PERFORMANCE WORK STATEMENT

Tohlakai Ladder and Fall Arrest System and 22B Ladder Fall Arrest Systems

IN RED - Revised 2/15/2021

1.0 Background

The Bureau of Reclamation, Four Corners Construction Office (FCCO), has a need for a ladder and a ladder fall arrest system for access to the Tohlakai Pumping Plant roof. The pumping plant is located approximately 8 miles north of Gallup, NM. Reclamation also has a need for ladder fall arrest systems for two regulating tanks at 22B about 18 miles SE of Bloomfield, NM in San Juan County, NM

2.0 Scope

The contractor is to supply all personnel, equipment, and all materials and parts necessary to provide the tasks described in Section 4.0, Tasks, under the conditions and schedule described in Section 5.0, Delivery. Contractor shall be responsible for their safety and comply with OSHA and Reclamation Safety and Health Standards.

3.0 Objectives

The goal is to design, supply and install a ladder and fall arrest system at the Tohlakai Pumping Plant and fall arrest systems for two regulating tanks at 22B. Ladders are already installed at the regulating tanks.

Tasks

1. The contractor shall supply and install a permanent ladder for access to the roof at Tohlakai Pumping Plant. The ladder shall also have a fall arrest system. Ladder shall be installed on the south side of the plant as approximately located on the drawings.

Coordination with the Contracting Officer’s Representative shall be required. Roof is flat that slopes slightly for drainage. Building is Concrete Masonry Unit (CMU) and it is expected that rebar is installed approximately every 4 feet. See for information drawings.

Ladder and fall arrest system shall be designed by the contractor and mounting tabs shall be anchored per manufacture’s recommendations. Contractor shall provide all labor, materials and equipment (including safety equipment). Contractor shall take every precaution not to hit conduit and lighting that is located on the south side of the building.

Any damage to the building shall be repaired at the contractor’s expense.

A. Ladders:

a. Model 562 (NOT 562-C) fixed wall ladder with return and security door manufactured by ALACO Ladder Company, 5167 “G” Street, Chino CA 91710-5143; or equal, having the following essential characteristics:

1. Conforms to ANSI A 14.3 and 29 CFR 1910.27.

2. Fixed wall ladder type with return/grab bar and security door.

a. Height of return: 42-inches above top ladder rung.

b. Fabricated from aluminum alloy.

3. Rungs:

a. Raised button, serrated edge, or metal bonded encapsulated grit surface.

b. Diameter or Width: 1 1/8 inch.

c. Concentrated design load at center of rung: 200 pounds

d. Rung length: 18 inches maximum.

e. Drawings 1695-D-115, 117 and 146 detail the CMU and interior panels.

f. Height of building is approximately 28’5”.

g. Contractor shall core drill through the CMU and may hit solid grout and rebar. Any damage to the blocks shall be repaired by the contractor.

h. Contractor shall cut interior panels with a hole saw.

Any damage to the panels shall be repaired at the contractor’s expense.

B. Security Door:

a. Fabricated from aluminum alloy sheet, 0.063-inch thick, minimum

b. Hinged and fabricated with hasps for padlocking.

C. Provide all materials required (including fasteners and attachment accessories) for complete installation of the ladders, safety rail and security door.

D. Install in accordance with manufacture’s recommendations.

a. Attach ladder to the CMU on the south side of the wall.

E. Contractor shall supply and install the fall arrest system for the ladder as specified in task 2.

2. The contractor shall supply and install fall arrest systems for ladders that are installed on two regulating tanks. Contractor shall provide all labor, materials and equipment (including safety equipment) to install the safety rails. The regulating tanks are glass lined bolted steel tanks. Contractor shall perform work in the manner not to damage to glass lining. Safety cages for ladders are installed on the tanks. Contractor shall not remove the safety cages.

A. Safety rail: Miller Saf-T-Climb as manufactured by Honeywell (800.836.8006) with essential characteristics:

a. Round cross section.

b. Allow sleeve to swing completely around when climber reaches the top platform, to allow the climber to step onto the top platform without disconnecting the sleeve.

c. Flat safety rail: Not acceptable.

d. Cable: Not acceptable

e. Provide one sleeve and harness for each tank and for the Tohlakai ladder (3 total)

B. Install in accordance with manufacture’s recommendations.

C. Any damage to the tanks shall be corrected at the contractor’s expense.

D. Test and certify system after installation is complete.

E. TESTING: Follow manufacturer’s warranty. If manufacture does not recommend a testing procedure, climb ladder with climbing sleeve and harness and test the range of motion

3. Submittals:

A. Submit manufacture’s data and drawings for ladder and safety rails 21 days prior to starting work.

B. Submit installation procedures for ladder and safety rails 21 prior to starting work.

C. Contractor shall submit a site-specific Job Hazard Analysis (Job Safety Analysis) prior to starting work for all 3 sites. All work shall be performed in accordance with Reclamation Safety and Health Standards (RSHS) and Occupational Safety and Health Administration (OSHA). RSHS is located at:

https://www.usbr.gov/ssle/safety/RSHS-all.pdf. The JHA/JSA shall be approved 21 days prior to starting work. The safety analysis shall include how the contractor will mitigate working at high elevations. The pumping plant roof does not have a fall protection system in place. Note: there are no existing ladders to the roof at Tohlakai. The installation contractor utilized a man lift/sky lift to access the roof.

Review OSHA’s requirement for ladders over 20 feet if a ladder is utilized. RSHS and OSHA requirements will be strictly followed by the contractor for working at elevations exceeding 4’, ladder usage, man lifts and working on roofs.

D. Submittals shall be submitted to the Contracting Officer’s Representative (COR):

Emma Manzanares at emanzanares@usbr.gov. Phone: (505)324-5017.

5.0 Delivery

The contractor shall complete the work 90 days after notice to proceed.

A site tour of Tohlakai Pumping Plant is encouraged to interested contractors in order to become familiar with the project and will be scheduled on a date to be posted. The site tour will be the only opportunity to visit the Tohlakai Pumping Plant.

mailto:emanzanares@usbr.gov

6.0 Government-Furnished Property

There will be no GFE for this requirement.

7.0 Security

Reclamation personnel will be on-site for the duration of the contractor’s work. Contractor shall contact COR prior to beginning on-site work.

On-site facilities are not available to the contractor. Contractor shall arrange for lavatory facilities. Limited electric power may be available for contractor’s use but is not guaranteed.

8.0 Place of Performance

Tohlakai Pumping Plant is located approximately 8 miles north of Gallup, New Mexico, in McKinley County. The 22B tanks are located southeast of Bloomfield, New Mexico. The regulating tank 1 site is located at 373 County Road 7007 in San Juan County, approximately 28 miles southeast of Bloomfield, NM. The regulating tank 2 site is located approximately halfway between County Roads 7425 and 7575 in San Juan County, approximately 30 miles southeast of Bloomfield, NM.

9.0 Period of Performance

The period of performance is from award to 90 days after notice to proceed.

Questions and Answer # 1:

1. Should the base bid for ladder be 562 or 562-C? The 'C' in the part number indicates ‘cage’, so we wanted to clarify whether or not that was intentional, since there is a FP system on this ladder. Model 562 should be the correct number. Work statement has been amended above.

2. What type of security door is preferred? One that swings down from base of cage, or hinged on the rail and covering the rungs? preference is hinged on the rail

3. Can you please detail the testing of the system requested per the 2D of the work statement?

Follow manufacturer’s warranty. If manufacture does not recommend a testing procedure, climb ladder with climbing sleeve and harness and test the range of motion

4. Do you want a swing-gate for the top of the existing two ladders and mid-height of the 34ft (replacing existing chains), and one also for the new 27ft ladder? 4x total? No

5. What is the current condition of the tanks in order to secure the ladder and fall arrest system in the scope of work? Tank is currently in operation to deliver water to the facilities. We cannot impact the water delivery.

6. What is the age of tanks and silo? Approx. 3 years

7. May we have some pictures of the current status and condition of the tanks and silo?

Unavailable at the present time. Please reference the for information drawings in the specification on the tanks.

8. Are the silos and tanks currently empty or is it being utilized? Utilized and filled with water

9. Is there a priority in which tank to complete first? No priority. Note that the contractor is to also install a ladder with climbers at Tohlakai Pumping Plant

PERFORMANCE WORK STATEMENT
Tohlakai Ladder and Fall Arrest System and 22B Ladder Fall Arrest Systems
IN RED - Revised 2/15/2021