ATTACHMENT I

Statement of Requirements Water & Wastewater Utility Service FCC Coleman

Water and Wastewater Service

The estimated annual services requirement in gallons for water and wastewater is: 475,731, 875 (Water) and 427,780,000 (Wastewater). The usage amounts shown herein are estimates only and do not constitute a Government usage guarantee.

(1) Water The water provided shall be potable water, firefighting, industrial use water, irrigation water, other, and meet the Government’s everyday needs for the proper operation of the stated facility. All services provided by the Contractor shall be in conformity with all applicable laws, rules codes, industry standards, permits, and regulations, promulgated by any and all governmental authorities having jurisdiction.

Water shall be continuously available to the Government facility at a rate of 905 gals/min (based on average daily) at a minimum pressure of 50-PSI kpa (psig). The contractor shall provide the Government with reserve capacity, best efforts for reserve capacity of up to 1.5 for fire-fighting purposes at a rate of 2500 gals/min at a residential pressure of 59 psig. The water shall be measured at the Government facility by the existing meters (two-10”). All meters shall be installed by the Contractor in a manner that allows verification by Government personnel.

Nonpotable water will not be used and shall not be provided.

(2) Wastewater Service The wastewater service provided by the Contractor shall meet the Government’s everyday needs for proper operation of the stated facility. The Contractor shall operate its wastewater disposal and treatment facilities in conformity with all applicable laws, rules, codes, industry standards, permits and regulations, promulgated by any and all governmental authorities having jurisdiction.

Estimated annual service requirements are:

Maximum daily volume 1,172,000 gals (average)* Total annual volume 427,780,000 gals (annual)

The wastewater services to be delivered by the Contractor are non-metered. The total wastewater outflow shall be established by subtracting the recorded volumes of non-consumptive water (i.e. cooling towers, recreation, etc.), from the total metered water entering the facility. The Government’s delivery of wastewater to the Contractor shall be by forced main. The wastewater to be delivered shall be pretreated by the Government in the following manner: Barscreen to allow compliance with the town of Wildwood’s wastewater use ordinance.

The point of service connection between the Government facility and the Contractor’s system is, Federal Correctional Complex, Coleman, Florida.

*FBOP total purchase of 4,688 ERC’s (Equivalent Residential Connections) at 250 GPD each.