This document is a Standard Form 30 Amendment of Solicitation/Modification of Contract for Solicitation 140P9725Q0025, issued by the National Park Service Alaska Regional Office. The amendment extends the response due date to May 16, 2025, by 5:00 PM Alaska Standard Time, and changes the period of performance to May 18, 2025 - August 16, 2025.

The amendment includes detailed questions and answers regarding a 1,350-gallon fuel tank replacement, specifying technical requirements such as overfill protection, anti-siphon valve, emergency vents, fuel lines, leak detectors, and coating specifications. The tank must conform to specific standards including IFC 5704.2.7-9, NFPA 30 21.4, NFPA 31 7.2, UL 142 (STI F921), or UL 2085, with all fuel storage and piping systems to be installed in accordance with IMC 13. The solicitation will result in a firm fixed-price contract, with the point of contact being Francisco Velasco.

View the file

Other files for this federal contract opportunity

Other files attached to SITK - REPLACE VISITOR CENTER FUEL TANK, newest first.
File Type Posted
Sol_140P9725Q0025_Amd_0001.pdf PDF
Sol_140P9725Q0025.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(x)

140P9725Q0025 x x copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE

RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR

OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

x

PAK

Anchorage AK 99501-2327 240 W. 5th Ave, Room 114 NPS, ARO - Alaska Regional Office

05/07/20250002

13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

12. ACCOUNTING AND APPROPRIATION DATA (If required) is not extended.is extended, Items 8 and 15, and returning

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

FACILITY CODE CODE

10B. DATED (SEE ITEM 13)

10A. MODIFICATION OF CONTRACT/ORDER NO.

9B. DATED (SEE ITEM 11)

9A. AMENDMENT OF SOLICITATION NO.

CODE

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)

7. ADMINISTERED BY (If other than Item 6)CODE 6. ISSUED BY

PAGE OF PAGES

4. REQUISITION/PURCHASE REQ. NO.3. EFFECTIVE DATE2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO. (If applicable)

1. CONTRACT ID CODE

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

04/18/2025

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority) appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

E. IMPORTANT: Contractor is not is required to sign this document and return __________________ copies to the issuing office.

ORDER NO. IN ITEM 10A.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

An award from this RFQ will result in a firm fixed price

52.212-4 (c) Changes

Solicitation 140P9725Q0025 is hereby amended as follows:

1. Solicitation 140P9725Q0025 has been extended. The new response due date is May 16, 2025, by 5:00 PM Alaska Standard Time.

2. The period of performance is changed to 5/18/2025 - 8/16/2025.

3. Questions and Answers are annotated below.

4. POC for this action is Francisco Velasco / Francisco_Velasco@nps.gov

5. All other terms and conditions remain unchanged.

Continued ...

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)

15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED

(Signature of person authorized to sign) (Signature of Contracting Officer)

Francisco Velasco

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

Previous edition unusable

Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .

ITEM NO. SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT

NAME OF OFFEROR OR CONTRACTOR

2 3

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

140P9725Q0025/0002

Questions (Q) and Answers (A):

Q1) Does the overfill protection require a 9095AA w/ drop tube 6¿ off tank bottom?

A1) The ID¿d overfill valve would be appropriate.

Q2) Do you need an anti-siphon valve or 199

Anti-siphon valve?

A2) Yes, a 199 is acceptable and we do require an anti-siphon valve.

Q3) Do you need an 818 Clock gauge?

A3) Yes, an 818 Morrison is industry-standard and would be acceptable.

Q4) Do you need a primary and secondary emergency vent?

A4) Yes.

Q5) Is a Morrison 922 vent alarm acceptable?

A5) Yes.

Q6) Do you need SS Flex fuel lines 18¿ ?

A6) Yes.

Q7) Do you need Vent pipe extending 12¿ above ground?

A7) Yes, we do require a vent pipe that meets code.

Q8) Do you need Uni-strut for piping and fuel lines?

A8) Yes.

Q9) Do you need Interstitial leak detector?

A9) Yes.

Q10) Do you need a Ladder or fill platform?

A10) Yes.

Q11) Do you fill this tank yourself or is it a contract from someone in SITK?

A11) The new tank shall include an integrated ladder to perform periodic tank inspections and maintenance.

Q12) Should the pain not be less that a quality 3

Coat Marine Coating 30 yr corrosion protection?

A12) Yes.

Continued ...

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

Sponsored by GSA

FAR (48 CFR) 53.110

ITEM NO. SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT

NAME OF OFFEROR OR CONTRACTOR

3 3

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

140P9725Q0025/0002

Q13) Do you need a gauge port?

A13) Yes.

Q14) Is the STI F921 & UL 142 the appropriate specs to reference?

A14) Yes, STI F921 & UL 142 are the appropriate specs to reference.

Clarification on Requirements are as the following:

1.The installed tank shall hold 1,350-gallons.

Tanks larger than the specified volume are not acceptable for this requirement.

2.The tank shall be outfitted with appropriate vents, valves, gauges, leak detectors, and inspection ports such that the tank and associated components conform to the following standards. No basis-of-design items are identified for tank components, NPS will accept brands/models that contractors positively identify as meeting the cited code standards per the submittal requirements in Section 7.0, i, 2 of the Statement of Work.

2A. IFC 5704.2.7-9 (NFPA 30 21.4, NFPA 31 7.2)

2B. UL 142 (STI F921) or UL 2085

3.All fuel storage and piping systems will be installed in accordance with IMC 13

Period of Performance: 05/18/2025 to 08/16/2025