This is a Questions and Answers document for federal contract opportunity 140P8226Q0033 PUHO Fiber Optic and Network Modernization. The document addresses clarifications on infrastructure requirements across multiple buildings at what appears to be a Department of Interior (DOI) facility.

The first Q&A confirms fiber optic cable run distances, specifying that the fiber run between the Resource Management (RM) Building and Facilities Management (FM) Building measures approximately 1,247.77 feet according to the Statement of Work page 20, paragraph A.4.2. The FM Building to Bookstore Extension requires no fiber replacement; instead, the Bookstore Extension connects to the bookstore's backroom switch via approximately 150 feet of cabling, with a wireless access point providing DOI Wi-Fi coverage to an amphitheater area. The second Q&A details Cat6a cable requirements totaling eight drops across both buildings: RM Building requires 4 Cat6a cables in raceway running from the switch rack in the back room to the front room serving four different workstations (runs less than 50 feet), plus two additional drops in the back switch room to a single workstation (less than 25 feet); FM Building requires two Cat6a drops in raceway to the front office for the Facilities Chief (less than 50 feet from the adjacent switch rack location) and two drops to a workstation in the same room as the switch rack (less than 25 feet).

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Q&A for 140P8226Q0033 PUHO Fiber Optic and Network Modernization

Q: Please confirm the approximate cable run distances between: Resource Management (RM) Building and Facilities Management (FM) Building; Facilities Management (FM) Building and Bookstore Extension.

A: The estimated fiber cable run distance from the RM Building and FM Buildings is listed in the SOW, page 20, paragraph A.4.2.

According to the SOW, there should not be a replacement for fiber between the FM Building and the Bookstore Extension. The Bookstore Extension would be connected to the backroom switch of the bookstore at about 150 ft. where a wireless access point would provide DOI Wi-Fi to the amphitheater.

Q: Can you provide the number of Cat6a drops? Is this 1 run and does it follow same route as Fiber referenced in sec 1.2 and 6.2.2, section 6.2.3?

A: For RM Building, that would be 4 cat 6a cables in raceway from the switch rack in the back room to the front room going to 4 di erent workstations less than 50 foot run (two workstation areas will have two cables). In the back switch room, two drops in raceway to a single workstation less than 25 feet.

For FM Building, two to front o ice (Facil Chief) in raceway from adjacent room where switch rack will be, less than 50 feet. And Two drops to workstation in the same room as the switch rack in raceway, less than 25 feet.

File details come from the government source that posted it. Updated .