Solicitation Number 140L3922Q0117 Cold Springs Workplex Questions & Answers
Q1) The scope doesn’t mention windows, but I believe the drawings shows some. Are windows required?
A1) Yes, windows are required.
Q2) Where would you like the fourth door to the exterior placed?
A2) The 4th door location can be in any feasible location that does not compromise structural integrity.
Q3) Are data ports and phone jacks required?
A3) Data ports/phone jacks are required.
Q4) Does the main power from the office to the transformer need to be placed per our scope? If so; Aerial or underground? What is the distance?
A4) Main power will come off of the main drop for the fire station. Electrical hookup is the responsibility of the vendor. Will be aerial and depending on orientation of the temporary building anticipated to be less than 40'.
Q5) What is the voltage at the transformer?
A5) The line to the fire station is a standard drop and would tap the line post transformer/step down.