SOW.pdf

PDF 452 KB Posted

Attached to
REPAIR EXISTING WATER TANK FCI MCKEAN
Solicitation number
15B20924Q00000008
Issued by

About this file

This document is a Statement of Work (SOW) for a federal contract opportunity to repair an existing 500,000-gallon Aquastore, glass-coated, bolted-steel water storage tank at the Federal Correctional Institution (FCI) McKean in Lewis Run, Pennsylvania.

The SOW requires the contractor to recondition and/or recaulk all the horizontal and vertical interior and exterior tank seams and bottom manway, as well as inspect and repair any glass chips in the tank coating. The contractor must be factory trained for Aquastore or equivalent bolted, glass-coated steel tank repairs and maintenance. The contractor must also provide and install approximately 9,700 new exterior protective bolt caps with sealer. All sealants must be specifically formulated for chemical resistance, suitable for contact with potable water, and certified to meet ANSI/NSF Additives Standard 61. The contract is a firm-fixed price with the award going to the responsible offeror whose bid is most advantageous to the government, considering past performance, technical, lead time, warranty, and price. The solicitation will be posted on beta.sam.gov, with a deadline for quotes on July 9, 2024 at 3:00 PM EST.

View the file

Other files

File Type Posted
15B20924Q00000008.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Specification Sheet

Repair Water Tank

PROJECT 24Z2AX4

Federal Correctional Institution

SUMMARY OF WORK & PLACE OF PERFORMANCE:

APPROVED

� ,-1 t::>- loz.y McK��O FACILITIES ADMH�lSTRATOR

The Federal Bureau of Prisons (FBOP), Federal Correctional

Institution, McKean, located at 6975 Route 59, Lewis Run, Pennsylvania is soliciting a contract to repair existing, Aquastore, glass coated, bolted-steel water storage tank

(Approximately 500,000 gallons). Please see the required specifications below. The work to be performed under this contract and in accordance with this Statement of Work (SOW) shall consist of furnishing all necessary plant, labor, tools, transportation, supplies, supervision, equipment, materials, and incidentals necessary for providing all work shown in the SOW, and all applicable codes, regulations, standards, manufacturer's instructions and criteria in effect at the date of solicitation.

SCOPE OF WORK:

All work shall be completed as shown and in accordance with the manufacturer's recommendations. The Contractor shall visit the premises to become thoroughly familiar with details of the work and working conditions, field verify all dimensions and advise the Contracting Officer of any discrepancies before starting work.

CONTRACTOR PROVIDED MATERIALS (CPM): INTERIOR

• Must be factory trained for equivalent to Aquastore bolted, glass coating steel tank repairs and maintenance. Recondition and/or recaulk ALL the horizontal and vertical interior tank seams and bottom manway on the existing glass-coated, bolted-steel water storage tank. Sealants must be specifically formulated for chemical resistance appropriate to this application. The sealant must be approved and applied specifically for Aquastore glass coating or equivalent and meet the specifications and approval. The sealant must be suitable for contact with potable water and certified to meet ANSI/NSF Additives Standard 61 for indirect additives and must be chlorine resistant. Sealants must have excellent adhesion to the glass coating, low shrinkage and be utilized for both the interior and exterior of the tank.

• Inspect the interior of the tank and repair any other miscellaneous glass chips in the tank coating to prevent potential corrosion in accordance with tank manufacturer recommendations.

CONTRACTOR PROVIDED MATERIALS (CPM): EXTERIOR

• Must be factory trained for Aquastore or equivalent bolted, glass coating steel tank repairs and maintenance. Recondition/recaulk ALL the horizontal and vertical exterior tank seams, bottom manway, and roof assembly on the existing glass-coated, boltedsteel water storage tank. Sealants must be specifically formulated for chemical resistance appropriate to this application. The sealant must be approved and applied specifically for Aquastore glass coating or equivalent and meet the manufacturer's specifications and approval. The sealant must be suitable for contact with potable water and certified to meet ANSI/NSF Additives

Standard 61 for indirect additives and must be chlorine resistant. Sealants must have excellent adhesion to the glass coating, low shrinkage and be utilized for both the interior and exterior of the tank.

• Provide and install approximately 9,700 new exterior protective bolt caps with sealer to cover the exterior tank fasteners (i.e. nuts and washers) of the existing glass coated, bolted-steel water storage tank.

• Inspect the exterior of the tank and repair any miscellaneous minor glass chips, etc. in the tank