SPECIFICATIONS
115kV Disconnect Switches ---4 ea.
Nominal Voltage------115kV Continuous Amps-----1200A Short Circuit Rating---50kA BIL Rating----------------550kV Configuration-----------Vertical Mounting Seismic Rating--------High Seismic Zone Motor Operator for 115kV Switches -Motor Voltage ------ 125VDC -Heater Voltage ------ 240VAC
DIMENSIONS
-Maximum Mounting Base Length---------------100” -Maximum Height without blade assembly------60” -Maximum Height on open position-------------140” -Distance Between two main Insulators--------60”
230kV Disconnect Switches ---7 ea.
Nominal Voltage------230kV Continuous Amps-----1200A Short Circuit Rating---50kA BIL Rating----------------900kV Configuration-----------Vertical Mounting Seismic Rating---------High Seismic Zone Motor Operator for 230kV Switches -Motor Voltage ------- 125VDC -Heater Voltage ------- 240VAC
DIMENSIONS
-Maximum Mounting Base Length---------------135” -Maximum Height without blade assembly------98” -Maximum Height on open position-------------212” -Distance Between two main Insulators---------96”