This is a Request for Information (RFI) Answers document for National Park Service solicitation 140P8526Q0012, which addresses contractor questions regarding installation of a residential fire sprinkler system at a property in Yosemite National Park.
The RFI responses clarify key scope and site condition items for bidders. Notable confirmations include: drawings and as-builts must be submitted to NPS; attic access is available; NPS will provide power to the alarm bell and remove the existing pressure reducer valve; a standard wet system (rather than antifreeze) is preferred to prevent freezing; and NPS or its contractor will install the underground tee and stub-out connection in the crawlspace, with the fire sprinkler contractor's scope beginning at the provided connection point. NPS is also providing layouts from the Building and Grounds Supervisor for ceiling fan installation and HVAC register placement. The solicitation is set-aside for Small Business concerns only (NAICS 238220, size standard $19.0 million), with construction value less than $25,000. Proposals are due February 10, 2026 at 12:00 PM PST via email to Brian Roppolo at brian_roppolo@nps.gov. Buy American requirements (FAR 52.225-10) apply to this procurement.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
140P8526Q0012 Amendment 0003 RFI Answers V.2.
Q. Will drawing be required to be submitted to the local authorities for permit?
A. Yes, Drawings/As Builts are required to be submitted to NPS.
Q. Can you provide me with the exact address so I can call the city for the water flow information.
A. The address is provided in the SOW under the Location Paragraph.
Q. Will attic access be provided A. Yes there is attic access Q. Will NPS run power to the bell of the alarm?
A. Yes Q. What are the Buy American requirements, can parts come from another country?
A. The Buy American provision at 52.225-10 applies Q. When does the solicitation close/when do we submit bids?
A. 10 February22026 at 12:00 PST.
Q. Can the NPS provide a layout for the ceiling fans to be installed?
A. Yes, waiting on the layout from B&G Supervisor Q. Can the NPS provide a layout of where the HVAC registers will be placed?
A. Yes, waiting on the layout from B&G Supervisor Q. Will the NPS remove the existing pressure reducer valve?
A. Yes Q. Is there a Water Riser coming to the property that supplies the Fire Sprinkler System with water A. There is water plumbed to the residence.
Q. Would you prefer an antifreeze system versus a standard wet system to prevent possible freezing of piping in the attic?
A. Standard wet system.
Q. Please confirm that the underground tee and stub-out connection will be installed by NPS (or its contractor) A. Confirmed Q. Please confirm that the fire sprinkler contractor’s scope will begin at the provided connection point within the crawlspace, with no underground piping included in the scope.
A. Confirmed.