15B50818B00000004_CLAR_SET_ONE_REP_GEN_FCC_FOX.pdf

PDF 178 KB Posted

Attached to
Replacement Generator - Low Facility Federal contract opportunity
Solicitation number
15B50818B00000004
Issued by
Department of Justice Bureau of Prisons South Central Regional Office

View the file

Other files for this federal contract opportunity

Other files attached to Replacement Generator - Low Facility, newest first.
File Type Posted
15B50818B00000004_ABSTRACT_OF_BIDS_REP_GEN_FCC_FOX.pdf PDF
15B50818B00000004_AMENDMENT_THREE_REP_GEN_FCC_FOX.pdf PDF
15B50818B00000004_AMEND_ONE_REP_GEN_FCC_FOX.pdf PDF
15B50818B00000004_PRE_BID_MIN_REP_GEN_FCC_FOX.zip ZIP file

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U.S. Department of Justice

Federal Bureau of Prisons Administrative Division

Field Acquisition Office Grand Prairie, Texas 75051

August 2, 2018

ATTN: ALL BIDDERS

RE: Clarification Set Number One

Solicitation 15B50818B00000004 FCC Forrest City, Arkansas Replacement Generator (Low Facility)

Dear Bidders, In reference to the above solicitation, enclosed are clarifications. These clarifications are for informational purposes only.

If you have any questions, feel free to contact me at (972) 352-4641 or e-mail at dpatton@bop.gov

Sincerely, Douglas V. Patton Contracting Officer Federal Bureau of Prisons Field Acquisition Office U.S. Armed Forces Reserve Complex 346 Marine Forces Drive Grand Prairie, Texas 75051

Enclosure cc: File

SCS, FCC Forrest City COR, FCC Forrest City Facility Manager, FCC Forrest City Regional Facilities Administrator, SCRO

CLARIFICATION SET NUMBER ONE

SOLICITATION NUMBER 15B50818B00000004

REPLACEMENT GENERATOR (LOW FACILITY)

FCC FORREST CITY, ARKANSAS

1. On sheet E001: There is a Fire Alarm System (Design/Build System) section. Is this required for this project??

No, design and installation of a new fire alarm system is not a requirement of this contract.

Refer to Amendment #2

2. On sheet E201: In order to save cost and time, would it be possible to install new conductors within the existing conduits feeding "DPF”

We would allow reuse of existing conduits. Contractor shall rework/extend conduits as needed to connect to new equipment. Refer to Amendment #2.