The purpose of this amendment 001 is to provide clarification to questions and extend the solicitation until Monday, May 17, 2010 at 3:00 pm EST.

1. What is the Flow rate – in terms of GPM?

The flow rate in terms of GPM is 3,000.

2. What is the temperature of the water entering the cooling tower(s)?

The temperature of the water entering the cooling tower(s) is 95 deg F.

3. What is the desired temperature of the water leaving the cooling tower(s)?

The desired temperature of the water leaving the cooling tower (s) is 85 deg F

4. Water pumps – Do we need to supply them or can we use the ones in the building. If we have to supply them, how much head pressure is required?

The head pressure is 100HP, 3000 GPM at 85 FT HD.