This document appears to be a set of contractor questions and the National Park Service's (NPS) responses regarding a federal contract opportunity for JEFF - AHU Balancing Services (Solicitation Number: 140P6024Q0072).

The key details are:

  • The contractor requested existing as-built drawings for the mechanical room, boilers, pumps, ductwork, HVAC, and air devices so they can provide a proper count of the items to be checked per the scope of work. NPS confirmed these drawings have been uploaded to SAM.gov.
  • The contractor inquired about the location of the Air Handling Unit (AHU), and NPS stated it is located in the grounds maintenance complex's mechanical room on the lower level.
  • NPS confirmed that TABB certification is acceptable for this contract opportunity.

View the file

Other files for this federal contract opportunity

Other files attached to JEFF - AHU Balancing Services, newest first.
File Type Posted
A21_MISC_(Grounds_Building_-_Mechanical_as_builts)_0001.pdf PDF
Sol_140P6024Q0072_Amd_0001.pdf PDF
Sol_140P6024Q0072.pdf PDF
A04_SOW.docx DOCX document
B03_DOL_Wage_Determination.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Contractor’s Questions – NPS Response

1. Scope of Work document. It asks to check Pumps, VAVS existing diffusers duct work dampers and other items. Can you send me the existing As Built Drawings of the mechanical room, boiler pumps and also the duct work with VAVS and air devices so we may get a count on the items you are requesting us the check. Yes, uploaded to SAM.gov

2. Is the AHU in the large equipment room on the lower level or is this one in the “Grounds Building”? It is at the ground's maintenance complex inside a large mechanical room on the lower level of the complex.

3. Is TABB Certified acceptable. Yes.