19-09_AttachmentD_Drawings.pdf
PDF 4 MB Posted
- Attached to
- 19-09: Controller Replacement
- Solicitation number
- BD-19-1064-1064-02481-38137
- Issued by
- Norfolk County, Massachusetts
About this file
This document contains drawings for a state and local contract opportunity from Mass Bay Community College for the 3rd and 4th Floor Tech Tower Controllers Replacement project. The key details are:
The project involves the removal and replacement of existing Siemens-Talon controllers from unit ventilators (UVs) and fan coil units (FCUs) with new Johnson Controls FX-PCG BACnet MSTP controllers on the 3rd and 4th floors of the Tech Tower. New controls enclosures, space temperature sensors, discharge air temperature sensors, and other associated equipment will also be installed. The work is described in detail across multiple drawing sheets. This is a 100% CD set dated April 8, 2019.
The pricing terms, funding requirements, and other salient details are not included in this drawing set. The related state and local contract opportunity ID is 66abea7c24b406932d030ae5, with a base bid plus two add alternates. The opportunity is from the state of Massachusetts, ID 65a95d78d947088ac30981f7.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Standard_Contract_Form.doc | DOC document | |
| 19-09_AttachmentA_Prevailing Wage.pdf | ||
| 19-09_AttachmentB_ClassSchedule.xls | XLS spreadsheet | |
| 19-09_AttachmentC_Specifications.pdf | ||
| 19-09_IFB_Controller Replacement.doc | DOC document | |
| Commonwealth_Terms_Conditions.doc | DOC document | |
| Massachusetts_Substitute_W9_Form.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
issued for date revisions item date scale sheet title sheet number drawn by:
© 2018 STUDIO ENÉE
WOBURN, MASSACHUSETTS O1801
(781) 935-7228 FAX (781) 935-1822
400 WEST CUMMINGS PARK S.4700
CONSULTING MECHANICAL ENGINEERS
VAV International Inc.
WWW.VAVINT.COM
460 Hillside Avenue, Suite J project name/owner's name
3RD & 4TH FLR TECH
TOWER CONTROLLERS
REPLACEMENT
seal/signature
MASS BAY COMMUNITY
COLLEGE
Needham, Massachusetts 02494 781.858.3011
50 Oakland Street Wellesley Hills, MA 02481
100% CD
APRIL 8TH, 2019
PM
COVER SHEET
M-1
NONE
MASSBAY COMMUNITY COLLEGE
3RD & 4TH FLOOR TECH TOWER CONTROLLERS REPLACEMENT
50 OAKLAND STREET
WELLESLEY HILLS, MA 02481
AutoCAD SHX Text
STUDIO ENÉE
DN UP
UP DN
DN
UP
PLATFORM
BELOW
FL. ELEV. 130'-6"
FL. ELEV. 130'-6"
COPIER
MA
ILB
OX
ES
SHELVING
SH
EL
VI
NG
60 S.F.
SHELVING SHELVING
OUTLINE OF STAIR
ENCLOSURE ABOVE
UP DN DN
UPDN
FE
FE
OPEN TO LIBRARY
BELOW
FE
DN
OPEN TO
COMPUTER ROOM
BELOW
UPDN
OPEN TO BELOW
UP
UP
DN
DN
UP
ROOF BELOW
DN
FL. ELEV. +2'-0" AFF
OF OFFICE
UP
UP
CLASSROOM
CLASSROOM
CLASSROOM
303CLASSROOM
STAIR 1
3RD
OFFICE
STOR.
S302A
CLASSROOM
CLASSROOM
STAIR 14
3RD
JAN.
J300M
WOMEN'S
T300K
FL. ELEV. 130'-6"
STAIR 4
3RD
MULTI-CULTURAL MENTOR PROG.
STOR.
S308A
ELEV1
3RD
CL.
S309A
CL.
S311A
CL.
S313A
CL.
S315A
CL.
S310A
CL.
S312A
CL.
S314A
CL.
S316A
CL.
S316B
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
STAIR 5
3RD
MEN'S
T300BB
JAN.
J300CC
CORRIDOR
300A
CORR.
318A
STOR.
CORRIDOR
300DD
STAIR 6
3RDCAD LAB
INTEL RETENTION LAB
CORR.
300MM
CORRIDOR
300EE
DEAN'S OFFICE
326B
CONF.
326A
CLASSROOM
OFFICE
OBSV.
325A
ELECT.
M323
STOR.
S300GG
CORR.
300FF
RECEPTION
ELEV2
3RD
ASSOC. DEAN
326C
ADMIN ASST.
326D
STAIR 7
3RD
ADJUNCT FACULTY
OFFICE
328A
STOR.
S300JJ
CORR.
300KK
ALL GENDER
T300LL WOMEN'S
T300HH
OFFICE
328C
OFFICE
328B COMP. CNTRL. RM.
328H
IT CLOSET
M328J
CONF.
328K
OFFICE
328G
CORR.
328L
OFFICE
328F
OFFICE
328E
OFFICE
328D
IT TECH LAB
STAIR 15
3RD
STAIR 8
3RD
STAIR 11
3RD
OFFICE
336ACORR.
336D
OFFICE
336B
OFFICE
336C
STOR.
S336
STAIR 13
3RD STOR.
S336E
UP
DN UP
UP
UP DN
DN
UP DN
FE
FE
DN
UP
ROOF CAVITY ABOVE
VAULTED
CATHEDRAL CEILING
DN
FL. ELEV. 133'-7 1/4"
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
STAIR 15
4TH
CORR.
400KK
OFFICE
430A
CL.
S433
CL.
S434
OFFICE
WOMEN'S
T400HH MEN'S
T400LL
OFFICE
OFFICE
STAIR 7
4TH
CLOSET
S425B
COMP. LAB CLRM.
STOR.
S424A
CLASSROOM
ELECT.
M431 CORR.
400FF
ELEV2
4TH
CORR.
400GG
CORRIDOR
400EE
PHYSICS LAB
ELECTRONCS LAB
STAIR 6
4TH
CORRIDOR
400DD
STOR.
S414
STOR.
S412D
STOR.
S412C
BIOLOGICAL SCIENCE
STAIR 5
4TH
MEN'S
T400BB
JAN.
J400CC
ANATOMY / PHYSIOLOGY
CORRIDOR
CL.
S413A
CL.
S411A
CL.
S409A
PREP.
412A
PREP.
412B
PHYSICAL SCIENCE
411 STOR.
S425
CLASSROOM
WOMEN'S
T400K
JAN.
J400M
CHEMISTRY LAB
410B
SCIENCE CLASSRM
410A
ELEV1
4TH
TEL/DATA
M408A
AT&T
STAIR 4
4TH CLASSROOM
CLASSROOM
STAIR 1
4TH
OFFICE
CLASSROOM
CORR.
400A
MECH.
M405
OFFICE
STORAGE
S403D
CLASSROOM
403C
CORR.
400B
ART STUDIO
403B CLASSROOM
403A issued for date revisions item date scale sheet title sheet number drawn by:
© 2018 STUDIO ENÉE
WOBURN, MASSACHUSETTS O1801
(781) 935-7228 FAX (781) 935-1822
400 WEST CUMMINGS PARK S.4700
CONSULTING MECHANICAL ENGINEERS
VAV International Inc.
WWW.VAVINT.COM
460 Hillside Avenue, Suite J project name/owner's name
3RD & 4TH FLR TECH
TOWER CONTROLLERS
REPLACEMENT
seal/signature
MASS BAY COMMUNITY
COLLEGE
Needham, Massachusetts 02494 781.858.3011
50 Oakland Street Wellesley Hills, MA 02481
100% CD
APRIL 8TH, 2019
PM
KEY PLANS
M-2
NONE
3RD FLOOR KEY PLAN
SCALE: NOT TO SCALE
A
M-2
N
N
4TH FLOOR KEY PLAN
SCALE: NOT TO SCALE
B
M-2
AREA OF WORK
3RD FLOOR TECH TOWER
AREA OF WORK
4TH FLOOR TECH TOWER
12.1
19.4
16.9
16.2
19.8
FL. ELEV. 130'-6"
FL. ELEV. 130'-6"
COPIER
MA
ILB
OX
ES
SHELVING
SH
EL
VI
NG
60 S.F.
SHELVING SHELVING
UPDN
UP
UP
DN
DN
DN
UP
FL. ELEV. 130'-6"
STAIR 6
3RDCAD LAB
INTEL RETENTION LAB
CORR.
300MM
CORRIDOR
300EE
DEAN'S OFFICE
326B
CONF.
326A
CLASSROOM
OFFICE
OBSV.
325A
ELECT.
M323
STOR.
S300GG
CORR.
300FF
RECEPTION
ELEV2
3RD
ASSOC. DEAN
326C
ADMIN ASST.
326D
STAIR 7
3RD
ADJUNCT FACULTY
OFFICE
328A
STOR.
S300JJ
CORR.
300KK
ALL GENDER
T300LL WOMEN'S
T300HH
OFFICE
328C
OFFICE
328B COMP. CNTRL. RM.
328H
IT CLOSET
M328J
CONF.
328K
OFFICE
328G
CORR.
328L
OFFICE
328F
OFFICE
328E
OFFICE
328D
IT TECH LAB
STAIR 8
3RD
C D G H J REB F IA K M P QL N SE.6
issued for date revisions item date scale sheet title sheet number drawn by:
© 2018 STUDIO ENÉE
WOBURN, MASSACHUSETTS O1801
(781) 935-7228 FAX (781) 935-1822
400 WEST CUMMINGS PARK S.4700
CONSULTING MECHANICAL ENGINEERS
VAV International Inc.
WWW.VAVINT.COM
460 Hillside Avenue, Suite J project name/owner's name
3RD & 4TH FLR TECH
TOWER CONTROLLERS
REPLACEMENT
seal/signature
MASS BAY COMMUNITY
COLLEGE
Needham, Massachusetts 02494 781.858.3011
50 Oakland Street Wellesley Hills, MA 02481
100% CD
APRIL 8TH, 2019
PM
3RD FLOOR FCU/UV
LOCATIONS
M-3
3RD FLOOR FCU/UV LOCATIONS
SCALE: 1/16" = 1'-0"
A
M-3
1/16" = 1'-0"
AutoCAD SHX Text
(EXIST.)
AutoCAD SHX Text SUMMARY OF WORK 1. REMOVE EXISTING SIEMENS-TALON CONTROLLERS FROM UNIT VENTILATORS(UVS) AND FAN COIL REMOVE EXISTING SIEMENS-TALON CONTROLLERS FROM UNIT VENTILATORS(UVS) AND FAN COIL UNITS(FCUS). 2. FURNISH AND INSTALL NEW JOHNSON CONTROLS FX-PCG BACNET MSTP CONTROLLERS FOR EACH UV AND FURNISH AND INSTALL NEW JOHNSON CONTROLS FX-PCG BACNET MSTP CONTROLLERS FOR EACH UV AND FCU. 3. FURNISH AND INSTALL NEW CONTROLS ENCLOSURE FOR EACH UV AND FCU. ENCLOSURE MOUNTED EITHER FURNISH AND INSTALL NEW CONTROLS ENCLOSURE FOR EACH UV AND FCU. ENCLOSURE MOUNTED EITHER ABOVE CEILING OR ON UNIT, CONFIRM/COORDINATE W/ OWNER. 4. FURNISH AND INSTALL NEW SPACE TEMPERATURE SENSORS W/ OCCUPANCY SENSOR BUILT IN FOR EACH FURNISH AND INSTALL NEW SPACE TEMPERATURE SENSORS W/ OCCUPANCY SENSOR BUILT IN FOR EACH ASSOCIATED SPACE. EXISTING SPACE OCCUPANCY SENSORS CAN BE USED IN LIEU OF NEW SENSORS IF APPLICABLE. 5. FURNISH AND INSTALL NEW DISCHARGE AIR TEMP SENSORS FOR EACH UV AND FCU. FURNISH AND INSTALL NEW DISCHARGE AIR TEMP SENSORS FOR EACH UV AND FCU. 6. FURNISH AND INSTALL NEW MIXED AIR TEMP SENSORS FOR EACH UV WITH ECONOMIZER. FURNISH AND INSTALL NEW MIXED AIR TEMP SENSORS FOR EACH UV WITH ECONOMIZER. 7. FURNISH AND INSTALL NEW FAN PROOF CT SENSOR FOR EACH UV AND FCU. FURNISH AND INSTALL NEW FAN PROOF CT SENSOR FOR EACH UV AND FCU. 8. FURNISH AND INSTALL NEW FAN RELAY(S) FOR EACH UV AND FCU. FURNISH AND INSTALL NEW FAN RELAY(S) FOR EACH UV AND FCU. 9. FURNISH AND INSTALL NEW 0-10V DAMPER ACTUATORS FOR EACH UV. FURNISH AND INSTALL NEW 0-10V DAMPER ACTUATORS FOR EACH UV. 10. FURNISH AND INSTALL NEW 0-10V DUAL TEMPERATURE CONTROL VALVE ACTUATORS FOR EACH UV(IF FURNISH AND INSTALL NEW 0-10V DUAL TEMPERATURE CONTROL VALVE ACTUATORS FOR EACH UV(IF APPLICABLE) AND FCU. 11. ALL OTHER UV AND FCU COMPONENTS ARE EXISTING TO REMAIN AND ARE TO BE REUSED. ASSUMPTION IS ALL OTHER UV AND FCU COMPONENTS ARE EXISTING TO REMAIN AND ARE TO BE REUSED. ASSUMPTION IS THAT ALL EXISTING COMPONENTS ARE IN WORKING ORDER. 12. PERFORM POINT TO POINT CHECKOUT FOR EACH UV AND FCU, IF ANY EXISTING COMPONENTS ARE PERFORM POINT TO POINT CHECKOUT FOR EACH UV AND FCU, IF ANY EXISTING COMPONENTS ARE DEFECTIVE IT SHOULD BE BROUGHT TO THE ENGINEERS AND OWNERS ATTENTION. 13. FURNISH PROGRAMMING AS REQUIRED. FURNISH PROGRAMMING AS REQUIRED. 14. REFER TO SPECIFICATIONS FOR MBCC NODE NAMING SYSTEM. REFER TO SPECIFICATIONS FOR MBCC NODE NAMING SYSTEM. 15. FOR ADDITIONAL INFORMATION REFER TO SPECIFICATIONS AND HVAC CONTROLS DRAWINGS.FOR ADDITIONAL INFORMATION REFER TO SPECIFICATIONS AND HVAC CONTROLS DRAWINGS.
AutoCAD SHX Text
AREA OF WORK 3RD FLOOR TECH TOWER
AutoCAD SHX Text
(ADD. ALT. #1)
AutoCAD SHX Text
325_FC
AutoCAD SHX Text
(EXIST.)
AutoCAD SHX Text
(ADD. ALT. #2)
AutoCAD SHX Text
324_FC
AutoCAD SHX Text
(EXIST.)
AutoCAD SHX Text
(BASE)
AutoCAD SHX Text
322_UV
AutoCAD SHX Text
(EXIST.)
AutoCAD SHX Text
(BASE)
AutoCAD SHX Text
320_UV
12.1
19.4
16.9
16.2
19.8
12.1
19.4
16.9
16.2
19.8
UP
DN UP
UP
DN
UP
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
CORR.
400KK
OFFICE
430A
CL.
S433
CL.
S434
OFFICE
WOMEN'S
T400HH MEN'S
T400LL
OFFICE
OFFICE
STAIR 7
4TH
CLOSET
S425B
COMP. LAB CLRM.
STOR.
S424A
CLASSROOM
ELECT.
M431 CORR.
400FF
ELEV2
4TH
CORR.
400GG
CORRIDOR
400EE
PHYSICS LAB
ELECTRONCS LAB
STAIR 6
4TH
CORRIDOR
C D G H J REB F IA K M P QL N SE.6C D G H J REB F IA K M P QL N SE.6
issued for date revisions item date scale sheet title sheet number drawn by:
© 2018 STUDIO ENÉE
WOBURN, MASSACHUSETTS O1801
(781) 935-7228 FAX (781) 935-1822
400 WEST CUMMINGS PARK S.4700
CONSULTING MECHANICAL ENGINEERS
VAV International Inc.
WWW.VAVINT.COM
460 Hillside Avenue, Suite J project name/owner's name
3RD & 4TH FLR TECH
TOWER CONTROLLERS
REPLACEMENT
seal/signature
MASS BAY COMMUNITY
COLLEGE
Needham, Massachusetts 02494 781.858.3011
50 Oakland Street Wellesley Hills, MA 02481
100% CD
APRIL 8TH, 2019
PM
4TH FLOOR FCU/UV
LOCATIONS
M-4
1/16" = 1'-0"
4TH FLOOR FCU/UV LOCATIONSA
M-4
SCALE: 1/16" = 1'-0"
AutoCAD SHX Text SUMMARY OF WORK 1. REMOVE EXISTING SIEMENS-TALON CONTROLLERS FROM UNIT VENTILATORS(UVS) AND FAN COIL REMOVE EXISTING SIEMENS-TALON CONTROLLERS FROM UNIT VENTILATORS(UVS) AND FAN COIL UNITS(FCUS). 2. FURNISH AND INSTALL NEW JOHNSON CONTROLS FX-PCG BACNET MSTP CONTROLLERS FOR EACH UV AND FURNISH AND INSTALL NEW JOHNSON CONTROLS FX-PCG BACNET MSTP CONTROLLERS FOR EACH UV AND FCU. 3. FURNISH AND INSTALL NEW CONTROLS ENCLOSURE FOR EACH UV AND FCU. ENCLOSURE MOUNTED EITHER FURNISH AND INSTALL NEW CONTROLS ENCLOSURE FOR EACH UV AND FCU. ENCLOSURE MOUNTED EITHER ABOVE CEILING OR ON UNIT, CONFIRM/COORDINATE W/ OWNER. 4. FURNISH AND INSTALL NEW SPACE TEMPERATURE SENSORS W/ OCCUPANCY SENSOR BUILT IN FOR EACH FURNISH AND INSTALL NEW SPACE TEMPERATURE SENSORS W/ OCCUPANCY SENSOR BUILT IN FOR EACH ASSOCIATED SPACE. EXISTING SPACE OCCUPANCY SENSORS CAN BE USED IN LIEU OF NEW SENSORS IF APPLICABLE. 5. FURNISH AND INSTALL NEW DISCHARGE AIR TEMP SENSORS FOR EACH UV AND FCU. FURNISH AND INSTALL NEW DISCHARGE AIR TEMP SENSORS FOR EACH UV AND FCU. 6. FURNISH AND INSTALL NEW MIXED AIR TEMP SENSORS FOR EACH UV WITH ECONOMIZER. FURNISH AND INSTALL NEW MIXED AIR TEMP SENSORS FOR EACH UV WITH ECONOMIZER. 7. FURNISH AND INSTALL NEW FAN PROOF CT SENSOR FOR EACH UV AND FCU. FURNISH AND INSTALL NEW FAN PROOF CT SENSOR FOR EACH UV AND FCU. 8. FURNISH AND INSTALL NEW FAN RELAY(S) FOR EACH UV AND FCU. FURNISH AND INSTALL NEW FAN RELAY(S) FOR EACH UV AND FCU. 9. FURNISH AND INSTALL NEW 0-10V DAMPER ACTUATORS FOR EACH UV. FURNISH AND INSTALL NEW 0-10V DAMPER ACTUATORS FOR EACH UV. 10. FURNISH AND INSTALL NEW 0-10V DUAL TEMPERATURE CONTROL VALVE ACTUATORS FOR EACH UV(IF FURNISH AND INSTALL NEW 0-10V DUAL TEMPERATURE CONTROL VALVE ACTUATORS FOR EACH UV(IF APPLICABLE) AND FCU. 11. ALL OTHER UV AND FCU COMPONENTS ARE EXISTING TO REMAIN AND ARE TO BE REUSED. ASSUMPTION IS ALL OTHER UV AND FCU COMPONENTS ARE EXISTING TO REMAIN AND ARE TO BE REUSED. ASSUMPTION IS THAT ALL EXISTING COMPONENTS ARE IN WORKING ORDER. 12. PERFORM POINT TO POINT CHECKOUT FOR EACH UV AND FCU, IF ANY EXISTING COMPONENTS ARE PERFORM POINT TO POINT CHECKOUT FOR EACH UV AND FCU, IF ANY EXISTING COMPONENTS ARE DEFECTIVE IT SHOULD BE BROUGHT TO THE ENGINEERS AND OWNERS ATTENTION. 13. FURNISH PROGRAMMING AS REQUIRED. FURNISH PROGRAMMING AS REQUIRED. 14. REFER TO SPECIFICATIONS FOR MBCC NODE NAMING SYSTEM. REFER TO SPECIFICATIONS FOR MBCC NODE NAMING SYSTEM. 15. FOR ADDITIONAL INFORMATION REFER TO SPECIFICATIONS AND HVAC CONTROLS DRAWINGS.FOR ADDITIONAL INFORMATION REFER TO SPECIFICATIONS AND HVAC CONTROLS DRAWINGS.
AutoCAD SHX Text
(EXIST.)
AutoCAD SHX Text
(BASE)
AutoCAD SHX Text
425_UV
AutoCAD SHX Text
(EXIST.)
AutoCAD SHX Text
(BASE)
AutoCAD SHX Text
424_UV
AutoCAD SHX Text
(EXIST.)
AutoCAD SHX Text
(BASE)
AutoCAD SHX Text
422_M_UV
AutoCAD SHX Text
(EXIST.)
AutoCAD SHX Text
(BASE)
AutoCAD SHX Text
422_S_UV
AutoCAD SHX Text
(EXIST.)
AutoCAD SHX Text
(BASE)
AutoCAD SHX Text
420_M_UV
AutoCAD SHX Text
(EXIST.)
AutoCAD SHX Text
(BASE)
AutoCAD SHX Text
420_S_UV
AutoCAD SHX Text
AREA OF WORK 4TH FLOOR TECH TOWER
revisions item date scale sheet title sheet number drawn by:
© 2018 STUDIO ENÉE
WOBURN, MASSACHUSETTS O1801
(781) 935-7228 FAX (781) 935-1822
400 WEST CUMMINGS PARK S.4700
CONSULTING MECHANICAL ENGINEERS
VAV International Inc.
WWW.VAVINT.COM
460 Hillside Avenue, Suite J project name/owner's name
3RD & 4TH FLR TECH
TOWER CONTROLLERS
REPLACEMENT
seal/signature
MASS BAY COMMUNITY
COLLEGE
Needham, Massachusetts 02494 781.858.3011
50 Oakland Street Wellesley Hills, MA 02481
100% CD
APRIL 8TH, 2019
PM
HVAC CONTROLS
(FAN COIL UNIT)
M-5
NONE
FAN COIL UNIT CONTROL SEQUENCEA
M-5
SCALE: NOT TO SCALE
AutoCAD SHX Text
FILTER
AutoCAD SHX Text
RETURN AIR
AutoCAD SHX Text
SUPPLY FAN
AutoCAD SHX Text T
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
ACV
AutoCAD SHX Text
DUAL TEMP. COIL
AutoCAD SHX Text
SUPPLY AIR
AutoCAD SHX Text
DAT
AutoCAD SHX Text PROVIDE NEW SPACE TEMP. SENSOR WITH INTEGRAL OCCUPANCY SENSOR, LOCAL ADJUSTMENT, UNOCCUPIED OVERRIDE SWITCH. EXISTING OCCUPANCY SENSORS CAN BE USED IN LIEU OF NEW SENSORS IF APPLICABLE.
AutoCAD SHX Text
PROVIDE NEW FAN RELAY.
AutoCAD SHX Text
PROVIDE NEW 0-10V SIEMENS DUAL TEMPERATURE CONTROL VALVE ACTUATOR.
AutoCAD SHX Text
AutoCAD SHX Text
FCU
AutoCAD SHX Text REPLACE EXIST. SIEMENS-TALON CONTROLLER WITH NEW JOHNSON CONTROLS FX-PCG BACNET MSTP CONTROLLER. PROVIDE NEW CONTROLS ENCLOSURE MOUNTED EITHER ABOVE THE CEILING OR ON THE UNIT, CONFIRM/COORDINATE W/ OWNER.
AutoCAD SHX Text
PROVIDE NEW DISCHARGE AIR TEMPERATURE SENSOR.
AutoCAD SHX Text A. GENERAL GENERAL 1. FAN COIL UNIT SHALL BE CONTROLLED VIA NEW DDC CONTROLLER. COORDINATE FAN COIL UNIT SHALL BE CONTROLLED VIA NEW DDC CONTROLLER. COORDINATE OCCUPIED/UNOCCUPIED SCHEDULES WITH OWNER. 2. ALL SET POINTS SHALL BE ADJUSTABLE. ALL SET POINTS SHALL BE ADJUSTABLE. 3. FAN COIL UNIT TEMPERATURE SENSOR SHALL ALLOW AN OCCUPANT TO ADJUST THE FAN COIL UNIT TEMPERATURE SENSOR SHALL ALLOW AN OCCUPANT TO ADJUST THE SPACE TEMPERATURE SETPOINT WITHIN AN ADJUSTABLE RANGE DURING OCCUPIED HOURS, INITIALLY THIS SHALL BE SET TO +/- 3°F. THIS SETPOINT CAN BEOVERRIDDEN FROM THE BMS. THIS FUNCTION IS NOT ALLOWED DURING UNOCCUPIED HOURS. 4. FAN COIL UNIT IS CONNECTED TO A TWO PIPE SYSTEM. WHETHER HEATING OR FAN COIL UNIT IS CONNECTED TO A TWO PIPE SYSTEM. WHETHER HEATING OR COOLING IS AVAILABLE SHOULD BE DICTATED BY CENTRAL PLANT VIA BMS. 5. FAN COIL UNIT COMPONENTS NOT SHOWN TO BE REPLACED ARE EXISTING TO REMAIN FAN COIL UNIT COMPONENTS NOT SHOWN TO BE REPLACED ARE EXISTING TO REMAIN AND ARE TO BE REUSED. ASSUMPTION IS THAT ALL EXISTING COMPONENTS ARE IN WORKING ORDER. 6. CONTRACTOR TO PERFORM POINT TO POINT CHECKOUT OF FAN COIL UNIT, IF ANY CONTRACTOR TO PERFORM POINT TO POINT CHECKOUT OF FAN COIL UNIT, IF ANY EXISTING COMPONENTS ARE DEFECTIVE IT SHOULD BE BROUGHT TO THE ENGINEERS AND OWNERS ATTENTION. 7. SPACES WITH (2) FAN COIL UNITS SHOULD HAVE UNITS CONTROLLED BY SAME SPACES WITH (2) FAN COIL UNITS SHOULD HAVE UNITS CONTROLLED BY SAME SIGNAL. 8. FAN COIL UNIT CONTROLS SHALL BE INTEGRATED INTO EXISTING BMS FAN COIL UNIT CONTROLS SHALL BE INTEGRATED INTO EXISTING BMS (SIEMENS/STAEFA JACE AND WEB SUPERVISOR). THIS SHALL INCLUDE BUT IS NOT LIMITED TO ALL PROGRAMMING, GRAPHICS, ALARMS, TRENDING DATA AND SCHEDULING AS REQUIRED FOR A COMPLETE OPERABLE SYSTEM. CONFIRM REQUIREMENTS/FORMATS WITH OWNER. 9. TREND ALL POINTS, ANALOG EVERY 15 MINUTES AND DIGITAL UPON CHANGE OF TREND ALL POINTS, ANALOG EVERY 15 MINUTES AND DIGITAL UPON CHANGE OF VALUE. 10. FAN COIL UNIT SHOULD BE ASSIGNED NAME/NODE ID AS DESCRIBED ON DESIGN FAN COIL UNIT SHOULD BE ASSIGNED NAME/NODE ID AS DESCRIBED ON DESIGN DRAWINGS AND SPECIFICATIONS. B. FAN CONTROL FAN CONTROL 1. WHILE IN OCCUPIED MODE, THE SUPPLY FAN SHALL CYCLE AS REQUIRED. THE SUPPLY WHILE IN OCCUPIED MODE, THE SUPPLY FAN SHALL CYCLE AS REQUIRED. THE SUPPLY FAN SHALL BE CAPABLE OF BEING CHANGED BY BMS TO CONTINUOUS OPERATION DURING OCCUPIED HOURS REGARDLESS OF A CALL FOR HEATING OR COOLING. SUPPLY FAN AND CONTROL VALVE SHALL NOT BE CONTROLLED VIA SAME SIGNAL TO ACHIEVE THE ADJUSTABILITY LISTED ABOVE. 2. WHILE IN THE UNOCCUPIED MODE, THE SUPPLY FAN SHALL CYCLE AS REQUIRED. WHILE IN THE UNOCCUPIED MODE, THE SUPPLY FAN SHALL CYCLE AS REQUIRED. 3. FAN COIL UNIT FAN SPEED IS MANUALLY CONTROLLED VIA UNIT MOUNTED THREE FAN COIL UNIT FAN SPEED IS MANUALLY CONTROLLED VIA UNIT MOUNTED THREE SPEED FAN SWITCH. C. OCCUPIED COOLING CONTROL OCCUPIED COOLING CONTROL 1. WHEN COOLING IS AVAILABLE AS DICTATED BY THE CENTRAL PLANT VIA BMS. UPON A WHEN COOLING IS AVAILABLE AS DICTATED BY THE CENTRAL PLANT VIA BMS. UPON A CALL FOR OCCUPIED COOLING FROM THE SPACE TEMPERATURE SENSOR THE DUAL TEMPERATURE ACV SHALL MODULATE AS REQUIRED TO MAINTAIN THE SETPOINT (OCCUPIED COOLING SETPOINT TO BE 75°F).2. STANDBY COOLING CONTROL - IF SPACE IS UNOCCUPIED DURING OCCUPIED HOURS AS STANDBY COOLING CONTROL - IF SPACE IS UNOCCUPIED DURING OCCUPIED HOURS AS SEEN BE THE OCCUPANCY SENSOR THE OCCUPIED SET POINT SHALL BE SETUP (STANDBY COOLING SETPOINT TO BE 78°F).D. UNOCCUPIED COOLING CONTROL UNOCCUPIED COOLING CONTROL 1. WHEN COOLING IS AVAILABLE AS DICTATED BY THE CENTRAL PLANT VIA BMS. UPON A WHEN COOLING IS AVAILABLE AS DICTATED BY THE CENTRAL PLANT VIA BMS. UPON A CALL FOR UNOCCUPIED COOLING FROM THE SPACE TEMPERATURE SENSOR THE DUAL TEMPERATURE ACV SHALL MODULATE AS REQUIRED TO MAINTAIN THE SETPOINT (OCCUPIED COOLING SETPOINT TO BE 85°F).E. OCCUPIED HEATING CONTROL OCCUPIED HEATING CONTROL 1. WHEN HEATING IS AVAILABLE AS DICTATED BY THE CENTRAL PLANT VIA BMS. UPON A WHEN HEATING IS AVAILABLE AS DICTATED BY THE CENTRAL PLANT VIA BMS. UPON A CALL FOR OCCUPIED HEATING FROM THE SPACE TEMPERATURE SENSOR THE DUAL TEMPERATURE ACV SHALL MODULATE AS REQUIRED TO MAINTAIN THE SETPOINT (OCCUPIED HEATING SETPOINT TO BE 72°F).2. STANDBY HEATING CONTROL - IF SPACE IS UNOCCUPIED DURING OCCUPIED HOURS AS STANDBY HEATING CONTROL - IF SPACE IS UNOCCUPIED DURING OCCUPIED HOURS AS SEEN BE THE OCCUPANCY SENSOR THE OCCUPIED SET POINT SHALL BE SETBACK (STANDBY HEATING SETPOINT TO BE 68°F).F. UNOCCUPIED HEATING CONTROL UNOCCUPIED HEATING CONTROL 1. WHEN HEATING IS AVAILABLE AS DICTATED BY THE CENTRAL PLANT VIA BMS. UPON A WHEN HEATING IS AVAILABLE AS DICTATED BY THE CENTRAL PLANT VIA BMS. UPON A CALL FOR UNOCCUPIED HEATING FROM THE SPACE TEMPERATURE SENSOR THE DUAL TEMPERATURE ACV SHALL MODULATE AS REQUIRED TO MAINTAIN THE SETPOINT (OCCUPIED HEATING SETPOINT TO BE 55°F).G. OVERRIDE DURING UNOCCUPIED MODE OVERRIDE DURING UNOCCUPIED MODE 1. THE PUSH BUTTON ON THE SPACE TEMPERATURE SENOR SHALL OVERRIDE THE THE PUSH BUTTON ON THE SPACE TEMPERATURE SENOR SHALL OVERRIDE THE UNOCCUPIED MODE AND FOLLOW THE OCCUPIED MODE FOR 2 HOURS (ADJ.) AND THEN RETURN TO THE UNOCCUPIED MODE. H. ALARMS ALARMS 1. IF THE SUPPLY FAN FAILS OR ANY SAFETY IS TRIPPED, THE AUTOMATIC TEMPERATURE IF THE SUPPLY FAN FAILS OR ANY SAFETY IS TRIPPED, THE AUTOMATIC TEMPERATURE CONTROL SYSTEM SHALL GIVE A DETAILED ALARM SIGNAL TO THE FRONT END AND EMAIL NOTIFICATION SHALL BE SENT (CONFIRM WITH OWNER).
AutoCAD SHX Text
PROVIDE CT SENSOR FOR FAN PROOF.
revisions item date scale sheet title sheet number drawn by:
© 2018 STUDIO ENÉE
WOBURN, MASSACHUSETTS O1801
(781) 935-7228 FAX (781) 935-1822
400 WEST CUMMINGS PARK S.4700
CONSULTING MECHANICAL ENGINEERS
VAV International Inc.
WWW.VAVINT.COM
460 Hillside Avenue, Suite J project name/owner's name
3RD & 4TH FLR TECH
TOWER CONTROLLERS
REPLACEMENT
seal/signature
MASS BAY COMMUNITY
COLLEGE
Needham, Massachusetts 02494 781.858.3011
50 Oakland Street Wellesley Hills, MA 02481
100% CD
APRIL 8TH, 2019
PM
HVAC CONTROLS
(UNIT VENTILATOR)
M-6
NONE
UNIT VENTILATOR CONTROL SEQUENCEA
M-5
SCALE: NOT TO SCALE
AutoCAD SHX Text
FILTER
AutoCAD SHX Text
RETURN AIR
AutoCAD SHX Text
SUPPLY FAN
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
DUAL TEMP. COIL
AutoCAD SHX Text
SUPPLY AIR
AutoCAD SHX Text
DAT
AutoCAD SHX Text PROVIDE NEW SPACE TEMP. SENSOR WITH INTEGRAL OCCUPANCY AND RH SENSORS, LOCAL ADJUSTMENT, UNOCCUPIED OVERRIDE SWITCH. EXISTING OCCUPANCY SENSORS CAN BE USED IN LIEU OF NEW SENSORS IF APPLICABLE.
AutoCAD SHX Text
PROVIDE NEW FAN RELAY.
AutoCAD SHX Text
AutoCAD SHX Text
UV
AutoCAD SHX Text REPLACE EXIST. SIEMENS-TALON CONTROLLER WITH NEW JOHNSON CONTROLS FX-PCG BACNET MSTP CONTROLLER. PROVIDE NEW CONTROLS ENCLOSURE MOUNTED EITHER ABOVE THE CEILING OR ON THE UNIT, CONFIRM/COORDINATE W/ OWNER.
AutoCAD SHX Text
PROVIDE NEW DISCHARGE AIR TEMPERATURE SENSOR.
AutoCAD SHX Text A. GENERAL GENERAL 1. UNIT VENTILATOR SHALL BE CONTROLLED VIA NEW DDC CONTROLLER. COORDINATE OCCUPIED/UNOCCUPIED UNIT VENTILATOR SHALL BE CONTROLLED VIA NEW DDC CONTROLLER. COORDINATE OCCUPIED/UNOCCUPIED SCHEDULES WITH OWNER. 2. ALL SET POINTS SHALL BE ADJUSTABLE. ALL SET POINTS SHALL BE ADJUSTABLE. 3. TIE EXISTING FREEZESTAT INTO NEW CONTROLLER AND FAIL SAFE TO HEAT. TIE EXISTING FREEZESTAT INTO NEW CONTROLLER AND FAIL SAFE TO HEAT. 4. UNIT VENTILATOR TEMPERATURE SENSOR SHALL ALLOW AN OCCUPANT TO ADJUST THE SPACE TEMPERATURE UNIT VENTILATOR TEMPERATURE SENSOR SHALL ALLOW AN OCCUPANT TO ADJUST THE SPACE TEMPERATURE SETPOINT WITHIN AN ADJUSTABLE RANGE DURING OCCUPIED HOURS, INITIALLY THIS SHALL BE SET TO +/- 3°F. THIS SETPOINT CAN BE OVERRIDDEN FROM THE BMS. THIS FUNCTION IS NOT ALLOWED DURINGUNOCCUPIED HOURS. 5. UNIT VENTILATOR IS CONNECTED TO A TWO PIPE SYSTEM. WHETHER HEATING OR COOLING IS AVAILABLE UNIT VENTILATOR IS CONNECTED TO A TWO PIPE SYSTEM. WHETHER HEATING OR COOLING IS AVAILABLE SHOULD BE DICTATED BY CENTRAL PLANT VIA BMS. 6. UNIT VENTILATOR COMPONENTS NOT SHOWN TO BE REPLACED ARE EXISTING TO REMAIN AND ARE TO BE UNIT VENTILATOR COMPONENTS NOT SHOWN TO BE REPLACED ARE EXISTING TO REMAIN AND ARE TO BE REUSED. ASSUMPTION IS THAT ALL EXISTING COMPONENTS ARE IN WORKING ORDER. 7. CONTRACTOR TO PERFORM POINT TO POINT CHECKOUT OF UNIT VENTILATOR, IF ANY EXISTING COMPONENTS CONTRACTOR TO PERFORM POINT TO POINT CHECKOUT OF UNIT VENTILATOR, IF ANY EXISTING COMPONENTS ARE DEFECTIVE IT SHOULD BE BROUGHT TO THE ENGINEERS AND OWNERS ATTENTION. 8. SPACES WITH (1) UNIT VENTILATOR HAVE ECONOMIZER AND FACE & BYPASS DAMPERS, NO CONTROL VALVE. SPACES WITH (1) UNIT VENTILATOR HAVE ECONOMIZER AND FACE & BYPASS DAMPERS, NO CONTROL VALVE. 9. SPACES WITH (2) UNIT VENTILATORS HAVE MASTER AND SLAVE ARRANGEMENT. MASTER UNIT VENTILATOR SPACES WITH (2) UNIT VENTILATORS HAVE MASTER AND SLAVE ARRANGEMENT. MASTER UNIT VENTILATOR HAS ECONOMIZER AND SLAVE DOES NOT. MASTER UNIT VENTILATOR HAS FACE & BYPASS DAMPERS, NO CONTROL VALVE AND SLAVE HAS CONTROL VALVE. 10. TREND ALL POINTS, ANALOG EVERY 15 MINUTES AND DIGITAL UPON CHANGE OF VALUE. TREND ALL POINTS, ANALOG EVERY 15 MINUTES AND DIGITAL UPON CHANGE OF VALUE. 11. UNIT VENTILATORS SHOULD BE ASSIGNED NAME/NODE ID AS DESCRIBED ON DESIGN DRAWINGS AND UNIT VENTILATORS SHOULD BE ASSIGNED NAME/NODE ID AS DESCRIBED ON DESIGN DRAWINGS AND SPECIFICATIONS. B. FAN CONTROL FAN CONTROL 9. WHILE IN OCCUPIED MODE, THE SUPPLY FAN SHALL BE ON, ONCE FAN OPERATION IS STABLE OUTSIDE AIR WHILE IN OCCUPIED MODE, THE SUPPLY FAN SHALL BE ON, ONCE FAN OPERATION IS STABLE OUTSIDE AIR OUTSIDE AIR DAMPER (OAD) AND RETURN AIR DAMPER (RAD) SHALL SLOWLY OPEN TO MINIMUM OUTDOOR AIR POSITION. TO MINIMUM OUTDOOR AIR POSITION. TO MINIMUM OUTDOOR AIR POSITION. . 10. WHILE IN THE UNOCCUPIED MODE, THE SUPPLY FAN SHALL CYCLE AS REQUIRED WITH OUTSIDE AIR DAMPER WHILE IN THE UNOCCUPIED MODE, THE SUPPLY FAN SHALL CYCLE AS REQUIRED WITH OUTSIDE AIR DAMPER WITH OUTSIDE AIR DAMPER (OAD) CLOSED AND RETURN AIR DAMPER (RAD) OPEN. . 11. UNIT VENTILATOR FAN SPEED IS MANUALLY CONTROLLED VIA UNIT MOUNTED THREE SPEED FAN SWITCH. UNIT VENTILATOR FAN SPEED IS MANUALLY CONTROLLED VIA UNIT MOUNTED THREE SPEED FAN SWITCH. C. OCCUPIED COOLING CONTROL OCCUPIED COOLING CONTROL 1. THE FIRST MEANS OF COOLING SHALL BE ACTIVATION OF THE ECONOMIZER. IF THE GLOBAL OUTSIDE AIR THE FIRST MEANS OF COOLING SHALL BE ACTIVATION OF THE ECONOMIZER. IF THE GLOBAL OUTSIDE AIR ENTHALPY IS BELOW THE SPECIFIC ROOM ENTHALPY, THE OUTSIDE AND RETURN AIR DAMPERS SHALL BE PROPORTIONALLY MODULATED UP TO 100% OUTDOOR AIR TO MAINTAIN THE SETPOINT. DAT SHALL OVERRIDE, IF REQUIRED, TO LIMIT SUPPLY AIR TEMPERATURE TO 55°F (ADJ.) MINIMUM DURING ECONOMIZER COOLING(LIMIT SHALL NOT RESULT IN REDUCTION OF THE MINIMUM OUTDOOR AIRFLOW). IF ADDITIONAL COOLING IS REQUIRED, THE FACE & BYPASS DAMPERS SHALL MODULATE AS REQUIRED. THE REVERSE SHALL OCCUR ON A DROP IN SPACE TEMPERATURE BELOW COOLING SETPOINT. 2. IF THE OUTSIDE AIR ENTHALPY RISES ABOVE THE ROOM AIR ENTHALPY THE ECONOMIZER SHALL BE IF THE OUTSIDE AIR ENTHALPY RISES ABOVE THE ROOM AIR ENTHALPY THE ECONOMIZER SHALL BE POSITIONED TO PROVED MINIMUM OUTDOOR AIRFLOW AND THE FACE & BYPASS DAMPERS MODULATED TO MAINTAIN THE SETPOINT. DAT SHALL LIMIT SUPPLY AIR TO 55°F (ADJ.) MINIMUM DURING MECHANICALCOOLING. 3. FOR UNITS WITHOUT FACE & BYPASS DAMPERS - WHEN COOLING IS AVAILABLE AS DICTATED BY THE FOR UNITS WITHOUT FACE & BYPASS DAMPERS - WHEN COOLING IS AVAILABLE AS DICTATED BY THE CENTRAL PLANT VIA BMS. UPON A CALL FOR OCCUPIED COOLING FROM THE SPACE TEMPERATURE SENSOR THE DUAL TEMPERATURE ACV SHALL MODULATE AS REQUIRED TO MAINTAIN THE SETPOINT (OCCUPIED COOLING SETPOINT TO BE 75°F).4. STANDBY COOLING CONTROL - IF SPACE IS UNOCCUPIED DURING OCCUPIED HOURS AS SEEN BE THE STANDBY COOLING CONTROL - IF SPACE IS UNOCCUPIED DURING OCCUPIED HOURS AS SEEN BE THE OCCUPANCY SENSOR THE OCCUPIED SET POINT SHALL BE SETUP (STANDBY COOLING SETPOINT TO BE 78°F).D. UNOCCUPIED COOLING CONTROL UNOCCUPIED COOLING CONTROL 1. WHEN COOLING IS AVAILABLE AS DICTATED BY THE CENTRAL PLANT VIA BMS. UPON A CALL FOR WHEN COOLING IS AVAILABLE AS DICTATED BY THE CENTRAL PLANT VIA BMS. UPON A CALL FOR UNOCCUPIED COOLING FROM THE SPACE TEMPERATURE SENSOR THE FACE & BYPASS DAMPERS AND/OR THE DUAL TEMPERATURE ACV SHALL MODULATE AS REQUIRED TO MAINTAIN THE SETPOINT (OCCUPIED COOLING SETPOINT TO BE 85°F).E. OCCUPIED HEATING CONTROL OCCUPIED HEATING CONTROL 1. WHEN HEATING IS AVAILABLE AS DICTATED BY THE CENTRAL PLANT VIA BMS. UPON A CALL FOR OCCUPIED WHEN HEATING IS AVAILABLE AS DICTATED BY THE CENTRAL PLANT VIA BMS. UPON A CALL FOR OCCUPIED HEATING FROM THE SPACE TEMPERATURE SENSOR THE FACE & BYPASS DAMPERS AND/OR THE DUAL TEMPERATURE ACV SHALL MODULATE AS REQUIRED TO MAINTAIN THE SETPOINT (OCCUPIED HEATING SETPOINT TO BE 72°F).2. STANDBY HEATING CONTROL - IF SPACE IS UNOCCUPIED DURING OCCUPIED HOURS AS SEEN BE THE STANDBY HEATING CONTROL - IF SPACE IS UNOCCUPIED DURING OCCUPIED HOURS AS SEEN BE THE OCCUPANCY SENSOR THE OCCUPIED SET POINT SHALL BE SETBACK (STANDBY HEATING SETPOINT TO BE 68°F).F. UNOCCUPIED HEATING CONTROL UNOCCUPIED HEATING CONTROL 1. WHEN HEATING IS AVAILABLE AS DICTATED BY THE CENTRAL PLANT VIA BMS. UPON A CALL FOR WHEN HEATING IS AVAILABLE AS DICTATED BY THE CENTRAL PLANT VIA BMS. UPON A CALL FOR UNOCCUPIED HEATING FROM THE SPACE TEMPERATURE SENSOR THE FACE & BYPASS DAMPERS AND/OR THE DUAL TEMPERATURE ACV SHALL MODULATE AS REQUIRED TO MAINTAIN THE SETPOINT (OCCUPIED HEATING SETPOINT TO BE 55°F).G. OVERRIDE DURING UNOCCUPIED MODE OVERRIDE DURING UNOCCUPIED MODE 1. THE PUSH BUTTON ON THE SPACE TEMPERATURE SENOR SHALL OVERRIDE THE UNOCCUPIED MODE AND THE PUSH BUTTON ON THE SPACE TEMPERATURE SENOR SHALL OVERRIDE THE UNOCCUPIED MODE AND FOLLOW THE OCCUPIED MODE FOR 2 HOURS (ADJ.) AND THEN RETURN TO THE UNOCCUPIED MODE. H. ALARMS ALARMS 1. IF THE SUPPLY FAN FAILS, DAT OR MAT SENSOR SENSES TEMPERATURE BELOW FREEZING W/ DURATION OR IF THE SUPPLY FAN FAILS, DAT OR MAT SENSOR SENSES TEMPERATURE BELOW FREEZING W/ DURATION OR ANY SAFETY IS TRIPPED, THE AUTOMATIC TEMPERATURE CONTROL SYSTEM SHALL GIVE A DETAILED ALARM SIGNAL TO THE FRONT END AND EMAIL NOTIFICATION SHALL BE SENT (CONFIRM WITH OWNER).
AutoCAD SHX Text
MAT
AutoCAD SHX Text
OUTDOOR AIR
AutoCAD SHX Text T/H
AutoCAD SHX Text PROVIDE NEW 0-10V ECONOMIZER DAMPER ACTUATOR(S) (IF APPLICABLE). SLAVE UNITS DO NOT HAVE ECONOMIZERS.
AutoCAD SHX Text PROVIDE NEW 0-10V FACE & BYPASS DAMPER ACTUATOR(S) (IF APPLICABLE). SLAVE UNITS DO NOT HAVE FACE & BYPASS DAMPERS.
AutoCAD SHX Text
OAT
AutoCAD SHX Text
OAH
AutoCAD SHX Text ASSUMPTION IS THAT THE BMS ALREADY HAS BOTH OUTSIDE AIR TEMPERATURE AND HUMIDITY SENSORS. IF THEY ARE NOT PRESENT THEY SHOULD BE INSTALLED AS NEW.
AutoCAD SHX Text
FACE & BYPASS DAMPERS
AutoCAD SHX Text
ECONOMIZER DAMPERS
AutoCAD SHX Text PROVIDE NEW ECONOMIZER MIXED AIR TEMPERATURE SENSOR (IF APPLICABLE). SLAVE UNITS DO NOT HAVE ECONOMIZERS.
AutoCAD SHX Text
ACV
AutoCAD SHX Text PROVIDE NEW 0-10V SIEMENS DUAL TEMPERATURE CONTROL VALVE ACTUATOR (IF APPLICABLE). MASTER UNITS DO NOT HAVE CONTROL VALVE.
AutoCAD SHX Text
RAD
AutoCAD SHX Text
OAD
AutoCAD SHX Text
BAD
AutoCAD SHX Text
FAD
AutoCAD SHX Text
FZ
AutoCAD SHX Text
TIE EXISTING FREEZESTAT INTO NEW CONTROLLER AND FAIL SAFE TO HEAT.
AutoCAD SHX Text
PROVIDE CT SENSOR FOR FAN PROOF.
| Sheets and Views |
| M-1 - Cover Page-M-1 |
| M-2 - Key Plans-M-2 |
| M-3 - 3rd Floor Plan-M-3 |
| M-4 - 4th Floor Plan-M-4 |
| M-5 - HVAC Controls (FCU)-M-5 |
| M-6 - HVAC Controls (UV)-M-6 |