ATTACHMENT 4 ‐ ITM Schedule
RFQ No. 140P8419Q0073
Amendment 2
Wet and Dry Pipe Fire Sprinkler System inspection, testing, maintenance shall be performed in accordance with this scope of work and NFPA 25 (2017). This listing of tasks is not all-inclusive. It provides additional details to supplement the Statement of Work.
Building/Facility No./Name
Sq Ft System Type
DCVA
Annual ITM Required for 2019 (base year)
3-Year Full Trip Flow
Test
5-Year Gauges
10-Year rep.
sampling (Survey)
10-Year rep.
sampling (remove & replace)
Number of
Samples
72 (Comfort Stn) 595 Dry P Yes 2019 & 2022 2019 2019 2020 1
66 (Kiser Studio) 1,046 Dry P Yes 2019 & 2022 2019 2019 2020 1
1 (Sager Bldg) 6,552 Dry n/a Yes 2019 & 2022 2019 2019 2020 4
3 (Canfield Bldg) 5,971 Dry P Yes 2019 & 2022 2019 2019 2020 4
4 (Warehouse) 3,549 Dry P Yes 2019 & 2022 2019 2019 2020 2
5 (Rat Hall) 4,606 Dry P Yes 2019 & 2022 2019 2019 2020 3
222 (Community Ctr) 5,920 Dry P Yes 2019 & 2022 2019 2019 2020 4
19 (Sci. & Learning) 2,256 Dry P No 2022 n/a 2019 2020 1
20 (Dorm) 1,276 Dry P No 2022 n/a 2019 2020 1
31 (Stone House) 876 Dry P No 2022 n/a 2019 2020 1
32 (Stone House) 876 Dry P No 2022 n/a 2019 2020 1
116 (Comm. House) 1,575 Wet P Yes n/a 2019 n/a n/a n/a
14 (Maint. Bldg) Boiler Rm & Bay 11
2,500 Wet P Yes n/a 2019 n/a n/a n/a
Mazama Sewage Lagoons n/a n/a P n/a n/a n/a n/a n/a n/a