Attachment_A_Specifications.docx

DOCX document 27 KB Posted

Attached to
FL STATION BATTERY CHARGER
Solicitation number
140R4025Q0087
Issued by

About this file

The document is a detailed Attachment A Specification for battery chargers for the Bureau of Reclamation's Fontenelle Power Plant at Flaming Gorge Field Division. The specification requires two replacement battery chargers with specific technical requirements, including 480 VAC/3 Phase input, 20-25 amps DC output, float voltage of 130 VDC, load sharing capabilities, and standalone operation. Key specifications include 80% efficiency, +/- 0.5% voltage regulation, temperature compensation, digital controller with alarm system, and convection cooling.

Vendors must submit comprehensive documentation with their quote, including performance specifications, physical dimensions, manufacturer's warranty, replacement parts information, and estimated delivery timeline. The chargers are critical for backup power to power plant protection systems, emergency lighting, and communications. Delivery is specified as freight on board to Fontenelle Dam in La Barge, Wyoming, with business hours Monday through Thursday from 7:30 AM to 4:30 PM. The solicitation is issued by the Department of the Interior Bureau of Reclamation under solicitation number 140R4025Q0087.

View the file

Other files

File Type Posted
Sol_140R4025Q0087.pdf PDF
Clauses_and_Provisions_140R4025Q0087.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fontenelle Station Battery Charger Specification REQUIREMENT: The Bureau of Reclamation, Flaming Gorge Field Division has a requirement to procure chargers for the Fontenelle Power Plant station battery systems.

PART 1 BACKGROUND

1.1 DESCRIPTION

The existing station battery system has two load sharing battery chargers operated in parallel on float charge. Each charger is capable of operating stand-alone. The chargers have proven to be unreliable and require replacement. This battery system provides the backup power to the power plant protection systems, power plant emergency lighting, and backup power for power plant communications.

1.2 SCOPE

A. Provide replacement chargers for the two battery chargers, connected in parallel, capable of load sharing. One system charger must continue to operate without interruption or failure in the event its counterpart fails. Each charger must be capable of operating in a stand-alone mode, no load sharing, one charger “Off” one charger “On”.

Part 2 REQUIREMENT

1.1 New Battery Charger Characteristics

A. Battery Charger shall be must meet the following characteristics:

Quantity:
2 each
Type:
Must be compatible with vented lead acid type batteries.
AC Input Voltage:
480 VAC/3 Phase/60 Hertz
AC Input Circuit Breaker:
Charger shall have properly sized, UL listed, AC input breaker.
DC Output Current:
Range of 20-25 amps

DC Output Circuit Breaker:

Charger shall have properly sized, UL Listed, DC rated output breaker.

DC Output Voltage:
Float – 130 Vdc Nominal, Adjustable 127-138 Vdc

Equalize – Adjustable 135-144

Load Sharing:
Must be capable of load sharing operation. Single charger must continue to operate, “stand-alone”, without interruption or failure if it’s counterpart fails or is turned off, even with load sharing wiring connected.
Efficiency:
80% and a 0.85 power factor or better at full load
DC Voltage Regulation:
+/- 0.5% of setting from no load to full load
Protection:
Provide reverse polarity protection
Current Limiting:
Adjustable from 50%-115% of rated output
Filtering:
Output ripple shall be 100mV RMS or less
Temperature Compensation:
Charger shall include external temperature probe. Charger shall incorporate external temperature to determine best charging output.
Controller:
Charger shall have a controller with display that provides charger information for maintenance, calibration and monitoring. Also provide digital adjustments for charger output (no potentiometers), alarms and communication settings. Shall include configurable alarm system for alarm thresholds, delays, and contact operations (latching/non-latching)
Ventilation
Convection Cooled only, no fans
Other Options/Accessories:
Charger shall include heat shrink wire markers and electrical schematic.
Battery system monitoring
Each charger shall have the capability to individually monitor the battery system. As part of the monitoring, each charger shall provide at a minimum the following outputs:

-Charger general trouble

PART 3 DELIVERY

A. All material shall be delivered freight on board destination to: BOR, Fontenelle Dam, 302 County road 316, La Barge WY, 83123. Contractor shall coordinate delivery with COR, contact information provided at award. Business hours for the Dam are Monday thru Thursday 7:30AM to 4:30 PM.

PART 4 SUBMITTALS

A. Vendors must submit the following with their quote:

1) Battery charger performance specifications

2) Physical dimensions

3) Manufacturer’s warranty information

4) Information on replacement parts accessibility for chargers.

5) Provide estimated delivery after the receipt of award.

If the above information is not included with the Contractors quote the quote can be found non-responsive and not considered for award.

File details come from the government source that posted it. Updated .