This solicitation seeks proposals for the stabilization and rehabilitation of the historic Peaceful Valley Ranch complex within Theodore Roosevelt National Park. Offerors must submit proposals by October 8, 2019. The work includes stabilization of three structures with exterior and interior improvements and accessible site improvements. The Department of the Interior National Park Service is the contracting agency. Amendment 08 provides answers to questions from offerors but does not otherwise amend the required scope of work.
Drawings
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT LOCATION
PROJECT LOCATION
OR
OR
Design (Title I)
Prepared in Accordance with Preliminary by Preliminary Design (Title I)
Construction Drawing Not Preceded
Approved by Superintendent on
Variance from Preliminary Design (Title I)
Project Manager
Drawing No.
Date
Date
QUALITY DESIGN CERTIFICATIONSheetMark REVISION Date Initial
STATEREGION COUNTY
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF DRAWING DRAWING NO.
DEPARTMENT OF THE INTERIOR
UNITED STATES
NATIONAL PARK SERVICE
DENVER SERVICE CENTER
PMIS
GOLDEN, CO 80401
ANDERSON HALLAS ARCHITECTS, PC
ARCHITECT
PMIS/PKG NO.
SHEET
OF8/
5/
2:
:0
P
M C
:\A ut oD es k S av e
Lo ca tio ns
\R ev it\
T
H R
O R an ch
H ou se _s us ie ha ck er an da rc h.
co m
.r vt
228216
228216
138248
1 120
NORTH DAKOTA
MIDWEST BILLINGS NORTH DAKOTA
THEODORE ROOSEVELT NATIONAL PARK
STABILIZE HISTORIC PEACEFUL
VALLEY RANCH
PEACEFUL VALLEY RANCH
FINAL CD SET
THEODORE ROOSEVELT NATIONAL PARK
susiehacker Snapshot
BID OPTIONS:
BASE BID: STABILIZATION OF ALL THREE STRUCTURES WITH EXTERIOR AND INTERIOR IMPROVEMENTS
AND ACCESSIBLE SITE IMPROVEMENTS. (EXCEPTIONS ARE NOTED IN BID OPTIONS BELOW)
BID OPTION #1: CUSTOM/REMOVEABLE ABAAS COMPLIANT RAMP FOR RANCH HOUSE OFFICE 104.
BID OPTION #2: NOT USED.
BID OPTION #3: INSTALL NEW CONCRETE SLAB IN THE BARN
BID OPTION #4: REHABILITATE WINDOWS IN THE BARN
BID OPTION #5: INSTALL CONCRETE WALKWAYS INSTEAD OF CRUSHED ROCK WALKWAYS
PRESERVATION TREATMENT:
WITH BUILDINGS CONSTRUCTED BETWEEN 1885 – 1920, PEACEFUL VALLEY RANCH IS ONE OF
THE FEW EXTANT RANCHES THAT TELLS THE STORY OF OPEN RANGE RANCHING IN
WESTERN NORTH DAKOTA. LISTED ON THE NATIONAL REGISTER OF HISTORIC PLACES, IT IS
COMPRISED OF THREE HISTORIC STRUCTURES (RANCH HOUSE, BUNKHOUSE AND BARN) AND
NUMEROUS NON-HISTORIC OUTBUILDINGS, STRUCTURES AND CORRALS.
HISTORICALLY, THE RANCH HOUSE AND BUNKHOUSE HOUSED RANCH OPERATORS AND
STAFF WHILE THE BARN SUPPORTED LIVESTOCK ACTIVITIES. MOST RECENTLY, THE
BUILDINGS SERVED SIMILAR PURPOSES FOR THE TRAIL RIDE CONCESSIONER.
A REHABILITATION TREATMENT APPROACH WAS TAKEN FOR ALL THREE BUILDINGS THAT
WILL RETAIN EXISTING HISTORIC FABRIC TO THE EXTENT POSSIBLE. THIS PHASE OF THE
PROJECT IS FOCUSED ON STABILIZING THE STRUCTURES, WHILE MAKING MODIFICATIONS
FOR CODE AND ABAAS. DISCUSSIONS ABOUT NEW USES FOR THESE BUILDINGS ARE
ONGOING. ASSUMPTIONS BASED ON THE MOST LIKELY FUTURE USES WERE MADE TO
INFORM CODE AND ABAAS WORK IN THIS PHASE. IT HAS BEEN DETERMINED THAT THE FINAL
USE WILL NOT ALLOW OVERNIGHTING IN ANY OF THE THREE BUILDINGS. THIS PROJECT
ASSUMED STAFF USE IN THE RANCH HOUSE (BUSINESS), EDUCATIONAL USE IN THE
BUNKHOUSE AND UNTEMPERED EDUCATIONAL USE IN THE BARN.
GENERAL NOTES
1. DO NOT SCALE DRAWINGS.
2. ALL WORK TO BE PERFORMED TO APPLICABLE BUILDING CODES.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FAMILIARIZING HIMSELF OR HERSELF WITH THE
CONTRACT DOCUMENTS, VERIFYING FIELD CONDITIONS AND DIMENSIONS, AND CONFIRMING THAT
THE WORK MAY BE ACCOMPLISHED AS SHOWN PRIOR TO PROCEEDING WITH CONSTRUCTION.
4. SHOULD THERE BE ANY QUESTIONS CONCERNING THE CONTRACT DOCUMENTS, EXISTING
CONDITIONS AND/OR DESIGN INTENT, THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING A CLARIFICATION FROM THE CONTRACTING OFFICER PRIOR TO PROCEEDING WITH THE WORK OR
RELATED WORK IN QUESTION.
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FAMILIARIZING HIMSELF OR HERSELF WITH THE
PROJECT SCOPE OF WORK, SCHEDULE AND DEADLINES. UPON NOTICE TO PROCEED, THE
CONTRACTOR SHALL BE RESPONSIBLE FOR ADVISING THE CONTRACTING OFFICER OF ALL ITEMS
REQUIRING A LONG LEAD TIME THAT WILL AFFECT THE SCHEDULE AND SHALL, UPON REQUEST
FROM THE CONTRACTING OFFICER, SUBMIT ORDER CONFIRMATIONS AND DELIVERY DATES FOR
THE ITEMS IN QUESTION TO THE CONTRACTING OFFICER.
6. EXISTING WORK WHICH IS TO REMAIN BUT THAT IS DAMAGED OR AFFECTED BY THE WORK, SHALL
BE REPAIRED AND/OR RECONDITIONED TO MATCH AND BLEND WITH ALL NEW WORK.
7. INSTALL ALL MANUFACTURED ITEMS, MATERIALS AND EQUIPMENT IN STRICT ACCORDANCE WITH
THE MANUFACTURERS' RECOMMENDED SPECIFICATIONS, EXCEPT WHERE THE CONTRACT
DOCUMENTS ARE MORE STRINGENT. ANY MISCELLANEOUS ITEMS OR MATERIALS NOT
SPECIFICALLY NOTED BUT REQUIRED FOR PROPER INSTALLATION SHALL BE FURNISHED AND
INSTALLED BY THE CONTRACTOR. THE CONTRACTOR SHALL FURNISH TO THE OWNER ALL
WARRANTIES AND GUARANTEES REQUIRED AT THE CONCLUSION OF THE PROJECT.
8. CONTRACTOR IS TO RESTORE THE LANDSCAPED AREAS TO PRE-CONSTRUCTION CONDITIONS
U.O.N. WHEN THE WORK IS COMPLETE.
9. ALL WORK SHALL CONFORM TO THE SECRETARY OF THE INTERIOR'S 'STANDARDS FOR THE
REHABILITATION OF HISTORIC BUILDINGS'.
SEPTIC SYSTEM
THE EXISTING SEPTIC SYSTEM WAS REPORTEDLY INSTALLED IN THE 1980S AND SERVED A RESIDENTIAL USE FOR THE SITE’S CONCESSIONER UNTIL THE CONCESSIONER CLOSED OPERATIONS IN 2015. SINCE THEN, THERE’S BEEN LITTLE TO NO USE OF THE SYSTEM. A VAULT TOILET WAS INSTALLED ON THE SITE AT SOME POINT AND IS CURRENTLY IN USE FOR SITE ACTIVITIES – BOTH FOR VISITORS AND STAFF. AS PART OF THIS PROJECT, A SEPTIC SYSTEM DESIGNER CONFIRMED THAT THE EXISTING SEPTIC SYSTEM WILL FUNCTION FOR ITS ORIGINALLY-INTENDED USE FOR AT LEAST SEVERAL YEARS AND THAT THERE APPEARS TO BE VERY GOOD SOIL FOR INFILTRATION. ULTIMATELY, THE SEPTIC SYSTEM WILL NEED TO BE REPLACED. THIS PROJECT IS A “STABILIZATION PROJECT” AND THE FINAL USE OF THE BUILDINGS HAS NOT BEEN DETERMINED. FUTURE PHASES WILL NEED TO ADDRESS SEPTIC SYSTEM UPGRADE OR REPLACEMENT, SOONER VS. LATER IF PROPOSED USE INCREASES FROM THE HISTORIC USE. UTILIZATION OF THE EXISTING SEPTIC SYSTEM SHOULD BE LIMITED ACCORDINGLY, UNTIL THE SEPTIC SYSTEM IS REPLACED OR EXPANDED.
FIRE SUPPRESSION MEMO
DISCUSSIONS REGARDING INSTALLATION OF FIRE SUPPRESSION AT THE BUILDINGS WERE PART OF EARLY PROJECT PLANNING BY THE NPS AND WERE FURTHER STUDIED BY THE DESIGN TEAM. AFTER
REVIEWING ALL THE REQUIREMENTS AND ASSOCIATED CHALLENGES, THE NPS DECIDED NOT TO
INSTALL A FIRE SUPPRESSION SYSTEM.
PER INTERNATIONAL BUILDING CODE SECTION 903 (IBC, 2015), AN AUTOMATIC FIRE SPRINKLER SYSTEM
IS NOT REQUIRED FOR GROUP B OCCUPANCIES WITH AT LEAST ONE EXTERIOR WALL OPENING
LOCATED WITHIN 50 LINEAR FEET ON ONE SIDE AND OPENINGS SPACED NO MORE THAN 50 FEET APART.
SIMILARLY, AN AUTOMATIC FIRE SPRINKLER SYSTEM IS NOT REQUIRED FOR GROUP E OCCUPANCIES
LESS THAN 12,000 SQUARE FEET WITH EXTERIOR EXIT DOORS AT GROUND LEVEL. ALL THREE
BUILDINGS MEET THESE REQUIREMENTS, THEREFORE AN AUTOMATIC FIRE SPRINKLER SYSTEM IS NOT REQUIRED BY THE IBC. DON BOUCHER (NPS), MIDWEST REGION STRUCTURAL FIRE MANAGER (AHJ) STATED THAT, ASSUMING THERE IS NO RESIDENTIAL USE IN THE BUILDINGS, HE ACCEPTED THE DESIGN
TEAM'S RECOMMENDATION NOT TO INSTALL AUTOMATIC FIRE SUPPRESSION SYSTEMS IN THE
BUILDINGS (PER EMAIL TO NPS DENVER SERVICE CENTER PROJECT MANAGER, DENNIS BROOKIE ON 2/27/2018).
NPS DIRECTOR’S ORDER 58 REQUIRES CONSIDERATION OF FIRE SUPPRESSION OF STRUCTURAL FIRES “TO PREVENT LOSS OF HUMAN LIFE AND MINIMIZE DAMAGE TO HISTORIC RESOURCES.” HOWEVER, IT
ACKNOWLEDGES THAT WHEN THESE REQUIREMENTS WOULD REQUIRE WORK THAT WOULD DAMAGE
THE HISTORIC CHARACTER AND INTEGRITY OF THE BUILDING THEN OTHER CHANGES CAN BE MADE IN
LIEU OF ALTERING THE BUILDING AND AN ALTERNATE PLAN SHOULD BE DEVELOPED BASED ON
RECOMMENDATIONS FROM AN INTERDISCIPLINARY TEAM.
INSTALLATION OF A FIRE SUPPRESSION SYSTEM IN THE BUILDINGS AT PEACEFUL VALLEY RANCH
WOULD REQUIRE SIGNIFICANT WORK WITHIN THE BUILDINGS AND WOULD DAMAGE HISTORIC
FINISHES. ADDITIONALLY, THERE ARE A NUMBER OF CHALLENGES WHICH WOULD HAVE TO BE
ADDRESSED FOR THIS INSTALLATION. THE BUILDINGS ARE NOT CONNECTED TO A CITY WATER
SOURCE, SO A METHOD FOR PROVIDING WATER FOR A SUPPRESSION SYSTEM WOULD NEED TO BE DEVELOPED. THE WELL HOUSE IS AN EXISTING BUILDING THAT SUPPLIES DOMESTIC COLD WATER TO
THE RANCH HOUSE AND BUNKHOUSE. THE BUILDING IS UN-HEATED AND HAS NON-FIRE RATED
WALLS. WATER SUPPLY IS FROM A FRESH WATER WELL AND NFPA 13 DOES NOT CONSIDER A WELL AN ACCEPTABLE WATER SUPPLY SOURCE FOR AUTOMATIC FIRE SPRINKLER SYSTEMS. IT COULD BE USED HOWEVER TO FILL A DEDICATED FIRE WATER TANK ON SITE, WHICH WOULD NEED TO BE DESIGNED TO ADDRESS FREEZE CONCERNS IN THE WINTER. WHILE IT IS ANTICIPATED THAT THE RANCH HOUSE MAY SOME DAY BE USED YEAR ROUND, THE BARN WILL BE UNTEMPERED AND THE BUNKHOUSE MAY ALSO BE WINTERIZED. THIS PROVIDES AN ADDITIONAL CHALLENGE OF NEEDING TO PROVIDE FREEZE PROTECTION FOR THE SUPPRESSION SYSTEM IN THE WINTER. FIRE PROTECTION SYSTEMS THAT ARE USED IN FREEZE PRONE AREAS WOULD TYPICALLY BE A DRY PIPE SYSTEM, HOWEVER THE DRY PIPE SYSTEM REQUIRES A WET PIPE SUPPLY CONNECTION WHICH IS KEPT FROM FREEZING AND REQUIRES WEEKLY MAINTENANCE DURING WINTER MONTHS. THIS WOULD DEFEAT THE IDEA OF WINTERIZING THE BUILDINGS, CREATE A MAINTENANCE CHALLENGE AND THE POSSIBILITY OF PIPE DAMAGE ANNUALLY.
AFTER REVIEWING RECOMMENDATIONS IN THE 2014 HSR, DISCUSSIONS WITH DON BOUCHER AND CHALLENGES RELATED TO INSTALLING A SUPPRESSION SYSTEM, THE DESIGN TEAM RECOMMENDED NOT INSTALLING A SYSTEM. INSTEAD, THE RECOMMENDATION WAS TO PROVIDE A FIRE DETECTION SYSTEM AND PLACE FIRE EXTINGUISHERS IN EACH ROOM FOR EACH BUILDING. THIS APPROACH WAS APPROVED BY THE PARK AND WILL BE INTEGRATED INTO THE PARK’S FIRE MANAGEMENT PLAN.
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF8/
5/
2:
:0
P
M C
:\A ut oD es k S av e
Lo ca tio ns
\R ev it\
T
H R
O R an ch
H ou se _s us ie ha ck er an da rc h.
co m
.r vt
G0.0
NAA
THEODORE ROOSEVELT NATIONAL PARK
PEACEFUL VALLEY RANCH
138248
228216
CN
KAC
08/06/2019 2 120
PRESERVATION
TREATMENT NOTES
MATERIAL LEGEND
PLYWOOD
FINISH WOOD
GWB
CONCRETE
BATT INSULATION
STEEL
EARTH
FOAM INSULATION
KEY NOTE
XXX DOOR TAG
NORTH ARROW
XXX
ROOM
ROOM TAG
EXTERIOR
ELEVATION
TAG
INTERIOR
ELEVATION
TAG
X
A5.0
SECTION TAG
SYMBOLS
X WALL TAG
THRESHOLD
X
B L D G
N O R T H
A4.0
X
A8.0
X
X
X
X
X WINDOW TAG
TD
DETAIL CALLOUT
X
A5.3
DRAWING INDEX:
DISCIPLINE SHEET SHEET NAME DISCIPLINE SHEET SHEET NAME
OC ON CENTER
OD OUTSIDE DIAMETER
OH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OSB ORIENTED STRAND BOARD
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLUMB PLUMBING
PT PAINT
PTD PAINTED
PWD PLYWOOD
QT QUARRY TILE
RAD RADIUS
RB RUBBER BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFER TO or REFERENCE
REINF REINFORCED
RELOC RELOCATE(D)
REQ REQUIRED
REV REVISE, REVISED or
REVISION
RM ROOM
RO ROUGH OPENING
RS ROUGH SAWN
(S) SEALANT
S SOUTH
SCHED SCHEDULE
SF SQUARE FEET
SHTG SHEATHING
SIM SIMILAR
SOG SLAB ON GRADE
SPEC SPECIFICATION(S)
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STL STEEL
STN STAIN
STRUC STRUCTURE or
STRUCTURAL
(T) TEMPERED
T&G TONGUE AND GROOVE
T.O. TOP OF
TD THRESHOLD
TYP TYPICAL
UON UNLESS OTHERWISE
NOTED
VB VAPOR BARRIER
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VIN VINYL
VTR VENT THROUGH ROOF
W WEST
W/ WITH
W/O WITHOUT
WD WOOD
WIN WINDOW
EXT EXTERIOR
FACP FIRE ALARM CONTROL
PANEL
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER
CABINET
FIN FINISH(ED)
FIXT FIXTURE
FLR FLOOR(ING)
FO FACE OF
FP FIRE PROTECTION
FRP FIBERGLASS REINFORCED
PANEL(ING)
FT FEET
FTG FOOTING
FURR FURRING
GA GAUGE OR GYPSUM
ASSOCIATION
GALV GLAVANIZED
GC GENERAL CONTRACTOR
GD GRADE
GL GLASS or GLAZING
GND GROUND
GWB GYPSUM WALLBOARD
HM HOLLOW METAL
HAZMAT HAZARDOUS MATERIAL
HDR HEADER
HDW HARDWARE
HORIZ HORIZONTAL
HT HEIGHT
HVAC HEATING, VENTILATION and
AIR CONDITIONING
IBC INTERNATIONAL BUILDING
CODE
ID INSIDE DIAMETER
INFO INFORMATION
INS INSULATION or INSULATED
INT INTERIOR
JT JOINT
LAV LAVATORY
LIN LINOLEUM
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL
and PLUMBING
MFG MANUFACTURING
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MTD MOUNTED
MTL METAL
<N> NEW
N NORTH
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO. NUMBER
NOM NOMINAL
NTS NOT TO SCALE
# POUND(S) or NUMBER
& AND
< ANGLE
@ AT
A/V AUDIO VISUAL
ABA AMERICAN BARRIERS ACT
ABV ABOVE
ACM ASBESTOS CONTAINING
MATERIAL
ACT ACCOUSTICAL CEILING TILE
ADD ADDENDUM
ADJ ADJACENT or ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
APPROX APPROXIMATE(LY)
ARCH ARCHITECTURAL
ASPH ASPHALT
B.O. BOTTOM OF
BLDG BUILDING
BLKG BLOCKING
BR BACKER ROD
BTWN BETWEEN
C.O. CONTRACTING OFFICER
CAB CABINET
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CORR CORRIDOR
CPT CARPET
CT CERAMIC TILE
CTBB CEMENTITIOUS TILE
BACKER BOARD
CTR CENTER
DBL DOUBLE
DEMO DEMOLITION
DET DETAIL
DF DRINKING FOUNTAIN
DIAM DIAMETER
DIM DIMENSION
DN DOWN
DS DOWNSPOUT
<E> EXISTING
E EAST
EA EACH
EG FOR EXAMPLE
ELEC ELECTRICAL
ELEV ELEVATION
EMER EMERGENCY
ENGR ENGINEER
EQ EQUAL
EQP EQUIPMENT
ETR EXISTING TO REMAIN
ABBREVIATIONS
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF8/
5/
2:
:0
P
M C
:\A ut oD es k S av e
Lo ca tio ns
\R ev it\
T
H R
O R an ch
H ou se _s us ie ha ck er an da rc h.
co m
.r vt
G0.1
NAA
THEODORE ROOSEVELT NATIONAL PARK
PEACEFUL VALLEY RANCH
138248
228216
CN
KAC
08/06/2019 3 120
GENERAL
INFORMATION &
INDEX
SITE
15 C1.0 TESC AND DEMOLITION PLAN
16 C2.0 SITE PLAN
17 C3.0 GRADING PLAN
18 C4.0 DETAILS
19 ES1 ELECTRICAL SITE DEMOLITION PLAN
20 ES2 ELECTRICAL SITE PLAN
21 ES3 ELECTRICAL SITE SIGNAL PLAN
22 ES4 ELECTRICAL ONE-LINE DIAGRAMS
23 ES5 LIGHTNING PROTECTION DETAILS
24 ES6 ELECTRICAL AND FIRE ALARM DETAILS
25 ES7 ELECTRICAL DETAILS & DIAGRAMS
RANCH HOUSE
26 ADR1.1 RANCH HOUSE 1ST & 2ND DEMO PLAN
27 ADR2.0 RANCH HOUSE ROOF DEMO PLAN
28 ADR2.1 RANCH HOUSE 1ST & 2ND FLOOR DEMO RCP
29 ADR4.0 RANCH HOUSE DEMO ELEVATIONS
30 AR1.1 RANCH HOUSE 1ST & 2ND FLOOR PLANS
31 AR1.2 RANCH HOUSE ROOF PLAN
32 AR2.1 RANCH HOUSE 1ST & 2ND REFLECTED CEILING PLAN
33 AR3.1 RANCH HOUSE DOOR SCHEDULE
34 AR3.2 RANCH HOUSE DOOR DETAILS
35 AR3.3 RANCH HOUSE DOOR DETAILS
36 AR3.4 RANCH HOUSE WINDOW AND FRAME SCHEDULE
37 AR3.5 RANCH HOUSE FINISH PLAN AND SCHEDULE
38 AR4.1 RANCH HOUSE ELEVATIONS
39 AR5.1 RANCH HOUSE BUILDING SECTION
40 AR6.1 RANCH HOUSE RAMP PLANS & SECTIONS
41 AR7.1 RANCH HOUSE ENLARGED PLAN - RESTROOM 106
42 AR8.1 RANCH HOUSE INTERIOR ELEVATIONS
43 AR9.1 RANCH HOUSE DETAILS
44 AR9.2 RANCH HOUSE PHOTO SHEETS
45 SR1.1 RANCH HOUSE FOUNDATION PLAN
46 SR1.2 RANCH HOUSE ROOF FRAMING PLAN
47 SR1.3 RANCH HOUSE DETAILS
48 SR1.4 RANCH HOUSE DETAILS
49 MR0.1 RANCH HOUSE MECHANICAL ABBREVIATIONS AND LEGENDS
50 MDR2.1 RANCH HOUSE HVAC 1ST FLOOR DEMO PLAN
51 MDR3.1 RANCH HOUSE WATER SUPPLY 1ST AND 2ND FLOOR DEMO PLAN
52 MDR4.1 RANCH HOUSE WASTE AND VENT 1ST AND 2ND FLOOR DEMO PLAN
53 MR2.1 RANCH HOUSE HVAC 1ST FLOOR PLAN
54 MR3.1 RANCH HOUSE WATER SUPPLY 1ST FLOOR PLAN
55 MR4.1 RANCH HOUSE WASTE AND VENT 1ST FLOOR PLAN
56 MR5.1 RANCH HOUSE MECHANICAL DETAILS / DIAGRAMS
57 MR6.1 RANCH HOUSE MECHANICAL SCHEDULES
58 ER0.1 RANCH HOUSE ELECTRICAL ABBREVIATIONS AND LEGENDS
59 EDR2.1 RANCH HOUSE ELECTRICAL 1ST AND 2ND FLOOR DEMO PLANS
60 EDR3.1 RANCH HOUSE LIGHTING 1ST AND 2ND FLOOR DEMO PLANS
61 ER2.1 RANCH HOUSE POWER/SIGNAL 1ST AND 2ND FLOOR PLANS
62 ER3.1 RANCH HOUSE LIGHTING 1ST AND 2ND FLOOR PLANS
63 ER4.1 RANCH HOUSE TECHNOLOGY 1ST AND 2ND FLOOR PLANS
64 ER5.1 RANCH HOUSE LIGHTNING PROTECTION SYSTEM ROOF PLAN
65 ER6.1 RANCH HOUSE ELECTRICAL DETAILS & SCHEDULES
GENERAL
1 G0.00 COVER SHEET
2 G0.0 PRESERVATION TREATMENT NOTES
3 G0.1 GENERAL INFORMATION & INDEX
4 G0.2 CONSTRUCTION STAGING
5 G0.3 CODE SHEET - RANCH HOUSE
6 G0.4 ACCESSIBILITY SHEET - RANCH HOUSE
7 G0.5 CODE SHEET - BUNKHOUSE
8 G0.6 ACCESSIBILITY SHEET - BUNKHOUSE
9 G0.7 CODE SHEET - BARN
10 G0.8 ACCESSIBILITY SHEET - BARN
11 G1.0 EXISTING CONDITIONS
12 G1.1 GENERAL NOTES - STRUCTURAL
13 G1.2 GENERAL NOTES - STRUCTURAL
14 G1.3 GENERAL NOTES - STRUCTURAL
BUNKHOUSE
66 ADH1.1 BUNKHOUSE - DEMO FLOOR AND ROOF PLANS
67 ADH2.1 BUNKHOUSE - DEMO REFLECTED CEILING PLAN
68 ADH4.0 BUNKHOUSE - DEMO ELEVATIONS
69 AH1.1 BUNKHOUSE - FLOOR AND ROOF PLAN
70 AH2.1 BUNKHOUSE - FIRST FLOOR REFLECTED CEILING PLAN
71 AH3.0 BUNKHOUSE - DOOR SCHEDULE AND DETAILS
72 AH3.1 BUNKHOUSE - DOOR DETAILS
73 AH3.2 BUNKHOUSE - WINDOW AND FRAME SCHEDULE
74 AH3.3 BUNKHOUSE - FINISH PLAN AND SCHEDULE
75 AH4.0 BUNKHOUSE - EXTERIOR ELEVATIONS
76 AH5.0 BUNKHOUSE - BUILDING SECTIONS
77 AH7.1 BUNKHOUSE - ENLARGED FLOOR PLANS - RESTROOMS
78 AH8.0 BUNKHOUSE - ELEVATIONS & DETAILS
79 SH2.1 BUNKHOUSE FOUNDATION PLAN
80 SH2.2 BUNKHOUSE ROOF FRAMING PLAN
81 SH2.3 BUNKHOUSE DETAILS
82 SH2.4 BUNKHOUSE DETAILS
83 MH0.1 BUNKHOUSE MECHANICAL ABBREVIATIONS AND LEGENDS
84 MDH2.1 BUNKHOUSE HVAC 1ST FLOOR DEMO PLAN
85 MDH3.1 BUNKHOUSE WATER SUPPLY 1ST FLOOR DEMO PLAN
86 MDH4.1 BUNKHOUSE WASTE AND VENT 1ST FLOOR VENT
87 MH2.1 BUNKHOUSE HVAC 1ST FLOOR PLAN
88 MH3.1 BUNKHOUSE WATER SUPPY 1ST FLOOR PLAN
89 MH4.1 BUNKHOUSE WASTE AND VENT 1ST FLOOR PLAN
90 MH5.1 BUNKHOUSE MECHANICAL DETAILS / DIAGRAMS
91 MH6.1 BUNKHOUSE MECHANICAL SCHEDULES
92 EH0.1 BUNKHOUSE ELECTRICAL ABBREVIATIONS AND LEGENDS
93 EDH2.1 BUNKHOUSE ELECTRICAL 1ST FLOOR DEMO PLAN
94 EDH3.1 BUNKHOUSE LIGHTING 1ST FLOOR DEMO PLAN
95 EH2.1 BUNKHOUSE POWER 1ST FLOOR PLAN
96 EH3.1 BUNKHOUSE LIGHTING 1ST FLOOR PLAN
97 EH4.1 BUNKHOUSE TECHNOLOGY 1ST FLOOR PLAN
98 EH5.1 BUNKHOUSE LIGHTNING PROTECTION SYSTEM ROOF PLAN
99 EH6.1 BUNKHOUSE ELECTRICAL SCHEDULES
BARN
100 ADB1.1 BARN 1ST FLOOR DEMO PLAN
101 ADB2.0 BARN ROOF DEMO PLAN
102 ADB4.0 BARN DEMO ELEVATIONS
103 AB1.1 BARN 1ST FLOOR PLAN
104 AB2.0 BARN ROOF PLAN
105 AB4.0 BARN EXTERIOR ELEVATIONS
106 AB5.1 BARN BUILDING SECTIONS
107 AB8.2 BARN DOOR SCHEDULE
108 AB8.3 BARN WINDOW AND FRAME SCHEDULE BID OPTION #4
109 AB9.0 BARN SECTION DETAILS
110 SB3.1 BARN FOUNDATION PLAN
111 SB3.2 BARN ROOF FRAMING PLAN
112 SB3.3 BARN DETAILS
113 SB3.4 BARN DETAILS
114 EB0.1 BARN ELECTRICAL ABBREVIATIONS AND LEGENDS
115 EDB2.1 BARN ELECTRICAL 1ST FLOOR DEMO PLAN
116 EDB3.1 BARN LIGHTING 1ST FLOOR DEMO PLAN
117 EB2.1 BARN POWER/SIGNAL 1ST FLOOR PLAN
118 EB3.1 BARN LIGHTING 1ST FLOOR PLAN
119 EB5.1 BARN LIGHTNING PROTECTION SYSTEM ROOF PLAN
120 EB6.1 BARN ELECTRICAL DETAILS & SCHEDULES
C
A
LIMITS OF WORK
STAGING LEGEND:
B
E
F
D
E
A
E
G
I
H
STAGING KEY NOTES:
A. PARK VISITORS AND STAFF SHALL BE
ALLOWED TRAILHEAD PARKING AND
ACCESS IN THIS AREA THROUGHOUT THE
CONSTRUCTION DURATION.
B. CONTRACTOR TO PROVIDE SANOLET FOR
CONSTRUCTION CREW USE.
C. PARK HOSTS AUGUST & SEPTEMBER
ASTRONOMY PROGAMS IN THIS CORRAL
AND FIELD AREA. COORDINATE WITH PARK
TO PROVIDE UNOBSTRUCTED ACCESS.
D. CONTRACTOR TO PROVIDE ROAD ACCESS
FOR PUBLIC AND NPS THROUGHOUT
CONSTRUCTION. NPS WILL USE A MINIMUM
2X DAILY FROM MAY TO NOVEMBER AND
PUBLIC USE WILL BE SPORADIC.
E. DUMPSTER AND MATERIAL STAGING
SHOULD BE ON NON-VEGETATED AREAS.
F. EXISTING VAULT TOILET IS FOR NPS AND
VISITOR USE ONLY. CONTRACTOR SHALL
PROVIDE UNOBSTRUCTED ACCESS FOR
NPS USE AND SERVICING THROUGHOUT
CONSTRUCTION.
G. CONTRACTOR MAY USE EXISTING CORRAL
FOR ADDITIONAL LAY DOWN BUT ONLY IF
RUTTING FROM EQUIPMENT ACTIVITY IS
MINIMIZED. CONTRACTOR SHALL SEED
THIS CORRAL WITH GOVERNMENT-
PROVIDED SEED AT THE END OF
CONSTRUCTION ACTIVITIES.
H. LOCATION OF NON-POTABLE WATER
I. APPROXIMATE LOCATION OF EXISTING
SEPTIC LEACH FIELD SYSTEM.
GENERAL NOTES:
1. RANCH HOUSE, BUNKHOUSE AND BARN WILL
BE CLOSED TO THE PUBLIC THROUGHOUT
CONSTRUCTION BUT OTHER AREAS OF SITE
WILL BE OPEN TO PARK AND VISITOR USE AS
NOTED.
2. ALL CONSTRUCTION LAYDOWN SHALL BE
WITHIN ESTABLISHED PARKING AREAS AND
SHALL NOT IMPEDE VEHICULAR SITE ACCESS.
3. WILD BISON AND HORSES ROAM THROUGH THE
SITE AT ANY TIME OF THE YEAR. DO NOT
APPROACH THEM.
4. CONSTRUCTION FENCING SHALL BE
SUPPORTED BY CONCRETE BASES. NO
GROUND PENETRATING STAKING IS ALLOWED.
5. PARK WILL BE RESPONSIBLE FOR SNOW
REMOVAL TO THE SITE AND DRIVE LANE THRU
SITE. ALL OTHER DETAILED SNOW REMOVAL
AROUND WORK AREAS SHALL BE
CONTRACTOR'S RESPONSIBILITY.
6. NON-POTABLE WATER WILL NOT BE AVAILABLE
TO THE CONTRACTOR OCTOBER-APRIL
PROJECT IDENTIFICATION SIGNAGE:
TO BE PROVIDED BY THE PARK
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF8/
5/
2:
:0
P
M C
:\A ut oD es k S av e
Lo ca tio ns
\R ev it\
T
H R
O R an ch
H ou se _s us ie ha ck er an da rc h.
co m
.r vt
G0.2
NAA
THEODORE ROOSEVELT NATIONAL PARK
PEACEFUL VALLEY RANCH
138248
228216
CN
KAC
08/06/2019 4 120
CONSTRUCTION
STAGING
G0.2
CONSTRUCTION STAGING PLAN2
SCALE OF FEET
10050050
UP
DN
PORCH
OFFICE
KITCHEN
OFFICE
RESTROOM
CLOSET
OFFICE
60'-4" / 2 = 30'-2"
FE FE
FE
FE FE
FE
*FE
OFFICE
CLOSET
FE
MEANS OF EGRESS
TABLE 1004.1.2 – MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT
BUSINESS AREAS = 100 GROSS
1006.2.1 EGRESS BASED ON OCCUPANT LOAD AND COMMON PATH OF EGRESS TRAVEL DISTANCE. TWO EXITS
OR EXIT ACCESS DOORWAYS FROM ANY SPACE SHALL BE PROVIDED WHERE THE DESIGN OCCUPANT LOAD OR THE COMMON PATH OF EGRESS TRAVEL DISTANCE EXCEEDS THE VALUES LISTED IN TABLE 1006.2.1.
TABLE 1006.2.1 – SPACES WITH ONCE EXIT OR EXIT ACCESS DOORWAY
B OCCUPANCY WITHOUT SPRINKLER: OCCUPANT LOAD < 30 = 100’ MAX COMMON PATH OF EGRESS TRAVEL
DISTANCE
1006.3.2 SINGLE EXITS – SHALL BE PERMITTED WHEN OCCUPANT LOAD AND EXIT ACCESS TRAVEL DISTANCE DO
NOT EXCEED THE VALUES IN TABLE 1006.3.2
TABLE 1006.3.2 – STORIES WITH ONE EXIT OR ACCESS TO ONE EXIT
STORY OCCUPANCY MAX OCCUPANT MAX. COMMON PATH OF
PER STORY EGRESS TRAVEL DISTANCE
FIRST STORY ABOVE OR BELOW GRADE PLANE:
B OCCUPANCY 49 75’
EXITS REQUIRED BASED ON TABLE 1006.3.2
OCCUPANTS REQUIRED PROVIDED
BASEMENT 3 1 2
FIRST FLOOR 17 1 3
SECOND FLOOR 4 1 1
SECOND FLOOR IS AN EXISTING CONDITION. SIZE OF THE SPACE SUPPORTS 4 OCCUPANTS AND PATH OF
EGRESS TRAVEL IS LESS THAN 75’.
STAIRWAYS
1005.3.1 STAIRWAYS THE CAPACITY, IN INCHES, OF MEANS OF EGRESS STAIRWAYS SHALL BE CALCULATED BY MULTIPLYING THE OCCUPANT LOAD SERVED BY SUCH STAIRWAYS BY A MEANS OF EGRESS CAPACITY FACTOR
OF 0.3 INCH (7.6 MM) PER OCCUPANT.
OCC FACTOR REQUIRED PROVIDED
BASEMENT 3 .3 0.9” 23 ¾”
SECOND FLOOR 4 .3 1.2” 33 ¾” (BASE BID)
NOTE: 36” IS THE MINIMUM REQUIRED EGRESS STAIRWELL WIDTH FOR A STAIRWAY SERVING AN OCCUPANT LOAD OF LESS THAN 50. THEREFORE, 36” IS THE MINIMUM REQUIRED WIDTH. BASEMENT AND SECOND FLOOR STAIRS ARE EXISTING CONDITIONS. BID OPTION #1 PROVIDES A NEW SECOND FLOOR STAIR THAT IS CODE
COMPLIANT.
MEANS OF EGRESS ILLUMINATION
1008.3.2 BUILDINGS - IN THE EVENT OF POWER FAILURE IN BUILDINGS THAT REQUIRE TWO OR MORE MEANS OF EGRESS, AN EMERGENCY ELECTRICAL SYSTEM SHALL AUTOMATICALLY ILLUMINATE ALL OF THE FOLLOWING
AREAS.
ONLY ONE EXIT IS REQUIRED IN THE RANCH HOUSE, THEREFORE EMERGENCY ILLUMINATION IS NOT REQUIRED.
BUILDING CODE ANALYSIS
BUILDING CODE ANALYSIS
2015 INTERNATIONAL BUILDING CODE (IBC); 2015 INTERNATIONAL EXISTING BUILDING CODE (IEBC)
CODE ASSUMPTIONS FOR THE RANCH HOUSE
THIS PHASE OF CONSTRUCTION IS FOCUSED ON REHABILITATION AND STABILIZATION OF THE
BUILDING. FUTURE PHASE(S) OF CONSTRUCTION WILL PROVIDE WORK SPECIFIC TO THE FINAL
DETERMINED USE OF THE BUILDING AND SITE. FOR THIS SET, THE FOLLOWING USE
ASSUMPTIONS WERE MADE FOR THE RANCH HOUSE:
FIRST AND SECOND FLOORS – BUSINESS OCCUPANCY.
BASEMENT HAS BEEN DETERMINED TO BE UNINHIBITABLE DUE TO FLOOD CONCERNS IN THIS AND ALL FUTURE PHASES. IT WILL NOT BE USED AND NO EQUIPMENT WILL BE INSTALLED IN THIS
SPACE.
THE RANCH HOUSE IS LISTED ON THE NATIONAL REGISTER OF HISTORIC PLACES AND THE CODE
ANALYSIS WAS PERFORMED UNDER CHAPTER 12 OF THE IEBC.
THE RANCH HOUSE IS CHANGING USE FROM RESIDENTIAL TO BUSINESS OCCUPANCY. THE
DESIGN MEETS 2015 IBC CODE REQUIREMENTS AS LISTED BELOW. EXCEPTIONS FROM MEETING
CURRENT CODE AT THE EXISTING STAIR TO THE SECOND FLOOR FALLS WITHIN IEBC ALLOWANCE PER SECTION 1205.1, WHICH PROVIDES AN EXCEPTION “FOR BUILDINGS LESS THAN 3,000 SQUARE FEET, EXISTING CONDITIONS ARE PERMITTED TO REMAIN AT ALL STAIRWAYS AND GUARDS.” THE EXISTING STAIR CONFIGURATION WILL BE MAINTAINED, HOWEVER A CONTINUOUS HANDRAIL WILL
BE INSTALLED ON THE WALL SIDE OF THE STAIR TO IMPROVE SAFETY.
THE RANCH HOUSE IS LISTED ON THE NATIONAL REGISTER OF HISTORIC PLACES AND THE CODE
ANALYSIS WAS PERFORMED UNDER CHAPTER 12 OF THE IEBC.
THE RANCH HOUSE IS CHANGING USE FROM RESIDENTIAL TO BUSINESS OCCUPANCY. THE
DESIGN MEETS 2015 IBC CODE REQUIREMENTS AS LISTED BELOW. EXCEPTIONS FROM MEETING
CURRENT CODE AT THE EXISTING STAIR TO THE SECOND FLOOR FALLS WITHIN IEBC ALLOWANCE PER SECTION 1205.1, WHICH PROVIDES AN EXCEPTION “FOR BUILDINGS LESS THAN 3,000 SQUARE FEET, EXISTING CONDITIONS ARE PERMITTED TO REMAIN AT ALL STAIRWAYS AND GUARDS.” THE EXISTING STAIR CONFIGURATION WILL BE MAINTAINED, HOWEVER A CONTINUOUS HANDRAIL WILL
BE INSTALLED ON THE WALL SIDE OF THE STAIR TO IMPROVE SAFETY.
BUILDING HEIGHT AND NUMBER OF STORIES
TABLE 504.3 - AVAILABLE BUILDING HEIGHT AND NUMBER OF STORIES
B OCCUPANCY: ALLOWABLE HEIGHT FOR TYPE VB = 40’ ABOVE GRADE
TABLE 504.4 – ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE
B OCCUPANCY: TYPE VB NON-SPRINKLERED = 2
ACTUAL BUILDING HEIGHT = 20’-3” ABOVE GRADE
ACTUAL STORIES = 2
BUILDING HEIGHT COMPLIES WITH CODE.
ALLOWABLE FLOOR AREA
TABLE 506.2 - ALLOWABLE AREA
B OCCUPANCY: TYPE VB NON-SPRINKLERED = 9,000 SF
ACTUAL FLOOR AREA
BASEMENT 817 SF
FIRST FLOOR 1,343 SF
SECOND FLOOR 355 SF
TOTAL 2,515 SF
BUILDING FLOOR AREA COMPLIES WITH CODE.
MIXED USE AND OCCUPANCY
508.3 NONSEPARATED OCCUPANCIES. BUILDINGS OR PORTIONS OF BUILDINGS THAT COMPLY WITH THE
PROVISIONS OF THIS SECTION SHALL BE CONSIDERED AS NONSEPARATED OCCUPANCIES.
508.3.2 ALLOWABLE BUILDING AREA AND HEIGHT. THE ALLOWABLE BUILDING AREA AND HEIGHT OF THE BUILDING OR PORTION THEREOF SHALL BE BASED ON THE MOST RESTRICTIVE ALLOWANCES FOR THE OCCUPANCY GROUPS UNDER CONSIDERATION FOR THE TYPE OF CONSTRUCTION OF THE BUILDING IN
ACCORDANCE WITH SECTION 503.1.
508.3.3 SEPARATION. NO SEPARATION IS REQUIRED BETWEEN NONSEPARATED OCCUPANCIES.
TYPES OF CONSTRUCTION
TABLE 601 - FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (HOURS)
STRUCTURAL FRAME = 0 HOURS
BEARING WALLS
EXTERIOR = 0 HOURS
INTERIOR = 0 HOURS
NONBEARING WALLS AND PARTITIONS
EXTERIOR = 0 HOURS
INTERIOR = 0 HOURS
FLOOR CONSTRUCTION = 0 HOURS
ROOF CONSTRUCTION = 0 HOURS
TABLE 602 – FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION
DISTANCE
VB CONSTRUCTION FOR OCCUPANCY B IN VB
DISTANCE REQUIRED
10 < X < 30 0 X > 30 0
SEE FIRE SPRINKLER MEMO ON G0.0.
FIRE EXTINGUISHERS TO BE PROVIDED IN ALL ROOMS, INCLUDING THE BASEMENT.
REFER TO ELECTRICAL SHEETS FOR FIRE ALARM LOCATIONS.
OCCUPANT AREA AND LOAD
AREA OCCUPANCY TYPE LOAD FACTOR OCCUPANT LOAD
BASEMENT
BASEMENT 817 U 300 3
FIRST FLOOR
100 OFFICE 221 BUSINESS 100 3
101 PORCH 230 BUSINESS 100 3
102 OFFICE 354 BUSINESS 100 4
103 KITCHEN 222 BUSINESS 100 3
104 OFFICE 208 BUSINESS 100 3
105 CLOSET 36 BUSINESS 100 1
TOTAL 17
SECOND FLOOR
OFFICE 355 BUSINESS 100 4
FIRE SAFETY/EGRESS LEGEND
- EGRESS DOOR
- DIRECTION OF EGRESS TRAVEL
- FIRE EXTINGUISHER
- TACTILE EXIT SIGN ~ SEE SHEET G0.4
FE
BASEMENT
CRAWL
SPACE
CRAWL
SPACE
FE
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF8/
5/
2:
:0
P
M C
:\A ut oD es k S av e
Lo ca tio ns
\R ev it\
T
H R
O R an ch
H ou se _s us ie ha ck er an da rc h.
co m
.r vt
G0.3
NAA
THEODORE ROOSEVELT NATIONAL PARK
PEACEFUL VALLEY RANCH
138248
228216
CN
KAC
08/06/2019 5 120
CODE SHEET - RANCH
HOUSE
G0.3
CODE PLAN - FIRST FLOOR3
G0.3
CODE PLAN - SECOND FLOOR PLAN4
SCALE A
SCALE OF FEET
16808
SCALE A
SCALE A
G0.3
CODE PLAN - BASEMENT1
SCALE A
PORCH
OFFICE
OFFICE
KITCHEN
OFFICE
RESTROOM
CLOSET
GENERAL NOTES:
1. ALL SIGNAGE SHALL COMPLY W/ ABAAS AND WILL BE REVIEWED IN
SUBMITTAL FORMAT PRIOR TO FABRICATION AND INSTALLATION.
2. SIGNAGE NEEDS TO COMPLY WITH F216.6 & 703.2.1
3. ALL NEW WALK, RAMP AND LANDING ELEMENTS SHALL MEET ABA SURFACE
REQUIREMENTS.
4. ALL NEW HANDRAILS SHALL MEET ABA REQUIREMENTS.
ACCESSIBILITY ANALYSIS:
FIRST FLOOR - PARTIALLY ACCESSIBLE
SECOND FLOOR - NON-ACCESSIBLE
BASEMENT - NON-ACCESSIBLE
RAMP SLOPE:
405.2 EXCEPTION 2 ALLOWS:
1:8 RAMP MAX SLOPE FOR 3" MAX RISE
1:10 RAMP MAY SLOPE FOR 6" MAX RISE
USE EXCEPTION SLOPES ONLY WHERE INDICATED.
PER CODE:
1:12 MAX SLOPE FOR 30" MAX RISE
1:20 MAX WALK SLOPE ALL OTHER LOCATIONS
NPS GUIDELINES TO ENSURE RAMP MEETS ABAAS WHEN CONSTRUCTED:
1:13.5 RAMP MAX SLOPE FOR 30" MAX RISE
1:25 WALK SLOPE ALL OTHER LOCATIONS
ALL SLOPES ARE SHOWN AS A MAXIMUM, ALL RAMPS INSTALLED SHALL HAVE
SHALLOWER SLOPES THAN INDICATED.
DOORWAY WIDTH:
404.2.3 CLEAR WIDTH = 32" MIN.
ALL DOORS SHOWN ON ACCESSIBLE PATH MEET OR SHALL MEET 32" MINIMUM
WIDTH.
TURNING CIRCLE - 60" DIAMETER
T-SHAPED TURNING SPACE
ACCESSIBLE ROUTE - 36" CLEAR
ACCESSIBLE ENTRY
MANEUVERING CLEARANCE AT DOOR;
ARROW INDICATES APPROACH DIRECTION
TACTILE EXIT SIGN
PLAN LEGEND
48"
4"
EXIT
ROUNDED EDGESSIGNS SHALL BE PROVIDED IN
ACCORDANCE WITH F216 AND SHALL
COMPLY WITH 703.
703.4.1 HEIGHT ABOVE FINISH FLOOR OR
GROUND. TACTILE CHARACTERS ON SIGNS
SHALL BE LOCATED 48" MINIMUM FROM
THE FINISH FLOOR OR GROUND SURFACE,
MEASURED FROM THE BASELINE OF THE
LOWEST TACTILE CHARACTER AND 60"
MAXIMUM ABOVE THE FINISH FLOOR OR
GROUND SURFACE, MEASURED FROM THE
BASELINE OF THE HIGHEST TACTILE
CHARACTER
703.4.2 LOCATION. WHERE TACILE SIGN IS
PROVIDED AT A DOOR, THE SIGN SHALL BE
LOCATED ALONSIDE THE DOOR AT THE
LATCH SIDE.
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF8/
5/
2:
:0
P
M C
:\A ut oD es k S av e
Lo ca tio ns
\R ev it\
T
H R
O R an ch
H ou se _s us ie ha ck er an da rc h.
co m
.r vt
G0.4
NAA
THEODORE ROOSEVELT NATIONAL PARK
PEACEFUL VALLEY RANCH
138248
228216
CN
KAC
08/06/2019 6 120
ACCESSIBILITY
SHEET - RANCH
HOUSE
G0.4
ACCESSIBILITY PLAN - FIRST FLOOR1
SCALE A
SCALE OF FEET
16808
SCALE A
G0.4
TACTILE EXIT SIGN3
SCALE OF INCH
606 3
SCALE B
SCALE B
CLASSROOM
MECHANICAL
RESTROOM
KITCHENETTE
FE
FE
FE
FE
FIRE SAFETY/EGRESS LEGEND
- EGRESS DOOR
- DIRECTION OF EGRESS TRAVEL
- FIRE EXTINGUISHER
- TACTILE EXIT SIGN ~ SEE GO.6
FE
BUILDING CODE ANALYSIS
2015 INTERNATIONAL BUILDING CODE (IBC); 2015 INTERNATIONAL EXISTING BUILDING CODE (IEBC)
CODE ASSUMPTIONS FOR THE BUNKHOUSE
THIS PHASE OF CONSTRUCTION IS FOCUSED ON REHABILITATION AND STABILIZATION OF THE
BUILDING. FUTURE PHASE(S) OF CONSTRUCTION WILL PROVIDE WORK SPECIFIC TO THE FINAL DETERMINED USE OF THE BUILDING AND SITE. FOR THIS SET, THE FOLLOWING USE ASSUMPTIONS
WERE MADE FOR THE BUNKHOUSE:
FIRST FLOOR: EDUCATION OCCUPANCY.
THE BUNKHOUSE IS LISTED ON THE NATIONAL REGISTER OF HISTORIC PLACES AND THE CODE
ANALYSIS WAS PERFORMED UNDER CHAPTER 12 OF THE IEBC.
THE BUNKHOUSE IS CHANGING USE FROM RESIDENTIAL TO EDUCATION OCCUPANCY. THE DESIGN
MEETS 2015 IBC CODE REQUIREMENTS AS LISTED BELOW.
BUILDING HEIGHT AND NUMBER OF STORIES
TABLE 504.3 - AVAILABLE BUILDING HEIGHT AND NUMBER OF STORIES
E OCCUPANCY: ALLOWABLE HEIGHT FOR TYPE VB = 40’ ABOVE GRADE
TABLE 504.4 – ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE
E OCCUPANCY: TYPE VB NON-SPRINKLERED = 1
ACTUAL BUILDING HEIGHT = 10’-7” ABOVE GRADE
ACTUAL STORIES = 1
BUILDING HEIGHT COMPLIES WITH CODE.
ALLOWABLE FLOOR AREA
TABLE 506.2 - ALLOWABLE AREA
E OCCUPANCY: TYPE VB NON-SPRINKLERED = 9,500 SF
ACTUAL FLOOR AREA
FIRST FLOOR 855 SF
TOTAL 855 SF
BUILDING FLOOR AREA COMPLIES WITH CODE.
MIXED USE AND OCCUPANCY
508.2 ACCESSORY OCCUPANCIES. ACCESSORY OCCUPANCIES ARE THOSE OCCUPANCIES THAT ARE
ANCILLARY TO THE MAIN OCCUPANCY OF THE BUILDING OR PORTION THEREOF. ACCESSORY
OCCUPANCIES SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 508.2.1 THROUGH 508.2.4.
508.2.3 ALLOWABLE BUILDING AREA. THE ALLOWABLE AREA OF THE BUILDING SHALL BE BASED ON
THE APPLICABLE PROVISIONS OF SECTION 506 FOR THE MAIN OCCUPANCY OF THE BUILDING.
AGGREGATE ACCESSORY OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10 PERCENT OF THE
FLOOR AREA OF THE STORY IN WHICH THEY ARE LOCATED AND SHALL NOT EXCEED THE TABULAR
VALUES FOR NONSPRINKLERED BUILDINGS IN TABLE 506.2 FOR EACH SUCH ACCESSORY
OCCUPANCY.
508.3 NONSEPARATED OCCUPANCIES. BUILDINGS OR PORTIONS OF BUILDINGS THAT COMPLY WITH
THE PROVISIONS OF THIS SECTION SHALL BE CONSIDERED AS NONSEPARATED OCCUPANCIES.
TYPES OF CONSTRUCTION
TABLE 601 - FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (HOURS)
STRUCTURAL FRAME = 0 HOURS
BEARING WALLS
EXTERIOR = 0 HOURS
INTERIOR = 0 HOURS
NONBEARING WALLS AND PARTITIONS
EXTERIOR = 0 HOURS
INTERIOR = 0 HOURS
FLOOR CONSTRUCTION = 0 HOURS
ROOF CONSTRUCTION = 0 HOURS
BUILDING CODE ANALYSIS
2015 INTERNATIONAL BUILDING CODE (IBC); 2015 INTERNATIONAL EXISTING BUILDING CODE (IEBC)
BUILDING HEIGHT AND NUMBER OF STORIES
TABLE 504.3 - AVAILABLE BUILDING HEIGHT AND NUMBER OF STORIES
E OCCUPANCY: ALLOWABLE HEIGHT FOR TYPE VB = 40’ ABOVE GRADE
TABLE 504.4 – ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE
E OCCUPANCY: TYPE VB NON-SPRINKLERED = 1
ACTUAL BUILDING HEIGHT = 10’-7” ABOVE GRADE
ACTUAL STORIES = 1
BUILDING HEIGHT COMPLIES WITH CODE.
ALLOWABLE FLOOR AREA
TABLE 506.2 - ALLOWABLE AREA
E OCCUPANCY: TYPE VB NON-SPRINKLERED = 9,500 SF
ACTUAL FLOOR AREA
FIRST FLOOR 855 SF
TOTAL 855 SF
BUILDING FLOOR AREA COMPLIES WITH CODE.
SEE FIRE SPRINKLER MEMO ON G0.0.
FIRE EXTINGUISHERS SHALL BE PROVIDED IN ALL ROOMS.
REFER TO ELECTRICAL SHEETS FOR FIRE ALARM LOCATIONS.
TYPES OF CONSTRUCTION
TABLE 601 - FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (HOURS)
STRUCTURAL FRAME = 0 HOURS
BEARING WALLS
EXTERIOR = 0 HOURS
INTERIOR = 0 HOURS
NONBEARING WALLS AND PARTITIONS
EXTERIOR = 0 HOURS
INTERIOR = 0 HOURS
FLOOR CONSTRUCTION = 0 HOURS
ROOF CONSTRUCTION = 0 HOURS
TABLE 602 – FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE
SEPARATION DISTANCE
VB CONSTRUCTION FOR OCCUPANCY E, B AND S-1 IN VB
DISTANCE REQUIRED
10 < X < 30 0 X > 30 0
OCCUPANT AREA AND LOAD
AREA OCCUPANCY TYPE LOAD FACTOR OCCUPANT LOAD
FIRST FLOOR
CLASSROOM 105 621 EDUCATION 20 31
STORAGE 106 47 STORAGE 300 1
KITCHENETTE 109 62 EDUCATION 20 4
TOTAL 36
MEANS OF EGRESS
TABLE 1004.1.2 – MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT
CLASSROOM = 20 NET
1006.2.1 EGRESS BASED ON OCCUPANT LOAD AND COMMON PATH OF EGRESS TRAVEL DISTANCE. TWO
EXITS OR EXIT ACCESS DOORWAYS FROM ANY SPACE SHALL BE PROVIDED WHERE THE DESIGN
OCCUPANT LOAD OR THE COMMON PATH OF EGRESS TRAVEL DISTANCE EXCEEDS THE VALUES LISTED IN
TABLE 1006.2.1.
TABLE 1006.2.1 – SPACES WITH ONCE EXIT OR EXIT ACCESS DOORWAY
E OCCUPANCY WITHOUT SPRINKLER: OCCUPANT LOAD < 30 = 75’ MAX COMMON PATH OF EGRESS TRAVEL
DISTANCE
1006.3.2 SINGLE EXITS – SHALL BE PERMITTED WHEN OCCUPANT LOAD AND EXIT ACCESS TRAVEL
DISTANCE DO NOT EXCEED THE VALUES IN TABLE 1006.3.2
TABLE 1006.3.2 – STORIES WITH ONE EXIT OR ACCESS TO ONE EXIT
STORY OCCUPANCY MAX OCCUPANT MAX. COMMON PATH OF
PER STORY EGRESS TRAVEL DISTANCE
FIRST STORY ABOVE OR BELOW GRADE PLANE:
E OCCUPANCY 49 75’
EXITS REQUIRED BASED ON TABLE 1006.3.2
OCCUPANTS REQUIRED PROVIDED
FIRST FLOOR 36 1 2
MEANS OF EGRESS ILLUMINATION
1008.3.2 BUILDINGS - IN THE EVENT OF POWER FAILURE IN BUILDINGS THAT REQUIRE TWO OR MORE MEANS OF EGRESS, AN EMERGENCY ELECTRICAL SYSTEM SHALL AUTOMATICALLY ILLUMINATE ALL OF THE
FOLLOWING AREAS.
ONLY ONE EXIT IS REQUIRED IN THE RANCH HOUSE, THEREFORE EMERGENCY ILLUMINATION IS NOT
REQUIRED.
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF8/
5/
2:
:0
P
M C
:\A ut oD es k S av e
Lo ca tio ns
\R ev it\
T
H R
O B un kh ou se
_s us ie ha ck er an da rc h.
co m .r vt
G0.5
NAA
THEODORE ROOSEVELT NATIONAL PARK
PEACEFUL VALLEY RANCH
138248
228216
CN
KAC
08/06/2019 7 120
CODE SHEET -
BUNKHOUSE
G0.5
BUNKHOUSE FIRST FLOOR CODE PLAN1
SCALE OF FEET
16808
SCALE A
SCALE A
CLASSROOM
MECHANICAL
RESTROOM
KITCHENETTE
TURNING CIRCLE - 60" DIAMETER
ACCESSIBLE ROUTE - 36" CLEAR
ACCESSIBLE ENTRY
MANEUVERING CLEARANCE AT DOOR;
ARROW INDICATES APPROACH DIRECTION
TACTILE EXIT SIGN
PLAN LEGEND
48"
GENERAL NOTES:
1. ALL SIGNAGE SHALL COMPLY W/ ABAAS AND WILL BE REVIEWED IN
SUBMITTAL FORMAT PRIOR TO FABRICATION AND INSTALLATION.
2. SIGNAGE NEEDS TO COMPLY WITH F216.6 & 703.2.1
3. ALL NEW WALK, RAMP AND LANDING ELEMENTS SHALL MEET ABA SURFACE
REQUIREMENTS.
4. ALL NEW HANDRAILS SHALL MEET ABA REQUIREMENTS.
ACCESSIBILITY ANALYSIS:
FIRST FLOOR - FULLY ACCESSIBLE
RAMP SLOPE:
PER CODE:
1:12 MAX SLOPE FOR 30" MAX RISE
1:20 MAX WALK SLOPE ALL OTHER LOCATIONS
NPS GUIDELINES TO ENSURE RAMP MEETS ABAAS WHEN CONSTRUCTED:
1:13.5 RAMP MAX SLOPE FOR 30" MAX RISE
1:25 WALK SLOPE ALL OTHER LOCATIONS
ALL SLOPES ARE SHOWN AS A MAXIMUM, ALL RAMPS INSTALLED SHALL HAVE
SHALLOWER SLOPES THAN INDICATED.
DOORWAY WIDTH:
404.2.3 CLEAR WIDTH = 32" MIN.
ALL DOORS SHOWN ON ACCESSIBLE PATH MEET OR SHALL MEET 32" MINIMUM
WIDTH.
4"
EXIT
ROUNDED EDGES
SIGNS SHALL BE PROVIDED IN ACCORDANCE
WITH F216 AND SHALL COMPLY WITH 703.
703.4.1 HEIGHT ABOVE FINISH FLOOR OR
GROUND. TACTILE CHARACTERS ON SIGNS
SHALL BE LOCATED 48" MINIMUM FROM THE
FINISH FLOOR OR GROUND SURFACE,
MEASURED FROM THE BASELINE OF THE
LOWEST TACTILE CHARACTER AND 60"
MAXIMUM ABOVE THE FINISH FLOOR OR
GROUND SURFACE, MEASURED FROM THE
BASELINE OF THE HIGHEST TACTILE
CHARACTER
703.4.2 LOCATION. WHERE TACILE SIGN IS
PROVIDED AT A DOOR, THE SIGN SHALL BE
LOCATED ALONSIDE THE DOOR AT THE
LATCH SIDE.
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF8/
5/
2:
:1
P
M C
:\A ut oD es k S av e
Lo ca tio ns
\R ev it\
T
H R
O B un kh ou se
_s us ie ha ck er an da rc h.
co m .r vt
G0.6
NAA
THEODORE ROOSEVELT NATIONAL PARK
PEACEFUL VALLEY RANCH
138248
228216
CN
KAC
08/06/2019 8 120
ACCESSIBILITY
SHEET - BUNKHOUSE
G0.6
BUNKHOUSE FIRST FLOOR ACCESSIBILITY PLAN1
SCALE OF FEET
16808
SCALE A
SCALE A
G0.6
TACTILE EXIT SIGN2
SCALE A
SCALE OF INCH
606 3
SCALE B
SUPPORT
SPACE
SUPPORT
SPACE
SUPPORT
SPACE
STORAGE
72'-6"/2 = 36'-1
FE
FE
FE
FE
BUILDING CODE ANALYSIS
2015 INTERNATIONAL BUILDING CODE (IBC); 2015 INTERNATIONAL EXISTING BUILDING CODE (IEBC)
CODE ASSUMPTIONS FOR THE BARN
THIS PHASE OF CONSTRUCTION IS FOCUSED ON REHABILITATION AND STABILIZATION OF THE
BUILDING. FUTURE PHASE(S) OF CONSTRUCTION WILL PROVIDE WORK SPECIFIC TO THE FINAL DETERMINED USE OF THE BUILDING AND SITE. FOR THIS SET, THE FOLLOWING USE ASSUMPTIONS
WERE MADE FOR THE BARN:
FIRST FLOOR: EDUCATION OCCUPANCY WITH A SMALL STORAGE ROOM (104)
THE BARN IS LISTED ON THE NATIONAL REGISTER OF HISTORIC PLACES AND THE CODE ANALYSIS WAS
PERFORMED UNDER CHAPTER 12 OF THE IEBC.
THE BARN IS CHANGING USE FROM UTILITY TO EDUCATIONAL OCCUPANCY. THE DESIGN MEETS 2015 IBC CODE REQUIREMENTS AS LISTED BELOW. VARIANCE IS REQUESTED FOR THE TWO EXTERIOR EXIT DOORS ON THE WEST ELEVATION. DOOR HEADERS AT THOSE EXITS CANNOT BE EXTENDED TO 6’-8” WITHOUT RAISING THE ENTIRE ROOF OF THE BUILDING. BOTH OPENINGS WILL BE IMPROVED AS MUCH AS POSSIBLE WHILE MAINTAINING THE CURRENT ROOFING CONFIGURATION. CURRENTLY THE HEADER OF DOOR 100 IS AT 6’-0” AND WILL BE RAISED TO 6’-5”. THE HEADER OVER DOOR 104 IS CURRENTLY AT
5’-11” AND WILL BE RAISED TO 6’-4”.
BUILDING HEIGHT AND NUMBER OF STORIES
TABLE 504.3 - AVAILABLE BUILDING HEIGHT AND NUMBER OF STORIES
E OCCUPANCY: ALLOWABLE HEIGHT FOR TYPE VB = 40’ ABOVE GRADE
TABLE 504.4 – ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE
E OCCUPANCY: TYPE VB NON-SPRINKLERED = 1
ACTUAL BUILDING HEIGHT = 14’-5” ABOVE GRADE
ACTUAL STORIES = 1
BUILDING HEIGHT COMPLIES WITH CODE.
ALLOWABLE FLOOR AREA
TABLE 506.2 - ALLOWABLE AREA
E OCCUPANCY: TYPE VB NON-SPRINKLERED = 9,500 SF
ACTUAL FLOOR AREA
FIRST FLOOR 1,516 SF
TOTAL 1,516 SF
BUILDING FLOOR AREA COMPLIES WITH CODE.
MIXED USE AND OCCUPANCY
508.2 ACCESSORY OCCUPANCIES. ACCESSORY OCCUPANCIES ARE THOSE OCCUPANCIES THAT ARE
ANCILLARY TO THE MAIN OCCUPANCY OF THE BUILDING OR PORTION THEREOF. ACCESSORY
OCCUPANCIES SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 508.2.1 THROUGH 508.2.4.
508.2.3 ALLOWABLE BUILDING AREA. THE ALLOWABLE AREA OF THE BUILDING SHALL BE BASED ON THE APPLICABLE PROVISIONS OF SECTION 506 FOR THE MAIN OCCUPANCY OF THE BUILDING. AGGREGATE
ACCESSORY OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10 PERCENT OF THE FLOOR AREA OF
THE STORY IN WHICH THEY ARE LOCATED AND SHALL NOT EXCEED THE TABULAR VALUES FOR
NONSPRINKLERED BUILDINGS IN TABLE 506.2 FOR EACH SUCH ACCESSORY OCCUPANCY.
S-1 OCCUPANCY (STORAGE 104) = 47 SF
S-1 OCCUPANCY IS AN ACCESSORY OCCUPANCY.
508.3 NONSEPARATED OCCUPANCIES. BUILDINGS OR PORTIONS OF BUILDINGS THAT COMPLY WITH
THE PROVISIONS OF THIS SECTION SHALL BE CONSIDERED AS NONSEPARATED OCCUPANCIES.
TYPES OF CONSTRUCTION
TABLE 601 - FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (HOURS)
STRUCTURAL FRAME = 0 HOURS
BEARING WALLS
EXTERIOR = 0 HOURS
INTERIOR = 0 HOURS
NONBEARING WALLS AND PARTITIONS
EXTERIOR = 0 HOURS
INTERIOR = 0 HOURS
FLOOR CONSTRUCTION = 0 HOURS
ROOF CONSTRUCTION = 0 HOURS
TABLE 602 – FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE
SEPARATION DISTANCE
VB CONSTRUCTION FOR OCCUPANCY E AND S-1 IN VB
DISTANCE REQUIRED
X > 30 0
SEE FIRE SPRINKLER MEMO ON G0.0.
FIRE EXTINGUISHERS SHALL BE PROVIDED IN ALL ROOMS.
REFER TO ELECTRICAL SHEETS FOR FIRE ALARM LOCATIONS.
OCCUPANT AREA AND LOAD
AREA OCCUPANCY TYPE LOAD FACTOR OCCUPANT LOAD
FIRST FLOOR
SUPPORT SPACE 101 656 EDUCATION 20 33
SUPPORT SPACE 102 162 EDUCATION 20 9
CLASSROOM 103 643 EDUCATION 20 33
STORAGE 104 47 STORAGE 300 1
TOTAL 76
MEANS OF EGRESS
TABLE 1004.1.2 – MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT
CLASSROOM = 20 NET
STORAGE = 300 GROSS
1006.2.1 EGRESS BASED ON OCCUPANT LOAD AND COMMON PATH OF EGRESS TRAVEL DISTANCE.
TWO EXITS OR EXIT ACCESS DOORWAYS FROM ANY SPACE SHALL BE PROVIDED WHERE THE DESIGN
OCCUPANT LOAD OR THE COMMON PATH OF EGRESS TRAVEL DISTANCE EXCEEDS THE VALUES
LISTED IN TABLE 1006.2.1.
EXITS REQUIRED BASED ON TABLE 1006.3.2
OCCUPANTS REQUIRED PROVIDED
FIRST FLOOR 76 2 2
FIRE SAFETY/EGRESS LEGEND
- EGRESS DOOR W/ EXIT SIGNAGE
- DIRECTION OF EGRESS TRAVEL
- FIRE EXTINGUISHER
- TACTILE AND ILLUMINATED EXIT
SIGNAGE AND EMERGENCY LIGHT*
FE
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF8/
5/
2:
:0
P
M C
:\A ut oD es k S av e
Lo ca tio ns
\R ev it\
T
H R
O B ar n_ su si eh ac ke r@ an da rc h.
co m
.r vt
G0.7
NAA
THEODORE ROOSEVELT NATIONAL PARK
PEACEFUL VALLEY RANCH
138248
228216
DAM
KAC
08/06/2019 9 120
CODE SHEET - BARN
G0.7
BARN CODE PLAN1
SCALE OF FEET
16808
SCALE A
SCALE A
SUPPORT
SPACE
SUPPORT
SPACE
SUPPORT
SPACE
STORAGE
TURNING CIRCLE - 60" DIAMETER
ACCESSIBLE ROUTE - 36" CLEAR
ACCESSIBLE ENTRY
MANEUVERING CLEARANCE AT DOOR;
ARROW INDICATES APPROACH DIRECTION
PLAN LEGEND
48"
GENERAL NOTES:
1. ALL SIGNAGE SHALL COMPLY W/ ABAAS AND WILL BE REVIEWED IN
SUBMITTAL FORMAT PRIOR TO FABRICATION AND INSTALLATION.
2. SIGNAGE NEEDS TO COMPLY WITH F216.6 & 703.2.1
3. ALL NEW WALK, RAMP AND LANDING ELEMENTS SHALL MEET ABA SURFACE
REQUIREMENTS.
4. ALL NEW HANDRAILS SHALL MEET ABA REQUIREMENTS.
ACCESSIBILITY ANALYSIS:
FIRST FLOOR - PARTIALLY ACCESSIBLE
NOTE:
BASE BID INCLUDES COMPACTED SOIL INSIDE BARN SPACE 101, 102 AND 103.
CONTRACTOR SHALL COMPACT SOIL TO MEET ABAAS REQUIREMENTS FOR
ACCESSIBLE SURFACE.
DOORWAY WIDTH:
404.2.3 CLEAR WIDTH = 32" MIN.
ALL DOORS SHOWN ON ACCESSIBLE PATH MEET OR WILL MEET 32" MINIMUM
WIDTH.
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF8/
5/
2:
:0
P
M C
:\A ut oD es k S av e
Lo ca tio ns
\R ev it\
T
H R
O B ar n_ su si eh ac ke r@ an da rc h.
co m
.r vt
G0.8
NAA
THEODORE ROOSEVELT NATIONAL PARK
PEACEFUL VALLEY RANCH
138248
228216
DAM
KAC
08/06/2019 10 120
ACCESSIBILITY
SHEET - BARN
G0.8
BARN ACCESSIBILITY PLAN1
SCALE OF FEET
16808
SCALE A
SCALE A
NOTE:
CONCRETE FLOOR SLAB MUST BE INSTALLED FOR BARN TO BE
ACCESSIBLE. EITHER BY INCLUSION OF BID OPTION #3 IN THIS
PROJECT OR AS PART OF THE NEXT PHASE OF CONSTRUCTION.
EXISTING CONDITIONS
8-6-2019
TESC & DEMOLITION PLAN
SITE PLAN
GRADING PLAN
DETAILS I
N
O
R
T
H D
A
K
O
T
A
R
E
G I S
T
E
R
E
D
P
R
O
F
ES
S
I O
N
L
G
I N
E E
R
THANH
T. PHUONG
PE-10199
DATE 8/6/19
SCALE OF FEET
4020020
SCALE A
AutoCAD SHX Text METER / BASE (ROUGHRIDER NO. 110472) AND WP. 200A, 240/120V DIST. PANEL, MOUNTED TO POST.
AutoCAD SHX Text 12.47KV - 240/120V, PAD MOUNT TRANSFORMER ROUGHRIDER ELECTRIC COOPERATIVE NO. 7399.
AutoCAD SHX Text
MIDSTATE TELECOM, TELEPHONE SERVICE PEDESTAL
AutoCAD SHX Text
FLAG POLE WITHOUT ILLUMINATION SHALL REMAIN
AutoCAD SHX Text
SINGLE, DIRECT BURIED, TELEPHONE LINE BUILDING ENTRANCE POINT
AutoCAD SHX Text EXPOSED, 2" SCHED. 40 PVC LB TO CONDUIT BELOW GRADE FOR DIRECT BURIED 100A, 3W FEEDER. FEEDER TRANSITIONS TO 2" 'FMC IN BASEMENT TO ENTER LOAD CENTER.
AutoCAD SHX Text
DEMOLISH 100A BUS, 240/120V, LOAD CENTER IN BASEMENT.
AutoCAD SHX Text
DEMOLISH 240/120V, 8 CIRCUIT (60A BUS) LOAD CENTER
AutoCAD SHX Text
DEMOLISH 240/120V, 100A DISCONNECT IN WP ENCLOSURE
AutoCAD SHX Text
DEMOLISH 60A/2P LOAD CENTER
AutoCAD SHX Text
SINGLE, DIRECT BURIED, TELEPHONE LINE TO SERVICE PEDESTAL
AutoCAD SHX Text
DEMOLISH WP TERMINAL BOX WITH 100A TERMINALS FOR RANCH HOUSE FEEDER SPLICE.
AutoCAD SHX Text DEMOLISH TWO EXPOSED, 1-1/2" SCHED. 40 PVC LB TO CONDUIT BELOW GRADE FOR DIRECT BURIED 3W RANCH HOUSE FEEDER
AutoCAD SHX Text SINGLE, DB, TELEPHONE LINE BUILDING ENTRANCE POINT TO SERVICE PEDESTAL. ABANDON IN PLACE.
AutoCAD SHX Text M
AutoCAD SHX Text
BARN
AutoCAD SHX Text DEMOLISH 240V/120V, 60A DISCONNECT SWITCH IN WP ENCLOSURE WITH ADJACENT SURGE PROTECTION DEVICE.
AutoCAD SHX Text
PUMP HOUSE
AutoCAD SHX Text
POLE MOUNTED LUMINAIRE
AutoCAD SHX Text
RANCH HOUSE
AutoCAD SHX Text
BUNK HOUSE
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
TECH. REVIEW:
AutoCAD SHX Text
SUB SHEET NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
AutoCAD SHX Text
TITLE OF SHEET
AutoCAD SHX Text
ELECTRICAL SITE
AutoCAD SHX Text
DEMOLITION PLAN
AutoCAD SHX Text
AutoCAD SHX Text 138248
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 08/06/2019
AutoCAD SHX Text
THEODORE ROOSEVELT NATIONAL PARK
AutoCAD SHX Text
PEACEFUL VALLEY RANCH
AutoCAD SHX Text 228216
AutoCAD SHX Text
ES1
AutoCAD SHX Text
ELECTRICAL SITE DEMOLITION PLAN
AutoCAD SHX Text
AutoCAD SHX Text
ES1
AutoCAD SHX Text FILE: ES1 DEMO SITEPLN - PWR.DWG - LAYOUT1 | EDIT: 8/5/2019 10:34 AM BY KAYLAD | PLOT: 8/6/2019 3:34 PM BY KAYLA ES1 DEMO SITEPLN - PWR.DWG - LAYOUT1 | EDIT: 8/5/2019 10:34 AM BY KAYLAD | PLOT: 8/6/2019 3:34 PM BY KAYLA - LAYOUT1 | EDIT: 8/5/2019 10:34 AM BY KAYLAD | PLOT: 8/6/2019 3:34 PM BY KAYLA LAYOUT1 | EDIT: 8/5/2019 10:34 AM BY KAYLAD | PLOT: 8/6/2019 3:34 PM BY KAYLA | EDIT: 8/5/2019 10:34 AM BY KAYLAD | PLOT: 8/6/2019 3:34 PM BY KAYLA 8/5/2019 10:34 AM BY KAYLAD | PLOT: 8/6/2019 3:34 PM BY KAYLA BY KAYLAD | PLOT: 8/6/2019 3:34 PM BY KAYLA KAYLAD | PLOT: 8/6/2019 3:34 PM BY KAYLA | PLOT: 8/6/2019 3:34 PM BY KAYLA 8/6/2019 3:34 PM BY KAYLA BY KAYLA KAYLA DETTMANN
AutoCAD SHX Text
%%UKEYED SHEET NOTES
AutoCAD SHX Text EXISTING DIRECT BURY CONDUCTORS SHALL BE ABANDONED IN PLACE BELOW GRADE. REMOVE INTERIOR AND EXTERIOR, EXPOSED FEEDER CONDUIT AND CONDUCTORS. DISCONNECT AND REMOVE LUMINAIRE, ONLY. 10 INCH DIAMETER WOOD POLE AND CONDUCTORS IN EXPOSED RACEWAY SHALL REMAIN. REFER TO RANCH HOUSE PLANS FOR WORK TO INTERCEPT EXISITING BRANCH CIRCUIT AND EXTEND TO NEW LOAD CENTER. DEMOLISH EXISTING PAD AFTER ROUGHRIDER ELECTRIC COOPERATIVE REMOVES UTILITY TRANSFORMER #7399. EXISTING DIRECT BURIED COPPER TELEPHONE LINES SHALL BE ABANDONED IN PLACE. REMOVE INTERIOR AND EXTERIOR EXPOSED CABLE RACEWAY AND ENCLOSURES. COORDINATE WITH MIDSTATE TELECOM FOR REMOVAL OF EXISTING PEDESTAL. COORDINATE WITH OWNER FOR EXTENT OF NEW TELECOMMUNICATIONS SERVICE PROVIDED UNDER A SEPARATE CONTRACT. COORDINATE WITH MIDSTATE TELCOM.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SCALE OF FEET
4020020
SCALE A
N
O
R
T
H D
A
K
O
T
A
R
E
G I S
T
E
R
O
F
ES
S
I O
N
G
I N
E E
R
THANH
T. PHUONG
PE-10199
DATE 8/6/19
AutoCAD SHX Text PROVIDE VERTICAL, CORROSION RESISTANT STRUT ASSEMBLY, SUPPORTED WITH BELOW GRADE CONCRETE BASE. REFER TO SPECIFICATION SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS AND EQUIPMENT. SEE UTILITY SERVICE EQUIPMENT RACK DETAIL ON ES7.
AutoCAD SHX Text COORDINATE WITH ROUGHRIDER ELECTRIC TO REPLACE (E) PAD MOUNT TRANSFORMER NO. 7399 WITH NEW.
AutoCAD SHX Text
FLAG POLE WITHOUT ILLUMINATION
AutoCAD SHX Text BUILDING DISCONNECT. 125A/2P NEMA 3R. PROVIDE CB IN ENCLOSURE. INSTALL AT 5'-6" AFF. PROVIDE NEW GROUND ROD AND BOND TO EGC.
AutoCAD SHX Text
PROVIDE 125A/2P LOAD CENTER
AutoCAD SHX Text
PROVIDE NEW 24 CIRCUIT LOAD CENTER WITH 60A, 240/120V, 3W BUS
AutoCAD SHX Text
PROVIDE 200A BUS, 240/120V, LOAD CENTER.
AutoCAD SHX Text PROVIDE BUILDING DISCONNECT. 200A/2P CB IN NEMA 3R ENCLOSURE. INSTALL AT 5'-6" AFF. PROVIDE NEW GROUND RODS AND BOND TO GROUND AS SHOWN IN GROUNDING DETAIL ON ES7.
AutoCAD SHX Text EXPOSED, 1-1/2" SCHEDULE 40 PVC LB TO CONDUIT BELOW GRADE TO REMAIN WITH EXISTING 60A, 3W FEEDER WITH GND.
AutoCAD SHX Text M
AutoCAD SHX Text
BARN
AutoCAD SHX Text
PUMP HOUSE
AutoCAD SHX Text PROVIDE 240/120V, 60A DISCONNECT SWITCH IN WP ENCLOSURE WITH SURGE PROTECTION DEVICE. BOND EQUIPMENT GROUNDING CONDUCTOR TO ENCLOSURE.
AutoCAD SHX Text PROVIDE NEMA 3R TERMINAL/CT CABINET, METER BASE, MANUAL TRANSFER SWITCH, AND GENERATOR CONNECTION CABINET. MOUNT TO NEW STRUT ASSEMBLY.
AutoCAD SHX Text PROVIDE SERVICE RATED MAIN DISTRIBUTION PANELBOARD IN NEMA 3R ENCLOSURE. MOUNT TO NEW STRUT ASSEMBLY.
AutoCAD SHX Text
PROVIDE SUB METERS IN NEMA 3R LOCKING CABINET. MOUNT TO NEW STRUT ASSEMBLY.
AutoCAD SHX Text
WP
AutoCAD SHX Text
RANCH HOUSE
AutoCAD SHX Text
BUNKHOUSE
AutoCAD SHX Text
EXISTING DIRECT BURIED PUMP HOUSE FEEDER
AutoCAD SHX Text
'SE'
AutoCAD SHX Text
'SE'
AutoCAD SHX Text
'SE'
AutoCAD SHX Text
'SD'
AutoCAD SHX Text
PROVIDE 24" X 18" HANDHOLE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
RH-2
AutoCAD SHX Text
RH-2
AutoCAD SHX Text
RH-2
AutoCAD SHX Text
RH-31
AutoCAD SHX Text
RH-2
AutoCAD SHX Text
AutoCAD SHX Text
SEE DETAIL 3/ES6 FOR ROUND BOLLARD INSTALLATION.
AutoCAD SHX Text
INTERCEPT EXISTING FEEDER BELOW GRADE AND EXTEND NEW PANEL IN RIGID CONDUIT.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
UL/IP
AutoCAD SHX Text
RATING
AutoCAD SHX Text
DRIVER
AutoCAD SHX Text
LIGHT SOURCE(S)
AutoCAD SHX Text
MFG/CATALOG #
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
SD
AutoCAD SHX Text
REPLACEMENT EXTERIOR POLE MOUNTED LED RLM
AutoCAD SHX Text
NOMINAL 20-INCH DIAMETER BY 15-INCH HIGH SPUN ALUMINUM SHADE
AutoCAD SHX Text
4-INCH BY 4-INCH FROSTED GLASS GLOBE (MF2)
AutoCAD SHX Text MOUNTED TO EXISTING ROUND WOODEN POLE WITH CP104/PA15. COORDINATE INSTALLATION WITH EXISTING CONDUIT AND CONDITIONS.
AutoCAD SHX Text
STANDARD FINISH AS SELECTED BY CONTRACTING OFFICER
AutoCAD SHX Text
WET
AutoCAD SHX Text
0-10 VOLT DIMMING, ELECTRONIC DRIVER
AutoCAD SHX Text
NOMINAL 2000 LUMENS, 2700K, 80 CRI
AutoCAD SHX Text
16 WATTS
AutoCAD SHX Text
SPECTRUM LIGHTING EXPANDED DOME CLASSIC SERIES, BARN LIGHT ELECTRIC OR APPROVED
AutoCAD SHX Text
SE
AutoCAD SHX Text
EXTERIOR LED BOLLARD
AutoCAD SHX Text
NOMINAL 10-INCH WIDE BY 5.5-INCH DEEP BY 42-INCH TALL WOODEN HOUSING
AutoCAD SHX Text
CLEAR GLASS DIFFUSER
AutoCAD SHX Text
COORDINATE LOCATION WITH LANDSCAPE DRAWINGS. PROVIDE FLUSH MOUNTED BASE.
AutoCAD SHX Text
STANDARD FINISH AS SELECTED BY CONTRACTING OFFICER
AutoCAD SHX Text
WET
AutoCAD SHX Text
0-10 VOLT DIMMING, ELECTRONIC DRIVER
AutoCAD SHX Text
NOMINAL 435 LUMENS, 2700K,
AutoCAD SHX Text
12 WATTS
AutoCAD SHX Text
STRUCTURA MAC II SERIES, SISTEMALUX OR APPROVED
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LUMINAIRE SCHEDULE - SITE
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
HOUSING
AutoCAD SHX Text
SHIELDING
AutoCAD SHX Text
MOUNTING
AutoCAD SHX Text
FINISH
AutoCAD SHX Text
INPUT WATTS
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text THIS LUMINAIRE SCHEDULE IS NOT COMPLETE…