14_-_24-051_CCWF_BLDG508_Plans.pdf

PDF 14 MB Posted

Attached to
FPCM-CCWF-I001136-001-MF EIFS System
Solicitation number
0000036866
Issued by
Marin County, California

About this file

Project Summary: EIFS Building 508 Facility B

This is an architectural construction document package for the California Department of Corrections and Rehabilitation (CDCR) detailing the installation of an Exterior Insulating Finish System (EIFS) at Building 508 of the Central California Women's Facility (CCWF) in Chowchilla, California. The project scope involves installing 4-inch EIFS over exterior walls at the housing unit, with exposed finishes varying based on location and inmate accessibility. Work includes minor demolition to accommodate the new system, relocation of existing electrical outlets, intercom panels, hosebibs, fire alarms, and other building elements. The project is designated as Permit Application No. 25-S-1743-C-ER with Office of the State Fire Marshal approval dated July 14, 2025. Construction must comply with 2022 California Building Code, California Electrical Code, California Mechanical Code, California Plumbing Code, California Fire Code, and 2010 ADA Standards. The building is classified as I-3 (institutional) occupancy with a construction type of I-B, consisting of one story at 22 feet height, containing 21,182 square feet of space with 132 total occupants. The facility is sprinklered with automatic fire alarm and emergency responder radio coverage.

The project drawings include detailed site plans, floor plans, exterior elevations, wall sections, and EIFS construction details across multiple sheets. Existing conditions must be verified as operational before work commences, with the institution responsible for maintaining systems to accommodate new work. All construction debris must be removed and disposed of in compliance with local, state, and federal regulations. Building will remain occupied during demolition and construction, requiring maintenance of free egress/ingress and unobstructed fire apparatus roadways at all times. Hazardous materials identification and abatement, if required, must be performed by the Environmental Compliance Unit prior to construction commencement. The project includes electrical modifications documented in the electrical plan sheets showing relocated outlets, disconnects, fire alarm systems, and other electrical infrastructure adjustments necessitated by the EIFS installation.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

515516514513901701804401509510511512506507505

911907

903906902

704 702517703306503504501502518519308801

307 302303908404405 313300FIRIN GRANGE909910310311 304403601305312

402315 814811806807808

812813 809810317 913301912900

905914 314

520521700309STO RAGEPIAGEN ERATORSFU ELTANKS

705406 316FACILITYAFACILITYB

FACILITYCFACILITYD

SCALEINFEET0200400600800200

51 5

51 6

51 451 3

51 0

51 1

51 2

1 1 01

91 1

704 702

51 7

503504

51 8

51 9

31 3

FIRING RANGE

909 91 0

31 0 31 1

31 2

31 5

81 4

81 1

81 2 81 3

81 0

31 7

91 3

91 2

91 4

31 4

STORAGE

PIA

GENERATORS

FUEL TANKS

81 5

31 6

FACILITY A

FACILITY B

FACILITY C

FACILITY D

VICINITY MAP

CCWF

Avenue 24

R d

R d

Chowchilla

SCOPE OF WORK

THE SCOPE OF THIS PROJECT INVOLVES:

INSTALL EXTERIOR INSULATING FINISH SYSTEM (EIFS) AT EXTERIOR WALLS.

EXPOSED FINISH TO VARY DEPENDING UPON LOCATION (WHETHER

ACCESSIBLE BY INCARCERATED POPULATION), REVEAL LINES AND COLORS.

MINOR DEMOLITION OF ELEMENTS TO ACCOMMODATE THE ADDED

EXTERIOR INSULATING FINISH SYSTEM (EIFS).

GYPSUM BOARD

CONCRETE

CONCRETE BLOCK

BATT INSULATION

RIGID INSULATION

METAL

WOOD FRAMING (CONT.)

WOOD BLOCKING

FINISH WOOD

MATERIAL DESIGNATION ABBREVIATIONS

AB ANCHOR BOLT

AFF ABOVE FINISH FLOOR

AL ALUMINUM

ARCH('L) ARCHITECT(URAL)

AC ASPHALT CONCRETE

BD BOARD

BLDG BUILDING

BLK BLOCK

BLKG BLOCKING

BM BEAM

BOT BOTTOM

BUR BUILT-UP ROOFING

CEM CEMENT

CJ CONTROL JOINT

CLG CEILING

CLKG CAULKING

CMU CONCRETE MASONRY

UNIT

COL COLUMN

COMP COMPOSITION

CONC CONCRETE

CONST CONSTRUCTION

CONT CONTINUOUS

DBL DOUBLE

DET DETAIL

DF DOUGLAS FIR

DIA DIAMETER

DIAG DIAGONAL

DIM DIMENSION

DR DOOR

DWG DRAWING

DS DOWNSPOUT

E EAST

(E) EXISTING

EA EACH

EJ EXPANSION JOINT

EL ELEVATION

ELECT ELECTRICAL

EQ EQUIP

EXH EXHAUST

EXIST('G)EXISTING (SEE (E))

EXP EXPANSION

FB FLAT BAR

FD FLOOR DRAIN

FDN FOUNDATION

FE FIRE EXTINGUISHER

FIN FINISH

FLR FLOOR

FOC FACE OF CONCRETE

FOF FACE OF FINISH

FOM FACE OF MASONRY

FOS FACE OF STUD

FRAMG FRAMING

FT FOOT OR FEET

FTG FOOTING

FUR FURRING

GA GAUGE

GALV GALVANIZED

GI GALVANIZED IRON

GR GRADE

GSM GALVANIZED SHEET

METAL

GYP GYPSUM

HB HOSE BIB

HC HOLLOW CORE

HDR HEADER

HM HOLLOW METAL

HT HEIGHT

ID INSIDE DIAMETER

IN INCH OR INCHES

INSUL INSULATION

INV INVERT

JST JOIST

JT JOINT

LAG LAG BOLT(S)

LT LIGHT

MAX MAXIMUM

MB MACHINE BOLT

MECH MECHANICAL

MEM MEMBRANE

MO MASONRY OPENING

MTL METAL

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MTD MOUNTED

N NORTH

(N) NEW

NA NOT APPLICABLE

NIC NOT IN CONTRACT

NO NUMBER

NTS NOT TO SCALE

O/ OVER

OC ON CENTER

OD OUTSIDE DIAMETER

OPNG OPENING

OPP OPPOSITE

PL PLATE

PLAS PLASTER

PLYWDPLYWOOD

PMF PRESSED METAL FRAME

PR PAIR

PVC POLYVINYL CHLORIDE

R RISER

RA RETURN AIR

RDWDREDWOOD

RD ROOF DRAIN

REG REGISTER

REINF REINFORCE(D)(ING)

REQ'DREQUIRED

RWL RAIN WATER LEADER

S SOUTH

SC SOLID CORE

SCHEDSCHEDULE

SHT SHEET

SIM SIMILAR

SM SHEET METAL

SPECS SPECIFICATIONS

SQ SQUARE

SS STAINLESS STEEL

STD STANDARD

STL STEEL

STRUCT STRUCTURAL

SUSP SUSPENDED

SYM SYMMETRICAL

T&B TOP AND BOTTOM

TC TOP OF CURB OR

CONCRETE

THRU THROUGH

TW TOP OF WALL

TYP TYPICAL

UON UNLESS OTHERWISE NOTED

UR URINAL

VERT VERTICAL

W WEST

W/ WITH

W/O WITHOUT

WG WIRE GLASS

WH WATER HEATER

WP WEATHERPROOF OR

WATERPROOF

WWM WELDED WIRE MESH

WC WATER CLOSET

YD YARD

∠ ANGLE

@ AT

℄ CENTER LINE

Ø DIAMETER

± PLUS/MINUS

1t

1i

A101

A101

1 Ref

R e f

1 Ref

R e f

DOOR TAG

WINDOW TAG

WALL TAG

DETAIL NUMBER

SHEET NUMBER

A101

DETAIL NUMBER

SHEET NUMBER

DETAIL NUMBER

SHEET NUMBER

Room name

ROOM NAME

ROOM NUMBER

SYMBOLS

APPLICABLE CODES

ALL WORK SHALL COMPLY WITH AT LEAST THE MINIMUM STANDARDS OF THE

FOLLOWING:

• 2022 CALIFORNIA BUILDING CODE

• 2022 CALIFORNIA ELECTRICAL CODE

• 2022 CALIFORNIA MECHANICAL CODE

• 2022 CALIFORNIA PLUMBING CODE

• 2022 CALIFORNIA EMERGY CODE

• 2022 CALIFORNIA FIRE CODE

• 2022 CALIFORNIA EXISTING BUILDING CODE

• 2022 CALIFRONIA GREEN BUILDING STANDARDS CODE

• 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN

APPLICABLE REGULATIONS

• CDCR 2024 DESIGN CRITERIA GUILDLINES (DCG).

GENERAL NOTES

1. THE BUILDER SHALL VERIFY THAT THE EXISTING SYSTEM OR COMPONENTS

IMPACTING THIS NEW WORK ARE ENABLED, OPERATIONAL AND FUNCTIONING

PROPERLY BEFORE COMMENCING WITH NEW WORK. THE INSTITUTION IS

RESPONSIBLE FOR MAINTAINING THE SYSTEM IN ORIGINAL WORKING CONDITION

TO ACCOMMODATE THIS NEW WORK.

2. DETAILS MARKED TYPICAL SHALL APPLY IN ALL CASES UNLESS SPECIFICALLY

DETAILED OTHERWISE. WHERE NO DETAIL IS SHOWN CONSTRUCTION SHALL BE

AS SHOWN FOR OTHER SIMILAR WORK.

3. THE DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE.

THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE BUILDER SHALL

PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE AND

SAFETY OF THE WORKERS DURING CONSTRUCTION. SUCH MEASURES SHALL

INCLUDE BUT NOT BE LIMITED TO, BRACING, SHORING, FOR LOADS DUE TO

CONSTRUCTION EQUIPMENT, ETC.

4. PROVIDE CONSTRUCTION BARRIERS TO PROTECT PERSONNEL.

5. REPAIR ALL EXISTING SURFACES DAMAGED TO ACCOMMODATE NEW

CONSTRUCTION.

6. HAZARDOUS MATERIALS TO BE IDENTIFIED AND, IF REQUIRED, ABATED IN THE

AREAS AFFECTED BY THIS CONSTRUCTION, PRIOR TO THE BUILDER BEGINNING

HIS WORK. THE IDENTIFICATION AND ABATEMENT TO BE PERFORMED BY THE

ENVIRONMENTAL COMPLIANCE UNIT; CONTACT GREGOR LARABEE AT

(279) 223-2753.

7. PROVIDE SAFEGUARDS FOR CONSTRUCTION, ALTERATION AND DEMOLITION

OPERATIONS TO PROVIDE REASONABLE SAFETY TO LIFE AND PROPERTY FROM

FIRE DURING SUCH OPERATIONS PER COMPLIANCE WITH "FIRE SAFETY DURING

CONSTRUCTION AND DEMOLITION" IN ACCORDANCE WITH 2016 CALIFORNIA FIRE

CODE (CFC) CHAPTER 33. TITLE 19, DIVISION 1, CALIFORNIA CODE OF

REGULATIONS (CCR).

- PROJECT SITE -

HOUSING UNIT 508

SHEET #A2.1

ACCESS COMPLIANCE NOTES

THIS ALTERATION PROJECT IS EXEMPT FROM ACCESS COMPLIANCE

REQUIREMENTS PURSUANT TO CBC SECTIONS 11B-203.4 AND/OR 11B-203.5 AS

THE AREA OF THE SCOPE OF WORK IS IN A LIMITED ACCESS SPACE AND/OR IS

ACCESSED SOLELY FOR PURPOSES MAINTENANCE AND REPAIR.

H

L

ES

I

N

E C

AD CR

T

I

ET

C

C-34592

REN. 09-30-25

R A

M

HA

EC

T

ROIF

E

CO F AL

T

S

TA N

IA

RVA

N T E S

C A D

F

IL

E

DATE:

SHEET NUMBER

A

B

C

D

E

F

G

H

J

K

L

M

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

OF SHEETS V1

ARCHITECTURE & ENGINEERING

CALIFORNIA DEPARTMENT OF

CORRECTIONS AND REHABILITATION

CALIFORNIA DEPARTMENT OF

CORRECTIONS AND REHABILITATION

ACCESS COMPLIANCE REVIEW

APPROVAL OF THIS PLAN DOES NOT AUTHORIZE

OR APPROVE ANY OMMISION OR DEVIATION

FROM APPLICABLE REGULATIONS

SUPERVISING ARCHITECT

P D E S

IG

N S

E R V

IC

E S \C

C W

F \D

E S

IG

N \2

-0

E

IF

S B ld g

F a c ili ty

B \D ra w in g s \2

-0

C

C W

F B L D G

C D

.r v t

/2

/2

:4 :0

P

M

G1.0

C O

V E R

S H E E T

05/28/2025

E

IF

S B

L D G

F A C

IL

IT

Y B

24-051

C E N T R

A L C

A L

IF

O R

N

IA

W O

M E N 'S

F A C

IL

IT

Y C

C W

F

R

O A D

C H O

W C

H

IL

L A , C

A

CCWF

MARTHA CERVANTES

SENIOR ARCHITECT

JOHN RODRIGUEZ

SHEET # SHEET NAME

G1.0 COVER SHEET

EIFS BLDG. 508 FACILITY B

CENTRAL CALIFORNIA WOMEN'S FACILITY (CCWF)

OWNER AND OCCUPANT: CALIFORNIA DEPARTMENT OF CORRECTIONS AND REHABILITATION

A1.0 SITE PLAN

A2.1 HOUSING UNIT BLDG 508 FLOOR PLAN

A3.1 HOUSING UNIT BLDG 508 EXTERIOR ELEVATIONS

A3.2 HOUSING UNIT BLDG 508 EXTERIOR ELEVATIONS

A3.3 HOUSING UNIT BLDG 508 ENLARGED EXTERIOR ELEVATIONS

A3.4 HOUSING UNIT BLDG 508 ENLARGED EXTERIOR ELEVATIONS

A4.1 HOUSING UNIT BLDG 508 WALL SECTIONS

A5.1 EIFS DETAILS

A5.2 EIFS DETAILS

A5.3 EIFS DETAILS

NORTH

NORTH

CCWF SITE MAP

NTS

CHOWCHILLA, CALIFORNIA

SHEET INDEX

OSFM DEFERRED SUBMITTAL

• NONE

OSFM APPLICATION DATA

BUILDING. NO. PERMIT APPLICATION NO. PROJECT EMAIL PASSWORD

508 25-S-1743-C-ER m_CCWF_24-051@cdcr.ca.gov CCWF,mc@24-051

FIRE/LIFE-SAFETY NOTES

THIS ALTERATION PROJECT DOES NOT CHANGE USE OR OCCUPANCY, DOES NOT INCREASE BUILDING AREA, AND DOES NOT CHANGE THE CHARACTER OF THE AREA OF THE SCOPE OF WORK. AS SUCH, ONLY THE AREA OF ALTERATION IS REQUIRED TO MEET CURRENT APPLICABLE CODE REQUIREMENTS PER CEBC

SECTION #105 & #315.

BUILDING NAME BLDG NO. OCCUPANCY

CONSTRUCTION

TYPE NO. OF STORIES

BUIDING

HEIGHT

BUILDING AREA

IN SF

SERPARATED,

NON-SEPARATED,

ACCESSSORY USE

ALLOWABLE

AREA

AREA

INCREASE

HEIGHT

INCREASE SPRINKLERED FIRE ALARM

OTHER FIRE

PROTECTION SYSTEM

(TYPE)

SMOKE CONTROL

SYSTEM

OCCUPANT LOAD

(ENTIRE BLDG)

OCCUPANT LOAD

FOR EACH FLOOR

YEAR BLDG

CONSTRUCTED

HIGH FIRE

HAZARD ZONE

SEISMIC JOINTS

AND LOCATION

EMERGENCY

RESPONDER

RADIO COVERAGE NOTES

CROSS TOP BLDG HOUSING UNIT 508 I-3 I-B 1 22'-0" 21,182 NON - SEPARATED 30,600 NO NO Yes YES/AUTO - NO 132 - 1985 NO YES/EXIST YES

BUILDING DATA

E1.1 ELECTRICAL NOTES AND SYMBOL LEGEND

E2.1 BUILDING 508 ELECTRICAL PLAN

E3.1 BUILDING 508 ELECTRICAL EXTERIOR ELEVATIONS

E3.2 BUILDING 508 ELECTRICAL EXTERIOR ELEVATIONS

E4.1 ELECTRICAL DETAILS

REV. DATE: DESCRIPTION

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

07/14/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1743

#1337 7/21/2025 CASp-491

514513

704 702

503504

FIRING RANGE

909 910

812 813

STORAGE

PIA

GENERATORS

FUEL TANKS

FACILITY A

FACILITY B

FACILITY C

FACILITY D

SCALE IN FEET

0 200 400 600 800200

GENERAL NOTES

1. BUILDING WILL BE OCCUPIED DURING DEMOLITION AND CONSTRUCTION. EGRESS /INGRESS SHALL

REMAIN FREE OF DEBRIS AND OBSTRUCTION THROUGH OUT DEMOLITION AND CONSTRUCTION.

2. FIRE ACCESS AND FIRE APPARATUS ROAD WAY SHALL BE MAINTAINED FREE OF OBSTRUCTION AT

ALL TIMES.

3. LAY DOWN AREAS FOR REMOVED EQUIMENT AND CONTRCUTION WASTE COLLECTION TO BE

DETERMINED BY CDCR INSTITUTION PRIOR TO CONSTRUCTION. THESE AREA(S) SHALL NOT IMPACT, RESTRICT, OR PRECLUDE FIRE ACCESS OR IMPACT FIRE SAFETY OF THE CONSTRUCTION SITE OR CDCR INSTITUTION. THERE SHALL BE NO OBSTRUCTION TO FIRE APPLIANCES, NOR SHALL THESE

AREAS IMPACT SITE EGRESS.

LEGEND

EXISTING EGRESS ROUTE DIRECTION

TOWARDS SAFE DISPERSAL AREA

EXISTING FIRE TRUCK ACCESS

AREA OF WORK

H

L

ES

I

N

E C

AD CR

T

I

E T

C

C-34592

REN. 09-30-25

R A

M

HA

EC

T

R

OIF

E C

O F AL

T

S T

A N

IA

RVA

N T E S

C A D

F

IL

E

DATE:

SHEET NUMBER

A

B

C

D

E

F

G

H

J

K

L

M

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

OF SHEETS V1

ARCHITECTURE & ENGINEERING

CALIFORNIA DEPARTMENT OF

CORRECTIONS AND REHABILITATION

CALIFORNIA DEPARTMENT OF

CORRECTIONS AND REHABILITATION

ACCESS COMPLIANCE REVIEW

APPROVAL OF THIS PLAN DOES NOT AUTHORIZE

OR APPROVE ANY OMMISION OR DEVIATION

FROM APPLICABLE REGULATIONS

SUPERVISING ARCHITECT

P D E S

IG

N S E R V

IC

E S \C C W F \D E S

IG

N \2 -0 E

IF

S B ld g F a c ili ty B \D ra w in g s \2 -0 C C W F B L D G C D .r v t

/2 /2 :4 :0 P M

A1.0

S

IT

E P

L A N

05/28/2025

E

IF

S B

L D G

F A C

IL

IT

Y B

24-051

C E N T R

A L C

A L

IF

O R

N

IA

W O

M E N 'S

F A C

IL

IT

Y C

C W

F

R

O A D

C H O

W C

H

IL

L A , C

A

CCWF

MARTHA CERVANTES

SENIOR ARCHITECT

JOHN RODRIGUEZ

SCALE: 1" = 200'-0"1 SITE PLAN

REV. DATE: DESCRIPTION

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

07/14/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1743

514513

704 702

503504

FIRING RANGE

909 910

812 813

STORAGE

PIA

GENERATORS

FUEL TANKS

FACILITY A

FACILITY B

FACILITY C

FACILITY D

1 2 3 4 5 6 7 8 9 10 11 12 13

A

B

C

D

E

F

G

H

J

K

L

M

N

A3.2

A3.2

A3.1

A3.1

A3.3

A3.3

A3.3

A3.2

A3.2

A3.1

A3.1

DEMONEW

DEMO

NEW

DEMO

NEW

A3.3

A3.3

A3.3

A3.3

A3.3

A3.3

A3.3

A3.3

A3.3

DEMONEW

DEMO

NEW

DEMO

NEW

DEMO

NEW

NEW

DEMO

A4.1

A4.1

A4.1

A4.1

A4.1

A4.1

DEMO

NEW

DEMO

NEW

A5.1

53 65

248' - 8"

A5.2

A5.2

A5.2

A5.2

A5.2

A5.2

A5.1

KEY PLAN

CROSS TOP

HOUSING UNIT

BLDG 508

GENERAL NOTES

1. BUILDING WILL BE OCCUPIED DURING DEMOLITION AND CONSTRUCTION. EGRESS /INGRESS SHALL

REMAIN FREE OF DEBRIS AND OBSTRUCTION THROUGH OUT DEMOLITION AND CONSTRUCTION.

2. FIRE ACCESS AND FIRE APPARATUS ROAD WAY SHALL BE MAINTAINED FREE OF OBSTRUCTION AT

ALL TIMES.

3. ALL CONSTRUCTION DEBRIS GENERATED IN THE COURSE OF THIS PROJECT SHALL BE REMOVED

AND DISPOSED OF IN COMPLIANCE WITH LOCAL, STATE AND FEDERAL CODES AND REGULATIONS.

4. REPAIR / REPLACE ANY DAMAGED UTILITIES DURING THE COURSE OF WORK.

5. PROTECT BUILDING FROM DAMAGE WHICH MAY OCCUR FROM DEMOLITION, DUST, WATER ADVERSE

WEATHER, ETC.

6. CONTRACTOR TO PATCH AND REPAIR ALL AREAS DAMAGED BY, OR INCIDENTAL TO DEMOLITION

AND /OR NEW WORK TO MATCH ADJACENT FINISHES UNLESS OTHERWISE NOTED.

7. ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO (E) CONDITIONS IS GIVEN AS BEST

PRESENT KNOWLEDGE. WHERE ACTUAL CONDITIONS CONFLICT WITH THE DRAWINGS, THEY SHALL BE REPORTED TO THE ARCHITECT SO THAT THE CORRECTION/CLARIFICATION CAN BE PROVIDED.

8. ALL DIMENSIONS ARE TO BE VERIFIED IN FIELD.

9. COORDINATE WITH PLANT OPS BEFORE AND AFTER SHUTTING OFF ANY UTILITIES.

LEGEND

EXISTING DOOR TO REMAIN

EXISTING WALL TO REMAIN

NEW EXTERIOR INSULATION AND FINISH SYSTEM

H

L

ES

I

N

E C

AD CR

T

I

ET

C

C-34592

REN. 09-30-25

R A

M

HA

EC

T

ROIF

E

CO F AL

T

S

TA N

IA

RVA

N T E S

C A D

F

IL

E

DATE:

SHEET NUMBER

A

B

C

D

E

F

G

H

J

K

L

M

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

OF SHEETS V1

ARCHITECTURE & ENGINEERING

CALIFORNIA DEPARTMENT OF

CORRECTIONS AND REHABILITATION

CALIFORNIA DEPARTMENT OF

CORRECTIONS AND REHABILITATION

ACCESS COMPLIANCE REVIEW

APPROVAL OF THIS PLAN DOES NOT AUTHORIZE

OR APPROVE ANY OMMISION OR DEVIATION

FROM APPLICABLE REGULATIONS

SUPERVISING ARCHITECT

P D E S

IG

N S

E R V

IC

E S \C

C W

F \D

E S

IG

N \2

-0

E

IF

S B ld g

F a c ili ty

B \D ra w in g s \2

-0

C

C W

F B L D G

C D

.r v t

/2

/2

:4 :0

P

M

A2.1

H O

U S

IN

G U

N

IT

B L D

G

F

L O

O R P

L A N

05/28/2025

E

IF

S B

L D G

F A C

IL

IT

Y B

24-051

C E N T R

A L C

A L

IF

O R

N

IA

W O

M E N 'S

F A C

IL

IT

Y C

C W

F

R

O A D

C H O

W C

H

IL

L A , C

A

CCWF

MARTHA CERVANTES

SENIOR ARCHITECT

JOHN RODRIGUEZ

SCALE: 1/16" = 1'-0"1 HOUSING UNIT 508 FIRST FLOOR PLAN

NORTH

NORTH

KEYNOTES

2(E) STANDARD AND SPLITFACE CMU WALL TO REMAIN

18 (E) CONCRETE STOOP TO REMAIN

19 (E) CONCRETE PAD TO REMAIN

20 (E) FENCE POST TO REMAIN

21 (E) CHAIN LINK FENCE AND RAZOR WIRE TO REMAIN

53 (N) 4" (R16) EXTERIOR INSULATION AND FINISH SYSTEM (EIFS)

65 PROVIDE PAPER BACKED GALVANIZED METAL LATH AT EIFS SYSTEM

OVER SPLITFACE CMU.

REV. DATE: DESCRIPTION

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

07/14/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1743

FF

0' - 0"

A3.4

A4.1

5 4 3 2 1 6 7 8 9 10 11 12 13

555555

5454 52

80 53 555555

SKEWED ELEVATION

53 555555

SKEWED ELEVATION

555555 53 53 555555

80 5454

80 545453

80 555555 5373 73 65

C -2

C -1

A3.4

ED C B A F G H J K L M N

55555553

80 5454

80 53 5454

SKEWED ELEVATION

555555

53 555555

53 52

80 53 555555 5454 73 5454

71 555555

SKEWED ELEVATION

80 555555

656565

C -2

54 3 2 1 6 7 8 9 10 11 12 13

D2

D30 4

12 13 16

D2

D30 3 4

D2

D30 4 73

SKEWED ELEVATION

8 4 71 4 8

D2

D30

10 12 13 16 15 24 10 9

D23

D20

D21

3 2

SKEWED ELEVATION

D2

D30

4 4

4 4

15 10 12 13 16 10 15

12 13 16

4 D23 2

D2

3 4D30

D2

D30 4 3

D2

D30 2 4

D5D5

D5

D5D5

D5 D5

FF

0' - 0"

E D C B A F G H J K L M N

D2

D30 3 4

D2

D30 4 3

D2

D30 D23 4 SKEWED ELEVATION

4 4

4 4

15 10 1013 16 12 15 9 15 6

D2

D30

D20

D21

D23

3 2

D2

D30

15 24 10

SKEWED ELEVATION

8 4 4 8

12 13 16 10 15 12 13 16

D23 2 4

D2

D30 4 3

D2

D302 3 4

D2

D30 4 2

D5D5D5

D5

D5D5

D5

D5

1. BUILDING WILL BE OCCUPIED DURING DEMOLITION AND CONSTRUCTION. EGRESS /INGRESS

SHALL REMAIN FREE OF DEBRIS AND OBSTRUCTION THROUGH OUT DEMOLITION AND

CONSTRUCTION.

2. FIRE ACCESS AND FIRE APPARATUS ROAD WAY SHALL BE MAINTAINED FREE OF

OBSTRUCTION AT ALL TIMES.

3. ALL CONSTRUCTION DEBRIS GENERATED IN THE COURSE OF THIS PROJECT SHALL BE

REMOVED AND DISPOSED OF IN COMPLIANCE WITH LOCAL, STATE AND FEDERAL CODES

AND REGULATIONS.

4. REPAIR / REPLACE ANY DAMAGED UTILITIES DURING THE COURSE OF WORK.

5. PROTECT BUILDING FROM DAMAGE WHICH MAY OCCUR FROM DEMOLITION, DUST, WATER

ADVERSE WEATHER, ETC.

6. CONTRACTOR TO PATCH AND REPAIR ALL AREAS DAMAGED BY, OR INCIDENTAL TO

DEMOLITION

AND /OR NEW WORK TO MATCH ADJACENT FINISHES UNLESS OTHERWISE NOTED.

7. ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO (E) CONDITIONS IS GIVEN AS

BEST PRESENT KNOWLEDGE. WHERE ACTUAL CONDITIONS CONFLICT WITH THE

DRAWINGS, THEY SHALL BE REPORTED TO THE ARCHITECT SO THAT THE

CORRECTION/CLARIFICATION CAN BE PROVIDED.

8. ALL DIMENSIONS ARE TO BE VERIFIED IN FIELD.

9. COORDINATE WITH PLANT OPS BEFORE AND AFTER SHUTTING OFF ANY UTILITIES.

GENERAL NOTES

LEGEND

EXISTING TO REMAIN

TO BE REMOVED

NEW

EXTERIOR FINISH & COLOR LEGEND

C-2:

C-1:

INMATE ACCESSIBLE AREA

C-4:

C-3:

H

L

ES

I

N

E C

AD CR

T

I

ET

C

C-34592

REN. 09-30-25

R A

M

HA

EC

T

ROIF

E

CO F AL

T

S

TA N

IA

RVA

N T E S

C A D

F

IL

E

DATE:

SHEET NUMBER

A

B

C

D

E

F

G

H

J

K

L

M

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

OF SHEETS V1

ARCHITECTURE & ENGINEERING

CALIFORNIA DEPARTMENT OF

CORRECTIONS AND REHABILITATION

CALIFORNIA DEPARTMENT OF

CORRECTIONS AND REHABILITATION

ACCESS COMPLIANCE REVIEW

APPROVAL OF THIS PLAN DOES NOT AUTHORIZE

OR APPROVE ANY OMMISION OR DEVIATION

FROM APPLICABLE REGULATIONS

SUPERVISING ARCHITECT

P D E S

IG

N S

E R V

IC

E S \C

C W

F \D

E S

IG

N \2

-0

E

IF

S B ld g

F a c ili ty

B \D ra w in g s \2

-0

C

C W

F B L D G

C D

.r v t

/2

/2

:4 :1

P

M

A3.1

H O

U S

IN

G U

N

IT

B L D G

E X T E R

IO

R

E L E V A T

IO

N S

05/28/2025

E

IF

S B

L D G

F A C

IL

IT

Y B

24-051

C E N T R

A L C

A L

IF

O R

N

IA

W O

M E N 'S

F A C

IL

IT

Y C

C W

F

R

O A D

C H O

W C

H

IL

L A , C

A

CCWF

MARTHA CERVANTES

SENIOR ARCHITECT

JOHN RODRIGUEZ

SCALE: 3/32" = 1'-0"2 BLDG 508 SOUTH ELEVATION

SCALE: 3/32" = 1'-0"4 BLDG 508 WEST ELEVATION

SCALE: 3/32" = 1'-0"1 BLDG 508 SOUTH EAST EXISTING/DEMOLITION ELEVATION

SCALE: 3/32" = 1'-0"3 BLDG 508 WEST EXISTING/DEMOLITION ELEVATION

KEYNOTES - DEMO

2 (E) STANDARD AND SPLITFACE CMU WALL TO REMAIN

3 (E) CMU CONTROL JOINT TO REMAIN

4 (E) WINDOW TO REMAIN. PAINT METAL WINDOW FRAME TO MATCH

6 (E) LOUVER TO REMAIN. PAINT TO MATCH

8 (E) METAL DOOR AND FRAME TO REMAIN. PAINT TO MATCH

9 (E) STUCCO ON CMU TO REMAIN

10 (E) STUCCO ON METAL FRAMING TO REMAIN

12 (E) CONCRETE TILE ROOF TO REMAIN

13 (E) GUTTER TO REMAIN. PAINT TO MATCH

15 (E) METAL COPING TO REMAIN

16 (E) PREFINISH METAL FASCIA SYSTEM TO REMAIN

17 (E) PREFINISH METAL FLASHING TO REMAIN

18 (E) CONCRETE STOOP TO REMAIN

20 (E) FENCE POST TO REMAIN

21 (E) CHAIN LINK FENCE AND RAZOR WIRE TO REMAIN

24 (E) BUILDING NUMBER TO REMAIN

30 (E) STEEL BAR TO REMAIN. PAINT TO MATCH

52 (N) DOWNSPOUT. PAINT TO MATCH

53 (N) 4" (R16) EXTERIOR INSULATION AND FINISH SYSTEM (EIFS)

54 (N) EXTERIOR INSULATION AND FINISH SYSTEM (EIFS) CONTROL

JOINT. MATCH LOCATION OF (E) CONTROL JOINT U.N.O.

55 (N) EXTERIOR INSULATION AND FINISH SYSTEM (EIFS) REVEAL

65 PROVIDE PAPER BACKED GALVANIZED METAL LATH AT EIFS SYSTEM

OVER SPLITFACE CMU.

70 RELOCATED (E) ELECTRICAL OUTLET

71 RELOCATED (E) INTERCOM PANEL

73 RELOCATED (E) HOSEBIB, SEE DTL 10/A5.3

80 RELOCATED (E) PRECAST CONCRETE SPLASH BLOCK

D2 REMOVE (E) DOWNSPOUT PATCH & REPAIR IN-KIND AND PREP FOR

NEW WORK

D5 GRIND DOWN HIGH SPOTS OF SPLITFACE CMU AS NEEDED TO

ACCOMODATE THE (N) EIFS SYSTEM OVER PAPER BACKED

GALVANIZED METAL LATH

D20 REMOVE AND RELOCATE (E) ELECTRICAL OUTLET TO ACCOMODATE

(N) EIFS SYSTEM. (N)LOCATION TO MATCH (E). SEE ELECTRICAL

DRAWINGS.

D21 REMOVE AND RELOCATE (E) INTERCOM PANEL TO ACCOMODATE (N)

EIFS SYSTEM. (N)LOCATION TO MATCH (E). SEE ELECTRICAL

DRAWINGS.

D23 REMOVE AND RELOCATE (E) HOSEBIB TO ACCOMODATE (N) EIFS

SYSTEM. (N)LOCATION TO MATCH (E).

D30 REMOVE AND RELOCATE (E) PRECAST CONCRETE SPLASH BLOCK

TO ACCOMODATE (N) EIFS SYSTEM. (N)LOCATION TO MATCH (E).

KEYNOTES

REV. DATE: DESCRIPTION

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

07/14/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1743

5 4 3 2 16 7 8 9 10 11 12 13

D2

D30 4 3

D2

D30

3 4

D2

D30 4

D23 26

SKEWED ELEVATION

D32

2828 8

D33 9 15 12 13 16

15 9

D2

D30

D23

D21

70 3 2

SKEWED ELEVATION

D2

D30

4 4

4 4

1510 12 13 16 10 15 12 13 16

4 D23 2

D2

D30 3 4

D2

D30 4 3 2

D2

D30 2 4

D5 D5 D5 D5

D5 D5

D5

D5 D5 D5

FF

0' - 0"

E D C B AF GH J K L M N

2 D2

D30 3 4

D2

D30

12 13 16

4 3

D2

D30 D23 4 SKEWED ELEVATION SKEWED ELEVATION

15 10 121316 10 15

D2

D30

9 15

3 D21

D20

D23

D2

D30

D23 4

D2

D30 2 3

D2

D30 3 4

D2

D30 4 2

12 13 16

4 4 4 4

D5

D5

D5 D5

28 8429

D33

D5

D5 D5

FF

0' - 0"

A4.1

5 4 3 2 16 7 8 9 10 11 12 13

555555

80 5454

555555

SKEWED ELEVATION SKEWED ELEVATION

555555

80 53 555555

73 5454

53 5454 555555

60 555555 53 73 555555

80 5454 53

80 5454 53

80 55555565 65 65

65 65

65 65

65 65 65

-2

FF

0' - 0"

A3.4

E D C B AF G H J K L M N

SKEWED ELEVATION SKEWED ELEVATION

80 53 555555 5454

80 555555

71 73 53555555

80 5454 555555

80 53 5454

80 53555555

555555

5454 83

555555 65

65 65 65

C -2

1. BUILDING WILL BE OCCUPIED DURING DEMOLITION AND CONSTRUCTION. EGRESS /INGRESS

SHALL REMAIN FREE OF DEBRIS AND OBSTRUCTION THROUGH OUT DEMOLITION AND

CONSTRUCTION.

2. FIRE ACCESS AND FIRE APPARATUS ROAD WAY SHALL BE MAINTAINED FREE OF

OBSTRUCTION AT ALL TIMES.

3. ALL CONSTRUCTION DEBRIS GENERATED IN THE COURSE OF THIS PROJECT SHALL BE

REMOVED AND DISPOSED OF IN COMPLIANCE WITH LOCAL, STATE AND FEDERAL CODES

AND REGULATIONS.

4. REPAIR / REPLACE ANY DAMAGED UTILITIES DURING THE COURSE OF WORK.

5. PROTECT BUILDING FROM DAMAGE WHICH MAY OCCUR FROM DEMOLITION, DUST, WATER

ADVERSE WEATHER, ETC.

6. CONTRACTOR TO PATCH AND REPAIR ALL AREAS DAMAGED BY, OR INCIDENTAL TO

DEMOLITION

AND /OR NEW WORK TO MATCH ADJACENT FINISHES UNLESS OTHERWISE NOTED.

7. ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO (E) CONDITIONS IS GIVEN AS

BEST PRESENT KNOWLEDGE. WHERE ACTUAL CONDITIONS CONFLICT WITH THE

DRAWINGS, THEY SHALL BE REPORTED TO THE ARCHITECT SO THAT THE

CORRECTION/CLARIFICATION CAN BE PROVIDED.

8. ALL DIMENSIONS ARE TO BE VERIFIED IN FIELD.

9. COORDINATE WITH PLANT OPS BEFORE AND AFTER SHUTTING OFF ANY UTILITIES.

GENERAL NOTES

LEGEND

EXISTING TO REMAIN

TO BE REMOVED

NEW

EXTERIOR FINISH & COLOR LEGEND

C-2:

C-1:

INMATE ACCESSIBLE AREA

C-4:

C-3:

H

L

ES

I

N

E C

AD CR

T

I

ET

C

C-34592

REN. 09-30-25

R A

M

HA

EC

T

ROIF

E

CO F AL

T

S

TA N

IA

RVA

N T E S

C A D

F

IL

E

DATE:

SHEET NUMBER

A

B

C

D

E

F

G

H

J

K

L

M

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

OF SHEETS V1

ARCHITECTURE & ENGINEERING

CALIFORNIA DEPARTMENT OF

CORRECTIONS AND REHABILITATION

CALIFORNIA DEPARTMENT OF

CORRECTIONS AND REHABILITATION

ACCESS COMPLIANCE REVIEW

APPROVAL OF THIS PLAN DOES NOT AUTHORIZE

OR APPROVE ANY OMMISION OR DEVIATION

FROM APPLICABLE REGULATIONS

SUPERVISING ARCHITECT

P D E S

IG

N S

E R V

IC

E S \C

C W

F \D

E S

IG

N \2

-0

E

IF

S B ld g

F a c ili ty

B \D ra w in g s \2

-0

C

C W

F B L D G

C D

.r v t

/2

/2

:4 :1

P

M

A3.2

H O

U S

IN

G U

N

IT

B L D G

E X T E R

IO

R

E L E V A T

IO

N S

05/28/2025

E

IF

S B

L D G

F A C

IL

IT

Y B

24-051

C E N T R

A L C

A L

IF

O R

N

IA

W O

M E N 'S

F A C

IL

IT

Y C

C W

F

R

O A D

C H O

W C

H

IL

L A , C

A

CCWF

MARTHA CERVANTES

SENIOR ARCHITECT

JOHN RODRIGUEZ

SCALE: 3/32" = 1'-0"1 BLDG 508 NORTH EXISTING/DEMOLITION ELEVATION

SCALE: 3/32" = 1'-0"3 BLDG 508 EAST EXISTING/DEMOLITION ELEVATION

SCALE: 3/32" = 1'-0"2 BLDG 508 NORTH ELEVATION

SCALE: 3/32" = 1'-0"4 BLDG 508 EAST ELEVATION

D2 REMOVE (E) DOWNSPOUT PATCH & REPAIR IN-KIND AND PREP FOR

NEW WORK

D5 GRIND DOWN HIGH SPOTS OF SPLITFACE CMU AS NEEDED TO

ACCOMODATE THE (N) EIFS SYSTEM OVER PAPER BACKED

GALVANIZED METAL LATH

D20REMOVE AND RELOCATE (E) ELECTRICAL OUTLET TO ACCOMODATE

(N) EIFS SYSTEM. (N)LOCATION TO MATCH (E). SEE ELECTRICAL

DRAWINGS.

D21 REMOVE AND RELOCATE (E) INTERCOM PANEL TO ACCOMODATE (N)

EIFS SYSTEM. (N)LOCATION TO MATCH (E). SEE ELECTRICAL

DRAWINGS.

D23 REMOVE AND RELOCATE (E) HOSEBIB TO ACCOMODATE (N) EIFS

SYSTEM. (N)LOCATION TO MATCH (E).

D30 REMOVE AND RELOCATE (E) PRECAST CONCRETE SPLASH BLOCK

TO ACCOMODATE (N) EIFS SYSTEM. (N)LOCATION TO MATCH (E).

D32 REMOVE AND RELOCATE (E) FIRE ALARM TO ACCOMODATE (N) EIFS

SYSTEM. (N)LOCATION TO MATCH (E). SEE ELECTRICAL DRAWINGS.

D33 REMOVE AND RELOCATE (E) ELECTRICAL PANEL TO ACCOMODATE

(N) EIFS SYSTEM. (N)LOCATION TO MATCH (E). SEE ELECTRICAL

DRAWINGS.

KEYNOTES - DEMO

2 (E) STANDARD AND SPLITFACE CMU WALL TO REMAIN

3 (E) CMU CONTROL JOINT TO REMAIN

4 (E) WINDOW TO REMAIN. PAINT METAL WINDOW FRAME TO MATCH

6 (E) LOUVER TO REMAIN. PAINT TO MATCH

8 (E) METAL DOOR AND FRAME TO REMAIN. PAINT TO MATCH

9 (E) STUCCO ON CMU TO REMAIN

10 (E) STUCCO ON METAL FRAMING TO REMAIN

11 (E) STUCCO CONTROL JOINT TO REMAIN

12 (E) CONCRETE TILE ROOF TO REMAIN

13 (E) GUTTER TO REMAIN. PAINT TO MATCH

15 (E) METAL COPING TO REMAIN

16 (E) PREFINISH METAL FASCIA SYSTEM TO REMAIN

17 (E) PREFINISH METAL FLASHING TO REMAIN

18 (E) CONCRETE STOOP TO REMAIN

20 (E) FENCE POST TO REMAIN

21 (E) CHAIN LINK FENCE AND RAZOR WIRE TO REMAIN

26 (E) GAS METER TO REMAIN

27 (E) WALL THRU ROOF LEADERS TO REMAIN, SEE DTL 10/A5.3

28 (E) ELECTRICAL CONDUIT AND HOUSING TO REMAIN

29 (E) CONDENSOR UNIT AND WALL MOUNT FRAME TO REMAIN

30 (E) STEEL BAR TO REMAIN. PAINT TO MATCH

52 (N) DOWNSPOUT. PAINT TO MATCH

53 (N) 4" (R16) EXTERIOR INSULATION AND FINISH SYSTEM (EIFS)

54 (N) EXTERIOR INSULATION AND FINISH SYSTEM (EIFS) CONTROL

JOINT. MATCH LOCATION OF (E) CONTROL JOINT U.N.O.

55 (N) EXTERIOR INSULATION AND FINISH SYSTEM (EIFS) REVEAL

56 (N) 1 1/2" EXTERIOR INSULATION AND FINISH SYSTEM (EIFS) AT (E)

GAS METER

57 (N) 1 1/2" EXTERIOR INSULATION AND FINISH SYSTEM (EIFS) AT (E)

CONDENSER UNIT

60 NO EIFS BEHIND (E) ELECTRICAL CONDUIT AND HOUSING

65 PROVIDE PAPER BACKED GALVANIZED METAL LATH AT EIFS SYSTEM

OVER SPLITFACE CMU.

70 RELOCATED (E) ELECTRICAL OUTLET

71 RELOCATED (E) INTERCOM PANEL

73 RELOCATED (E) HOSEBIB, SEE DTL 10/A5.3

80 RELOCATED (E) PRECAST CONCRETE SPLASH BLOCK

83 RELOCATED (E) ELECTRICAL PANEL

KEYNOTES

REV. DATE: DESCRIPTION

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

07/14/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1743

4 24

42 22

D22

D21

D20

D5D5

FF

0' - 0"

A4.1

53555555 53 555555

65 65

FF

0' - 0"

555555 53

FF

0' - 0"

2 8

D5

FF

0' - 0"

D5

FF

0' - 0"

53 555555

FF

0' - 0"

A4.1

53555555

C -2

4 4 2 4 4

D5

FF

0' - 0"

4 4 2 4 4

D5

FF

0' - 0"

53555555

C -2

15 9 15 9 159D33

3 3

11 11

26 8 6 29 2727 D32 8284 4 4 2

D5

D35

FF

0' - 0"

A4.1

53 535454

60555555 57 53

65 65

A5.1

A5.1

C -2

LEGEND

EXISTING TO REMAIN

TO BE REMOVED

NEW

1. BUILDING WILL BE OCCUPIED DURING DEMOLITION AND CONSTRUCTION. EGRESS /INGRESS

SHALL REMAIN FREE OF DEBRIS AND OBSTRUCTION THROUGH OUT DEMOLITION AND

CONSTRUCTION.

2. FIRE ACCESS AND FIRE APPARATUS ROAD WAY SHALL BE MAINTAINED FREE OF

OBSTRUCTION AT ALL TIMES.

3. ALL CONSTRUCTION DEBRIS GENERATED IN THE COURSE OF THIS PROJECT SHALL BE

REMOVED AND DISPOSED OF IN COMPLIANCE WITH LOCAL, STATE AND FEDERAL CODES

AND REGULATIONS.

4. REPAIR / REPLACE ANY DAMAGED UTILITIES DURING THE COURSE OF WORK.

5. PROTECT BUILDING FROM DAMAGE WHICH MAY OCCUR FROM DEMOLITION, DUST, WATER

ADVERSE WEATHER, ETC.

6. CONTRACTOR TO PATCH AND REPAIR ALL AREAS DAMAGED BY, OR INCIDENTAL TO

DEMOLITION

AND /OR NEW WORK TO MATCH ADJACENT FINISHES UNLESS OTHERWISE NOTED.

7. ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO (E) CONDITIONS IS GIVEN AS

BEST PRESENT KNOWLEDGE. WHERE ACTUAL CONDITIONS CONFLICT WITH THE

DRAWINGS, THEY SHALL BE REPORTED TO THE ARCHITECT SO THAT THE

CORRECTION/CLARIFICATION CAN BE PROVIDED.

8. ALL DIMENSIONS ARE TO BE VERIFIED IN FIELD.

9. COORDINATE WITH PLANT OPS BEFORE AND AFTER SHUTTING OFF ANY UTILITIES.

GENERAL NOTES EXTERIOR FINISH & COLOR LEGEND

C-2:

C-1:

INMATE ACCESSIBLE AREA

C-4:

C-3:

H

L

ES

I

N

E C

AD CR

T

I

ET

C

C-34592

REN. 09-30-25

R A

M

HA

EC

T

ROIF

E

CO F AL

T

S

TA N

IA

RVA

N T E S

C A D

F

IL

E

DATE:

SHEET NUMBER

A

B

C

D

E

F

G

H

J

K

L

M

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

OF SHEETS V1

ARCHITECTURE & ENGINEERING

CALIFORNIA DEPARTMENT OF

CORRECTIONS AND REHABILITATION

CALIFORNIA DEPARTMENT OF

CORRECTIONS AND REHABILITATION

ACCESS COMPLIANCE REVIEW

APPROVAL OF THIS PLAN DOES NOT AUTHORIZE

OR APPROVE ANY OMMISION OR DEVIATION

FROM APPLICABLE REGULATIONS

SUPERVISING ARCHITECT

P D E S

IG

N S

E R V

IC

E S \C

C W

F \D

E S

IG

N \2

-0

E

IF

S B ld g

F a c ili ty

B \D ra w in g s \2

-0

C

C W

F B L D G

C D

.r v t

/2

/2

:4 :1

P

M

A3.3

H O

U S

IN

G U

N

IT

B L D G

E N L A R G

E D

E X

TE

R

IO

R E

L E V A T

IO

N S

05/28/2025

E

IF

S B

L D G

F A C

IL

IT

Y B

24-051

C E N T R

A L C

A L

IF

O R

N

IA

W O

M E N 'S

F A C

IL

IT

Y C C

W F

R

O A D

C H O

W C

H

IL

L A , C

A

CCWF

MARTHA CERVANTES

SENIOR ARCHITECT

JOHN RODRIGUEZ

SCALE: 3/16" = 1'-0"1 BLDG 508 SW EXIST/DEMO ELEVATION

SCALE: 3/16" = 1'-0"2 BLDG 508 SW ELEVATION

SCALE: 3/16" = 1'-0"4BLDG SW ELEVATION

SCALE: 3/16" = 1'-0"3BLDG 508 SW EXIST/DEMO ELEVATION

SCALE: 3/16" = 1'-0"5 BLDG 508 SE EXIST/DEMO ELEVATION

SCALE: 3/16" = 1'-0"6 BLDG 508 SE ELEVATION

SCALE: 3/16" = 1'-0"8 BLDG 508 SE ELEVATION

SCALE: 3/16" = 1'-0"7 BLDG 508 SE EXIST/DEMO ELEVATION

SCALE: 3/16" = 1'-0"9 BLDG 508 SW EXIST/DEMO ELEVATION

SCALE: 3/16" = 1'-0"10 BLDG 508 SW ELEVATION

SCALE: 3/16" = 1'-0"11 BLDG 508 NORTH EAST ELEVATION

SCALE: 3/16" = 1'-0"12 BLDG 508 NORTH EAST ELEVATION

KEYNOTES - DEMO

2 (E) STANDARD AND SPLITFACE CMU WALL TO REMAIN

3 (E) CMU CONTROL JOINT TO REMAIN

4 (E) WINDOW TO REMAIN. PAINT METAL WINDOW FRAME TO

MATCH

6 (E) LOUVER TO REMAIN. PAINT TO MATCH

8 (E) METAL DOOR AND FRAME TO REMAIN. PAINT TO MATCH

9 (E) STUCCO ON CMU TO REMAIN

11 (E) STUCCO CONTROL JOINT TO REMAIN

15 (E) METAL COPING TO REMAIN

22 (E) ELECTRICAL PANEL TO REMAIN

26 (E) GAS METER TO REMAIN

27(E) WALL THRU ROOF LEADERS TO REMAIN, SEE DTL 10/A5.3

28 (E) ELECTRICAL CONDUIT AND HOUSING TO REMAIN

29 (E) CONDENSOR UNIT AND WALL MOUNT FRAME TO REMAIN

53 (N) 4" (R16) EXTERIOR INSULATION AND FINISH SYSTEM

(EIFS)

54 (N) EXTERIOR INSULATION AND FINISH SYSTEM (EIFS)

CONTROL JOINT. MATCH LOCATION OF (E) CONTROL JOINT

U.N.O.

55 (N) EXTERIOR INSULATION AND FINISH SYSTEM (EIFS)

REVEAL

57(N) 1 1/2" EXTERIOR INSULATION AND FINISH SYSTEM (EIFS)

AT (E) CONDENSER UNIT

60 NO EIFS BEHIND (E) ELECTRICAL CONDUIT AND HOUSING

65 PROVIDE PAPER BACKED GALVANIZED METAL LATH AT EIFS

SYSTEM OVER SPLITFACE CMU.

D5 GRIND DOWN HIGH SPOTS OF SPLITFACE CMU AS NEEDED

TO ACCOMODATE THE (N) EIFS SYSTEM OVER PAPER

BACKED GALVANIZED METAL LATH

D20 REMOVE AND RELOCATE (E) ELECTRICAL OUTLET TO

ACCOMODATE (N) EIFS SYSTEM. (N)LOCATION TO MATCH

(E). SEE ELECTRICAL DRAWINGS.

D21 REMOVE AND RELOCATE (E) INTERCOM PANEL TO

ACCOMODATE (N) EIFS SYSTEM. (N)LOCATION TO MATCH

(E). SEE ELECTRICAL DRAWINGS.

D22 REMOVE AND RELOCATE (E) KEYSWITCH PANEL TO

ACCOMODATE (N) EIFS SYSTEM. (N)LOCATION TO MATCH

(E). SEE ELECTRICAL DRAWINGS.

D32 REMOVE AND RELOCATE (E) FIRE ALARM TO ACCOMODATE

(N) EIFS SYSTEM. (N)LOCATION TO MATCH (E). SEE

ELECTRICAL DRAWINGS.

D33 REMOVE AND RELOCATE (E) ELECTRICAL PANEL TO

ACCOMODATE (N) EIFS SYSTEM. (N)LOCATION TO MATCH

(E). SEE ELECTRICAL DRAWINGS.

D35 REMOVE AND RELOCATE (E) DISCONNECT TO

ACCOMODATE (N) EIFS SYSTEM. (N) LOCATION TO MATCH

(E). SEE ELECTRICAL DRAWINGS.

KEYNOTES

REV. DATE: DESCRIPTION

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

07/14/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1743

A4.1

6 7 8

12 24 15 10 15 9

12 15 10 12

6' - 0"6' - 0"

V .I .F

E Q

E Q

E Q

V .I .F

5454 53

55555530

555555 53

17 52

80 65

A5.2

A5.2

C -2

N M L K J

E Q

E Q

E Q

V .I .F

1' - 3"

7' - 2" 7' - 1 1/2"

4555555

ALIGN

ALIGN

A

LI

G N

1213 16

5454 453

4 5454 52

73 555555 53

7' - 1 1/2" 7' - 2"

1' - 3"

A5.2

C -2

J K L M N

12 13 16

2' - 0"

1' - 3"

E Q

E Q

E Q

V .I .F

53 555555

4 52

ALIGN

ALIGN

4 5454

7' - 1 1/2" 7' - 1 1/2"

A

LI

G N

5454 4 52

4 555555 73 53

A5.2

C -2

1. BUILDING WILL BE OCCUPIED DURING DEMOLITION AND CONSTRUCTION. EGRESS /INGRESS

SHALL REMAIN FREE OF DEBRIS AND OBSTRUCTION THROUGH OUT DEMOLITION AND

CONSTRUCTION.

2. FIRE ACCESS AND FIRE APPARATUS ROAD WAY SHALL BE MAINTAINED FREE OF

OBSTRUCTION AT ALL TIMES.

3. ALL CONSTRUCTION DEBRIS GENERATED IN THE COURSE OF THIS PROJECT SHALL BE

REMOVED AND DISPOSED OF IN COMPLIANCE WITH LOCAL, STATE AND FEDERAL CODES

AND REGULATIONS.

4. REPAIR / REPLACE ANY DAMAGED UTILITIES DURING THE COURSE OF WORK.

5. PROTECT BUILDING FROM DAMAGE WHICH MAY OCCUR FROM DEMOLITION, DUST, WATER

ADVERSE WEATHER, ETC.

6. CONTRACTOR TO PATCH AND REPAIR ALL AREAS DAMAGED BY, OR INCIDENTAL TO

DEMOLITION

AND /OR NEW WORK TO MATCH ADJACENT FINISHES UNLESS OTHERWISE NOTED.

7. ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO (E) CONDITIONS IS GIVEN AS

BEST PRESENT KNOWLEDGE. WHERE ACTUAL CONDITIONS CONFLICT WITH THE

DRAWINGS, THEY SHALL BE REPORTED TO THE ARCHITECT SO THAT THE

CORRECTION/CLARIFICATION CAN BE PROVIDED.

8. ALL DIMENSIONS ARE TO BE VERIFIED IN FIELD.

9. COORDINATE WITH PLANT OPS BEFORE AND AFTER SHUTTING OFF ANY UTILITIES.

GENERAL NOTES

LEGEND

EXISTING TO REMAIN

NEW

EXTERIOR FINISH & COLOR LEGEND

C-2:

C-1:

INMATE ACCESSIBLE AREA

C-4:

C-3:

H

L

ES

I

N

E C

AD CR

T

I

ET

C

C-34592

REN. 09-30-25

R A

M

HA

EC

T

ROIF

E

CO F AL

T

S

TA N

IA

RVA

N T E S

C A D

F

IL

E

DATE:

SHEET NUMBER

A

B

C

D

E

F

G

H

J

K

L

M

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

OF SHEETS V1

ARCHITECTURE & ENGINEERING

CALIFORNIA DEPARTMENT OF

CORRECTIONS AND REHABILITATION

CALIFORNIA DEPARTMENT OF

CORRECTIONS AND REHABILITATION

ACCESS COMPLIANCE REVIEW

APPROVAL OF THIS PLAN DOES NOT AUTHORIZE

OR APPROVE ANY OMMISION OR DEVIATION

FROM APPLICABLE REGULATIONS

SUPERVISING ARCHITECT

P D E S

IG

N S

E R V

IC

E S \C

C W

F \D

E S

IG

N \2

-0

E

IF

S B ld g

F a c ili ty

B \D ra w in g s \2

-0

C

C W

F B L D G

C D

.r v t

/2

/2

:4 :1

P

M

A3.4

H O

U S

IN

G U

N

IT

B L D G

E N L A R G

E D

E X

TE

R

IO

R E

L E V A T

IO

N S

05/28/2025

E

IF

S B

L D G

F A C

IL

IT

Y B

24-051

C E N T R

A L C

A L

IF

O R

N

IA

W O

M E N 'S

F A C

IL

IT

Y C C

W F

R

O A D

C H O

W C

H

IL

L A , C

A

CCWF

MARTHA CERVANTES

SENIOR ARCHITECT

JOHN RODRIGUEZ

SCALE: 3/16" = 1'-0"1 BLDG 508 ENLARGED ELEVATION - HOUSING WING

SCALE: 3/16" = 1'-0"2BLDG 508 ENLARGED ELEVATION - HOUSING WING

SCALE: 3/16" = 1'-0"3 BLDG 508 ENLARGED ELEVATION - HOUSING WING

4 (E) WINDOW TO REMAIN. PAINT METAL WINDOW FRAME TO MATCH

6 (E) LOUVER TO REMAIN. PAINT TO MATCH

8 (E) METAL DOOR AND FRAME TO REMAIN. PAINT TO MATCH

9 (E) STUCCO ON CMU TO REMAIN

10 (E) STUCCO ON METAL FRAMING TO REMAIN

12 (E) CONCRETE TILE ROOF TO REMAIN

13 (E) GUTTER TO REMAIN. PAINT TO MATCH

15 (E) METAL COPING TO REMAIN

16 (E) PREFINISH METAL FASCIA SYSTEM TO REMAIN

17 (E) PREFINISH METAL FLASHING TO REMAIN

24 (E) BUILDING NUMBER TO REMAIN

30 (E) STEEL BAR TO REMAIN. PAINT TO MATCH

52 (N) DOWNSPOUT. PAINT TO MATCH

53 (N) 4" (R16) EXTERIOR INSULATION AND FINISH SYSTEM (EIFS)

54 (N) EXTERIOR INSULATION AND FINISH SYSTEM (EIFS) CONTROL

JOINT. MATCH LOCATION OF (E) CONTROL JOINT U.N.O.

55 (N) EXTERIOR INSULATION AND FINISH SYSTEM (EIFS) REVEAL

65 PROVIDE PAPER BACKED GALVANIZED METAL LATH AT EIFS SYSTEM

OVER SPLITFACE CMU.

70 RELOCATED (E) ELECTRICAL OUTLET

71 RELOCATED (E) INTERCOM PANEL

73 RELOCATED (E) HOSEBIB, SEE DTL 10/A5.3

80 RELOCATED (E) PRECAST CONCRETE SPLASH BLOCK

KEYNOTES

ALIGN

ALIGN

A

LI

G N

REV. DATE: DESCRIPTION

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

07/14/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1743

A5.2

A5.1

A5.1

A5.1

(N) 4" EIFS SYSTEM

O/GALVANIZED METAL

LATH O/ (E) SPLIT FACE

& STANDARD CMU WALL

FF

0' - 0"

A5.1

(N) 4" EIFS SYSTEM

O/GALVANIZED METAL

LATH O/ (E) SPLIT FACE

& STANDARD CMU

WALL, BEYOND

(E) SOFFIT VENT.

STOP (N) EIFS WALL

SYSTEM 4" BELOW VENT.

PROVIDE CAP FLASHING.

SEE SIMILAR DETAIL

FF

0' - 0"

A5.1

A5.1

A5.2

A5.1

A5.1

(N) 4" EIFS SYSTEM

O/GALVANIZED METAL

LATH O/ (E) SPLIT FACE

& STANDARD CMU WALL

FF

0' - 0"

A5.1

A5.1

A5.1

A5.1

(N) 4" EIFS SYSTEM

O/GALVANIZED METAL

LATH O/ (E) SPLIT FACE

& STANDARD CMU WALL

A5.2

FF

0' - 0"

A5.2

A5.1

A5.2

A5.1

A5.1

(N) 4" EIFS SYSTEM

O/GALVANIZED METAL

LATH O/ (E) SPLIT FACE

& STANDARD CMU WALL

FF

0' - 0"

A5.1

A5.1

A5.1

A5.1

A5.2

(N) 4" EIFS SYSTEM

O/GALVANIZED METAL

LATH O/ (E) SPLIT FACE

& STANDARD CMU WALL

H

L

ES

I

N

E C

AD CR

T

I

E T

C

C-34592

REN. 09-30-25

R A

M

HA

EC

T

R

OIF

E C

OF AL

T

S T

A N

IA

RVA

N T E S

C A D

F

IL

E

DATE:

SHEET NUMBER

A

B

C

D

E

F

G

H

J

K

L

M

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

OF SHEETS V1

ARCHITECTURE & ENGINEERING

CALIFORNIA DEPARTMENT OF

CORRECTIONS AND REHABILITATION

CALIFORNIA DEPARTMENT OF

CORRECTIONS AND REHABILITATION

ACCESS COMPLIANCE REVIEW

APPROVAL OF THIS PLAN DOES NOT AUTHORIZE

OR APPROVE ANY OMMISION OR DEVIATION

FROM APPLICABLE REGULATIONS

SUPERVISING ARCHITECT

P D E S

IG

N S

E R V

IC

E S \C

C W

F \D

E S

IG

N \2

-0

E

IF

S B ld g

F a c ili ty

B \D ra w in g s \2

-0

C

C W

F B L D G

C D

.r v t

/2

/2

:4 :1

P

M

A4.1

H O

U S

IN

G U

N

IT

B L D G

W A L L S

E C

TI

O

N S

05/28/2025

E

IF

S B

L D G

F A C

IL

IT

Y B

24-051

C E N T R

A L C

A L

IF

O R

N

IA

W O

M E N 'S

F A C

IL

IT

Y C C

W F

R

O A D

C H O

W C

H

IL

L A , C

A

CCWF

MARTHA CERVANTES

SENIOR ARCHITECT

JOHN RODRIGUEZ

SCALE: 1/2" = 1'-0"1 BLDG 508 WALL SECTION

SCALE: 1/2" = 1'-0"2 BLDG 508 WALL SECTION

SCALE: 1/2" = 1'-0" 3 BLDG 508 WALL SECTION

SCALE: 1/2" = 1'-0"5 BLDG 508 WALL SECTION

SCALE: 1/2" = 1'-0"4 BLDG 508 WALL SECTION

SCALE: 1/2" = 1'-0"6 BLDG 508 WALL SECTION

REV. DATE: DESCRIPTION

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

07/14/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1743

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

07/14/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1743

07/14/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1743

07/14/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1743

07/14/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1743

07/14/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1743

07/14/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1743

07/14/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1743

07/14/25

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

25-1743

File details come from the government source that posted it. Updated .