST UNIT HEATERS TO REMAIN.
1 1
1 1
N o
D a te
R e v is io n s
GENERAL DEMO NOTES:
1. AREAS WITH NO UNITS SHOWN ARE OUT OF SCOPE.
2. EXISTING DUCTWORK INCLUDING OUTSIDE AIR CONNECTIONS SHALL REMAIN IN PLACE.
3. EXISTING PIPING EXCEPT CONTROL VALVES AND BALANCING VALVES SHALL REMAIN IN PLACE.
4. DEMOLISH EXISTING UV AND FC THERMOSTATS.
3 3
UPUP
FC-A101
EXIST.
FC-A106
EXIST.
FC-A102
EXIST.
CUH-A102
EXIST.
CUH-A101
EXIST.
CUH-A103
EXIST.
UV-A102
EXIST.
UV-A105
EXIST.
UV-A108
EXIST.
UV-A109
EXIST.
UV-A110
EXIST.
UV-A111
EXIST.
UV-A106
EXIST.
FC-A107
EXIST.
UV-A103
EXIST.
UV-104
EXIST.
UV-A107
EXIST.
FC-A103
EXIST.
UV-A101
1-1/4" CWS & CWR
1" HWS & HWR
1" HWS
& HWR
1-1/4" CWS
& CWR
1-1/4" CWS & CWR
1" HWS & HWR
1-1/4" CWS & CWR
1" HWS & HWR
1-1/4" CWS & CWR
1" HWS & HWR
1" CWS & CWR
3/4" HWS & HWR
1" CWS & CWR
3/4" HWS & HWR
1" HWS & HWR
1-1/4" CWS & CWR
1" HWS & HWR
1-1/4" CWS & CWR
1-1/4" CWS & CWR
1" HWS & HWR
1" CWS & CWR
3/4" HWS & HWR
1-1/4" CWS
& CWR
1" HWS &
HWR
1-1/4" CWS & CWR
1" HWS & HWR
1-1/4" CWS & CWR
1" HWS & HWR
1-1/4" CWS & CWR
1" HWS & HWR
22x8 OA
44x8 OA 32x8 SA x8 S
A x8
R A x6 S
A x8
S A
16x10 RA 16x8 SA
24x6 SA 24x10 RA 24x10 RA 24x8 SA x6 S
A
16x5 RA
22x8 OA
22x8 OA 22x8 OA
22x8 OA
22x8 OA36x8 SA x8 S
A
22x8 OA
36x6 SA
T
T
T
T
T
T
T
T
T
T T T T
T
EXIST.
B-1
EXIST.
B-2
EXIST.
HWP-1
EXIST.
HWP-2
EXIST.
CWP-1
EXIST.
CH-1
LIFE MGMT
STORAGE/KILN
ART
CORRIDOR
OFFICE
WORK
AUDIO/VISUAL
R.R. FOYER
JAN.
STALL
STALL
ADA STALL
BOOK STORE
AUDITORIUM
WORK
WAITING
COT
EXAM
TOILET
TOILET
STORAGE
CONFERENCE
OFFICE
WAITING
SEC
OFFICE
STORAGE
WAIT.
REC.
CONF.
OFF.
OFF.
Room
TOILET
102B
TOILET
102A
PASSAGE
BREAK
WORK
REMED. CLASS
CLASS
CLASS
CLASS
SCIENCE
PREP.
SCIENCE
CORR.
STOR.
STAGE
165A
KITCHEN
OFFICE
JAN.
TOILET
DRY FOOD
MECHANICAL
COOLING TOWER
LIBRARY
OPEN COURT
177B
STALL
230A
STALL
STALL
EXISTING BOILERS
AND PADS TO REMAIN
EXISTING CHILLER
TO REMAIN
EXIST.
FC-A104
EXIST.
FC-A105
EXISTING
KITCHEN
HOOD
SUPPLY
FAN
EXISITNG
KITCHEN
HOOD
EXHAUST
FAN
Sheet No.
Designed
Drawn
Checked
Date
Project No.
D a te /T im e
F il e
N a m e
/9 /2
:3
:4
P M
C
U se rs \j o h n n y ca rr
\D o cu m e n ts \1
V ir g in ia M id d le S ch o o l M e ch
R jc a rr
Z
LX
X Q
.r v t
MD102
F
IR
S T
F
LO
O R
-S O
U T
H W
IN
G
H V
A C
D E
M O
P
LA
N
B R
IS
T
O L
V
IR
G
IN
IA
P
U B
LI
C
S C
H O
O
LS
V
IR
G
IN
IA
M
ID
D
LE
S
C H
O O
L H
V A
C R
E P
LA
C
E M
E N
T
19710
04/10/2026
JRC
LRF
LRF
IS
S
U E
D F
O R
R E
V
IE
W
SCALE: 1/8" = 1'-0"
4' 8'0 16'
PLAN NORTH
1/8" = 1'-0"
FIRST FLOOR-SOUTH WING HVAC DEMO PLAN
NORTH WING
SOUTH WING
KEY PLAN
NTS
DEMOLITION KEYED NOTES:
1 DISCONNECT EXISTING PIPING, CONDENSATE AND DUCTWORK AND REMOVE EXISTING UNIT VENTILATORS.
2 DISCONNECT EXISTING PIPING, CONDENSATE AND DUCTWORK AND REMOVE EXISTING FAN COILS.
3 EXIST UNIT HEATERS TO REMAIN.
4 EXISTING HWP-1, HWP-2 & CWP-1, SUCTION DIFFUSERS AND TRIPLE-DUTY VALVES TO BE REMOVED. ALLOTHER
PIPING AND MECH ROOM EQUIPMENT SHALL REMAIN.
5 KITCHEN HOOD SUPPLY AND EXHAUST FANS TO BE REMOVED BUT DUCTWORK TO REMAIN. EXISTING KITCHEN
HOOD IN KITCHEN SHALL REMAIN.
1 1
N o
D a te
R e v is io n s
GENERAL DEMO NOTES:
1. AREAS WITH NO UNITS SHOWN ARE OUT OF SCOPE.
2. EXISTING DUCTWORK INCLUDING OUTSIDE AIR CONNECTIONS SHALL REMAIN IN PLACE.
3. EXISTING PIPING EXCEPT CONTROL VALVES AND BALANCING VALVES SHALL REMAIN IN PLACE.
4. DEMOLISH EXISTING UV AND FC THERMOSTATS.
3 3
FC-B203
EXIST.
UV-B204
EXIST.
UV-B203
EXIST.
UV-B202
EXIST.
UV-B201
EXIST.
FC-B201
EXIST.
FC-B202
EXIST.
H&V-1
EXIST.
H&V-2
2" HWS & HWR2" HWS & HWR
1" CWS & CWR
3/4" HWS & HWR
1" CWS & CWR
3/4" HWS & HWR
1-1/4" CWS & CWR
1" HWS & HWR
UP FROM BELOW
1-1/4" CWS & CWR
1" HWS & HWR
UP FROM BELOW
1-1/4" CWS & CWR
1" HWS & HWR
UP FROM BELOW
1-1/4" CWS & CWR
1" HWS & HWR
UP FROM BELOW
x6 S
A x8
R A x6 S
A x8
R A
22x8 OA
22x8 OA
22x8 OA
22x8 OA
T
T
T
T
T
T
THIS UNIT WAS NEVER LOCATED IN
THE FIELD. FIELD VERIFY AND
CONTACT ENGINEER OF FINDINGS
CLASS
CLASS
CORRIDOR
CORRIDOR
CLASS
BOYS TOILET
BLEACHERS
GIRLS
CORRIDOR
CLASS
2" CWS & CWR
2" CWS & CWR
EX
IS
T.
S
U P
P
LY
A P
P R
O X
. 8
X
EX
IS
T.
S
U P
P
LY
A P
P R
O X
. 8
X
Sheet No.
Designed
Drawn
Checked
Date
Project No.
D a te /T im e
F il e
N a m e
/9 /2
:3
:4
P M
C
U se rs \j o h n n y ca rr
\D o cu m e n ts \1
V ir g in ia M id d le S ch o o l M e ch
R jc a rr
Z
LX
X Q
.r v t
MD103
S E
C O
N D
F
LO
O R
-N O
R T
H W
IN
G
H V
A C
D E
M O
P
LA
N
B R
IS
T
O L
V
IR
G
IN
IA
P
U B
LI
C
S C
H O
O
LS
V
IR
G
IN
IA
M
ID
D
LE
S
C H
O O
L H
V A
C R
E P
LA
C
E M
E N
T
19710
04/10/2026
JRC
LRF
LRF
IS
S
U E
D F
O R
R E
V
IE
W
SCALE: 1/8" = 1'-0"
4' 8'0 16'
PLAN NORTH
1/8" = 1'-0"
SECOND FLOOR-NORTH WING HVAC DEMO PLAN
NORTH WING
SOUTH WING
KEY PLAN
NTS
DEMOLITION KEYED NOTES:
1 DISCONNECT EXISTING PIPING, CONDENSATE AND DUCTWORK AND REMOVE EXISTING UNIT VENTILATORS.
2 DISCONNECT EXISTING PIPING, CONDENSATE AND DUCTWORK AND REMOVE EXISTING FAN COILS.
3 DISCONNECT…
This is the start of the file's text. The full file is on GovTribe.