PART 1 (Coolers)

Details

ALL equipment must be UL listed. The condensers will be located on a concrete pad outside of building.

This quote will be for the purchase of multi condensing units, evaporator coils and required associated parts.

1. All compressor motors must be 208-230 volt, 3 phase, and 60 hertz. The compressors should be semi-hermetically sealed or scroll.

2. There should be a minimum of two condenser fans. All condenser fan motors should be 2 phase or 3 phase style motors, 208-230 volt, 60 hertz.

3. The condenser fan motor should be a minimum of ½ horsepower with 18” or larger blades and a venturi contoured air scoop with guard/shroud to service the multi-circuited condensing unit.

4. The compressor and condenser equipment should be sized to operate at an average temperature differential between the ambient and condensing temperatures of 20 degrees.

5. All unit’s refrigerant type shall be that of R404A and oil compatible supplied by the manufacturer for the same.

6. All the compressor units shall include discharge and suction line vibration protection, liquid line filter drier, moisture indicating sight glass, dual pressure control and crankcase heater.

Service ports shall be on suction and discharge line of compressor.

7. All systems shall also include a receiving tank capable of receiving all system type refrigerant without exceeding 90% of its capacity. Each receiver will be supplied with a pressure relief vent at its outlet and an isolation valve at its service port.

8. All condensing unit internal piping shall be neat, orderly and accessible for future maintenance. Each units piping run shall be refrigerant grade ACR or type L piping.

9. The framing of the outdoor condensing unit shall include a welded, deburred and clean structural base frame made of a minimum 12 gauge steel. All housing and access doors shall be of a minimum of 16 gauge galvanized steel and must be painted with an epoxy based primer coat and a minimum of a second finish coat of polyurethane acrylic enamel based paint

10. The evaporator units with cooling fans and the associated parts provided by the supplier shall include a matching TXV, liquid line solenoid valve and thermostat. The fan motors should be 115 volt, 60 hertz.

11. The multi condensing unit electrical control panel shall be either interior or exterior mounted and must be weatherproof. The electrical control panel shall be manufactured of a minimum 16 gauge galvanized steel which has to be assembled, welded, deburred and cleaned. If exterior mounted, it must be painted with an epoxy based primer coat and a minimum of a second finish coat of polyurethane acrylic enamel based paint. The control panel shall be protected by an exterior mounted NEMA 3R rated fusible disconnect switch.

The electrical control panel will include a removable cover, circuit breakers and contactors for each compressor, circuit breakers, start capacitors and fan cycle control thermostats for each of condenser fan motors. The electrical control panel will also include a mounted wiring diagram of the refrigeration system and its electrical wiring. A separate copy of the wiring diagram of the refrigeration system will also be provided.

12. The footprint of the equipment and its associated length can be no longer than 6’ 4”. The width can be no wider than 3’ 4”. The height can be no taller than 4’. Access doors must be located on one of the long sides of the unit. The connection points of the refrigerant piping from the multi condensing unit shall be on the short side to the left of the access doors and can be no higher than 16” from the bottom of the unit. The electrical disconnect shall be mounted near the top and on the same side as the refrigerant line connections.

PART 1

Refer to attached excel document of existing equipment for cooler information. The cooling capacities of the units should be equivalent to or be slightly larger than the original equipment on the document.

Multi Condenser Unit 1

Size of room/cooler in inches

1. Vegetable Cooler – system F L – 203 W – 108 H - 88

2. Vegetable Prep Cooler – size the same as Meat Prep Cooler (system A)

3. Egg Cooler – system G L – 155 W – 88 H - 88

4. Bread Cooler – system J L – 156 W – 130 H - 88

Multi Condenser Unit 2

Size of room/cooler in inches

1. Meat Prep Cooler – system A L – 178 W – 218 H - 110

2. Meat Cooler – system B L – 121 W – 148 H - 88

3. Bakery Cooler – system D L – 97 W – 179 H - 88

4. Milk Cooler – system E L – 158 W – 97 H - 88

(Evaporator coils and associated equipment for each cooler system shall be included. Refer to details.)

System Description Fixture Suction H.P FLA V PH MBH @ 90deg F A Meat Prep Cooler 35 25 2 6.6 208 3 18.2

B Meat Cooler 35 25 1.5 5.4 208 3 10.6

D Bakery Cooler 35 25 2 6.6 208 3 15.2

E Milk Cooler 35 25 2 6.6 208 3 15.2

System Description AMP V Total FLA Suction Liquid A Meat Prep Cooler 4.4 115 6.6 1 1/8 1/2

B Meat Cooler 1.8 115 5.4 7/8 3/8

D Bakery Cooler 3.3 115 6.6 1 1/8 3/8

E Milk Cooler 6 115 6.6 1 1/8 3/8

FAN 1 PH

LINE SIZES

PART 1 (COOLERS)

FIXTURE CONDENSING UNIT

EVAPORATOR

F Vegetable Cooler 35 25 2 6.6 208 3 15.2

G Egg Cooler 35 25 1.5 5.4 208 3 10.6

J Bread Cooler 35 25 2 6.6 208 3 15.2

System Description AMP V Total FLA Suction Liquid F Vegetable Cooler 6 115 6.6 1 1/8 3/8

G Egg Cooler 4 115 5.4 7/8 3/8

J Bread Cooler 6 115 6.6 1 1/8 3/8

FAN 1 PH

PART 1 (COOLERS)

FIXTURE CONDENSING UNIT

EVAPORATOR LINE SIZES

PART 2 (Freezers)

Details

ALL equipment must be UL listed. The condensers will be located on a concrete pad outside of building.

This quote will be for the purchase of condensing units, evaporator coils and required associated parts.

1. All compressor motors must be 208-230 volt, 3 phase, 60 hertz. The compressors should be low cost hermetic or efficient scroll.

2. All condenser fan motors should be 2 phase or 3 phase style motors, 208-230 volt, 60 hertz.

3. The condenser fan motor should be a minimum of 1/3 horsepower with guard/shroud.

4. All unit’s refrigerant type shall be that of R404A and oil compatible supplied by the manufacturer for the same.

5. All the compressor units shall include discharge and suction line vibration protection, liquid line filter drier, moisture indicating sight glass, dual pressure control and crankcase heater.

The shut off valves should be easily accessed from the exterior. They shall also be supplied with a pump down toggle switch and phase monitor.

6. The system must include encapsulated high pressure and low-pressure auto reset controls with adjustable low-pressure control.

7. All systems shall also include a heated and insulated oversized receiving tank. Each receiver will be supplied with a pressure relief plug and an isolation valve.

8. All condensing unit internal piping shall be neat, orderly and accessible for future maintenance. Each units piping run shall be refrigerant grade ACR or type L piping.

9. The condensing unit must include an electronic defrost timer with associated defroster contactor/relay.

10. The housing of the condensing unit shall be all weather painted galvanized steel.

11. An appropriately sized evaporator unit with cooling fans and the associated parts shall be provided for each compressor system and include a matching TXV, liquid line solenoid valve and thermostat and 230 Volt defrost heaters. The fan motors should be single phase, 230 Volt, 60 hertz. It should have a minimum of 3 fans.

12. The condensing unit electrical control panel shall be mounted on the interior of the condensing unit and should be rust resistant. The electrical control panel will include a hinged/removable cover, circuit breakers and contactors for the compressor, start capacitors, electronic defrost timer circuitry and fan cycle control thermostats for the condenser fan motor. The electrical control panel will also include a mounted wiring diagram of the refrigeration system and its electrical wiring. A separate copy of the wiring diagram of the refrigeration system will also be provided.

13. The footprint of the equipment and its associated length can be no longer than 33”. The width can be no wider than 45”. The height can be no taller than 36”.

PART 2

Refer to attached excel document of existing equipment for freezer information. The cooling capacities of the units should be equivalent to or be slightly larger than the original equipment on the document.

Condenser Unit 1

1. Walk-in Freezer – system H L – 156 W – 88 H - 88

Condenser Unit 2

1. Meat Freezer - system C L – 238 W – 133 H - 88

(Evaporator coils and associated equipment for each freezer system shall be included. Refer to details.)

C Meat Freezer -10 -20 3 10 208 3 14.8

System Description AMP V AMP V PH Total FLA Suction Liquid C Meat Freezer 3 230 13 230 1 13 1 1/8 3/8

DEFROST HEATER

PART 2 (FREEZERS)

FIXTURE CONDENSING UNIT

LINE SIZES

FAN 1 PH

H Walk In Freezer -10 -20 3 10.7 208 3 12.5

System Description AMP V AMP V PH Total FLA Suction Liquid H Walk In Freezer 3.3 230 13 230 1 14 1 1/8 3/8

DEFROST HEATER

PART 2 (FREEZERS)

FIXTURE CONDENSING UNIT

LINE SIZES

FAN 1 PH