A06_G1G2G3.pdf
PDF 2 MB Posted
- Attached to
- GAOA MT LEWIS RADIO SAFETY REPAIRS
- Solicitation number
- 140L3924Q0127
About this file
This document appears to be a set of typical construction drawings and specifications related to a federal contract opportunity for radio safety repairs at Mt. Lewis.
The drawings provide detailed technical specifications for the grounding system, equipment racks, electrical distribution, underground utilities, fencing, and ice bridge construction. Key elements include grounding bus bars, ground rings, lightning protection, equipment layout, electrical service, and perimeter security fencing. The related federal contract opportunity is for the GAOA MT LEWIS RADIO SAFETY REPAIRS, solicited by the Department of the Interior Bureau of Land Management Nevada Region. The solicitation number is 140L3924Q0127. No additional details about the contract opportunity, such as response dates, award information, or pricing, are provided in this document.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| A04_Mt_Lewis_SOW_5-24-24.docx | DOCX document | |
| Sol_140L3924Q0127.pdf | ||
| A06_Mount_Lewis_-_dwg_set_5-20-24.pdf | ||
| B03_Wage_Determinations_Lander_Building_NV20240036.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
G1
T Y
P
IC
A L
D R
A W
IN
G
/2
8/
S ta nd ar d C o ns tr u ct io n S p ec ifi ca tio ns
C on tr ac to r
T ec h ni ca l E va lu a tio n
D e ve lo pm en t S e rv ic e s, L
LC
Te d
Su m ne rs
1 3
NOT TO SCALE NOT TO SCALE NOT TO SCALE
TYPCAL FACILITY GROUNDING DETAILS
RF CABLE GROUND KIT
TOWER GROUND BUS BAR (TGB)
NOTE: EXOTHERMIC WELD CONNECTIONS BELOW GRADE
#2 AWG OR COARSER, BARE, SOLID, TINNED
COPPER WIRE USING TWO-HOLE CONNECTION W/
STAINLESS STEEL HARDWARE TO GRIPSTRUT
RF SURGE PROTECTION DEVICE
MASTER GROUND BUS BAR (MGB)
EXTERNAL GROUND BUS BAR (EGB)
RF CABLE GROUND KIT
#2 AWG TINNED, SOLID COPPER
CONDUCTOR BONDING TGB TO
TOWER GROUND RING
EXOTHERMIC WELD
CONNECTIONS TO POSTS
#2 AWG TINNED, SOLID COPPER
CONDUCTOR BONDING MGB TO
SHELTER GROUND RING
EXOTHERMIC WELD
CONNECTIONS TO POSTS
9 TOWER LEG GROUNDING
#2 AWG TINNED, SOLID COPPER
CONDUCTOR BONDING EACH TOWER
LEG TO TOWER GROUND RING
TOWER GROUND RING
#2 AWG TINNED, SOLID COPPER
CONDUCTOR
SHELTER GROUND RING
#2 AWG TINNED, SOLID COPPER
CONDUCTOR
SELF-SUPPORTING ICE
BRIDGE GROUNDING
13GROUND SHELTER
FRAME AT EACH CORNER
Grade
EXTERNAL GROUND BUS BAR (EGB) DETAIL
RF CABLE ENTRANCE
PANEL AND OTHER
ANCILLARY DEVICES WITH
SINGLE-HOLE IRREVERSIBLE
HIGH-COMPRESSION LUGS
NOTE: CONTRACTOR TO USE LISTED ANTIOXIDANT AGENT BETWEEN
MECHANICAL BONDING CONNECTIONS.
RF CABLE GROUND KITS OR OTHER DEVICES WITH
TWO-HOLE IRREVERSIBLE HIGH-COMPRESSION LUGS
4.6"
7"
0.25"
#2 AWG, SOLID TINNED COPPER CONDUCTORS TO SHELTER
GROUND RING WITH EXOTHERMIC OR IRREVERSIBLE HIGH
COMPRESSION CONNECTIONS
TINNED COPPER GROUND BUS BAR
(TYPICAL: 4" x 12" x 1/4" ) (MINIMUM: 2" x 12" x 1/4" )
12"
4"
EXTERNAL GROUND BUS BAR (EGB) DETAIL
RF CABLE ENTRANCE
PANEL AND OTHER
ANCILLARY DEVICES WITH
SINGLE-HOLE IRREVERSIBLE
HIGH-COMPRESSION LUGS
NOTE: CONTRACTOR TO USE LISTED ANTIOXIDANT AGENT BETWEEN
MECHANICAL BONDING CONNECTIONS.
RF CABLE GROUND KITS OR OTHER DEVICES WITH
TWO-HOLE IRREVERSIBLE HIGH-COMPRESSION LUGS
4.6"
7"
0.25"
#2 AWG, SOLID TINNED COPPER CONDUCTORS TO SHELTER
GROUND RING WITH EXOTHERMIC OR IRREVERSIBLE HIGH
COMPRESSION CONNECTIONS
TINNED COPPER GROUND BUS BAR
(TYPICAL: 4" x 12" x 1/4" ) (MINIMUM: 2" x 12" x 1/4" )
12"
4"
TOWER GROUND BUS BAR (TGB) DETAIL
RF CABLE
GROUND KIT TINNED COPPER GROUND BUS BAR
(TYPICAL: 4" x 12" x 1/4" ) (MINIMUM: 2" x 12" x 1/4" )
#2 AWG, SOLID TINNED COPPER
CONDUCTORS TO TOWER GROUND RING WITH EXOTHERMIC
OR IRREVERSIBLE HIGH COMPRESSION CONNECTIONS
4"
12"
0.25"0.25"
0.25"0.25"
OPTION 2: TINNED COPPER BUS
BARS MAY BE FASTENED
DIRECTLY TO TOWER WITH NO
ISOLATORS USING BEAM CLAMPS
OR ROUND MEMBER ADAPTERS
OPTION 1: BARE AND TINNED COPPER
BUS BARS FASTENED TO THE TOWER
WITH ISOLATORS (PREFFERED)
TOWER GROUND BUS BAR (TGB) DETAIL
RF CABLE
GROUND KIT TINNED COPPER GROUND BUS BAR
(TYPICAL: 4" x 12" x 1/4" ) (MINIMUM: 2" x 12" x 1/4" )
#2 AWG, SOLID TINNED COPPER
CONDUCTORS TO TOWER GROUND RING WITH EXOTHERMIC
OR IRREVERSIBLE HIGH COMPRESSION CONNECTIONS
4"
12"
0.25"
0.25"
OPTION 2: TINNED COPPER BUS
BARS MAY BE FASTENED
DIRECTLY TO TOWER WITH NO
ISOLATORS USING BEAM CLAMPS
OR ROUND MEMBER ADAPTERS
OPTION 1: BARE AND TINNED COPPER
BUS BARS FASTENED TO THE TOWER
WITH ISOLATORS (PREFFERED)
MASTER GROUND BUS BAR (MGB) DETAIL
NOT TO SCALE
INTERNAL PERIMETER GROUND
#2 AWG Green-Jacketed (Two-Hole)
NOTE:
CONTRACTOR TO USE LISTED ANTIOXIDANT AGENT BETWEEN MECHANICAL BONDING CONNECTIONS.
RF SURGE PROTECTION DEVICES
#6 AWG Green-Jacketed (Single-Hole) 22
4.6"
7"
0.25"
#2 AWG, SOLID TINNED COPPER CONDUCTOR TO
SHELTER GROUND RING WITH EXOTHERMIC OR
IRREVERSIBLE HIGH COMPRESSION CONNECTIONS
16 16
RACK GROUND BUS BARS
#2 AWG Green-Jacketed (Two-Hole) 17 13 ANCILLARY DEVICE GROUNDING
#6 AWG Green-Jacketed (Two-Hole)
BARE COPPER GROUND BUS BAR
(TYPICAL: 4" x 12" x 1/4" ) (MINIMUM: 2" x 12" x 1/4" )
INTERNAL PERIMETER GROUND
#2 AWG Green-Jacketed (Two-Hole)
MASTER GROUND BUS BAR (MGB) DETAIL
NOT TO SCALE
INTERNAL PERIMETER GROUND
#2 AWG Green-Jacketed (Two-Hole)
NOTE:
CONTRACTOR TO USE LISTED ANTIOXIDANT AGENT BETWEEN MECHANICAL BONDING CONNECTIONS.
RF SURGE PROTECTION DEVICES
#6 AWG Green-Jacketed (Single-Hole) 22
4.6"
7"
0.25"
#2 AWG, SOLID TINNED COPPER CONDUCTOR TO
SHELTER GROUND RING WITH EXOTHERMIC OR
IRREVERSIBLE HIGH COMPRESSION CONNECTIONS
16 16
RACK GROUND BUS BARS
#2 AWG Green-Jacketed (Two-Hole) 17 13 ANCILLARY DEVICE GROUNDING
#6 AWG Green-Jacketed (Two-Hole)
BARE COPPER GROUND BUS BAR
(TYPICAL: 4" x 12" x 1/4" ) (MINIMUM: 2" x 12" x 1/4" )
INTERNAL PERIMETER GROUND
#2 AWG Green-Jacketed (Two-Hole)
GROUNDING SYSTEM INSPECTION WELL
3/4" CRUSHED
STONE OR EQUAL
5/8" DIA. X 10'-0" LONG COPPER
CLAD GROUND ROD
EXOTHERMIC WELD
CONNECTION (TYPE GT)
#2 AWG OR COARSER, BARE, SOLID,
TINNED, COPPER CONDUCTOR
EXOTHERMIC WELD CONNECTION TO
GROUND BAR.
SHELTER AND TOWER
GROUND RINGS
#2 AWG OR COARSER, BARE, SOLID,
TINNED COPPER WIRE TEST LOOP
EXTENSION
10" DIA. X 30" DEEP INSPECTION WELL.
#2 AWG OR COARSER, BARE,
SOLID, TINNED COPPER WIRE
EXOTHERMIC WELD
CONNECTION TO GROUND ROD.
2' -6
B
E
LO
W G
R A
D E
1" M
A X
7 8
GROUNDING SYSTEM INSPECTION WELL
3/4" CRUSHED
STONE OR EQUAL
5/8" DIA. X 10'-0" LONG COPPER
CLAD GROUND ROD
EXOTHERMIC WELD
CONNECTION (TYPE GT)
#2 AWG OR COARSER, BARE, SOLID,
TINNED, COPPER CONDUCTOR
EXOTHERMIC WELD CONNECTION TO
GROUND BAR.
SHELTER AND TOWER
GROUND RINGS
#2 AWG OR COARSER, BARE, SOLID,
TINNED COPPER WIRE TEST LOOP
EXTENSION
10" DIA. X 30" DEEP INSPECTION WELL.
#2 AWG OR COARSER, BARE,
SOLID, TINNED COPPER WIRE
EXOTHERMIC WELD
CONNECTION TO GROUND ROD.
2' -6
B
E
LO
W G
R A
D E
1" M
A X
7 8
MECHANICAL GROUND
CONNECTION DETAILS
ANCILLARY DEVICE
BONDING
SURFACE OR BUS
BAR
REMOVE PAINT (IF PRESENT) AND APPLY A LISTED ANTIOXIDANT
COMPOUND BETWEEN MECHANICAL CONNECTIONS
TWO-HOLE
CONNECTOR
NOTE:
USE UL-467 LISTED IRREVERSABLE HIGH COMPRESSION CRIMP
CONNECTORS FASTENED WITH STAINLESS STEEL THRU BOLTED
HARDWARE INCLUDING STAR AND LOCKWASHERS
SINGLE-HOLE
CONNECTOR
EXOTHERMIC WELD CONNECTION DETAILS
TYPE GT
THROUGH CABLE TO
TOP OF GROUND ROD
TYPE HS
HORIZONTAL CABLE TAP
TO HORIZONTAL STEEL
SURFACE OR PIPE
TYPE TA
TEE OF HORIZONTAL
RUN AND TAP CABLES
TYPE XB
CROSS OF
HORIZONTAL CABLES.
LAPPED AND NOT CUT.
TYPE VN
HORIZONTAL CABLE
TAP TO VERTICAL
STEEL SURFACE OR
THE SIDE OF
HORIZONTAL PIPE
TYPE VS
CABLE TAP DOWN AT 45°
TO VERTICAL STEEL
SURFACE OR SIDE OF
HORIZONTAL OR VERTICAL
PIPE.
TYPE NC
THROUGH AN TAP
CABLES TO GROUND
ROD
EXOTHERMIC WELD CONNECTION DETAILS
TYPE GT
THROUGH CABLE TO
TOP OF GROUND ROD
TYPE HS
HORIZONTAL CABLE TAP
TO HORIZONTAL STEEL
SURFACE OR PIPE
TYPE TA
TEE OF HORIZONTAL
RUN AND TAP CABLES
TYPE XB
CROSS OF
HORIZONTAL CABLES.
LAPPED AND NOT CUT.
TYPE VN
HORIZONTAL CABLE
TAP TO VERTICAL
STEEL SURFACE OR
THE SIDE OF
HORIZONTAL PIPE
TYPE VS
CABLE TAP DOWN AT 45°
TO VERTICAL STEEL
SURFACE OR SIDE OF
HORIZONTAL OR VERTICAL
PIPE.
TYPE NC
THROUGH AN TAP
CABLES TO GROUND
ROD
26"
MAX
11"
27"
38"
6" WIDE UTILITY WARNING TAPE (12" ABOVE
UNDERGROUND INSTALLATION)
UNDISTURBED SOIL
COMPACTED BACKFILL 95% STANDARD
PROCTOR, WITHIN 2% OF OPTIMUM
MOISTURE CONTENT
BACKFILL (CLEAN GRANULAR FILL SAND)
ELECTRICAL CONDUIT BELOW GRADE,
GENERATOR TO TRANSFER SWITCH (4"
SCHED 40 PVC CONDUIT)
TELEPHONE/DATA CONDUIT
(2" SCHED 40 PVC CONDUIT)
NOTES:
1. SEPARATION DIMENSION TO BE VERIFIED WITH LOCAL UTILITY COMPANY REQUIREMENTS.
2. PULL STRINGS SHALL BE INSTALLED IN CONDUITS
3. ELECTRICAL INSTALLATION WORK SHALL BE IN ACCORDANCE WITH THE CURRENT
EDITION OF THE NFPA 70.
4. UNDERGROUND SERVICE ENTRANCE CONDUCTORS SHALL BE PROTECTED FROM
PHYSICAL DAMAGE PER NFPA 70 ARTICLE 300.5
ELECTRICAL CONDUIT BELOW GRADE, PRIMARY
DIST PANEL TO SUBPANEL (2" SCHED 40 PVC
CONDUIT)
JOINT UTILITY TRENCH DETAILUTILITY TRENCH DETAIL
NOTES:
1. ALL UNDERGROUND PRIMARY CABLE SHALL BE MARKED USING MARKING TAPE.
2. THE MARKING TAPE SHALL BE PLACED APPROXIMATELY 12 INCHES ABOVE THE
UNDERGROUND INSTALLATION, WHILE BACKFILLING CABLE TRENCH.
3. SELECTED BACKFILL OF ROCK-FREE SOIL SHALL BE PLACED IN 6 INCH LAYERS AT A
TIME AND EACH LAYER WELL COMPACTED.
4. MINIMUM 24" COVER OVER CONDUIT.
4" ELECTRICAL SERVICE (SCH 40 PVC
CONDUIT) OR DIRECT BURY SERVICE CABLE
COMPACTED SELECT, ROCK FREE
BACKFILL (SUITABLE ON SITE MATERIAL)
OR SAND OR PEA GRAVEL DEPENDING ON
SITE CONDITIONS.
6" WIDE UTILITY WARNING TAPE (12"
ABOVE UNDERGROUND INSTALLATION)
COMPACTED SELECT BACKFILL (ROCK-FREE)
12"
M
IN
C O
V E
R
8"
26"
MAX
CONCRETE ENCASED ELECTRODE (UFER)
20-foot minimum
Concrete Encased Electrode using Reinforcing Bar
UL 467 Listed Clamp Suitable for Encasement or Exothermic Weld
20-foot minimum
Concrete Encased Electrode using #4 AWG or Larger Conductor
#2 AWG, Copper Conductor
#2 AWG, Copper Conductor
UL 467 Listed Clamp Suitable for
Encasement or Exothermic Weld
#2 AWG, Copper Conductor
2" Min
2" Min
½� Diameter Reinforcing Bar or Greater
BOLLARD INSTALLATION
4" WIDE PAINTED BANDS
(8 EACH)(2"- 8") ALTERNATE
YELLOW AND BLACK BANDS.
TELLOW BAND AT TOP (CARSONITE
SAV-T-SLEEVE GUARD POST
COVER)
4' -0
1'-0" DIA
YELLOW
FINISH GRADE
FOUNDATION4'
-0
6"
4" O.D. GALVANIZED
PIPE W/ DOME CAP
(FILL W/ CONCRETE)
G2
Y
P
IC
A L
D R
A W
IN
G
/2
8/
S ta nd ar d C o ns tr u ct io n S p ec ifi ca tr ac to r
T ec h ni ca l E va lu a tio n
D e ve lo pm en t S e rv ic e s, L
LC
Te d
Su m ne rs
2 3
EQUIPMENT RACK BASE INSTALLATION
Daniels VHF Repeater (21.9 lbs.)
Daniels VHF Repeater (21.9 lbs.)
Daniels TN445 Amp (10 lbs.)
Daniels TN445 Amp (10 lbs.)
Telewave Duplexer TPRD- 1554 UHF (19 lbs.)
Telewave Duplexer TPRD- 1554 UHF (19 lbs.)
Motorola Quantar � UHF (55 lbs.)
MOTO
ROLA
O
FF
O N
MOTO
ROLA
O
FF
O N
Motorola Quantar � UHF (55 lbs.)
MOTO
ROLA
O
FF
O N
Sunlyte 12-5000X Batteries (70.4 lbs. ea. x 3 = 281.6 lbs.)
PRIMARY SPD
PRIMARY SURGE PROTECTION DEVICE (SPD) TYPICAL
SURGE PROTECTION DEVICE (SPD
TYPE 1 SAD/MOV
METER
MAIN SERVICE
DISCONNECT
ELECTRICAL
DISTRIBUTION
PANEL
TYPE 3 SPD OPTIONAL WHEN
GREATER THAN 10 CONDUCTOR
FEET FROM PANELBOARD
CRITICAL
LOADS
ELECTRICAL SERVICE ENTRANCE 240/120 VAC
SINGLE PHASE OR 208/120 VAC 3 PHASE
TO ALARMS PANEL
(RECOMMENDED)
H
TYPE 3 SPD
AT EQUIPMENT
SEE SECTION 13 34 18
2 MASTER GROUND BUS BAR (MGB
2NEUTRAL-TO-GROUND BOND
EXOTHERMIC WELD CONNECTION (TYPE NC)
SHELTER GROUND RING 7
#2 AWG, TINNED SOLID COPPER CONDUCTOR 5
NON-CRITICAL
LOADS
NON-CRITICAL
LOADS
DEDICATED 20-AMP CIRCUIT TO EACH
RADIO/ EQUIPMENT RACK/DISPATCH EQUIP.
USE FOR SEISMIC ZONES 0-2b USE FOR ZONES 3-4
NON-SEISMIC SEISMIC
4 ANCHOR
BOLTS
6 ANCHOR
BOLTS
3 4
30 in.
Minimum Workspace
From Furthest Extending
Device
30 in.
Minimum Workspace
From Furthest Extending
Device
Attach Equipment Rack to Cable Ladder or Ceiling in Seismic Zones 3 and 4
84-inch High, 19-inch EIA Equipment Rack
TYPICAL EQUIPMENT RACK AND RADIO EQUIPMENT INSTALLATION
2 2
19"
Battery Shelf - 29"
17 Rack Ground Bus Bar
17"
16.5"
14.75"
84-inch High, 19-inch EIA Equipment Rack (87 lbs.)
TOTAL WEIGHT = 490.5 lbs.
Rack Base Dimensions:
1.25 ft. x 1.71 ft. =2.14 ft2
Floor Load = 229.2 lbs. ft2
Telewave Duplexer TPRD- 4546 UHF (16 lbs.)
Telewave Duplexer TPRD- 4546 UHF (16 lbs.)
H
N
Daniels Power Supply
Daniels Repeater
Motorola Quantar
Ground All Devices to RGB with #6 AWG, St randed Green-Jacketed Grounding
Conductors
To MGB
TYPICAL COMPOUND GRAVEL
INSTALLATION DETAIL
6 INCHES #57 WASHED STONE (SLOPE TO MAINTAIN POSITIVE
DRAINAGE. COMPACT TO 90% OF THE STANDARD PROCTOR
MAXIMUM DRY DENSITY (ASTMD-698)
6 MIL MIRAFI 500 WEED CONTROL FABRIC OR APPROVED EQUAL
WITH 36 INCHES MINIMUM OVERLAP. FABRIC TO BE INSTALLED
PER MANUFACTURER�S RECOMMENDATIONS
12 INCHES SUITABLE UNDISTRURBED SUBGRADE. REMOVE ALL
ORGANIC OR UNSUITABLE MATERIAL AND COMPACT TO 90% OF
THE STANDARD PROCTOR MAXIMUM DRY DENSITY (ASTMD-698)
AA
BB
CC
AA
B
C
A
B
C
NOT TO SCALE
DETERRENT WIRE GROUNDING CLAMP
(1 OF 3)
FENCE FABRIC GROUNDING CLAMP
(1 OF 3)
#2 AWG TINNED, SOLID COPPER
CONDUCTOR BONDING FENCE FABRIC
TO GROUND CONDUCTOR
CONNECT FENCE BONDING CONDUCTOR
TO FENCE GROUNDING CONDUCTOR
USING EXOTHERMIC WELD
FENCE CORNER GROUNDING DETAIL
#2 AWG TINNED, SOLID COPPER
CONDUCTOR BONDING FENCE POST TO
SHELTER OR TOWER GROUND RING
#6 AWG TINNED, SOLID COPPER
CONDUCTOR BONDING FENCE
RAIL TO FENCE POST WITH
EXOTHERMIC WELDS
NOT TO SCALE
DETERRENT WIRE GROUNDING CLAMP
(1 OF 3)
FENCE FABRIC GROUNDING CLAMP
(1 OF 3)
#2 AWG TINNED, SOLID COPPER
CONDUCTOR BONDING FENCE FABRIC
TO GROUND CONDUCTOR
CONNECT FENCE BONDING CONDUCTOR
TO FENCE GROUNDING CONDUCTOR
USING EXOTHERMIC WELD
FENCE CORNER GROUNDING DETAIL
#2 AWG TINNED, SOLID COPPER
CONDUCTOR BONDING FENCE POST TO
SHELTER OR TOWER GROUND RING
#6 AWG TINNED, SOLID COPPER
CONDUCTOR BONDING FENCE
RAIL TO FENCE POST WITH
EXOTHERMIC WELDS
TELEPHONE SERVICE ENTRANCE
4" DIA. SCHED 40 PVC CONDUIT
FOR TELEPHONE SERVICE
12" X 12" X 6" WEATHER PROOF JUNCTION
BOX FOR TELEPHONE SERVICE ENTRANCE
NOT TO SCALE
#2 AWG TINNED, SOLID COPPER
CONDUCTOR BONDING EACH
GATEPOST TO THE SHELTER OR
TOWER GROUND RING
#6 AWG FLEXIBLE,
STRANDED COPPER
CONDUCTOR BONDING
EACH GATE TO GATEPOST
#6 AWG TINNED, SOLID
COPPER CONDUCTOR
BONDING FENCE RAIL TO
GATEPOST WITH
EXOTHERMIC WELDS
#2 AWG TINNED, SOLID COPPER
CONDUCTOR BONDING EACH
GATEPOST TO THE SHELTER OR
TOWER GROUND RING
#6 AWG FLEXIBLE,
STRANDED COPPER
CONDUCTOR BONDING
EACH GATE TO GATEPOST
#6 AWG TINNED, SOLID
COPPER CONDUCTOR
BONDING FENCE RAIL TO
GATEPOST WITH
EXOTHERMIC WELDS
GATE GROUNDING DETAIL
#2 AWG TINNED, SOLID COPPER
CONDUCTOR BONDING EACH
GATEPOST TO THE SHELTER OR
TOWER GROUND RING
#6 AWG FLEXIBLE,
STRANDED COPPER
CONDUCTOR BONDING
EACH GATE TO GATEPOST
#6 AWG TINNED, SOLID
COPPER CONDUCTOR
BONDING FENCE RAIL TO
GATEPOST WITH
EXOTHERMIC WELDS
GATE GROUNDING DETAIL
30"
5/8" DIA. X 8'-0" LONG
COPPER CLAD GROUND ROD
EXOTHERMIC WELD
CONNECTION (TYPE NC)
36"
SHELTER
GROUND RING
GROUND TELEPHONE
SERVICE CABLE SHIELD
GROUND TELEPHONE SERVICE
ENTRANCE SURGE PROTECTION
#2 AWG, TINNED SOLID
COPPER CONDUCTOR
ELECTRICAL SERVICE GROUNDING - OCCUPIED
5/8" DIA. X 8'-0" LONG
COPPER CLAD GROUND ROD
BOND BETWEEN UTILITY
GROUND AND SHELTER
GROUND RING, #2 AWG, TINNED
SOLID COPPER CONDUCTOR
EXOTHERMIC WELD
CONNECTION (TYPE NC)
TWO-HOLE CONNECTION WITH
THRU-BOLTED STAINLESS
STEEL HARDWARE INCLUDING
STAR OR LOCK WASHER
SERVICE-DISCONNECT
SWITCH & METER 1
2NEUTRAL-TO-GROUND BOND
30"
36"
ELECTRICAL
DISTRIBUTION PANEL
PRIMARY SURGE
PROTECTION
2 MASTER GROUND BUS BAR
20 CONCRETE ENCASE
ELECTRODE (UFER)
G3
Y
P
IC
A L
D R
A W
IN
G
/2
8/
S ta nd ar d C o ns tr u ct io n S p ec ifi ca tr ac to r
T ec h ni ca l E va lu a tio n
D e ve lo pm en t S e rv ic e s, L
LC
Te d
Su m ne rs
3 3
RF CABLE
GROUND KIT
TOWER GROUND
BUS BAR (TGB)
GROUND ICE BRIDGE TO EGB and TGB
#2 AWG OR COARSER, BARE, SOLID, TINNED COPPER WIRE USING TWO-HOLE
CONNECTION W/STAINLESS STEEL HARDWARE TO GRIPSTRUT
EXTERNAL GROUND
BUS BAR (EGB)
RF CABLE
GROUND KIT
TOWER GROUND RING
#2 AWG TINNED, SOLID COPPER
CONDUCTOR
SHELTER GROUND RING
#2 AWG TINNED, SOLID COPPER
CONDUCTOR
NON-SELF-SUPPORTING ICE BRIDGE GROUNDING
Grade
15 kV ISOLATORS AT TOWER
CONNECTION
GROUND ICE BRIDGE TO EACH VERTICAL SUPPORT POST WITH #2 AWG OR COARSER, BARE,
SOLID, TINNED COPPER WIRE USING TWO-HOLE CONNECTION W/STAINLESS STEEL
HARDWARE TO GRIPSTRUT
EXOTHERMIC WELD
CONNECTIONS TO POSTS
SELF-SUPPORTING ICE BRIDGE
GROUNDING
Grade
RF CABLE
GROUND KIT
TOWER GROUND
BUS BAR (TGB)
EXTERNAL GROUND
BUS BAR (EGB)
RF CABLE
GROUND KIT
2 21
TOWER GROUND RING
#2 AWG TINNED, SOLID COPPER
CONDUCTOR
SHELTER GROUND RING
#2 AWG TINNED, SOLID COPPER
CONDUCTOR
SELF-SUPPORTING ICE BRIDGE GROUNDING
Grade
BOND ICE BRIDGE SEGMENTS
TOGETHER WITH #2BARE, SOLID,
TINNED COPPER WIRE USING
TWO-HOLE CONNECTION
MINIMUM 4-
INCH GAP
MINIMUM 4-
INCH GAP
GROUND VERTICAL SUPPORT POSTS
WITH #2 AWG OR COARSER, BARE,
SOLID, TINNED COPPER WIRE
ICE BRIDGE INSTALLATION DETAIL
SET POSTS IN CONCRETE
MIN. 300 psi
GRIP STRUT
EQUIPMENT
SHELTER
COAX
PORTS
4" to 6" DIAMETER
GALVANIZED
SUPPORT POSTS
7' MIN
3.5' MIN
8' MAX
BETWEEN POSTS
6" MAX
2" MIN
RF CABLE
SUPPORT
BRACKETS
24" O.C. MAX
6" MAX
2" MIN
TOWER
19 VERTICAL SUPPORT POST DETAIL
METAL PIPE CAP
SUPPORT ARM ANGLE 5" X 3"
X 1/4"
ICE BRIDGE CABLE SUPPORT
BRACKET (Trapeze) AT 24" O.C.
MAX
4" O.D. PIPE (SCH 40)
GRADE LEVEL
8' MIN
12"
MIN
12"
MIN
SAFETY GRATING
18"
3.5' MIN
18"
3.5' MIN
N3.5' MIN
ICE BRIDGE INSTALLATION DETAIL
SET POSTS IN CONCRETE
MIN. 300 psi
GRIP STRUT
EQUIPMENT
SHELTER
COAX
PORTS
4" to 6" DIAMETER
GALVANIZED
SUPPORT POSTS
7' MIN
3.5' MIN
8' MAX
BETWEEN POSTS
6" MAX
2" MIN
RF CABLE
SUPPORT
BRACKETS
24" O.C. MAX
6" MAX
2" MIN
TOWER
19 VERTICAL SUPPORT POST DETAIL
METAL PIPE CAP
SUPPORT ARM ANGLE 5" X 3"
X 1/4"
ICE BRIDGE CABLE SUPPORT
BRACKET (Trapeze) AT 24" O.C.
MAX
4" O.D. PIPE (SCH 40)
GRADE LEVEL
8' MIN
12"
NNMIN
12"
MIN
SAFETY GRATING
18"
3.5' MIN
PERIMETER FENCE INSTALLATION DETAIL
6'
0" 3'
10"
45°
THREE STRANDS, No. 12.5 GAUGE
BARBED WIRE WITH TYPE 1 ZINC GALVANIZING, 4 POINT
BARBS
SPACED 5" APART
TOP RAIL
FABRIC TIES TO BE MINIMUM No.
9 GAUGE ALUMINUM WIRE
2" MESH
ZINC-COATED STEEL, (TYPE 1 ZINC COATING), CHAIN LINK
FABRIC TO BE PROPERLY TENSIONED AND CLIPPED
SET ALL FENCE POSTS IN CONC., MIN. 300 psi
STRENGTH
NOTE:
ALL STEEL PIPE RAILS AND FITTINGS TO BE SCHEDULE 40 HOT
DIPPED GALVANIZED TO CLASS 1 STANDARDS
2" DIA POST
FIN. GRADE
No. 7 GAUGE SPRING COIL TENSION WIRE
PERIMETER FENCE INSTALLATION DETAIL
6'
0" 3'
10"
45°
THREE STRANDS, No. 12.5 GAUGE
BARBED WIRE WITH TYPE 1 ZINC GALVANIZING, 4 POINT
BARBS
SPACED 5" APART
TOP RAIL
FABRIC TIES TO BE MINIMUM No.
9 GAUGE ALUMINUM WIRE
2" MESH
ZINC-COATED STEEL, (TYPE 1 ZINC COATING), CHAIN LINK
FABRIC TO BE PROPERLY TENSIONED AND CLIPPED
SET ALL FENCE POSTS IN CONC., MIN. 300 psi
STRENGTH
NOTE:
ALL STEEL PIPE RAILS AND FITTINGS TO BE SCHEDULE 40 HOT
DIPPED GALVANIZED TO CLASS 1 STANDARDS
2" DIA POST
FIN. GRADE
No. 7 GAUGE SPRING COIL TENSION WIRE
File details come from the government source that posted it. Updated .