About this file
Architects Supplemental Instructions (ASI #001)
This is an Architects Supplemental Instructions document dated October 1, 2026, issued by the Bureau of Indian Affairs for the Rosebud Agency Boiler & HVAC System Design project for Building #1004. The ASI modifies the mechanical design by revising the Dedicated Outdoor Air System (DOAS) ductwork routing on sheets MH101 and MH102. Specifically, the instruction changes 74 existing ventilation air connections that were originally ducted directly to variable refrigerant flow fan coil units. Of these connections, 70 will be rerouted from direct unit connections to sidewall grille connections, while four basement areas will be ducted to supply diffusers inside their respective rooms. The ventilation air will terminate at a 4-inch round duct connected to a double deflection sidewall grille rather than connecting to the variable refrigerant blower coil as originally designed. The sidewall grilles must be positioned on the opposite side of the corridor wall, away from transfer grilles, to ensure proper air circulation and mixing. Revised mechanical sheets MH101 and MH102 and supplemental sheet MH702 (detailing the proper double deflection sidewall grille specifications) accompany this instruction and must be referenced for the new ductwork routing.
The document was issued by Bradley J. Kennedy, a Professional Mechanical Engineer (Nebraska License E-17695), and distributed to the project file and the Bureau of Indian Affairs. Supporting mechanical schedules on sheet M-702 provide detailed equipment specifications including dedicated outdoor air unit schedules, electric cabinet and unit heater schedules, fan schedules, register-grille-diffuser schedules, and plumbing pump specifications for the HVAC system design.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECTS SUPPLEMENTAL INSTRUCTIONS (ASI)
ASI NUMBER: 001
DATE: 10/1/2026
PROJECT: Rosebud Agency Boiler & HVAC System Design Building #1004 OWNER/AGENT: Bureau of Indian Affairs
CONTRACTOR:
DISTRIBUTION: X File X Owner/Agent (BIA) By BIA Contractor
1. Original Mechanical Sheets MH101 and MH102 need the Dedicated Outdoor Air System Ductwork changed. Replace the current connection to the variable refrigerant flow equipment with the following:
Mechanical sheets MH101 and MH102 will revise the ducting of ventilation air into each office. Currently, 74 connections show ventilation air ducted from the supply main to the room-located variable refrigerant fan coil. These connections will change: 70 of those connections will move from direct connections at the unit to a sidewall grille connection. Four areas in the basement will be ducted to supply diffusers inside their respective rooms. The ventilation air will not connect to the variable refrigerant blower coil as originally shown. Instead, the new 4” round ventilation duct will terminate at a sidewall grille. The sidewall grille will discharge all needed ventilation air into the room. The sidewall grille must be located on the opposite side of the corridor wall, away from the transfer grille to maintain good air circulation and mixing. Refer to revised sheets MH101 and MH102 for new routing of ventilation air ductwork. Sheet MH702 is also being submitted with the proper double deflection sidewall grille to be used for this change.
ISSUED BY: DATE: 10/1/2026
01 BASEMENT HVAC PLAN
1/8" = 1'-0"MH101
JOSEPH DAVID ASSOCIATES
REVISIONS
DRAWN BY
CHECKED BY
19970 CHLOE LAYNE RD.
SPIRO, OK 74959
JOSEPHDAVIDASSOCIATES.COM
FARRIS ENGINEERING
12700 West Dodge Road, Omaha, NE 68154
Proj ID
Project Status Issue Date 100% CD Issue for Construction
09-18-24
140A1622F0214 the copyright law.
OMAHA | LINCOLN | SIDNEY | COLORADO SPRINGS
FARRIS ENGINEERING
farris-usa.com
COPYRIGHT
This document and the information contained may not be reproduced or excerpted from without the express written permission of Farris Engineering, Inc. Unauthorized copying, disclosure or construction use are prohibited by
FEI #232013NOTICE:
DRAWINGS WERE DEVELOPED USING A 42X30 FORMAT.
PRINTS IN A DIFFERENT FORMAT MAY NOT BE
REPRESENTATIVE OF ACTUAL DIMENSIONS. VERIFY ALL
DIMENSIONS AND CLEARANCES ON SITE.
R O
SE
BU
D A
G
EN
C Y
BO
IL
ER
H
VA
C S
YS
TE
M (S
) D
ES
IG
N
BU
IL
D
IN
G
ASI #001 10-01-26
MH101
BASEMENT HVAC PLAN
MKM
RER
BA
SE
M
EN
T H
VA
C
P
LA
N
01 1ST FLOOR MECHANICAL PLAN
1/8" = 1'-0"MH102
JOSEPH DAVID ASSOCIATES
REVISIONS
DRAWN BY
CHECKED BY
19970 CHLOE LAYNE RD.
SPIRO, OK 74959
JOSEPHDAVIDASSOCIATES.COM
FARRIS ENGINEERING
12700 West Dodge Road, Omaha, NE 68154
Proj ID
Project Status Issue Date 100% CD Issue for Construction
09-18-24
140A1622F0214 the copyright law.
OMAHA | LINCOLN | SIDNEY | COLORADO SPRINGS
FARRIS ENGINEERING
farris-usa.com
COPYRIGHT
This document and the information contained may not be reproduced or excerpted from without the express written permission of Farris Engineering, Inc. Unauthorized copying, disclosure or construction use are prohibited by
FEI #232013NOTICE:
DRAWINGS WERE DEVELOPED USING A 42X30 FORMAT.
PRINTS IN A DIFFERENT FORMAT MAY NOT BE
REPRESENTATIVE OF ACTUAL DIMENSIONS. VERIFY ALL
DIMENSIONS AND CLEARANCES ON SITE.
R O
SE
BU
D A
G
EN
C Y
BO
IL
ER
H
VA
C S
YS
TE
M (S
) D
ES
IG
N
BU
IL
D
IN
G
ASI #001 10-01-26
MH102
1ST FLOOR HVAC PLAN
MKM
RER
1S T
FL
O
O R
H
VA
C P
LA
DEDICATED OUTDOOR AIR UNIT SCHEDULE
MARK LOCATION APPLICATION /
SERVES
SUPPLY AIR
(CFM)
OA
(CFM)
HEATING SECTION (ELECTRIC) COOLING SECTION SUPPLY FAN EXHAUST FAN ELECTRICAL
REFRIG WEIGHT
(LBS)
MANUFACTURER &
MODEL NO. REMARKSEAT
DB (°F)
DES
LAT
(°F)
ELEC
STAGES
EAT
DB/WB
(°F)
LAT
DB/WB
(°F)
TOTAL
CAP
(MBH)
SENS
CAP
(MBH)
COMP.
FACE
VEL.
(FPM)
EER NO.
FANS
ESP
(IN
WG)
POWER
(BHP)
NO.
FANS
AIRFLOW
(CFM)
ESP
(IN
WG)
POWER
(HP) V PH SCCR
(A)KW
DOAS-1 ON GRADE WEST WING 1,500 1,500 55.8 89.1 15.0 MOD 79 /
63.6
50.9 /
50.1 37.2 29.8 -- 239.0 13.8 1.0 1.00 0.42 1 1,130 1.00 0.47 208 3 R-410a 2,040 HORIZON ASHP
B072 1, 2
DOAS-2 ON GRADE EAST WING 1,500 1,500 55.8 89.1 15.0 MOD 79 /
63.6
50.9 /
50.1 37.2 29.8 -- 239.0 13.8 1.0 1.00 0.42 1 1,130 1.00 0.47 208 3 R-410a 2,040 HORIZON ASHP
B072 1, 2
DOAS-3 ON GRADE INTERIOR 1,500 1,500 55.8 89.1 15.0 MOD 79 /
63.6
50.9 /
50.1 37.2 29.8 -- 239.0 13.8 1.0 1.00 0.42 1 1,130 1.00 0.47 208 3 R-410a 2,040 HORIZON ASHP
B072 1, 2
REMARKS:
1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.
2. CAPACITY BASED ON 95°F OUTDOOR AIR TEMPERATURE.
ELECTRIC BASEBOARD HEATER
MARK TYPE LOCATION CAPACITY
(KW)
LENGTH
(FT)
ELECTRICAL DATA MANUFACTURER &
MODEL NO. REMARKS
V PH AMPS
BH-1 SLANT TOP SEE PLANS 1.5 6 120 1 7.2 INDEECO 903U015 1
REMARKS:
1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.
JOSEPH DAVID ASSOCIATES
REVISIONS
DRAWN BY
CHECKED BY
19970 CHLOE LAYNE RD.
SPIRO, OK 74959
JOSEPHDAVIDASSOCIATES.COM
FARRIS ENGINEERING
12700 West Dodge Road, Omaha, NE 68154
Proj ID
Project Status Issue Date 100% CD Issue for Construction
09-18-24
140A1622F0214 the copyright law.
OMAHA | LINCOLN | SIDNEY | COLORADO SPRINGS
FARRIS ENGINEERING
farris-usa.com
COPYRIGHT
This document and the information contained may not be reproduced or excerpted from without the express written permission of Farris Engineering, Inc. Unauthorized copying, disclosure or construction use are prohibited by
FEI #232013NOTICE:
DRAWINGS WERE DEVELOPED USING A 42X30 FORMAT.
PRINTS IN A DIFFERENT FORMAT MAY NOT BE
REPRESENTATIVE OF ACTUAL DIMENSIONS. VERIFY ALL
DIMENSIONS AND CLEARANCES ON SITE.
R O
SE
BU
D A
G
EN
C Y
BO
IL
ER
H
VA
C S
YS
TE
M (S
) D
ES
IG
N
BU
IL
D
IN
G
ASI #001 10-01-26
ELECTRIC CABINET AND UNIT HEATER SCHEDULE
MARK TYPE ARRANGEMENT LOCATION AIRFLOW
(CFM)
CAPACITY
(KW)
ELECTRICAL DATA MANUFACTURER &
MODEL NO. REMARKS
V PH TOTAL AMPS
EUH-1 FAN-FORCED HORIZONTAL STORAGE 300 1.5 208 1 7.6 INDEECO ULIR 925U020 1, 2, 3, 4, 5, 6
EUH-2 FAN-FORCED HORIZONTAL STORAGE 300 1.5 208 1 7.6 INDEECO ULIR 925U020 1, 2, 3, 4, 5, 6
ECUH-1 FAN-FORCED HORIZONTAL
SURFACE MOUNT VESTIBULE 250 2.0 208 1 11.0 INDEECO CUI 922U020 1, 3, 4, 5
ECUH-2 FAN-FORCED HORIZONTAL
SURFACE MOUNT VESTIBULE 250 2.0 208 1 11.0 INDEECO CUI 922U020 1, 3, 4, 5
ECUH-3 FAN-FORCED HORIZONTAL
SURFACE MOUNT VESTIBULE 250 2.0 208 1 11.0 INDEECO CUI 922U020 1, 3, 4, 5
ECUH-4 FAN-FORCED HORIZONTAL
SURFACE MOUNT VESTIBULE 250 2.0 208 1 11.0 INDEECO CUI 922U020 1, 3, 4, 5
ECUH-5 FAN-FORCED HORIZONTAL
SURFACE MOUNT VESTIBULE 250 2.0 208 1 11.0 INDEECO CUI 922U020 1, 3, 4, 5
ECUH-6 FAN-FORCED HORIZONTAL
SURFACE MOUNT VESTIBULE 250 2.0 208 1 11.0 INDEECO CUI 922U020 1, 3, 4, 5
ECUH-7 FAN-FORCED HORIZONTAL
SURFACE MOUNT VESTIBULE 250 2.0 208 1 11.0 INDEECO CUI 922U020 1, 3, 4, 5
REMARKS:
1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.
2. PROVIDE WITH TWO STAGE HEATING.
3. PROVIDE WITH INTEGRAL DISCONNECT.
4. PROVIDE WITH INTERGRAL THERMOSTAT.
5. PROVIDE WITH WALL MOUNTING BRACKETS.
6. MOUNT UNIT AT 8'-0" A.F.F.
DOMESTIC WATER HEATER SCHEDULE (ELECTRIC)
MARK CAPACITY
(GAL)
RECOVERY
(GPH)
TEMP. RISE
(°F)
INPUT
(KW)
ELECTRICAL MANUFACTURER &
MODEL NO. REMARKS
V PH
EWH-1 50 12 100 3 208 3 BRADFORD WHITE
LE350S3 1
REMARKS:
1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.
FAN SCHEDULE
MARK TYPE
FAN POWER AIRFLOW
(CFM)
ESP
(IN WG)
MANUFACTURER &
MODEL NO. REMARKS
(W)
TF-1 TRANSFER FAN 82 360 0.25 LOREN COOK CBF 1
TF-2 TRANSFER FAN 82 360 0.25 LOREN COOK CBF 1
REMARKS:
1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.
REGISTER - GRILLE - DIFFUSER SCHEDULE
MARK FUNCTION TYPE
CFM MAX FACE SIZE NECK SIZE
MATERIAL FINISH
MANUFACTURER
REMARKS
RANGE N.C. (INCHES) (INCHES) & MODEL NO.
S-1 SUPPLY SQUARE FACE NOMINAL
PANEL 0 - 100 25 24 x 24 6" Ø STEEL WHITE KRUEGER 1450 1, 2, 3
S-2 SUPPLY SQUARE FACE NOMINAL
PANEL 101 - 150 25 24 x 24 8" Ø STEEL WHITE KRUEGER 1450 1, 2, 3
S-3 SUPPLY DOUBLE DEFLECTION 0 - 150 25 6 x 6 - STEEL WHITE KRUEGER 5880H 1, 2, 3
R-1 RETURN SINGLE DEFL. 35° BLADE 0 - 300 25 12 X 8 - STEEL WHITE KRUEGER 5880H 1, 2, 3
R-2 RETURN SINGLE DEFL. 35° BLADE 301 - 425 25 12 X 12 - STEEL WHITE KRUEGER 5880H 1, 2, 3
R-3 RETURN SINGLE DEFL. 35° BLADE 426 - 920 25 24 X 12 - STEEL WHITE KRUEGER 5880H 1, 2, 3
REMARKS:
1. PROVIDE SPECIFIC NOISE CRITERIA (NC) DATA FOR EACH LINE ITEM WITH SHOP DRAWINGS.
2. COORDINATE BORDER OR FRAME TYPE WITH CEILING TYPE.
3. COORDINATE FINISH/COLOR WITH ARCHITECT.
M-702
MECHANICAL SCHEDULES
MKM
RER
M
EC
H
AN
IC
AL
S C
H
ED
U
LE
S
PLUMBING PUMP SCHEDULE
MARK SERVES TYPE GPM
HEAD
RPM HP
MANUFACTURER
REMARKS
FT. & MODEL NO.
PP-1 HOT WATER
CIRCULATING INLINE 3.0 8 3,250 1/40 TACO MODEL 006-BC4 1, 2
REMARKS:
1. SEE MECHANICAL/ELECTRICAL COORDINATION SCHEDULE FOR ELECTRICAL DATA.
2. ALL BRONZE CONSTRUCTION.
ARCHITECTS SUPPLEMENTAL INSTRUCTIONS (ASI)
| 2026-10-08T10:43:52-0500 | |
| David Markwardt |
File details come from the government source that posted it. Updated .