SALIENT CHARACTERISTICS:
1. Equipment: The Flow Meters shall be a complete system that meets the following requirements:
a. For use with water.
b. Electromagnetic Flow Sensor
c. Metal flow meter body
d. Flanged Connections to Pipe meeting AWWA C207 and ASME class 150
e. Suitable for pipes below 150 psi internal pressure
f. Water Temperature Range: 40 deg F – 100 deg F
g. Signal Output: 4-20 mA
h. Two tunable Relay Outputs for Alarming and Tripping
i. Has a Human Machine Interface (HMI)
(1) Liquid Cristal Display
(2) Display Flow in GPM
(3) Remotely mounted within 45 ft
j. Designed for industrial applications and continuous duty
k. Includes calibration certificate
l. Transmitter uses HART Communication protocol
m. Accuracy better or equal to +/- 0.25%
n. Includes cable for remote mounting of transmitter from flow sensor
o. Nominal Diameter: See Flow Meter Application Table below
p. Power Supply: VDC or AC acceptable
Quantity and Size: Flow Meter Application Table
Item No. Facility Qty Pipe Dia. Pressure Minimum Flow Range
(GPM)
1 Folsom 3 1” 150 psi 0 – 30 gpm
2 Nimbus 2 1” 150 psi 0 – 30 gpm
3 New Melones 2 2” 150 psi 0 – 50 gpm
4 Spare 1 1” 150 psi 0 - 30 gpm
5 Spare 1 2” 150 psi 0 - 50 gpm