MT TIBER MARINA ABOVE GROUND STORAGE TANK

Solicitation No. 140R6022Q0078

Amendment 00001 Q&A

Questions:

1. Should the tank be UL-142 (double wall, fire resistant) or should it be listed as UL-2085 (double wall, fire and ballistic resistant)?

2. Should the tank be supplied and shipped with all of the necessary Valves, Vents, Gauges, Spill & Overfill required devices?

3. Does the government want the required OSHA approved top of tank access stairs and platform included?

4. Does the location for this tank already have the necessary concrete pad sized properly for this tank ready for the tank to be installed?

5. Does the tank pad location have steel bollard type crash protection around it?

6. Does the government intend to install this tank themselves or will that be the responsibility of the tank supplier/contractor?

7. Will the government provide unloading for the tank from a flatbed semi-truck?

8. What type of pump does the government want, top of tank type or ground mounted?

9. What type of power & voltage should the pump operate on?

10. Is this power already present at the tank installation location?

11. What length of pump hose will be required?

12. What types of vehicles will the fuel be pumped into? (To determine pump dispensing nozzle type)

13. The RFQ indicates that this will be used by a concessionaire for retail fuel sales, does the government want the pump meter to have a pulse output for a retail control device?

14. Is a retail control device also required for the pump metering system to track fuel sales?

15. Will all price quotes be required to include FOB to the government's location?

Answers:

1 UL-142

2 Yes, complete with vents, valves, etc.

3 No, not necessary 4 Not yet, site will be prepped once the dimensions of the tank are determined 5 Will be installed after the tank is set 6 Vendor will need to set the tank and hook up the plumbing, Reclamation will provide electrical hookup 7 Vendor will need to set the tank 8 Ground mounted preferred, either are acceptable 9 110v, standard residential power 10 Will be installed by Reclamation after tank is set 11 20 feet of hose 12 Boats mostly, ATV/UTV’s, rarely vehicles 13 Yes

14 Yes 15 Yes, quote must include all freight charges