19-003527-ps-hp-protectus-iii-s-06.19.pdf
PDF 611 KB Posted
- Attached to
- Astana Post: Fire Service Water Meter
- Solicitation number
- PR12440551
- Issued by
-
Department of State
About this file
This document is a product sheet for the Neptune HP PROTECTUS III Stainless Steel (S) fire service meter. The HP PROTECTUS III S is designed to measure both domestic and fire service water usage through a single water line, with a wide operating range and accuracy of 98.5%-101.5%. Key features include compact size, component repair and maintenance, and roll-sealed registers. The meter is available in sizes from 4" to 10" and is NSF/ANSI 61 and 372 certified, UL Listed, and FM Approved for fire service use.
The related federal contract opportunity is a pre-solicitation for the U.S. Embassy in Astana, Kazakhstan to procure one 4" Neptune HP Protectus III fire service water meter. This is for market research purposes, and the Embassy will launch the full solicitation when available. No other details about the solicitation, such as response dates, award information, or set asides, are provided in the document.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
High Performance PROTECTUS® III Stainless Steel (S) Fire Service Meter SIZES: 4”, 6”, 8”, and 10”
The Neptune® HP PROTECTUS® III Stainless Steel (S) fire service meter measures extremely wide flow ranges at 100% ± 1.5% accuracy. All HP fire service meters meet or exceed AWWA C703 Standard, are certified to NSF/ ANSI 61 and 372 requirements, and are Underwriters Laboratory (UL) Listed and Factory Manual (FM) Approved for fire service use.
Application The HP PROTECTUS III S fire service meter is designed to measure both domestic and fire service water usage through a single water line. A typical application would be in a warehouse, hotel, or hospital where one water line may supply any number of faucets or bathrooms as well as an automatic sprinkler system.
Operation At low flow rates, all flow is through the bypass meter. As flow increases, pressure loss through the bypass meter increases and the detector check valve automatically opens. This condition occurs, for example, when a fire sprinkler system goes into operation. This permits flow through the mainline turbine meter. As flow decreases, reduced pressure loss closes the detector check valve and flow is again directed through the bypass meter.
Construction The combined readings of the mainline turbine and the bypass meter indicate total consumption through the HP PROTECTUS III S meter.
• 300 series stainless steel mainline body
• Integral detector check valve (stainless steel spring-loaded type)
• 300 series stainless steel strainer body with stainless steel basket
• Epoxy-coated steel strainer and valve cover
• HP Turbine measuring element
• Lockable ball valves used on bypass
• Check valve used on bypass
• 1” T-10® meter (on 4” size)
• 11 ⁄2” T-10 or 11 ⁄2” HP Turbine meter (on 6” size)
• 2” T-10 or 2” HP Turbine meter (on 8” and 10” sizes)
A PRODUCT SHEET OF NEPTUNE TECHNOLOGY GROUP
P R O D U C T S H E E T
KEY FEATURES
Compact Size
• Standard laying length fits existing installations
• Lowers new installation and replacement costs
Wide Operating Range
• Measures extremely wide flow ranges at 98.5%–101.5% accuracy
• Combines low-flow sensitivity of disc meter with high-flow capacity of turbine meter
• Registers leaks or unauthorized use of water from fire service lines
Component Repair and Maintenance
• Owner maintenance easily accomplished by replacement of major components
• Calibration vane allows in-field calibration of unitized measuring element (UME)
Roll-Sealed Registers
• Eliminates leaking and fogging
• In-line serviceability
• Magnetic driven, low-torque registration
• Tamperproof seal design
4” Accuracy 4” Headloss
6” Accuracy 6” Headloss
8” Accuracy 8” Headloss
10” Accuracy 10” Headloss
These charts show typical meter performance. Individual results may vary.
Ac cu ra cy
Flow Rate (gpm) Flow Rate (gpm)
He ad lo ss
(P
SI
Ac cu ra cy
Flow Rate (gpm) Flow Rate (gpm)
He ad lo ss
(P
SI
Ac cu ra cy
Flow Rate (gpm) Flow Rate (gpm)
He ad lo ss
(P
SI
Ac cu ra cy
Flow Rate (gpm) Flow Rate (gpm)
He ad lo ss
(P
SI
Operating Characteristics
Meter Size Normal Operating Range
@ 100% Accuracy (+/- 1.5%)
AWWA Standard Low Flow @ 95% - 101% Accuracy
Maximum Intermittent Flow Rate
4” ¾ to 1200 US gpm
0.171 to 272.55 m3/h 4 to 700 US gpm
0.91 to 159 m3/h
3⁄8 US gpm
0.09 m3/h
1500 US gpm
340.7 m3/h
6” 1½ to 2500 US gpm
0.34 to 567.81 m3/h
5 to 1600 US gpm
1.14 to 363 m3/h ¾ US gpm
0.17 m3/h
3100 US gpm
704.1 m3/h
8” 2 to 4000 US gpm
0.45 to 908.5 m3/h 8 to 2800 US gpm
1.8 to 636 m3/h 1 US gpm
0.23 m3/h 5000 US gpm
1135.6 m3/h
10” 2 to 6500 US gpm
0.45 to 1476.31 m3/h 8 to 4400 US gpm
1.8 to 999 m3/h 1 US gpm
0.23 m3/h 8000 US gpm
1817 m3/h
Dimensions Meter
Size A in/mm B in/mm C in/mm D in/mm E in/mm F in/mm G in/mm H in/mm I in/mm J in/mm Weight Ibs/kg
4” 33
10 3⁄4
17 1⁄2
15 1⁄4
6 3⁄4
6” 45
11 1⁄16
11 3⁄8
21 1⁄4
19½
9 1⁄2
8” 53
11 13⁄16
13 29⁄64
25 7⁄8
34 1⁄4
21 3⁄4
12 1⁄2
10” 68
14 13⁄16
30 1⁄16
36 1⁄4
22 1⁄2
13 3⁄4
D C
B
A
J
E
G
H
I
F
HEIGHT TO REMOVE
STRAINER ELEMENT
D C
B
A
J
E
G
H
I
F
HEIGHT TO REMOVE
STRAINER ELEMENT
Registration
Registration (per sweep hand revolution)
Disc Side Turbine Side
1” 1 ½” 2” 4” 6” 8” & 10”
1,000 US Gallons 3 3
100 Gallons 3 3 3
100 Cubic Feet 3 3
10 US Gallons 3
10 Cubic Feet 3 3 3
1 Cubic Foot 3
10 Cubic Metres 3 3
1 Cubic Metre 3 3
0.1 Cubic Metre 3 3
Register Capacity (6 active wheel odometer)
Disc Side Turbine Side
1” 1 ½” 2” 4” 6” 8” & 10”
1,000,000,000 Gallons 3 3
100,000,000 Gallons 3 3 3
100,000,000 Cubic Feet 3 3
10,000,000 Gallons 3
10,000,000 Cubic Feet 3 3 3
10,000,000 Cubic Metres 3 3
1,000,000 Cubic Metres 3 3
1,000,000 Cubic Feet 3
100,000 Cubic Metres 3 3
Neptune Technology Group 1600 Alabama Highway 229 Tallassee, AL 36078 800-633-8754 f 334-283-7293 neptunetg.com
© 2019 Neptune Technology Group Inc. All Rights Reserved. The trademarks, logos and service marks displayed in this document herein are the property of Neptune Technology Group Inc., its affiliates or other third parties. Availability and technical specifications are subject to change without notice. 19-003527 PS HP PROTECTUS III S 06.19
Guaranteed Systems Compatibility All HP PROTECTUS III S fire service meters are guaranteed adaptable to our ProRead, ProCoder, E-CODER, E-CODER)R900i, E-CODER)R450i, TRICON/S, TRICON/E3, and Neptune meter reading systems without removing the meter from service.
Warranty Neptune provides a limited warranty with respect to its HP PROTECTUS III S fire service meter for performance, materials, and workmanship.
When desired, owner maintenance is easily accomplished by in-line replacement of the UME.
Specifications Application
• Cold water measurement of flow in one direction
Maximum Operating Pressure
• 175 psi (1206 kPa)
Register
• Direct reading, center sweep, roll-sealed magnetic drive with low-flow indicator
Measuring Element
• AWWA Class II Turbine, hydrodynamically-balanced rotor, nutating disc
Flanges
• Round flanged ends per
AWWA C207, Class D
Approvals
• NSF/ANSI 61
• NSF/ANSI 372
• UL Listed
• FM Approved
Options Sizes
• 4”, 6”, 8”, and 10” 300 Series Stainless Steel Strainer Cover and Valve Cover
300 Series Stainless Steel Bolts
Left Side Bypass
Units Of Measure
• U.S. gallons, Imperial gallons, cubic feet, cubic metres
Register types
• Remote reading systems*:
ProRead™, ProCoder™, E-CODER®, E-CODER®)R900i
™, E-CODER®)R450i
TRICON®/S, TRICON/E®3
• Reclaim
Companion Flanges
• Cast iron
• Bronze (4” only)
Special Meter Flanges**
• 12” (for 10” meter size) *Consult factory for meter performance specifications when fitted with ARB.
**Non-UL/FM approved.
File details come from the government source that posted it. Updated .