This document provides technical specifications and installation details for a metal roofing system. It includes drawings and part numbers for various roof components like eave plates, gutter systems, ridge and hip flashing, closure details, and fastener patterns. The specifications cover material requirements and installation procedures for a Mirage II standing seam metal roof across different roof configurations, such as simple eaves, eaves with gutters, rake start and end details, and tie-in details. This level of technical specification and drawing appears to support a solicitation for roof repair services included to replace or repair an existing Mirage II metal roof system. The related federal contract opportunity is for roof repairs at an unnamed facility for the Department of the Interior Bureau of Reclamation, but no further details are provided on response dates, award timing, or pricing requirements.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TABLE OF CONTENTS

A-1

PAGE NUMBER: DETAIL DESCRIPTION

A-1........................................TABLE OF CONTENTS

A-2........................................GENERAL NOTES

B-1.........................................FASTENER PATTERN

B-2.........................................GENERAL INFORMATION

C-1.........................................SIMPLE EAVE DETAIL

C-2.........................................EAVE with 5" GUTTER DETAIL

C-3.........................................SCULPTURED EAVE DETAIL

C-4.........................................HIGH-SIDE EAVE DETAIL (5" BARGE)

C-5.........................................RAKE START DETAIL (5" BARGE)

C-6.........................................RAKE END DETAIL (5" BARGE)

C-7.........................................EAVE w/ 7" GUTTER DETAIL

C-8.........................................HIGH-SIDE EAVE DETAIL (7" BARGE)

C-9.........................................RAKE START DETAIL (7" BARGE)

C-10.......................................RAKE END DETAIL (7" BARGE)

C-11.......................................RAKE START TIE-IN DETAIL

C-12.......................................RAKE END TIE-IN DETAIL

C-13.......................................HIGH-SIDE TIE-IN DETAIL

C-14.......................................FLOATING RIDGE DETAIL

C-15.......................................FIXED RIDGE DETAIL

C-16.......................................FLOATING HIP DETAIL

C-17.......................................FIXED HIP DETAIL

C-18.......................................SIDE-LAP DETAIL

C-19.......................................BARGE TRIM LAPS

GENERAL NOTES

A-2

The details shown on the following pages are suggestions or guidelines for installing the Mirage II roof panel system. The installation details shown here are proven methods of construction, but they are not intended to cover all building requirements, designs or codes. The details may require changes or revisions due to individual project conditions.

Installation procedures shall be in accordance with the manufacturer's printed instructions, details or approved shop drawings. Installers should thoroughly familiarize themselves with all instructions prior to beginning the installation process.

The designer/installer is responsible to ensure the following:

That the details here meet the particular building requirements.

Awareness of and allowance for expansion/contraction of the roof panels.

That adequate water tightness is maintained.

That a proper uniform substructure is used to avoid panel distortion and that the substructure meets necessary code requirements.

That all supporting members have been examined and are straight, level and plumb.

McElroy Metal can provide all flashings and accessories shown in the installation drawings unless noted otherwise. Panels, flashing and trim shall be installed true and in proper alignment with any exposed fasteners equally spaced for the best appearance. Sealant shall be field applied on a clean, dry surface.

Some field cutting and fitting of panels and flashings is to be expected and to be considered a part of normal installation work. Workmanship shall be of the best industry standards and with installation performed by experienced metal craftsmen.

Oil canning of metal panels is in the product and is not a cause for rejection. Striated panels are recommended as they reduce the appearance of oil canning.

Contents of this manual are subject to change without notice. To confirm this book is the most current copy, please visit McElroy Metal's website at www.mcelroymetal.com.

http://www.mcelroymetal.com./

GENERAL INFORMATION

B-1

FASTENER PATTERNS

1/4-14 X 1 1/4" TEK2 ZAC

FASTENERS

GENERAL INFORMATION

B-2

PANEL FOLDING

SIMPLE EAVE DETAIL

NOTES: 1. Eave Plate to run from steel line to steel line. Attach to Eave Structural Member with

2. Simple Eave Trim to run from out of wall to out of wall. Attach to Eave Plate with #10-16 x 1" Pancake

EAVE TRIM

C-1

3. Install Inside Closure with continuous run of 1" Roll Tape Sealant on bottom and Butyl Tube Sealant

4. Attach roof panel to Eave Plate with 1/4-14 x 1 1/4" TEK2 ZAC. Fasteners must penetrate sealant.

WALL PANEL

1/4-14 X 7/8" LAP TEK

(@ MAJOR RIBS)

SIMPLE EAVE

TRIM

EAVE STRUCTURAL

MEMBER

WALL FASTENER

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (@ 1'-0" O.C.)

ROOF LINE

UTILITY EAVE

PLATE

OUTSIDE CLOSURE

(RECOMMENDED)

MIRAGE II

PANEL

WALL PANEL

1/4-14 X 7/8" LAP TEK

FASTENER (@ MAJOR RIBS)

SIMPLE EAVE

TRIM

1/4-14 X 1 1/4" TEK2 ZAC

FASTENER (SEE B-1

FOR FASTENER PAT.)

INSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(BOTTOM OF CLOSURE)

EAVE STRUCTURAL

MEMBER

UTILITY EAVE

PLATE

MIRAGE II

PANEL

WALL FASTENER

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (@ 1'-0" O.C.)

OUTSIDE CLOSURE

(RECOMMENDED)

BUYTL TUBE SEALANT

(TOP OF CLOSURE)

FIELD FORM

DRIP EDGE

FIELD FORM

DRIP EDGE

5. Field form Drip Edge on panel using panel bending tool.

Head Fasteners at 5'-0" O.C.

#10-16 x 1" Pancake Head Fasteners at 1'-0" O.C.

1/4-14 X 1 1/4" TEK2 ZAC

FASTENER (SEE B-1

FOR FASTENER PAT.)

INSIDE CLOSURE W/ 1" ROLL TAPE

SEALANT (BOTTOM OF CLOSURE

& BUTYL TUBE SEALANT

(TOP OF CLOSURE)

on top.

EAVE w/ 5" GUTTER DETAIL

2. Simple Eave Trim to run from out of wall to out of wall. Attach to Eave Plate with #10-16 x 1"

EAVE TRIM

C-2

3. Install Inside Closure with continuous run of 1" Roll Tape Sealant on bottom and Butyl Tube Sealant

4. Attach roof panel to Eave Plate with 1/4-14 x 1 1/4" TEK2 ZAC. Fasteners must penetrate sealant.

WALL PANEL

1/4-14 X 7/8" LAP TEK

(@ MAJOR RIBS)

SIMPLE EAVE

TRIM

1/4-14 X 1 1/4" TEK2 ZAC

FASTENER (SEE B-1

FOR FASTENER PAT.)

INSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(BOTTOM OF CLOSURE) &

BUTYL TUBE SEALANT

(TOP OF CLOSURE)

EAVE STRUCTURAL

MEMBER

WALL FASTENER

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (@ 1'-0" O.C.)

ROOF LINE

UTILITY EAVE

PLATE

OUTSIDE CLOSURE

(RECOMMENDED)

MIRAGE II

PANEL

WALL PANEL

1/4-14 X 7/8" LAP TEK

(@ MAJOR RIBS)

SIMPLE EAVE

TRIM

1/4-14 X 1 1/4" TEK2 ZAC

FASTENER (SEE B-1

FOR FASTENER PAT.)

INSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(BOTTOM OF CLOSURE)

EAVE STRUCTURAL

MEMBER

UTILITY EAVE

PLATE

MIRAGE II

PANEL

WALL FASTENER

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (@ 1'-0" O.C.)

OUTSIDE CLOSURE

(RECOMMENDED)

BUTYL TUBE SEALANT

(TOP OF CLOSURE)

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (1 PER STRAP)

GUTTER STRAP

(@ EVERY OTHER SEAM)

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (2 PER PANEL)

GUTTER

5. Gutter straps are to be placed between the two roof sheets and in line from end to end as show.

NOTE: SLIDING SNOW AND ICE COULD

CAUSE DAMAGE TO GUTTER SYSTEM.

6. The gutter is not required to be fastened to the gutter straps on pitches less than 2:12.

GUTTER

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (2 PER PANEL)

GUTTER STRAP

(@ EVERY OTHER SEAM)

GUTTER

#10-16 x 1" Pancake Head Fasteners at 1'-0" O.C.

Pancake Head Fasteners at 5'-0" O.C.

DOWNSPOUT

SCULPTURED EAVE DETAIL

SCULPTURED EAVE TRIM

C-3

WALL PANEL

1/4-14 X 7/8" LAP TEK

(@ MAJOR RIBS)

SCULPTURED EAVE

TRIM

1/4-14 X 1 1/4" TEK2 ZAC

FASTENER (SEE PAGE B-1

FOR FASTENER PAT.)

INSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(BOTTOM OF CLOSURE) &

BUYTL TUBE SEALANT

(TOP OF CLOSURE)

EAVE STRUCTURAL

MEMBER

WALL FASTENER

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (@ 1'-0" O.C.)

ROOF LINE

UTILITY EAVE

PLATE

OUTSIDE CLOSURE

(RECOMMENDED)

MIRAGE II

PANEL

WALL PANEL

1/4-14 X 7/8" LAP TEK

(@ MAJOR RIBS)

SCULPTURED EAVE

TRIM

1/4-14 X 1 1/4" TEK2 ZAC

FASTENER (SEE PAGE B-1

FOR FASTENER PAT.)

INSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(BOTTOM OF CLOSURE)

EAVE STRUCTURAL

MEMBER

UTILITY EAVE

PLATE

MIRAGE II

PANEL

WALL FASTENER

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (@ 1'-0" O.C.)

OUTSIDE CLOSURE

(RECOMMENDED)

BUTYL TUBE SEALANT

(TOP OF CLOSURE)

FIELD FORMED

DRIP EDGE

FIELD FORMED

DRIP EDGE

NOTES: 1. Eave Plate to run from steel line to steel line. Attach to Eave Structural Member with

2. Sculptured Eave Trim to run from out of wall to out of wall. Attach to Eave Plate with #10-16 x 1"

3. Install Inside Closure with continuous run of 1" Roll Tape Sealant on bottom and Butyl Tube Sealant

4. Attach roof panel to Eave Plate with 1/4-14 x 1 1/4" TEK2 ZAC. Fasteners must penetrate sealant.

5. Field form Drip Edge on panel using panel bending tool.

Pancake Head Fasteners at 5'-0" O.C.

#10-16 x 1" Pancake Head Fasteners at 1'-0" O.C.

HIGH-SIDE EAVE DETAIL - 5" BARGE

BARGE TRIM

C-4

WALL PANEL

EAVE STRUCTURAL

MEMBER

MIRAGE II CLIP

MIRAGE II

PANEL

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (2 PER CLIP)

OUTSIDE CLOSURE

(RECOMMENDED)

MIRAGE II

PANEL

OUTSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(TOP & BOTTOM OF CLOSURE)

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ EA. PANEL RIB)

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (2 PER CLIP)

EAVE STRUCTURAL

MEMBER

MIRAGE II PANEL

CLIP

BARGE TRIM

(FIELD BREAK TO PITCH

AND NOTCH OUT AT RIBS)

WALL FRAMING

FASTENER

OUTSIDE CLOSURE

(RECOMMENDED)

2. Attach Barge Cleat to wall panels with 1/4-14 x 7/8" Lap Tek fasteners at each major rib.

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ EACH PANEL RIB)

1/4-14 X 7/8" LAP TEK

FASTENER (@ MAJOR RIBS)

WALL PANEL

BARGE CLEAT

*BARGE CLEAT

*BARGE CLEAT

1/4-14 X 7/8" LAP TEK

FASTENER (@ MAJOR RIBS)

BARGE TRIM

(FIELD BREAK TO PITCH

AND NOTCH OUT AT RIBS)

PAN-UP PANEL

NOTES: 1. Field form End Dam using End Dam tool.

3. Notch Barge Trim around ribs of roof panels and attach with 1/4-14 x 7/8" Lap Tek Zac at Major Ribs.

Fasteners must penetrate tape sealant.

OUTSIDE CLOSURE w/

1" ROLL TAPE SEALANT

(TOP & BOTTOM OF CLOSURE)

WALL FASTENER

RAKE START DETAIL - 5" BARGE

NOTES: 1. Place continuous run of Roll Tape Sealant on top of panel rib.

2. Install Barge Cleat to wall panel at major ribs with (1) 1/4-14 x 7/8" Lap Tek fastener.

BARGE TRIM

C-5

3. Attach Barge Trim to roof panel at 1'-0" O.C. using 1/4-14 x 7/8" Lap Tek ZAC fasteners.

MIRAGE II PANEL

MIRAGE II CLIP

ROOF STRUCTURAL

MEMBER

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (2 PER CLIP)

BARGE TRIM

RAKE ANGLE

1/4-14 X 7/8" LAP TEK

FASTENER (@ MAJOR RIBS)

*BARGE CLEAT

WALL FRAMING

FASTENER

WALL PANEL

3/32" X 3/8" ROLL TAPE

SEALANT (CONT. ALONG

TOP OF PANEL RIB)

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ 1'-0" O.C.)

(DO NOT FASTEN

THROUGH CLIP)

MIRAGE II PANEL

MIRAGE II CLIP

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (2 PER CLIP)

ROOF STRUCTURAL

MEMBER

3/32" X 3/8" ROLL TAPE

SEALANT (CONT. ALONG

TOP OF PANEL RIB)

1/4-14 X 1 1/4" HWH TEK2

FASTENER (@ EACH

STRUCTURAL MEMBER)

WALL PANEL

1/4-14 X 7/8" LAP TEK

FASTENER (@ MAJOR RIBS)

OUTSIDE CLOSURE

(RECOMMENDED)

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ 1'-0" O.C.)

(DO NOT FASTEN

THROUGH CLIP)

BARGE TRIM

BARGE CLEAT

OUTSIDE CLOSURE

(RECOMMENDED)

*BARGE CLEAT

RAKE ANGLE

WALL FASTENER

1/4-14 X 1 1/4" HWH TEK2

FASTENER (@ EACH

STRUCTURAL MEMBER)

RAKE END DETAIL - 5" BARGE

C-6

MIRAGE II PANEL

MIRAGE II PANEL

CLIP

BARGE TRIM

3/32" X 3/8" ROLL TAPE

SEALANT (CONT. ALONG

TOP OF PANEL RIB)

1/4-14 X 1 1/4" HWH TEK2

FASTENER (1 PER CLIP)

1/4-14 X 7/8" LAP TEK

FASTENER (@ MAJOR

RIBS)

OUTSIDE CLOSURE

(RECOMMENDED)

RAKE ANGLE

FRAMING FASTENER

WALL PANEL

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER

MIRAGE II PANEL

MIRAGE II CLIP

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (2 PER CLIP)

ROOF STRUCTURAL

MEMBER

WALL PANEL

1/4-14 X 7/8" LAP TEK

FASTENER (@ MAJOR RIBS)

BARGE CLEAT

OUTSIDE CLOSURE

(RECOMMENDED)

RAKE ANGLE

3/32" X 3/8" ROLL TAPE

SEALANT (CONT. ALONG

TOP OF PANEL RIB)

WALL FASTENER

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ 1'-0" O.C.)

(DO NOT FASTEN

THROUGH CLIP)

BARGE TRIM

FIELD CUT CLIP

AS REQUIRED

FIELD CUT CLIP

AS REQUIRED

ROOF STRUCTURAL

MEMBER

NOTES: 1. Place continuous run of Roll Tape Sealant on top of panel rib.

2. Install Barge Cleat to wall panel at major ribs with (1) 1/4-14 x 7/8" Lap Tek fastener.

3. Attach Barge Trim to roof panel at 1'-0" O.C. using 1/4-14 x 7/8" Lap Tek ZAC fasteners.

BARGE CLEAT

*BARGE CLEAT

1/4-14 X 1 1/4" HWH TEK2

FASTENER (1 PER CLIP)

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ 1'-0" O.C.)

(DO NOT FASTEN

THROUGH CLIP)

EAVE w/ 7" GUTTER DETAIL

2. Simple Eave Trim to run from out of wall to out of wall. Attach to Eave Plate with #10-16 x 1"

EAVE TRIM

C-7

3. Install Inside Closure with continuous run of 1" Roll Tape Sealant on bottom and Butyl Tube Sealant

4. Attach roof panel to Eave Plate with 1/4-14 x 1 1/4" TEK2 ZAC. Fasteners must penetrate sealant.

WALL PANEL

1/4-14 X 7/8" LAP TEK

(@ MAJOR RIBS)

SIMPLE EAVE

TRIM

1/4-14 X 1 1/4" TEK2 ZAC

FASTENER (SEE B-1

FOR FASTENER PAT.)

INSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(BOTTOM OF CLOSURE)

& BUTYL TUBE SEALANT

(TOP OF CLOSURE)

EAVE STRUCTURAL

MEMBER

WALL FASTENER

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (@ 1'-0" O.C.)

ROOF LINE

UTILITY EAVE

PLATE

MIRAGE II

PANEL

WALL PANEL

SIMPLE EAVE

TRIM

1/4-14 X 1 1/4" TEK2 ZAC

FASTENER (SEE B-1

FOR FASTENER PAT.)

INSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(BOTTOM OF CLOSURE)

EAVE STRUCTURAL

MEMBER

UTILITY EAVE

PLATE

MIRAGE II

PANEL

WALL FASTENER

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (@ 1'-0" O.C.)

OUTSIDE CLOSURE

(RECOMMENDED)

BUYTL TUBE SEALANT

(TOP OF CLOSURE)

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (1 PER STRAP)

GUTTER STRAP

(@ EVERY OTHER SEAM)

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (2 PER PANEL)

GUTTER

5. Gutter straps are to be placed between the two roof sheets and in line from end to end as show.

NOTE: SLIDING SNOW AND ICE COULD

CAUSE DAMAGE TO GUTTER SYSTEM.

6. The gutter is not required to be fastened to the gutter straps on pitches less than 2:12.

GUTTER

1/4-14 X 7/8" TEK2 ZAC

FASTENER (2 PER PANEL)

GUTTER STRAP

(@ EVERY OTHER SEAM)

GUTTER

#10-16 x 1" Pancake Head Fasteners at 1'-0" O.C.

Pancake Head Fasteners at 5'-0" O.C.

DOWNSPOUT

OUTSIDE CLOSURE

(RECOMMENDED)

HIGH-SIDE EAVE DETAIL - 7" BARGE

C-8

WALL PANEL

EAVE STRUCTURAL

MEMBER

MIRAGE II CLIP

MIRAGE II

PANEL

WALL FASTENER

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (2 PER CLIP)

OUTSIDE CLOSURE

(RECOMMENDED)

MIRAGE II

PANEL

OUTSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(TOP & BOTTOM OF CLOSURE)

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ EA. PANEL RIB)

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (2 PER CLIP)

EAVE STRUCTURAL

MEMBER

MIRAGE II PANEL

CLIP

BARGE TRIM

(FIELD BREAK TO PITCH

AND NOTCH OUT AT RIBS)

OUTSIDE CLOSURE

(RECOMMENDED)

2. Attach Barge Clip to wall panels with 1/4-14 x 7/8" Lap Tek fasteners at each major rib.

1/4-14 X 7/8" LAP TEK

FASTENER (@ MAJOR RIBS)

WALL PANEL

BARGE CLEAT

BARGE CLIP

*BARGE CLIP

1/4-14 X 7/8" LAP TEK

FASTENER (@ MAJOR RIBS)

BARGE TRIM

(FIELD BREAK TO PITCH

AND NOTCH OUT AT RIBS)

PAN-UP PANEL

NOTES: 1. Field form End Dam using End Dam tool.

3. Notch Barge Trim around ribs of roof panels and attach with 1/4-14 x 7/8" Lap Tek Zac at Major Ribs.

Fasteners must penetrate tape sealant.

OUTSIDE CLOSURE w/

1" ROLL TAPE SEALANT

(TOP & BOTTOM

OF CLOSURE)

WALL FRAMING

FASTENER

BARGE CLIP

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ EACH PANEL RIB)

RAKE START - 7" BARGE

NOTES: 1. Place continuous run of Roll Tape Sealant on top of panel rib.

2. Install Barge Clip to wall panel at 5'-0" O.C. with (2) 1/4-14 x 7/8" Lap Tek fastener.

7" BARGE TRIM

C-9

3. Attach Barge Trim to roof panel at 1'-0" O.C. using 1/4-14 x 7/8" Lap Tek ZAC fasteners. **DO NOT

ATTACH TO CLIPS.**

MIRAGE II PANEL

MIRAGE II CLIP

ROOF STRUCTURAL

MEMBER

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (2 PER CLIP)

BARGE TRIM

RAKE ANGLE

1/4-14 X 7/8" LAP TEK

FASTENERS (2 PER CLIP

@ MAJOR RIBS)

BARGE CLIP

(@ 5'-0" O.C.)

WALL FRAMING

FASTENER

WALL PANEL

3/32" X 3/8" ROLL TAPE

SEALANT (CONT. ALONG

TOP OF PANEL RIB)

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ 1'-0" O.C.)

(DO NOT FASTEN THROUGH

TOP OF BARGE CLIP)

MIRAGE II PANEL

MIRAGE II CLIP

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER

(2 PER CLIP)

ROOF STRUCTURAL

MEMBER

3/32" X 3/8" ROLL TAPE

SEALANT (CONT. ALONG

TOP OF PANEL RIB)

1/4-14 X 1 1/4" HWH TEK2

FASTENERWALL PANEL

1/4-14 X 7/8" LAP TEK

FASTENER (2 PER CLIP

@ MAJOR RIBS)

FRAMING FASTENER

RAKE ANGLE

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ 1'-0" O.C.)

BARGE TRIM

BARGE CLEAT

1/4-14 X 1 1/4" HWH TEK2

FASTENER

BARGE CLIP

(@ 5'-0" O.C.)

RAKE ANGLE

BARGE CLIP

RAKE END DETAIL - 7" BARGE

7" BARGE TRIM

C-10

MIRAGE II PANEL

MIRAGE II PANEL

CLIP

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ 1'-0" O.C.)

BARGE TRIM

3/32" X 3/8" ROLL TAPE

SEALANT (CONT. ALONG

TOP OF PANEL RIB)

1/4-14 X 1 1/4" HWH TEK2

FASTENER

1/4-14 X 7/8" LAP TEK

FASTENER (2 PER CLIP

@ MAJOR RIBS)

RAKE ANGLE

FRAMING FASTENER

WALL PANEL

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER

MIRAGE II PANEL

MIRAGE II CLIP

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (2 PER CLIP)

ROOF STRUCTURAL

MEMBER

WALL PANEL

1/4-14 X 7/8" LAP TEK

FASTENER (2 PER CLIP

@ MAJOR RIBS)

BARGE CLIP

(@ 5'-0" O.C.)

FRAMING FASTENER

RAKE ANGLE

3/32" X 3/8" ROLL TAPE

SEALANT (CONT. ALONG

TOP OF PANEL RIB)

1/4-14 X 1 1/4" HWH TEK2

FASTENER

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ 1'-0" O.C.)

BARGE TRIM

FIELD CUT CLIP

AS REQUIRED

FIELD CUT CLIP

AS REQUIRED

ROOF STRUCTURAL

MEMBER

NOTES: 1. Place continuous run of Roll Tape Sealant on top of panel rib.

2. Install Barge Clip to wall panel at 5'-0" O.C. with (2) 1/4-14 x 7/8" Lap Tek fastener.

3. Attach Barge Trim to roof panel at 1'-0" O.C. using 1/4-14 x 7/8" Lap Tek ZAC fasteners.

**DO NOT ATTACH TO CLIPS.**

BARGE CLEAT

BARGE CLIP

(@ 5'-0" O.C.)

BARGE CLIP

RAKE START TIE-IN DETAIL

RAKE TIE-IN TRIM

C-11

FLEXABLE MEMBRANE

(NOT BY MCELROY)

RAKE ANGLE

1/4-14 X 1 1/4" HWH TEK2

FASTENER

ROOF STRUCTURAL

MEMBER

3/32" X 3/8" ROLL TAPE

SEALANT (CONT. ALONG

TOP OF PANEL RIB)

BUILDING LINE

(NOT BY MCELROY)

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ 1'-0" O.C.)

*DO NOT FASTEN THRU CLIP*

RAKE TIE-IN TRIM

MIRAGE II PANEL

COUNTER FLASHING

(NOT BY MCELROY)

COUNTER FLASHING SEALANT

(NOT BY MCELROY)

COUNTER FLASHING SEALANT

(NOT BY MCELROY)

COUNTER FLASHING

(NOT BY MCELROY)

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ 1'-0" O.C.)

*DO NOT FASTEN THRU CLIP*

MIRAGE II PANEL

FLEXABLE MEMBRANE

(NOT BY MCELROY)

FASTENER

(NOT BY MCELROY)

1/4-14 X 1 1/4" HWH TEK2

FASTENER

RAKE ANGLE

ROOF STRUCTURAL

MEMBER

BUILDING LINE

(NOT BY MCELROY)

3/32" X 3/8" ROLL TAPE

SEALANT (CONT. ALONG

TOP OF PANEL RIB)

RAKE TIE-IN TRIM

NOTES: 1. Place continuous run of Roll Tape Sealant on top of panel rib.

2. Install Rake Tie-In Trim to panel rib with 1/4-14 x 7/8" Lap Tek ZAC fastener at 1'-0" O.C.

**DO NOT ATTACH TO CLIPS.**

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENERS (2 PER CLIP)

MIRAGE II CLIP

RAKE END TIE-IN DETAIL

C-12

COUNTER FLASHING SEALANT

(NOT BY MCELROY)

COUNTER FLASHING

(NOT BY MCELROY)

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ 1'-0" O.C.)

MIRAGE II PANEL

FLEXABLE MEMBRANE

(NOT BY MCELROY)

FASTENER

(NOT BY MCELROY)

1/4-14 X 1 1/4" HWH TEK2

FASTENER (@ EACH

STRUCTURAL MEMBER)

RAKE ANGLE

ROOF STRUCTURAL

MEMBER

BUILDING LINE

(NOT BY MCELROY)

3/32" X 3/8" ROLL TAPE

SEALANT (CONT. ALONG

TOP OF PANEL RIB)

FIELD CUT CLIP

AS REQUIRED

RAKE TIE-IN TRIM

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER

FLEXABLE MEMBRANE

(NOT BY MCELROY)

RAKE ANGLE

1/4-14 X 1 1/4" HWH TEK2

FASTENER

ROOF STRUCTURAL

MEMBER

3/32" X 3/8" ROLL TAPE

SEALANT (CONT. ALONG

TOP OF PANEL RIB)

BUILDING LINE

(NOT BY MCELROY)

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ 1'-0" O.C.)

RAKE TIE-IN TRIM

MIRAGE II PANEL

COUNTER FLASHING

(NOT BY MCELROY)

COUNTER FLASHING SEALANT

(NOT BY MCELROY)

RAKE TIE-IN TRIM

NOTES: 1. Place continuous run of Roll Tape Sealant on top of panel rib.

2. Install Rake Tie-In Trim to panel rib with 1/4-14 x 7/8" Lap Tek ZAC fastener at 1'-0" O.C.

**DO NOT ATTACH TO CLIPS.**

MIRAGE II CLIP

HIGH SIDE TIE-IN DETAIL

NOTES: 1. Place continuous run of 1" Roll Tape Sealant on panels where Outside Closures will be installed.

2. Install Outside Closures and place a continuous run of 1" Roll Tape along top of Outside Closures.

C-13

3. Install High Side Tie-In Trim and fasten to each panel rib with 1/4-14 x 7/8" Lap Tek ZAC fasteners.

HIGH SIDE TIE-IN TRIM

BUILDING LINE

(NOT BY MCELROY)

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ MAJOR RIBS)

MIRAGE II CLIP

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (2 PER CLIP)

MIRAGE II PANEL

HIGH SIDE

TIE-IN TRIM

PAN-UP PANEL

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ PANEL RIBS)

HIGH SIDE TIE-IN TRIM

MIRAGE II PANEL

ROOF STRUCTURAL

MEMBER

BUILDING LINE

(NOT BY MCELROY)

PAN-UP PANEL

FASTENER

(NOT BY MCELROY)

OUTSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(TOP & BOTTOM)

COUNTER FLASHING

(NOT BY MCELROY)

COUNTER FLASHING

SEALANT

(NOT BY MCELROY)COUNTER FLASHING

(NOT BY MCELROY)

OUTSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(TOP & BOTTOM)

COUNTER FLASHING

SEALANT

(NOT BY MCELROY)

ALTERNATE HIGH

SIDE TIE-IN TRIM

Fasteners must penetrate sealant.

ROOF STRUCTURAL

MEMBER

FLOATING RIDGE DETAIL

C-14

FLOATING RIDGE FLASHING

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ MAJOR RIBS)

MIRAGE II CLIP

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (2 PER CLIP)

MIRAGE II PANEL

FLOATING RIDGE

FLASHING

ROOF STRUCTURAL

MEMBER

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ PANEL RIBS)

FLOATING RIDGE

FLASHING

MIRAGE II PANEL

ROOF STRUCTURAL

MEMBER

OUTSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(TOP & BOTTOM)

OUTSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(TOP & BOTTOM)

PAN-UP PANEL

PAN-UP PANEL

ALTERNATE FLOATING

RIDGE FLASHING

NOTES: 1. Place continuous run of 1" Roll Tape Sealant on panels where Outside Closures will be installed.

2. Install Outside Closures and place a continuous run of 1" Roll Tape along top of Outside Closures.

3. Install Ridge Flashing and fasten to each panel rib with 1/4-14 x 7/8" Lap Tek ZAC fasteners.

Fasteners must penetrate sealant.

FIXED RIDGE DETAIL

C-15

FIXED RIDGE FLASHING

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ MAJOR RIBS)

MIRAGE II CLIP

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (2 PER CLIP)

* MIRAGE II PANEL

FIXED RIDGE

FLASHING

ROOF STRUCTURAL

MEMBER

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ PANEL RIBS)

FIXED RIDGE

FLASHING

MIRAGE II PANEL

ROOF STRUCTURAL

MEMBER

OUTSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(TOP & BOTTOM)

OUTSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(TOP & BOTTOM)

PAN-UP PANEL

PAN-UP PANEL

ALTERNATE FIXED RIDGE FLASHING

NOTES: 1. Place continuous run of 1" Roll Tape Sealant on panels where Outside Closures will be installed.

2. Install Outside Closures and place a continuous run of 1" Roll Tape along top of Outside Closures.

3. Install Ridge Flashing and fasten to each panel rib with 1/4-14 x 7/8" Lap Tek ZAC fasteners.

FLOATING HIP DETAIL

C-16

FLOATING HIP FLASHING

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ MAJOR RIBS)

MIRAGE II CLIP

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (2 PER CLIP)

MIRAGE II PANEL

FLOATING HIP

FLASHING

ROOF STRUCTURAL

MEMBER

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ PANEL RIBS)

FLOATING HIP

FLASHING

MIRAGE II PANEL

ROOF STRUCTURAL

MEMBER

BEVELED OUTSIDE

CLOSURE W/ 1"

ROLL TAPE SEALANT

(TOP & BOTTOM)

OUTSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(TOP & BOTTOM)

PAN-UP PANEL

PAN-UP PANEL

HIP FLASHING

ALTERNATE FLOATING

NOTES: 1. Place continuous run of 1" Roll Tape Sealant on panels where Outside Closures will be installed.

2. Install Outside Closures and place a continuous run of 1" Roll Tape along top of Outside Closures.

3. Install Hip Flashing and fasten to each panel rib with 1/4-14 x 7/8" Lap Tek ZAC fasteners.

FIXED HIP DETAIL

C-17

FIXED HIP FLASHING

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ MAJOR RIBS)

MIRAGE II CLIP

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (2 PER CLIP)

MIRAGE II PANEL

FIXED HIP

FLASHING

ROOF STRUCTURAL

MEMBER

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ PANEL RIBS)

FIXED HIP

FLASHING

MIRAGE II PANEL

ROOF STRUCTURAL

MEMBER

OUTSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(TOP & BOTTOM)

OUTSIDE CLOSURE W/

1" ROLL TAPE SEALANT

(TOP & BOTTOM)

PAN-UP PANEL

PAN-UP PANEL

ALTERNATE FIXED HIP FLASHING

NOTES: 1. Place continuous run of 1" Roll Tape Sealant on panels where Outside Closures will be installed.

2. Install Outside Closures and place a continuous run of 1" Roll Tape along top of Outside Closures.

3. Install Hip Flashing and fasten to each panel rib with 1/4-14 x 7/8" Lap Tek ZAC fasteners.

SIDE LAP DETAIL

C-18

MIRAGE II

PANEL

FACTORY APPLIED

SEAM SEALANT

MIRAGE II

CLIP

PANCAKE HEAD FASTENER

(2 PER CLIP)

MIRAGE II

PANEL

ROOF STRUCTURAL

MEMBER

MIRAGE II

CLIP

FACTORY APPLIED

SEAM SEALANT

#10-16 X 1" TEK2 PANCAKE

HEAD FASTENER (2 PER CLIP)

MIRAGE II

PANEL

BARGE TRIM LAPS

C-19

BARGE CLIP OR

BARGE CLEAT UNDER

STOP END GUTTER

BARGE TRIM

ATTACH TRIM W/

1/4-14 X 7/8" LAP TEK ZAC

FASTENER (@ EACH RIB)

FIELD NOTCH TRIM

AS NEEDED FOR RIBS

STOP END SHEETS

UNDER TRIM

POP RIVET TOPS

TOGETHER AFTER

ASSEMBLY

BARGE TRIM

BARGE CLIP OR

BARGE CLEAT UNDER

_MM159 Mir II Inst Man NwCv 7-14
A1
A2
B1
B2
C1
C2
C3
C4
C5
C6
C7
C8
C9
C10
C11
C12
C13
C14
C15
C16
C17
C18
C19
MM159 Mirage II BkCv 01-23-18