(x)
140P9722Q0079 x x
0 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE
RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR
OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
x
PAK
Anchorage AK 99501-2327 240 W. 5th Ave, Room 114 NPS, ARO - Alaska Regional Office
09/13/20220002
13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
12. ACCOUNTING AND APPROPRIATION DATA (If required) is not extended.is extended, Items 8 and 15, and returning
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
FACILITY CODE CODE
10B. DATED (SEE ITEM 13)
10A. MODIFICATION OF CONTRACT/ORDER NO.
9B. DATED (SEE ITEM 11)
9A. AMENDMENT OF SOLICITATION NO.
CODE
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)
7. ADMINISTERED BY (If other than Item 6)CODE 6. ISSUED BY
PAGE OF PAGES
4. REQUISITION/PURCHASE REQ. NO.3. EFFECTIVE DATE2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO. (If applicable)
1. CONTRACT ID CODE
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
09/13/2022
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority) appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
E. IMPORTANT: Contractor is not is required to sign this document and return __________________ copies to the issuing office.
ORDER NO. IN ITEM 10A.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
REPLACE PUMPS AT WATER AND WASTEWATER TREATMENT FACILITIES
This acquisition is set-aside for small businesses, NAICS 333914, Size Standard 750 employees.
Quotes to be electronically submitted via email to darcy_skinner@nps.gov.
Shipping is FOB Destination to Denali National Park, Mile post 237 Parks Highway, Denali
Park, AK 99755.
PURPOSE OF AMENDMENT: Post questions and answers
Continued ...
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)
15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED
(Signature of person authorized to sign) (Signature of Contracting Officer)
Darcy Skinner
STANDARD FORM 30 (REV. 11/2016)
Prescribed by GSA FAR (48 CFR) 53.243
Previous edition unusable
Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .
ITEM NO. SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
NAME OF OFFEROR OR CONTRACTOR
2 4
CONTINUATION SHEET
REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF
(A) (B) (C) (D) (E) (F)
140P9722Q0079/0002
CHANGE IN CLOSING DATE: The closing date remains
September 21, 2022 at 3 PM Alaska time.
This is a brand-name or equal requirement. Need not quote all items. Per FAR 52.211-6, Brand Name or Equal, equipment from other manufacturers will be considered.
To submit a quote, return the following:
- SF-18 with pricing by Line Item
- Product specifications, drawing and/or brochure with sufficient information to show it meets requirements.
- Include estimated delivery date(s).
- Offeror Representations & Certifications if different from or not completed in SAM (See
52.212-3).
This will be a firm-fixed price best value award based on price, delivery date(s), and conformance with specifications. The Government reserves the right to to make multiple awards or to award only certain Line Items.
NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)
Sponsored by GSA
FAR (48 CFR) 53.110
140P9722Q0079 Amendment 0002 Q&A
QUESTION: My vendor had the following questions pertaining to item number 00030 “Submersible Pump ITT, model FLYGT 3085”:
1: What is the required Duty Point for the pump? GPM @ TDH – Ex: 250 GPM @ 20’ Total Dynamic Head
2: If this is for a replacement, can pictures of the existing pump tags be provided?
3: Can a complete model number be provided if question 1 or 2 cannot be answered? – Ex:
3085.060-0928
A: Model # NP 3085.190-MT
QUESTION - Could you please provide some specifications of the line item 1 required- solar pump (qty 2)?
Supply to pump 1 x 90 - 240 V –10%/+6%, 50/60 Hz. 30 - 300 VDC.
Run-up time Depending on power source.
Start/stop No limitation to the number of starts/stops per hour.
Enclosure class IP 68
140P9722Q0079 Amendment 0002 Q&A
Motor protection Built into the pump. Protection against: - Dry running by means of an external water level electrode. - Overvoltage and under voltage. - Overload. - Over temperature.
Sound pressure level
The sound pressure level is lower than the limiting values stated in the EEC Machinery Directive.
Radio noise SQF comply with EMC Directive 89/336/EEC. Approved according to EN 50081-1 and 50082-2.
Reset function SQF can be reset via CU 200 or by disconnecting the power from the power supply in 1 minute.
Power factor PF = 1.
Operation via generator Voltage: 230 VAC, –10%/+6.;
It is recommended that the generator output must be equal to the motor input power P1 [kW] plus 50%. Minimum: P1 [kW] plus 50%.
If the pump is connected to an electrical installation where an earth-leakage circuit breaker
Earth leakage circuit breaker
(ELCB) is used as an additional protection, this circuit breaker must trip out when earth fault currents with DC content (pulsating DC) occur.
Borehole diameter
SQF 0.6, SQ 1.2, SQF 2.5: Minimum: 76 mm. SQF 5A, SQF 8A, SQF 14A: Minimum: 104 mm.
Installation depth
Min.: The pump must be totally submerged in the pumped liquid.
Max.: 150 m below the static water table (15 bar).
Strainer Holes of the strainer:
SQF 0.6, SQF 1.2, SQF 2.5: ø2.3 mm. SQF 5A: ø2.5 mm. SQF 8A, SQF 14A: 4 mm x 20 mm.
Pumped liquids pH 5 to 9. Sand content up to 50 g/m³.
Marking CE
QUESTION: I have another question to pose for you on the Line 00050 LMI pump. I spoke with the factory rep and he said that the AD851’s are a very long lead time of 12 weeks or more because the A stands for 4-20 mA input.
A: Need to stay with the requested pump, even though the lead time may be longer than the others.
QUESTION: You’ve asked for a Emerson model Q2G2-1 and there is not any description of what it is. Emerson website doesn’t recognize that number when I conducted a search.
A: the model # on the Emerson pump should be NP 3085-SH