13643_-_Drawings.pdf
PDF 7 MB Posted
- Solicitation number
- 0000039770
- Issued by
- Los Angeles County, California
About this file
Summary
This is a 100% Construction Drawings document for the California Department of Water Resources (DWR) Electric Vehicle Supply Equipment (EVSE) Installation project at the Castaic Operations and Maintenance Center in Los Angeles County, California. The project involves the installation of charging infrastructure to support 18 total electric vehicle charging station ports: 16 Level 2 EVSE units and 2 Level 3 (DC Fast Charging) units distributed across two parking areas designated for fleet vehicles only. The scope encompasses electrical work including two transformers, three panelboards, one disconnect switch, new feeder conductors, underground conduit routing, conduit stub-ups, grounding systems, and structural support elements. The project also includes civil and structural work necessary to support the installation, such as concrete equipment pads, bollards, ground rings, ground wells, and site restoration. Sealed bids are due August 17, 2026, at 2:00 P.M. at the DGS Office of Business and Acquisition Services in West Sacramento. The contractor must possess a valid C-10 license and submit valid Certificates of Reported Compliance for any fleet vehicles used in the work. All work must comply with 2025 California Building Code, 2025 California Electrical Code, 2025 California Fire Code, NFPA standards, and applicable ADA requirements, with the exception that fleet-only EVCS are not required to meet CBC Section 11B-228.3.2 accessibility requirements.
The project requires the contractor to provide, install, and commission all EVCS units as commercial-grade equipment compliant with UL 2594, UL 223, UL 50E, NFPA 70, and FCC EMI standards. The EVCS must include minimum 18-foot cable lengths and cord management systems, with Level 2 units featuring SAE J1772 connectors and Level 3 units featuring SAE J3400 or SAE CCS1 connectors. The contractor is responsible for all final terminations and splicing of the EVCS, with the exception that early drawing iterations noted state vendor involvement in final installation; however, the revised notes clarify contractor responsibility for all installation and commissioning. Third-party testing is required for all new feeder conductors. The project location is the DWR Castaic O&M Center at 31849 Lake Hughes Road, Castaic, California 91384. Coordination with the DWR site representative is mandatory, with a minimum 72-hour notice required before any circuit shutdown or facility disruption. The contract is identified as Contract Number 25-324648, Project Number 13643, and the project was State Fire Marshal approved on April 21, 2026, with an issue date of July 10, 2026.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 13643_-_Bid_Package_Documents.pdf | ||
| 13643_-_Complete_Project_Manual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROACTIVE ENGINEERING CONSULTANTS
27051 TOWNE CENTRE DRIVE, SUITE 270
FOOTHILL RANCH, CA 92610
(949) 716-7460
CONTACT: FELIX GONZALEZ
MRP PLANNING CO.
130 CENTENNIAL WAY, UNIT C,
TUSTIN, CA 92780
(714) 923-8946
CONTACT: MIKE PAAR
Department of Water Resources Castaic O&M Center EVSE Installation
100% Construction Drawings
LOCATION MAP
NOT TO SCALE
INDEX OF DRAWINGS
SCOPE OF WORK
THE SCOPE OF THIS PROJECT CONSISTS OF THE INSTALLATION OF THE ELECTRIC
VEHICLE SUPPLY EQUIPMENT (EVSE) TO PROVIDE POWER TO (16) LEVEL 2 AND (2)
LEVEL 3 ELECTRIC VEHICLE CHARGING STATION (EVCS) PORTS WITHIN THE DWR
CASTAIC O&M CENTER. SEE EVCS NOTE ON THIS SHEET.
THE EVCS IS MADE UP OF (2) TRANSFORMERS, (3) PANELBOARDS, (1) DISCONNECT
SWITCH, AS WELL AS NEW FEEDERS TO THE EVCS PORTS LOCATIONS AS SHOWN ON
THESE PLANS. PROJECT INCLUDES STRUCTURAL AND CIVIL WORK EFFORT/S
NECESSARY TO SUPPORT THIS PROJECT. SEE SHEET E1.00 FOR A SUMMARY OF THE
EVCS PORTS.
ALL WORK PERTAINING TO AND ALL MATERIALS SUPPLIED FOR EXECUTING AND
COMPLETING THIS CONTRACT SHALL COMPLY WITH PROVISIONS SPECIFIED IN THE
CONTRACT DOCUMENTS AND WITH ALL APPLICABLE LAWS, REGULATIONS AND
ORDINANCES GOVERNING WORK INCLUDING, BUT NOT NECESSARILY LIMITED TO
THOSE OF THE APPLICABLE CODES LISTED ON SHEET E0.01.
ALTHOUGH THE CONTRACTOR MAY NOT PROCURE OR PERFORM THE FINAL
INSTALLATION OF THE EVCS, SUCH WORK IS WITHIN THE PERMIT SCOPE AND MAY BE
PERFORMED BY OTHERS.
ALL EVCS INSTALLED ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE
INTENDED FOR USE BY A DESIGNATED VEHICLE OR DRIVER; THEREFORE, PER CBC
SECTION 11B-228.3.2 EXCEPTION 1, THE EVCS SHALL NOT BE REQUIRED TO COMPLY
WITH CBC 11B-228.3.2 ACCESS REQUIREMENTS.
SHEET COUNT DWG. NO. DESCRIPTION
1 OF 22 T0.01 TITLE SHEET, LOCATION MAP, GENERAL NOTES &
SHEET INDEX
2 OF 22 E0.01 SYMBOLS, DESIGNATION AND ABBREVIATIONS
3 OF 22 E0.02 SITE SAFETY PLAN
4 OF 22 E0.03 SITE SAFETY PLANS
5 OF 22 E1.00 SITE PLAN
6 OF 22 E2.00 POWER PLAN
7 OF 22 E2.01 ENLARGED NORTH POWER PLANS
8 OF 22 E2.02 ENLARGED SOUTH POWER PLANS
9 OF 22 E4.00 ELECTRICAL DETAILS
10 OF 22 E4.01 ELECTRICAL DETAILS
11 OF 22 E5.00 SINGLE LINE DIAGRAM
12 OF 22 E5.01 ELECTRICAL SCHEDULES
13 OF 22 C1 TITLE SHEET
14 OF 22 C2 SITE PLAN
15 OF 22 C3 SITE PLAN
16 OF 22 C4 SITE PLAN
17 OF 22 S0.01 GENERAL NOTES
18 OF 22 S0.02 SPECIAL INSPECTION
19 OF 22 S2.00 WATER OPS BUILDING
ENLARGED EQUIPMENT SUPPORT PLAN
20 OF 22 S2.01 O & M CENTER
ENLARGED EQUIPMENT SUPPORT PLAN
21 OF 22 S4.00 STRUCTURAL DETAILS
22 OF 22 S4.00 STRUCTURAL DETAILS
1. THE ARRANGEMENT OF THE EQUIPMENT, ELECTRICAL DEVICES, ETC. SHOWN ON THESE DRAWINGS IS GENERAL AND IS SHOWN TO IDENTIFY THE GENERAL INTENT OF THE PROJECT. ALL DETAILS AND ARRANGEMENTS SHALL BE VERIFIED PRIOR TO THE START OF WORK. THE DRAWINGS ARE NOT INTENDED TO SHOW EXACT DIMENSIONS/LOCATIONS.
2. CODE COMPLIANCE: ALL WORK SHALL CONFORM TO BE PERFORMED IN ACCORDANCE WITH THE APPLICABLE CODES, STANDARDS, AND ORDINANCE AS SET FORTH BY THE AUTHORITIES HAVING JURISDICTION AND THEIR LATEST ADOPTED EDITIONS (IN EFFECT AT THE TIME OF THE BUILDING PERMIT APPLICATION) OF THE FOLLOWING PUBLICATIONS:
· CALIFORNIA CODE OF REGULATIONS TITLE 24: INCLUDES 2025 CALIFORNIA ELECTRICAL CODE, 2025 CALIFORNIA FIRE
CODE, 2025 CALIFORNIA BUILDING CODE, APPLICABLE YEARS OF NFPA ETC. WITH CALIFORNIA AND OTHER LOCAL
AMENDMENTS AS APPLICABLE.
· 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN.
3. SAFETY: THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO MAINTAIN ALL EQUIPMENT IN A SAFE AND RESPONSIBLE MANNER. KEEP DEAD FRONT EQUIPMENTS IN PLACE WHILE ENERGIZED. CONDUCT ALL CONSTRUCTION OPERATIONS IN A SAFE MANNER FOR EMPLOYEES AS WELL AS OTHER WORK PERSONS OR ANYONE VISITING THE JOB SITE. PROVIDE BARRIERS, FLAGS, TAPE, ETC. AS REQUIRED FOR SAFETY. THE CONTRACTOR SHALL HOLD ALL PARTIES HARMLESS OF
NEGLIGENT PRACTICES, WHICH MAY CAUSE INJURY TO OTHERS ON OR NEAR THE JOB SITE.
4. FIRE RATED ASSEMBLIES SHALL MAINTAIN RATINGS AS SPECIFIED IN THE CALIFORNIA BUILDING CODE, CHAPTER 7. ALL ASSEMBLIES TO BE PENETRATED SHALL BE INSTALLED WITH APPLICABLE THROUGH-PENETRATION FIRESTOP SYSTEM AS DETERMINED BY UL CLASSIFICATION. BEFORE CONSTRUCTION, VERIFY AND COMPLY WITH REQUIREMENTS.
5. PROVIDE THIRD-PARTY TESTING FOR ALL NEW FEEDER CONDUCTORS. BRANCH CIRCUITS ARE NOT REQUIRED TO BE
TESTED BY THIRD-PARTY. REFER TO PROJECT SPECIFICATIONS FOR MORE INFORMATION.
FOR EXISTING BUILDINGS:
1. ASBESTOS/LEAD PAINT: IF DURING THE COURSE OF WORK THE CONTRACTOR OBSERVES THE EXISTENCE OF ASBESTOS/LEAD PAINT, ASBESTOS BEARING MATERIALS, THE CONTRACTOR SHALL IMMEDIATELY TERMINATE FURTHER WORK ON THE PROJECT AND NOTIFY THE DWR SITE REPRESENTATIVE OF THE CONDITIONS. THE DWR SITE REPRESENTATIVE, AFTER CONSULTATION WITH THE DEPARTMENT OF GOVERNMENT (DGS) PROJECT MANAGER, WILL
DETERMINE THE FURTHER COURSE OF ACTION.
2. ANY DEMOLITION WORK SHOWN WAS PREPARED FOR THE CONVENIENCE OF THE CONTRACTOR. THE ENGINEER DOES NOT REPRESENT THAT ALL ITEMS WHICH MAY REQUIRE DEMOLITION HAVE BEEN SHOWN. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO CAREFULLY EXAMINE THE SITE AND CONTRACT DOCUMENTS AND TO PERFORM ALL DEMOLITION AND RECONSTRUCTION WHICH MAY BE REQUIRED FOR THE PROPER EXECUTION AND
COMPLETION OF THE WORK.
3. EXISTING CONDITIONS: INFORMATION SHOWN FOR EXISTING CONDITIONS WAS PRIMARILY GAINED FROM "AS-BUILT" DRAWINGS AND/OR LIMITED FIELD INVESTIGATION. BEFORE BID, VISIT SITE TO VERIFY EXISTING CONDITIONS AND MAKE
ALLOWANCE FOR VARIATION FROM THAT SHOWN.
4. CLOSELY COORDINATE OUTAGE AND FACILITY DISRUPTION TIMES WITH THE DWR SITE REPRESENTATIVE. A MINIMUM 72-HOURS NOTICE IS REQUIRED BEFORE ANY CIRCUIT SHUTDOWN OR DISRUPTION TO FACILITY OPERATIONS OR
PERSONNEL FUNCTIONS.
GENERAL NOTES
PROJECT TEAM
PROJECT DIRECTOR
STRUCTURAL ENGINEERCIVIL ENGINEER
ELECTRICAL ENGINEER
GOSS ENGINEERING, INC.
255 EAST RINCON STREET, SUITE 301,
CORONA, CA 92879
(951) 340-1977
CONTACT: ED BURTCH
R
CALL 811 BEFORE YOU DIG.
DGS PROJECT NUMBER: 000000000013643
PROJECT
LOCATION
BUILDING INFORMATION
CIVIL MAINTENANCE OFFICE
CONSTRUCTION TYPE: TYPE III-B
OCCUPANCY CLASSIFICATION: BUSINESS GROUP B / S-2
OCCUPANCY LOAD: N/A
ACTUAL BUILDING HEIGHT: 18'-11"
BUILDING AREA (SQ. FT.) 15,202
AREA OF PROJECT (SQ. FT.) 23,000
SEPARATED OR NON-SEPARATED USE: N/A
ALLOWABLE AREA: N/A
AREA INCREASED: N/A
HEIGHT INCREASED: N/A
FIRE SPRINKLERS: NO
FIRE ALARM: YES
OTHER FIRE PROTECTION SYSTEMS: NO
SMOKE CONTROL SYSTEM: NO
YEAR CONSTRUCTED: 1975
HIGH FIRE SEVERITY ZONE: NO
SEISMIC JOINTS: NO
EMERGENCY RESPONDER RADIO COVERAGE: N/A
NOTE: ALL WORK WITHIN THE SCOPE IS EXTERIOR.
OFFICE OF SUSTAINABILITY, DGS
707 3RD STREET, 4TH FLOOR
WEST SACRAMENTO, CA 95606
(916) 823-7059
CONTACT: JANELLE GOULDING
EVCS NOTE:
ELECTRICAL VEHICLE CHARGING STATION (EVCS)
SHALL BE PROVIDED BY THE STATE
(DEPARTMENT OF GENERAL SERVICES), AND
INSTALLED BY THE CURRENT ELECTRIC
VEHICLE CHARGING STATION STATE VENDOR.
ALL FINAL TERMINATIONS AND/OR SPLICING FOR
THE EVCS SHALL BE THE RESPONSIBILITY AND
PERFORMED BY THE STATE VENDOR.
SFM APPLICATION NUMBER: 26-S-0457-C
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
La ke H ug he s R oa d, Ca st ai c, C
A
E. Torres
E. Burtch
As Noted
D ep ar tm en t o f W at er R es ou rc es
C as ta ic
O
M C en te r E
V S
E In st al la tio n
124-01-02.64
12/18/2025
V1
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T
E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 26-S-0457-C
95% CD SUBMITTALEB12/18/20251
100% CD SUBMITTALEB02/06/20262
TITLE SHEET, LOCATION
MAP, GENERAL NOTES &
SHEET INDEX
T0.01
CASTAIC RO
AD
R
ID
G E
R
TE
R O
AD
LAKE HUGHES ROAD
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
4/21/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
26-0457
EVCS NOTE: LEVEL 2 EVCS AND LEVEL 3 (DCFC)
ELECTRICAL VEHICLE CHARGING STATIONS (EVCS) SHALL BE
PROVIDED, INSTALLED AND COMMISSIONED BY THE AWARDED
CONSTRUCTION CONTRACTOR (CONTRACTOR). EVCS UNITS
SHALL BE COMMERCIAL GRADE, SUITABLE FOR LONG TERM
OUTDOOR USE AND COMPLIANT WITH UL 2594, UL 223, UL 50E,
NFPA 70 AND EMI (FCC PART 15 CLASS A OR B). EVCS SHALL BE
COMPATIBLE WITH THE ASSOCIATED PROJECT STATE FIRE
MARSHAL STAMPED DRAWINGS. ALL EVCS SHALL BE EQUIPTED
WITH A MINIMUM CABLE LENGTH OF 18 FEET AND HAVE A CORD
MANAGEMENT SYSTEM. EVCS SHALL HAVE A SAE J1772
COMPLIANT CONNECTOR FOR LEVEL 2 EVCS AND SHALL HAVE
A SAE J3400 OR SAE CCS1 FOR LEVEL 3 (DCFC). EVCS TO BE
ANCHORED WITH HILTI 'KB-TZ2' STAINLESS STEEL ANCHOR
BOLTS OR APPROVED EQUAL. EVCS SHALL BE COMPATIBLE
WITH VOLTAGE RANGE, CIRCUIT BREAKERS, AND THE
ELECTRICAL CONDUCTOR SIZES ON THE PROJECT STATE FIRE
MARSHAL STAMPED DRAWINGS. ALL FINAL TERMINATIONS
AND/OR SPLICING FOR THE EVCS SHALL BE RESPONSIBILTY OF
THE CONTRACTOR AND PERFORMED BY THE CONTRACTOR.
EVCS NOTE: LEVEL 2 EVCS AND LEVEL 3 EVCS (DCFC)
ELECTRICAL VEHICLE CHARGING STATIONS (EVCS) SHALL BE PROVIDED, INSTALLED AND COMMISSIONED BY THE AWARDED CONSTRUCTION CONTRACTOR (CONTRACTOR). EVCS UNITS SHALL BE COMMERCIAL GRADE, SUITABLE FOR LONG TERM OUTDOOR USE AND COMPLIANT WITH UL 2594, UL 223, UL 50E, NFPA 70 AND EMI (FCC PART 15 CLASS A OR B). EVCS SHALL BE COMPATIBLE WITH THE ASSOCIATED PROJECT STATE FIRE MARSHAL STAMPED DRAWINGS. ALL EVCS SHALL BE EQUIPTED WITH A MINIMUM CABLE LENGTH OF 18 FEET AND HAVE A CORD MANAGEMENT SYSTEM. EVCS SHALL HAVE A SAE J1772 COMPLIANT CONNECTOR FOR LEVEL 2 EVCS AND SHALL HAVE A SAE J3400 OR SAE CCS1 FOR LEVEL 3 (DCFC). EVCS TO BE ANCHORED WITH HILTI 'KB-TZ2' STAINLESS STEEL ANCHOR BOLTS OR APPROVED EQUAL. EVCS SHALL BE COMPATIBLE WITH VOLTAGE RANGE, CIRCUIT BREAKERS, AND THE ELECTRICAL CONDUCTOR SIZES ON THE PROJECT STATE FIRE MARSHAL STAMPED DRAWINGS. ALL FINAL TERMINATIONS AND/OR SPLICING FOR THE EVCS SHALL BE RESPONSIBILTY OF THE CONTRACTOR AND PERFORMED BY THE CONTRACTOR.
DWR - Electric Vehicle Supply Equipment - Castaic O&M Center
PROJECT NUMBER: 000000000013643; ISSUE DATE 07/10/26
AutoCAD SHX Text O
AutoCAD SHX Text O
ABBREVIATIONS
ANNOTATION SYMBOLS
LEGEND
WIRING SYSTEM ABOVE FLOOR
LEVEL, CONCEALED IN WALL OR
ABOVE CEILING UON
WIRING SYSTEM IN OR UNDER
FLOOR OR CONCEALED IN OR
BEHIND STRUCTURE OR EQUIPMENT
CONDUIT STUB ENDING WITH CAP
E0.1
REMOVE/RELOCATE/DEMOLISH
EXISTING
FUSE
RECESSED PANELBOARD 120V/208V
SWITCH
COMBINATION MOTOR
STARTER/DISCONNECT SWITCH
(NUMBER INDICATES STARTER SIZE)
DISCONNECT SWITCH (FUSED),
HORSE POWER RATED
SURFACE MOUNTED PANELBOARD
277V/480V
DISTRIBUTION BOARD
FUSED DISCONNECT SWITCH
RECESSED PANELBOARD 277V/480V
SURFACE MOUNTED PANELBOARD
120V/208V
DISCONNECT SWITCH (NON-FUSED)
ELECTRICAL
SYMBOL
DESCRIPTION
F
SHEET WHERE DETAIL
IS DRAWN
OCCURRENCE
DETAIL IDENTIFICATION
(TYP.)
DETAIL
RECONSTRUCTION KEY NOTE
DEMOLITION KEY NOTE
REVISION
REVISED AREA
REVISION TAG
A AMPERE
ADA AMERICAN DISABILITIES ACT
AC ALTERNATING CURRENT
AF AMPERE FRAME
AS AMPERE SWITCH
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING CAPACITY
ANN ANNUNCIATOR
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AV AUDIO-VISUAL
AWG AMERICAN WIRE GAUGE
BKR BREAKER
BLDG BUILDING
C CONDUIT
CB CIRCUIT BREAKER
CATV CABLE TELEVISION
CEC CALIFORNIA ELECTRICAL CODE
CKT CIRCUIT
CLG CEILING
CO CONDUIT ONLY
COMM COMMUNICATIONS
COMP COMPUTER
DB DISTRIBUTION BOARD
DISC DISCONNECT
DIST DISTRIBUTION
DL DOUBLE LUG
DP DISTRIBUTION PANEL
DWG DRAWING
E EXISTING TO REMAIN
EEOR ELECTRICAL ENGINEER ON RECORD
EG EQUIPMENT GROUND
ELEC ELECTRICAL
EMH ELECTRICAL MAN HOLE
EHH ELECTRICAL HAND HOLE
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
EV ELECTRIC VEHICLE
EVCS ELECTRIC VEHICLE CHARGING STATION
EVSE ELECTRIC VEHICLE SUPPLY EQUIPMENT
F FUSE, FUSED
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPERES
GRD GROUND
GALV GALVANIZE, GALVANIZED
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HPF HEAT PUMP HIGH POWER FACTOR
HPS HIGH PRESSURE SODIUM
JB JUNCTION BOX
KA THOUSAND AMPERES
KCMIL THOUSAND CIRCULAR MILS
KVA KILOVOLT-AMPERE
KW KILOWATT
LCL LONG CONTINUOUS LOAD
LTG LIGHTING
MC METAL CLAD CABLE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCM THOUSAND CIRCULAR MILS
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MH METAL HALIDE
MIN MINIMUM
MLO MAIN LUGS ONLY
MTD MOUNTED
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
NEC NATIONAL ELECTRIC CODE
NF NON-FUSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NC NORMALLY CLOSED
P POLE, POLES
PF POWER FACTOR
PNL PANEL
PRI PRIMARY
PVC POLYVINYL CHLORIDE CONDUIT
PWR POWER
PH PHASE
Ø PHASE
R REMOVE
RR REMOVE AND RELOCATE
RL RELOCATED
RECEPT RECEPTACLE
RGS RIGID GALVANIZED STEEL CONDUIT
SEC SECONDARY
SUSP SUSPEND, SUSPENDED
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TBB TELECOMMUNICATIONS BACKBOARD
TMH TELECOMMUNICATIONS MAN HOLE
THH TELECOMMUNICATIONS HAND HOLE
TYP. TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLT, VOLTS
VA VOLT-AMPERES
VAV VARIABLE AIR VOLUME
WT WATERTIGHT
W WATT OR WIRE
WP WEATHER PROOF
XFMR TRANSFORMER
Y WYE CONNECTION
MISCELLANEOUS
LINE TYPES
JUNCTION BOX WITH COVER
(MINIMUM 4" SQUARE OR AS
REQUIRED)
CONCRETE BOLLARD
SINGLE PORT PEDESTAL TYPE
ELECTRIC VEHICLE CHARGING STATION
DUAL PORT PEDESTAL TYPE
ELECTRIC VEHICLE CHARGING STATION
T TRANSFORMER. "F" DENOTES FRONT
OF TRANSFORMER.
DIGITAL MULTI-METERDMM
UNDERGROUND PULL BOX
POST AND SIGNAGE
WHEELSTOP
SURFACE MOUNTED JUNCTION BOX
WITH COVER
(MINIMUM 4" SQUARE OR AS
REQUIRED)
PB
APPLICABLE CODES
J
J
PB SURFACE-MOUNTED PULL BOX
F
FENCE
2025 CALIFORNIA BUILDING CODE (CBC) PART 2, VOLUMES
1 AND 2, TITLE 24
(BASED ON 2024 INTERNATIONAL BUILDING CODE)
2025 CALIFORNIA ELECTRIC CODE (CEC) PART 3, TITLE 24
(BASED ON 2023 NATIONAL ELECTRIC CODE)
2025 CALIFORNIA FIRE CODE (CFC) PART 9, TITLE 24
(BASED ON 2024 INTERNATIONAL FIRE CODE)
2025 CALIFORNIA ENERGY CODE PART 6, TITLE 24
2025 CALIFORNIA REFERENCED STANDARD CODE PART 12,
TITLE 24
TITLE 19, PUBLIC SAFETY, STATE FIRE MARSHAL
REGULATIONS
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN
PARTIAL LIST OF APPLICABLE NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA) STANDARDS
NFPA 72, 2025 EDITION - NATIONAL FIRE ALARM AND
SIGNALING CODE (AMENDED BY CSFM)
NFPA 80, 2025 EDITION - FIRE DOORS AND OTHER OPENING
PROTECTIVES
REFER TO 2025 CBC CHAPTER 35 FOR ADDITIONAL
STANDARDS NOT PROVIDED ON THIS LIST
DC FAST CHARGER POWER BANK
DC FAST CHARGER DUAL PORT
POWER LINK 2000
COPPER GROUND ROD
COPPER GROUND ROD WITH
GROUND WELL
1. CONTRACTOR SHALL PERFORM INSTALLATION WORK IN CONFORMANCE WITH THE 2025 EDITION OF THE CALIFORNIA ELECTRICAL CODE (CEC) AND ALL APPLICABLE CODES, ORDINANCES, AND REGULATIONS.
2. CONDUIT ROUTING AND EQUIPMENT LOCATION AS SHOWN ON THE ELECTRICAL POWER PLAN ARE DIAGRAMMATIC IN NATURE. CONTRACTOR SHALL VERIFY FEASIBILITY OF THE INSTALLATION BEFORE COMMENCING THE JOB. ANY OBSERVATIONS TO THE EXECUTION OF THE WORK SHALL BE BROUGHT TO THE
ATTENTION OF THE ENGINEER OF RECORD IMMEDIATELY.
3. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER CONSTRUCTION TRADES. CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE OF ANY UNRESOLVED ISSUES THAT MAY DELAY INSTALLATION OF
WORK.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING PROPER WORKING SPACE PER CALIFORNIA
ELECTRICAL CODE (CEC), PARAGRAPH 110-26.
5. CONTRACTOR SHALL PROVIDE NECESSARY HARDWARE AND SUPPORTS AS REQUIRED FOR ELECTRICAL CONDUIT/WIRE NOT SCHEDULED FOR DEMOLITION PER CALIFORNIA ELECTRICAL CODE (CEC), PARAGRAPH 110-12.
6. THE SEISMIC BRACING AND ANCHORAGE OF ELECTRICAL CONDUITS SHALL BE IN ACCORDANCE WITH THE
CALIFORNIA BUILDING CODE, CHAPTER 16.
7. CONNECTIONS TO VIBRATING EQUIPMENT AND SEISMIC SEPARATIONS:
· LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN DRY INTERIOR LOCATIONS.
· LIQUID-TIGHT FLEXIBLE STEEL CONDUIT IN AREAS EXPOSED TO WEATHER, DAMP LOCATIONS, CONNECTIONS TO TRANSFORMER ENCLOSURES, AND FINAL CONNECTIONS TO MOTORS.
PROVIDE A SEPARATE INSULATED EQUIPMENT GROUNDING CONDUCTOR IN FLEXIBLE CONDUIT RUNS.
MAXIMUM LENGTH SHALL BE SIX FEET UNLESS OTHERWISE NOTED.
8. WHENEVER A DISCREPANCY IN QUANTITY OR SIZE OF CONDUIT, WIRE, EQUIPMENT DEVICES, CIRCUIT BREAKERS, GROUND FAULT PROTECTION SYSTEMS, ETC. (ALL MATERIALS), ARISES ON THE DRAWINGS OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE
SPECIFICATIONS TO ENSURE COMPLETE AND OPERABLE SYSTEMS.
9. ARC-FLASH LABELS SHALL BE PROVIDED TO THE CONTRACTOR TO INSTALL ON NEW LOW VOLTAGE (480V, 208V, 120V) SYSTEMS REPRESENTED ON THE PROJECT DRAWINGS. THIS INCLUDES SWITCHBOARDS, PANEL BOARDS, TRANSFORMERS, DISCONNECT SWITCHES AND OTHER REQUIRED ELECTRICAL EQUIPMENT. THESE LABELS SERVE AS A GUIDE TO ASSIST THE EMPLOYEES AND OTHERS IN THE SELECTION OF PROPER PERSONAL
PROTECTIVE EQUIPMENT WHEN WORKING AROUND EXPOSED AND ENERGIZED CONDUCTORS.
ELECTRICAL GENERAL NOTES
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
La ke H ug he s R oa d, Ca st ai c, C
A
E. Torres
E. Burtch
As Noted
D ep ar tm en t o f W at er R es ou rc es
C as ta ic
O
M C en te r E
V S
E In st al la tio n
124-01-02.64
12/18/2025
V1
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T
E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 26-S-0457-C
95% CD SUBMITTALEB12/18/20251
100% CD SUBMITTALEB02/06/20262
SYMBOLS,
DESIGNATION AND
ABBREVIATIONS
E0.01
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
4/21/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
26-0457
DWR - Electric Vehicle Supply Equipment - Castaic O&M Center
PROJECT NUMBER: 000000000013643; ISSUE DATE 07/10/26
AutoCAD SHX Text O
FIRE SAFETY PLAN - CONSTRUCTION
1. NAME AND CONTACT INFORMATION OF SITE SAFETY DIRECTOR:
HAL GOUNDER
ASSOCIATE SAFETY ENGINEER
CA DEPT. OF WATER RESOURCES
SAN JOAQUIN FIELD DIVISION
OFFICE: (661) 858-5529
CELL: (661) 301-4128
2. DOCUMENTATION OF THE TRAINING OF THE SITE SAFETY DIRECTOR AND FIRE WATCH PERSONNEL:
· FIRE EXTINGUISHER TRAINING
· ARC FLASH AWARENESS
· HAZARD ASSESSMENT & MITIGATION CSWP 1.06
· INJURY ILLNESS PREVENTION PLAN
· PERSONAL PROTECTIVE EQUIPMENT
· WORKPLACE SAFETY
· INCIDENT INVESTIGATION AWARENESS
· PROTECTIVE GROUNDING
· STANDARDIZED EMERGENCY MANAGEMENT SYSTEM (SEMS)
· NATIONAL EMERGENCY MANAGEMENT SYSTEM (NEMS)
3. PROCEDURES FOR REPORTING EMERGENCIES:
THIS INFORMATION WAS PROVIDED FROM THE SJFC EAP REDBOOK.
ANY FIRE WILL BE REPORTED TO THE OFFICE OF THE STATE FIRE MARSHAL. ANY FIRE ON STATE PROPERTY OR IN FACILITIES IS CONSIDERED A RESPONSE LEVEL SITUATION AND THE FIRE EVENT ACTIONS CHECKLIST OF THE EMERGENCY ACTION PLAN WILL BE FOLLOWED. THE AREA CONTROL CENTER (ACC) WILL BE NOTIFIED OF
AN INCIDENT. WHEN NOTIFYING ACC TRY TO DETERMINE AND DOCUMENT THE FOLLOWING:
1. TYPE AND TIME OF INCIDENT
2. LOCATION OF FIRE - EXTERNAL OR INTERNAL, DISTANCE FROM STRUCTURES, SIZE, PROXIMITY TO
POWER LINERS
3. WEATHER CONDITIONS, WIND SPEED/DIRECTION
4. INFORMATION ON INJURY OR FATALITY
5. EQUIPMENT AFFECTED
6. NAME AND CONTACT FOR PERSONNEL REPORTING
THE ACC WILL RECORD THE INFORMATION IN THE OPERATIONS LOG. THE ACC WILL THEN RUN THE EAP
CHECKLIST.
REFERENCES AND ORDERS THAT PERTAIN TO FIRES: STANDARD OPERATION ORDER (SOO) PC 600.36 REPORTING OF FIRES OR EXPLOSIONS. SJFD S00 18 PROTOCOL FOR ENTERING SJFD FACILITY WHEN SOKE IS
PRESENT. PLANT AND SITE-SPECIFIC CONTINGENCE PLANS.
4. FIRE DEPARTMENT VEHICLE ACCESS ROUTES:
SEE MAP ON SHEET E0.03.
CONSTRUCTION SITE SHALL BE READILY ACCESSIBLE BY FIRE DEPARTMENT APPARATUS BY MEANS OF ROADWAYS HAVING AN ALL-WEATHER DRIVING SERVICE OF NOT LESS THAN 20 FEET OF UNOBSTRUCTED WIDTH. THE ROADS SHALL WITHSTAND LIVE LOADS OF FIRE APPARATUS, AND HAVE A MINIMUM OF 13 FEED, 6 INCHES OF VERTICAL CLEARANCE. DEAD END FIRE ACCESS ROADS IN EXCESS OF 150 FEET IN LENGTH SHALL
BE PROVIDED WITH APPROVED TURNAROUNDS.
5. LOCATION OF FIRE PROTECTION EQUIPMENT, INCLUDING PORTABLE FIRE EXTINGUISHERS, STANDPIPES, FIRE
DEPARTMENT CONNECTIONS AND FIRE HYDRANTS:
SEE MAP ON PLANS.
6. SMOKING AND COOKING POLICIES, DESIGNATED AREAS TO BE USED WHERE APPROVED, AND SIGNAGE
LOCATIONS IN ACCORDANCE WITH SECTION 3305.8:
N/A (NO SMOKING OR COOKING ALLOWED ON PREMISES)
7. LOCATION AND SAFETY CONSIDERATIONS FOR TEMPORARY HEATING EQUIPMENT:
N/A (NO TEMPORARY HEATING EQUIPMENT FOR THIS PROJECT)
8. HOT WORK PERMIT PLAN:
N/A (NO HOT WORK FOR THIS PROJECT. ALL WELDING ON FENCING AND GATES SHALL BE SHOP FABRICATED
BEFORE INSTALLATION ON SITE).
9. PLANS FOR CONTROL OF COMBUSTIBLE WASTE MATERIAL:
ACCUMULATIONS OF COMBUSTIBLE WASTE MATERIAL, SUCH AS WOOD, PLASTIC, INSULATION, PAINTS AND VARNISHES, ADHESIVES AND SEALANTS, DUST, AND DEBRIS SHALL BE REMOVED FROM THE WORK SITE AT THE END OF EACH WORK SHIFT OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS. MATERIALS SUSCEPTIBLE TO SPONTANEOUS IGNITION, SUCH AS OILY RAGS, SHALL BE STORED IN A LISTED DISPOSAL CONTAINER. YARD STORAGE OF EQUIPMENT TO BE INSTALLED OR COMBUSTIBLE CONSTRUCTION MATERIALS
SHALL NOT BE STORES CLOSER THEN 30 FEET FROM ANY STRUCTURE UNDER CONSTRUCTION OR
ALTERATION.
10. LOCATIONS AND METHODS FOR STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS AND OTHER
HAZARDOUS MATERIALS:
STORAGE - FLAMMABLE AND COMBUSTIBLE LIQUID STORAGE AREAS SHALL BE MAINTAINED CLEAR OF COMBUSTIBLE VEGETATION AND WASTE MATERIALS. SUCH STORAGE AREAS SHALL NOT BE USED FOR THE STORAGE OF COMBUSTIBLE MATERIALS. SMOKING AND OTHER SOURCES OF IGNITION SHALL BE PROHIBITED IN AREAS WHERE FLAMMABLE AND COMBUSTIBLE LIQUIDS ARE STORED OR USED. STORAGE OF CLASS I AND CLASS II LIQUIDS SHALL NOT EXCEED 60 GALLONS WITHIN 50 FEET OF THE STRUCTURE UNLESS APPROVED BY
KERN COUNTY FD.
TANKS - TANKS AND CONTAINERS FOR THE STORAGE OF LIQUIDS ABOVE GROUND SHALL BE CONSPICUOUSLY MARKED WITH THE NAME OF THE PRODUCT THEY CONTAIN AND THE WORDS: "FLAMMABLE--KEEP FIRE AND FLAME AWAY." TANKS SHALL BEAR THE ADDITIONAL MARKING: "KEEP 50 FEET FROM BUILDINGS." A. TANKS MORE THAN 100 GALLONS IN CAPACITY, WHICH ARE PERMANENTLY INSTALLED OR MOUNTED AND USED FOR THE STORAGE OF CLASS I, II OR III LIQUIDS, SHALL BE PROVIDED WITH A PLACARD IN ACCORDANCE WITH NFPA 704.B. PORTABLE FIRE EXTINGUISHERS WITH A MINIMUM RATING OF 20-B:C SHALL BE PROVIDED WITHIN 30 FEET
OF THE TANK.
HANDLING AT POINT OF FINAL USE - THE STORAGE, USE AND HANDLING OF FLAMMABLE AND COMBUSTIBLE LIQUIDS AT CONSTRUCTION SITES SHALL BE IN ACCORDANCE WITH CFC SECTION 5706.2. VENTILATION SHALL BE PROVIDED FOR OPERATIONS INVOLVING THE APPLICATION OF MATERIALS CONTAINING FLAMMABLE SOLVENTS. CLASS I AND CLASS II LIQUIDS SHALL BE KEPT IN APPROVED SAFETY CONTAINERS, LEAKAGE AND SPILLS - LEAKING VESSELS SHALL BE IMMEDIATELY REPAIRED OR TAKEN OUT OF SERVICE AND SPILLS SHALL BE CLEANED UP AND DISPOSED OF PROPERLY. PROVISIONS FOR SITE SECURITY.
APPLICABLE CODES
STANDARD ADMINISTRATIVE CODE:
· 2025 CALIFORNIA BUILDING CODE (CBC)
· 2025 CALIFORNIA ELECTRICAL CODE (CEC)
· 2025 CALIFORNIA MECHANICAL CODE (CMC)
· 2025 CALIFORNIA PLUMBING CODE (CPC)
· 2025 CALIFORNIA ENERGY CODE
· 2025 CALIFORNIA FIRE CODE
· 2025 CALIFORNIA GREEN BUILDING CODE
· 2025 CALIFORNIA REFERENCE STANDARD CODE
· CCR-TITLE 19 PUBLIC SAFETY: DIVISION 1 STATE FIRE MARSHAL
· 2025 NFPA 13 INSTALLATION OF FIRE SPRINKLER
· 2024 NFPA 14 INSTALLATION OF STANDPIPE AND HOSE SYSTEM
· 2025 NFPA 20 INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION
· 2025 NFPA 24 INSTALLATION OF PRIVATE FIRE SERVICES MAINS AND THEIR APPURTENANCE
· 2013 NFPA 25 CALIFORNIA EDITION, INSPECTION, TESTING AND MAINTENANCE OF WATER BASED
FIRE PROTECTION SYSTEMS
· 2025 NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE "AS AMENDED BY CALIFORNIA" CSF
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
La ke H ug he s R oa d, Ca st ai c, C
A
E. Torres
E. Burtch
As Noted
D ep ar tm en t o f W at er R es ou rc es
C as ta ic
O
M C en te r E
V S
E In st al la tio n
124-01-02.64
12/18/2025
V1
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T
E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 26-S-0457-C
95% CD SUBMITTALEB12/18/20251
100% CD SUBMITTALEB02/06/20262
SITE SAFETY
PLAN
E0.02SCALE
FIRE ACCESS, FIRE HYDRANT AND FIRE EXTINGUISHER LOCATIONS 1N.T.S.
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
4/21/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
26-0457
DWR - Electric Vehicle Supply Equipment - Castaic O&M Center
PROJECT NUMBER: 000000000013643; ISSUE DATE 07/10/26
AutoCAD SHX Text O
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
La ke H ug he s R oa d, Ca st ai c, C
A
E. Torres
E. Burtch
As Noted
D ep ar tm en t o f W at er R es ou rc es
C as ta ic
O
M C en te r E
V S
E In st al la tio n
124-01-02.64
12/18/2025
V1
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T
E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 26-S-0457-C
95% CD SUBMITTALEB12/18/20251
100% CD SUBMITTALEB02/06/20262
SITE SAFETY
PLANS
E0.03SCALE
MOBILE EQUIPMENT REPAIR BUILDING FIRE EXTINGUISHER LOCATIONS 1N.T.S.
SCALE
CIVIL MAINTENANCE OFFICE FIRE EXTINGUISHER LOCATIONS 2N.T.S.
SCALE
WAREHOUSE 2 FIRE EXTINGUISHER LOCATIONS 1N.T.S.
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
4/21/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
26-0457
DWR - Electric Vehicle Supply Equipment - Castaic O&M Center
PROJECT NUMBER: 000000000013643; ISSUE DATE 07/10/26
AutoCAD SHX Text O
OPEN
STRUCTURE
OPEN
STRUCTURE
TR
A
IL
E
R
RIDGE RTE. ROAD RIDGE RTE. ROAD
LA
K
E H
U G
H E
S R
O A
D
LA
K E
H U
G H
E S
R O
A D
MOBILE EQUIPMENT
REPAIR BUILDING
WAREHOUSE 2
CIVIL
MAINTENANCE
OFFICE
CONTROL
BUILDING
WATER
QUALITY
BUILDING
ADMINISTRATION
BUILDING
FUEL STATION
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
La ke H ug he s R oa d, Ca st ai c, C
A
E. Torres
E. Burtch
As Noted
D ep ar tm en t o f W at er R es ou rc es
C as ta ic
O
M C en te r E
V S
E In st al la tio n
124-01-02.64
12/18/2025
V1
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T
E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 26-S-0457-C
95% CD SUBMITTALEB12/18/20251
100% CD SUBMITTALEB02/06/20262
SITE PLAN
E1.00
E2.00
EVCS SUMMARY
LOCATION PARKING TYPE SHEET EXISTING EVCS SPACES NEW EVCS SPACES
PARKING LOT
*FLEET E2.01 (0) LEVEL 2 (8) LEVEL 2
(2) LEVEL 3
*FLEET E2.02 (0) LEVEL 2 (8) LEVEL 2
TOTAL FLEET PORTS: (18) FLEET PORTS
* NOTE:
FLEET EVCS INSTALLED ARE NOT AVAILABLE TO THE GENERAL PUBLIC AND ARE INTENDED FOR USE BY A DESIGNATED VEHICLE OR DRIVER; THEREFORE, PER CBC SECTION 11B-228.3.2 EXCEPTION 1, THE EVCS SHALL NOT BE REQUIRED TO COMPLY WITH CBC
11B-228.3.2 ACCESS REQUIREMENTS.
SCOPE OF WORK
SCALE
CASTAIC O&M CENTER SITE PLAN 11/32" = 1'-0"
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
4/21/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
26-0457
DWR - Electric Vehicle Supply Equipment - Castaic O&M Center
PROJECT NUMBER: 000000000013643; ISSUE DATE 07/10/26
AutoCAD SHX Text O
1 2
MOBILE EQUIPMENT
REPAIR BUILDING
CIVIL
MAINTENANCE
OFFICE
FUEL STATION
T
EV
FLEET
ONLY
EV
FLEET
ONLY
EV FLEET ONLY
EV FLEET ONLY
EV FLEET ONLY
EV FLEET ONLY
EV FLEET ONLY
EV FLEET ONLY
EV FLEET ONLY
EV FLEET ONLY
T
EV
FLE
ET
ONLY
EV
FLE
ET
ONLY
EV
FLE
ET
ONLY
EV
FLE
ET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
PB
1 2
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
La ke H ug he s R oa d, Ca st ai c, C
A
E. Torres
E. Burtch
As Noted
D ep ar tm en t o f W at er R es ou rc es
C as ta ic
O
M C en te r E
V S
E In st al la tio n
124-01-02.64
12/18/2025
V1
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T
E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 26-S-0457-C
95% CD SUBMITTALEB12/18/20251
100% CD SUBMITTALEB02/06/20262
POWER PLAN
E2.00
R
CALL 811 BEFORE YOU DIG.
LEGEND:
EXISTING
NEW
NEW UNDERGROUND
E2.01
SHEET NOTES:
SEE DETAIL #1 SHEET E4.01 FOR UNDERGROUND
CONDUIT BURIAL DETAIL. FOR ALL ROUTING
THROUGH TRAFFIC CROSSINGS PROVIDE
SCHEDULE-80 PVC UNDERGROUND CONDUIT.
SEE SINGLE LINE DIAGRAM #1 SHEET E5.00 FOR
MORE INFORMATION.
APPROXIMATE LOCATION OF EXISTING
CONDUIT/S THAT SHALL BE PROTECTED AND
REMAIN IN-PLACE.
GENERAL NOTES:
1. ELECTRICAL ENGINEERING FOR THIS PROJECT
IS BASED ON EXISTING DRAWINGS AND A FIELD
VISIT OF THE ELECTRICAL SYSTEM. IN CASE OF
ANY DISCREPANCIES WITH EXISTING FIELD
CONDITIONS, ELECTRICAL CONTRACTOR SHALL
VERIFY THE EXACT DIFFERENCES AND NOTIFY
THE ELECTRICAL ENGINEER FOR POSSIBLE
REVISION TO THESE DOCUMENTS.
2. ANY ELECTRICAL AND/OR SIGNAL UTILITY
SHUTDOWNS WITHIN THE AREA OF WORK SHALL
BE COORDINATED AND SCHEDULED IN ADVANCE
WITH THE DWR SITE REPRESENTATIVE.
3. ELECTRIC VEHICLE CHARGING STATION/S
(EVCS) SHALL BE PROVIDED, INSTALLED AND
CONNECTED BY STATE VENDOR.
4. PROVIDE MINIMUM OF 2'-0" CLEARANCE BEHIND
ALL PEDESTAL MOUNTED CHARGERS AND DCFC
COMPONENTS FOR SERVICING. CONTRACTOR
SHALL FIELD VERIFY ALL DISTANCES PRIOR TO
BID.
5. EXISTING VEGETATION TO BE REMOVED,
PROTECTED AND RESTORED AFTER
CONSTRUCTION.
6. REMOVE AND REPLACE IN-GROUND
LANDSCAPING AND/OR IRRIGATION SYSTEM
AFFECTED BY THE WORK.
EXISTING 200kW
GENERATOR
EXISTING UTILITY
TRANSFORMER
SCALE
POWER PLAN 11/16" = 1'-0"
EXISTING MAIN
SWITCHBOARD "MSB"
E2.02
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
4/21/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
26-0457
DWR - Electric Vehicle Supply Equipment - Castaic O&M Center
PROJECT NUMBER: 000000000013643; ISSUE DATE 07/10/26
AutoCAD SHX Text O
T
EV
FLEET
ONLY
EV
FLEET
ONLY
EV FLEET ONLY
EV FLEET ONLY
EV FLEET ONLY
EV FLEET ONLY
EV FLEET ONLY
EV FLEET ONLY
EV FLEET ONLY
EV FLEET ONLY
PB
1 2
PB
PB
EXISTING MAIN
SWITCHBOARD "MSB"
EXISTING
200kW GENERATOREXISTING
UTILITY
TRANSFORMER
E2.00
114(TYP.)
4'-0" (TYP.)
9'-0"
(TYP.)
18'-0"
(TYP.)
(4 SETS) 1"C-4#6
& 1#8 GRD.
1"C-4#6
& 1#8 GRD.
1"C-4#6
& 1#8 GRD.
4'-0" (TYP.)
EVCS-1
DCFC
DCFC POWER
BLOCK
EVCS-4 3 7EVCS-373EVCS-273
1"C-4#6
& 1#8 GRD.
1"C-4#6
& 1#8 GRD.
2 1/2"C-3#250
& 1#4 GRD.
14 (TYP.)
9'-0"
(TYP.)
18'-0"
(TYP.)
12(TYP.)
13(TYP.)
EVCS-53 7
TO NEW DISCONNECT
SWITCH
3'-0"
(TYP.)
3'-0"
(TYP.)1'-0"
(TYP.)
EXISTING AUTOMATIC
TRANSFER SWITCH
6(TYP.)
12(TYP.)
T
G
4'-0"
(TYP.)
3/4"Ø x 10'-0" L
COPPER
GROUND ROD
1#4 GROUND RING9
GROUND-WELL9
4'-0"
(TYP.)
GG
PANELBOARD "EV-1A"
PANELBOARD "EV-1B"
TRANSFORMER "TEV-1"
DIGITAL MULTI-METER
3'-0"
E2.01
1 TO (4) DUAL PORT
LEVEL 2 EVCS
E2.01
1 TO (E) MAIN
SWITCHBOARD "MSB"
E2.01
1TO (1) DUAL PORT
LEVEL 3 DCFC
(4 SETS) 1"C-4#6
& 1#8 GRD.
2 1/2"C-3#250
& 1#4 GRD.
4 11
6 (TYP.)
GGG
G
G
GG
G
G
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
La ke H ug he s R oa d, Ca st ai c, C
A
E. Torres
E. Burtch
As Noted
D ep ar tm en t o f W at er R es ou rc es
C as ta ic
O
M C en te r E
V S
E In st al la tio n
124-01-02.64
12/18/2025
V1
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T
E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 26-S-0457-C
95% CD SUBMITTALEB12/18/20251
100% CD SUBMITTALEB02/06/20262
ENLARGED
NORTH
POWER PLANS
E2.01
PROPOSED EV CHARGERS
EVCS # WALL/PEDESTAL
MOUNT EVCS
SINGLE/DUAL
EVCS CHARGE PORT #
POWER SELECT
(FLA) VOLTAGE
POWER SHARE
(Y / N/A)
CHARGE PORT
TYPE
1 PEDESTAL DUAL 193 480V-3PH N/A FLEET
2 PEDESTAL DUAL 30 208V-1PH N/A FLEET
3 PEDESTAL DUAL 30 208V-1PH N/A FLEET
4 PEDESTAL DUAL 30 208V-1PH N/A FLEET
5 PEDESTAL DUAL 30 208V-1PH N/A FLEET
NOTES:
· (5) DUAL PORT EVCS SHALL SERVE (10) FLEET PARKING STALLS
· (FLA) STANDS FOR FULL LOAD AMPS
· (Y) STANDS FOR, YES WILL BE REQUIRED; (N/A) STANDS FOR, NOT APPLICABLE
1 2
1 2
1 2
1 2
1 2
R
CALL 811 BEFORE YOU DIG.
LEGEND:
EXISTING
NEW
NEW UNDERGROUND
GENERAL NOTES:
1. ELECTRICAL ENGINEERING FOR THIS PROJECT
IS BASED ON EXISTING DRAWINGS AND A FIELD
VISIT OF THE ELECTRICAL SYSTEM. IN CASE OF
ANY DISCREPANCIES WITH EXISTING FIELD
CONDITIONS, ELECTRICAL CONTRACTOR SHALL
VERIFY THE EXACT DIFFERENCES AND NOTIFY
THE ELECTRICAL ENGINEER FOR POSSIBLE
REVISION TO THESE DOCUMENTS.
2. ANY ELECTRICAL AND/OR SIGNAL UTILITY
SHUTDOWNS WITHIN THE AREA OF WORK SHALL
BE COORDINATED AND SCHEDULED IN ADVANCE
WITH THE DWR SITE REPRESENTATIVE.
3. ELECTRIC VEHICLE CHARGING STATION/S
(EVCS) SHALL BE PROVIDED, INSTALLED AND
CONNECTED BY STATE VENDOR.
4. PROVIDE MINIMUM OF 2'-0" CLEARANCE BEHIND
ALL PEDESTAL MOUNTED CHARGERS AND DCFC
COMPONENTS FOR SERVICING. CONTRACTOR
SHALL FIELD VERIFY ALL DISTANCES PRIOR TO
BID.
5. EXISTING VEGETATION TO BE REMOVED,
PROTECTED AND RESTORED AFTER
CONSTRUCTION.
6. REMOVE AND REPLACE IN-GROUND
LANDSCAPING AND/OR IRRIGATION SYSTEM
AFFECTED BY THE WORK.
SHEET NOTES:
DUAL PORT PEDESTAL TYPE DC FAST CHARGER
STATION. CHARGEPOINT POWER LINK 2000.
PROVIDE 10'-0" OF INCOMING WIRES COILED UP
AT ALL EVCS STUB-UPS FOR FINAL EVCS
INSTALLATION. SEE DETAIL #1 ON SHEET E4.00.
DC FAST CHARGER POWER BLOCK WITH (4)
POWER MODULES. 160KW OUTPUT. PROVIDE
10'-0" OF INCOMING AND OUTGOING WIRES
COILED UP AT ALL EVCS STUB-UPS FOR FINAL
EVCS INSTALLATION. SEE DETAIL #2 ON SHEET
E4.00.
DUAL PORT PEDESTAL TYPE LEVEL 2 EVCS WITH
7,200VA PER PORT. PROVIDE 10'-0" OF FEEDER
WIRE (4#6 + 1#8 GRD) COILED UP AT EVCS
STUB-UP LOCATION FOR FINAL EVCS
INSTALLATION. SEE DETAIL #3 ON SHEET E4.00.
SEE DETAIL #1 SHEET E4.01 FOR UNDERGROUND
CONDUIT BURIAL DETAIL. FOR ALL ROUTING
THROUGH TRAFFIC CROSSINGS PROVIDE
SCHEDULE 80 PVC UNDERGROUND CONDUIT.
PROVIDE 11" X 17" X DEPTH AS REQUIRED
TRAFFIC-RATED CONCRETE PULLBOX WITH
WEATHERPROOF COVER ENGRAVED 'POWER'.
SEE DETAIL #2 SHEET E4.01 FOR UNDERGROUND
PULL-BOX DETAIL.
PROVIDE 4" DIA. CONCRETE BOLLARD. REFER
TO DETAIL #3 ON SHEET E4.01 FOR MORE
INFORMATION.
SEE DETAIL #5 SHEET E4.00 FOR EV CHARGING
STATION PVC CONDUIT STUB-UP DETAIL.
SEE DETAIL #6 SHEET E4.00 FOR ELECTRIC
EQUIPMENT RGS CONDUIT STUB-UP DETAIL.
SEE DETAILS #4, #5 & #6 SHEET E4.01 FOR
TRANSFORMER GROUND RING AND
GROUND-WELL DETAILS.
PROVIDE DIGITAL MULTI-METER IN NEMA-3R
ENCLOSURE FOR MONITORING PANEL "EV-1A"
INCOMING FEEDERS. REFER TO DETAIL #7 ON
SHEET E4.00 FOR MORE INFORMATION.
SEE SINGLE LINE DIAGRAM #1 SHEET E5.00 FOR
MORE INFORMATION.
NEW SIGN AND POST PER CIVIL DRAWINGS.
NEW WHEELSTOP PER CIVIL DRAWINGS.
NEW STRIPING PER CIVIL DRAWINGS.
E2.01
SCALE
ENLARGED NORTH POWER PLAN 11/8" = 1'-0"
SCALE
ENLARGED NORTH ELECTRICAL EQUIPMENT POWER PLAN 23/8" = 1'-0"
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
4/21/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
26-0457
DWR - Electric Vehicle Supply Equipment - Castaic O&M Center
PROJECT NUMBER: 000000000013643; ISSUE DATE 07/10/26
AutoCAD SHX Text O
FLE
ET
ONLY
EV
FLE
ET
ONLY
EV
FLE
ET
ONLY
EV
FLE
ET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
EV
FLEET
ONLY
E2.00
PB
PB
TO (E) MAIN
SWITCHBOARD "MSB"
EVCS-6 1 4
EVCS-8 1 4
EVCS-7 1 4
EVCS-9 1 4
1"C-4#6
& 1#8 GRD.
1"C-4#6
& 1#8 GRD.
1"C-4#6
& 1#8 GRD.
1"C-4#6
& 1#8 GRD.
(4 SETS) 1"C-4#6
& 1#8 GRD.
(2 SETS) 1"C-4#6
& 1#8 GRD.
3 (TYP.)
9 (TYP.)
10(TYP.)
12(TYP.)
11(TYP.)
9'-0"
(TYP.)
18'-0"
(TYP.)
3'-0" (TYP.)
13 13
T
G GG
G G
G
G
G
G
G
E2.02
1TO (4) DUAL PORT
LEVEL 2 EVCS
3/4"Ø x 10'-0" L
COPPER
GROUND ROD
PANELBOARD "EV-2"
DIGITAL
MULTI-METER
DISCONNECT SWITCH 5 8
TRANSFORMER "TEV-2"6 8
TO EXISTING MAIN
SWITCHBOARD "MSB"
4'-0"
(TYP.)
4'-0"
(TYP.)
1#4 GROUND RING6
GROUND-WELL 6
3'-0"
EXISTING
ELECTRICAL
VAULT
EXISTING
COMMUNICATION
VAULT
(4 SETS) 1"C-4#6
& 1#8 GRD.
10(TYP.)
2 8
E2.02
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
La ke H ug he s R oa d, Ca st ai c, C
A
E. Torres
E. Burtch
As Noted
D ep ar tm en t o f W at er R es ou rc es
C as ta ic
O
M C en te r E
V S
E In st al la tio n
124-01-02.64
12/18/2025
V1
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T
E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 26-S-0457-C
95% CD SUBMITTALEB12/18/20251
100% CD SUBMITTALEB02/06/20262
ENLARGED
SOUTH
POWER PLANS
E2.02
PROPOSED EV CHARGERS
EVCS # WALL/PEDESTAL
MOUNT EVCS
SINGLE/DUAL
EVCS CHARGE PORT #
POWER SELECT
(FLA) VOLTAGE
POWER SHARE
(Y / N/A)
CHARGE PORT
TYPE
6 PEDESTAL DUAL 30 208V-1PH N/A FLEET
7 PEDESTAL DUAL 30 208V-1PH N/A FLEET
8 PEDESTAL DUAL 30 208V-1PH N/A FLEET
9 PEDESTAL DUAL 30 208V-1PH N/A FLEET
NOTES:
· (4) DUAL PORT EVCS SHALL SERVE (8) FLEET PARKING STALLS
· (FLA) STANDS FOR FULL LOAD AMPS
· (Y) STANDS FOR, YES WILL BE REQUIRED; (N/A) STANDS FOR, NOT APPLICABLE
1 2
1 2
1 2
1 2
R
CALL 811 BEFORE YOU DIG.
LEGEND:
EXISTING
NEW
NEW UNDERGROUND
GENERAL NOTES:
1. ELECTRICAL ENGINEERING FOR THIS PROJECT
IS BASED ON EXISTING DRAWINGS AND A FIELD
VISIT OF THE ELECTRICAL SYSTEM. IN CASE OF
ANY DISCREPANCIES WITH EXISTING FIELD
CONDITIONS, ELECTRICAL CONTRACTOR SHALL
VERIFY THE EXACT DIFFERENCES AND NOTIFY
THE ELECTRICAL ENGINEER FOR POSSIBLE
REVISION TO THESE DOCUMENTS.
2. ANY ELECTRICAL AND/OR SIGNAL UTILITY
SHUTDOWNS WITHIN THE AREA OF WORK SHALL
BE COORDINATED AND SCHEDULED IN ADVANCE
WITH THE DWR SITE REPRESENTATIVE.
3. ELECTRIC VEHICLE CHARGING STATION/S
(EVCS) SHALL BE PROVIDED, INSTALLED AND
CONNECTED BY STATE VENDOR.
4. PROVIDE MINIMUM OF 2'-0" CLEARANCE BEHIND
ALL PEDESTAL MOUNTED CHARGERS AND DCFC
COMPONENTS FOR SERVICING. CONTRACTOR
SHALL FIELD VERIFY ALL DISTANCES PRIOR TO
BID.
5. EXISTING VEGETATION TO BE REMOVED,
PROTECTED AND RESTORED AFTER
CONSTRUCTION.
6. REMOVE AND REPLACE IN-GROUND
LANDSCAPING AND/OR IRRIGATION SYSTEM
AFFECTED BY THE WORK.
SHEET NOTES:
DUAL PORT PEDESTAL TYPE LEVEL 2 EVCS WITH
7,200VA PER PORT. PROVIDE 10'-0" OF FEEDER
WIRE (4#6 + 1#8 GRD) COILED UP AT EVCS
STUB-UP LOCATION FOR FINAL EVCS
INSTALLATION. SEE DETAIL #3 ON SHEET E4.00.
SEE DETAIL #1 SHEET E4.01 FOR UNDERGROUND
CONDUIT BURIAL DETAIL. FOR ALL ROUTING
THROUGH TRAFFIC CROSSINGS PROVIDE
SCHEDULE 80 PVC UNDERGROUND CONDUIT.
PROVIDE 11" X 17" X DEPTH AS REQUIRED
CONCRETE PULLBOX WITH WEATHERPROOF
COVER ENGRAVED 'POWER'. SEE DETAIL #2
SHEET E4.01 FOR UNDERGROUND PULL-BOX
DETAIL.
SEE DETAIL #5 SHEET E4.00 FOR EV CHARGING
STATION PVC CONDUIT STUB-UP DETAIL.
SEE DETAIL #6 SHEET E4.00 FOR ELECTRIC
EQUIPMENT RGS CONDUIT STUB-UP DETAIL.
SEE DETAILS #4, #5 & #6 SHEET E4.01 FOR
TRANSFORMER GROUND RING AND
GROUND-WELL DETAILS.
PROVIDE DIGITAL MULTI-METER IN NEMA-3R
ENCLOSURE FOR MONITORING PANEL "EV-2"
INCOMING FEEDERS. REFER TO DETAIL #7 ON
SHEET E4.00 FOR MORE INFORMATION.
SEE SINGLE LINE DIAGRAM #1 SHEET E5.00 FOR
MORE INFORMATION.
NEW WHEELSTOP PER CIVIL DRAWINGS.
PROVIDE 4" DIA. CONCRETE BOLLARD. REFER
TO DETAIL #3 ON SHEET E4.01 FOR MORE
INFORMATION.
NEW STRIPING PER CIVIL DRAWINGS.
NEW SIGN AND POST PER CIVIL DRAWINGS.
APPROXIMATE LOCATION OF EXISTING
CONDUIT/S THAT SHALL BE PROTECTED AND
REMAIN IN PLACE.
E2.02
SCALE
ENLARGED SOUTH POWER PLAN 11/8" = 1'-0"
SCALE
ENLARGED SOUTH ELECTRICAL EQUIPMENT POWER PLAN 23/8" = 1'-0"
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
4/21/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
26-0457
DWR - Electric Vehicle Supply Equipment - Castaic O&M Center
PROJECT NUMBER: 000000000013643; ISSUE DATE 07/10/26
AutoCAD SHX Text O
SCALE
160KW DUAL PORT D.C. FAST CHARGER POWER LINK 2000 DETAIL 1N.T.S.
SCALE
EMERGENCY SHUT-OFF LABEL DETAIL 4N.T.S.
SCALE
ELECTRICAL EQUIPMENT RGS CONDUIT STUB-UP DETAIL 6N.T.S.
SCALE
EV CHARGING STATION PVC CONDUIT STUB-UP DETAIL 5N.T.S.
SCALE
DUAL PORT PEDESTAL ELECTRIC VEHICLE CHARGING STATION 3N.T.S.
SCALE
DIGITAL MULTI-METER DETAIL 7N.T.S.
SCALE
160KW D.C. FAST CHARGER POWER BLOCK DETAIL 2N.T.S.
DETAIL NOTES:
1. FOR DC FAST CHARGER POWER
BLOCK INFORMATION - REFER TO
INSTALLATION INSTRUCTIONS PER
MANUFACTURER.
2. DC FAST CHARGER POWER BLOCK
SHALL BE PROVIDED AND
INSTALLED BY CURRENT STATE
VENDOR. CONTRACTOR SHALL
PROVIDE INFRASTRUCTURE
NECESSARY TO SUPPORT THE
CHARGER AS SHOWN ON THESE
DRAWINGS.
3. ALL OUTPUTS SHALL BE ROUTED TO
THE DC FAST CHARGER POWER
LINK 2000 AS SHOWN ON E2.01.
(2) OUTGOING
CONDUITS WITH
HV DC CONDUCTORS
TO POWER LINK 2000. (1) INCOMING CONDUIT
WITH AC CONDUCTORS
24" MAX. CONDUIT
STUB-UPS (TYP.)
CONDUIT ENDS MUST NOT
HAVE BUSHINGS OR BELL ENDS.
REFER TO DETAIL #5 ON
THIS SHEET FOR ADDITIONAL
INFORMATION
OUTGOING CONDUITS WITH
LV CONDUCTORS AND
CAT-6 CABLE
4" MIN. TO 6-1/4" MAX.
CONDUIT STUB-UPS (TYP.)
CONDUIT ENDS MUST NOT
HAVE BUSHINGS OR BELL ENDS.
REFER TO DETAIL #5 ON
THIS SHEET FOR ADDITIONAL
INFORMATION.
DETAIL NOTES:
1. FOR DC FAST CHARGER POWER
LINK 2000 INFORMATION - REFER TO
INSTALLATION INSTRUCTIONS PER
MANUFACTURER.
2. DC FAST CHARGER POWER BLOCK
SHALL BE PROVIDED AND
INSTALLED BY CURRENT STATE
VENDOR. CONTRACTOR SHALL
PROVIDE INFRASTRUCTURE
NECESSARY TO SUPPORT THE
CHARGER AS SHOWN ON THESE
DRAWINGS.
NEW CONCRETE
EQPT. FOOTING.
SEE STRUCTURAL
SHEETS FOR MORE
INFORMATION.
CONDUIT ENTRIES
2"
ABOVE
EXISTING
GRADE1"
A.F.F.
CONDUIT & CONDUCTOR TABLE
TAG DESCRIPTION NUMBER OF
SETS CONDUIT SIZE CONDUCTOR/CABLE
SIZE & QUANTITIES
HV DC INPUT 2 3" PVC CONDUIT 4 #3/0 (3 PER POLE) & 1#2 GRD.
LV DC INPUT 1 3/4" PVC CONDUIT 2 #6
ETHERNET INPUT 1 3/4" PVC CONDUIT CAT-6 (STP)
NOTES:
· HV DC CONDUCTORS SHALL BE XHHW-2 AND RATED FOR 90°C AND FOR 1000V.
· LV DC CONDUCTORS SHALL BE XHHW-2 AND RATED FOR 75°C AND FOR 1000V.
· ETHERNET CABLE SHALL BE CAT-6 SHIELDED TWISTED PAIR (STP) AND OUTDOOR RATED.
CONDUIT & CONDUCTOR TABLE
TAG DESCRIPTION NUMBER OF
SETS CONDUIT SIZE CONDUCTOR/CABLE
SIZE & QUANTITIES
AC INPUT 1 2 1/2" PVC CONDUIT 3 #250 & 1 #4 GRD.
HV DC OUTPUT 2 3" PVC CONDUIT 4 #3/0 (3 PER POLE) & 1#2 GRD.
LV DC OUTPUT 1 3/4" PVC CONDUIT 2 #6
ETHERNET OUTPUT 1 3/4" PVC CONDUIT CAT-6 (STP)
NOTES:
· AC CONDUCTORS SHALL BE THWN-2 AND RATED FOR 90°C AND FOR 600V.
· HV DC CONDUCTORS SHALL BE XHHW-2 AND RATED FOR 90°C AND FOR 1000V.
· LV DC CONDUCTORS SHALL BE XHHW-2 AND RATED FOR 75°C AND FOR 1000V.
· ETHERNET CABLE SHALL BE CAT-6 SHIELDED TWISTED PAIR (STP) AND OUTDOOR RATED.
D.C. FAST CHARGER
POWER LINK 2000
350A OUTPUT
(DUAL PORT)
160kW D.C. FAST
CHARGER
POWER BLOCK,
350A OUTPUT WITH
(4) POWER MODULES
PROVIDE LABEL
IDENTIFYING SHUT-OFF
LOCATION. LABEL SHALL
CORRESPOND TO
CHARGER NUMBER.
REFER TO DETAIL #4
ON THIS SHEET.
NEW CONCRETE
EVCS FOOTING.
SEE STRUCTURAL
DRAWINGS FOR
MORE INFORMATION.
FRONT
ELEVATION
SIDE
ELEVATION
4'-0"
MAX.
1" PVC CONDUIT
4 #6 & 1 #8 GRD.
DUAL PORT PEDESTAL
EV CHARGING STATION
(7,200VA PER PORT)
PVC CONDUIT STUB-UP.
REFER TO DETAIL #5
ON THIS SHEET.
PROVIDE LABEL IDENTIFYING
SHUT-OFF LOCATION. LABEL
SHALL CORRESPOND TO
CHARGER NUMBER. REFER TO
DETAIL #6 ON THIS SHEET.
DETAIL NOTES:
1. FOR PEDESTAL TYPE EVCS MOUNTING INFORMATION,
REFER TO MANUFACTURER'S INSTALLATION
INSTRUCTION MANUAL.
2. SEE EVCS NOTE ON SHEET T0.01.
2"
ABOVE
EXISTING
GRADE
TOP OF EXISTING GRADE TOP OF EXISTING GRADE
2"
ABOVE
EXISTING
GRADE
4'-0"
MAX.
4"
3"
RED BACKGROUND
WITH WHITE LETTERING
RED STRIPING
WHITE STRIPING
DETAIL NOTES:
1. LABEL SHALL BE PROVIDED FOR ALL NEW EV CHARGING STATIONS SHOWN ON THESE DRAWINGS. LABEL SHALL
CORRESPOND WITH CHARGER NUMBER AND THE ASSOCIATED PANELBOARD PROVIDING POWER.
2. SEE BELOW FOR LABEL SPECIFICATIONS:
· MATERIAL: THERMAL PRINTED ON REFLECTIVE RED OUTDOOR LABEL STOCK (MEETS ASTMD 4956-99)
· COLOR: WHITE TEXT ON RED BACKGROUND WITH RED AND WHITE ALTERNATING STRIPES
· DAMAGE RESISTANT FROM COMMON CHEMICALS AND SOLVENTS.
· MINIMUM SERVICE TEMPERATURE: -40 DEG FAHRENHEIT
· MAXIMUM SERVICE TEMPERATURE: 180 DEG FAHRENHEIT
· APPLICATION TEMPERATURE: 50 DEG FAHRENHEIT
· FILM THICKNESS: 5.5 MIL
· ADHESIVE THICKNESS: 1 MIL
6"
MINIMUM
PVC CONDUIT
TRANSITION
COUPLING
BEND RADIUS
R = 10 x DIA. OF CONDUIT
(MINIMUM)
INSULATED METALLIC
GROUNDING BUSHING
(THREADED)
CONTINUOUS GALVANIZED RIGID
METAL CONDUIT WRAPPED AROUND
WITH 40 MIL. BLACK ELECTRICAL
PLASTIC INSULATING TAPE TO 6"
ABOVE FINISH GRADE
TOP OF EXISTING GRADE
1'-6"
OR
AS SHOWN
ON
EQUIPMENT
DETAIL
PVC CONDUIT
PVC
COUPLING
PVC CONDUIT
BEND RADIUS
R = 10 x DIA. OF CONDUIT
(MINIMUM)
PVC
BELL END
OR
BUSHING
PVC CONDUIT
TOP OF EXISTING GRADE
PVC
COUPLING
TOP OF EXISTING GRADE
38 EVCS
MANUFACTURER'S
CLEARANCE
REQUIREMENTS
CLEAR WORKING
SPACE PER
CEC 110.26(A)(1).
CONCRETE
FOOTING PER
STRUCTURAL
12 12
CLEARANCES
8 8
CLEARANCESCLEARANCES
CLEAR WORKING
SPACE PER CEC
110.26(A)(1).
CONCRETE
FOOTING PER
STRUCTURAL
EVCS
MANUFACTURER'S
CLEARANCE
REQUIREMENTS
EVCS
MANUFACTURER'S
CONCRETE MOUNTING
TEMPLATE (CMT)
EVCS
MANUFACTURER'S
CONCRETE MOUNTING
TEMPLATE (CMT)
(2) INCOMING
CONDUITS WITH
HV DC CONDUCTORS
FROM POWER BLOCK.
INCOMING CONDUITS WITH
LV CONDUCTORS AND
CAT-6 CABLE
2"
ABOVE
EXISTING
GRADE1"
A.F.F.
TOP OF EXISTING GRADE
CONDUIT ENTRIES
NEW CONCRETE
EQPT. FOOTING.
SEE STRUCTURAL
SHEETS FOR MORE
INFORMATION.
FU
S
E
DIGITAL MULTI-METER
WITH NEMA-1
ENCLOSURE
DETAIL NOTES:
PROVIDE DIGITAL MULTI-METER WITH
CAPABILITIES OF MONITORING kWH, MAX.
PEAK DEMAND AMPS AND VOLTAGE.
PROVIDE IN-LINE FUSE. REFER TO
MANUFACTURER'S INSTALLATION MANUAL
FOR TYPE AND SIZE.
PROVIDE CURRENT TRANSFORMERS. REFER
TO MANUFACTURER'S INSTALLATION MANUAL
FOR TYPE AND SIZE.
DEDICATED CIRCUIT BREAKER FOR DIGITAL
MULTI-METER. ACTUAL LOCATION WITHIN
PANEL MAY DIFFER.
VERIFY POWER CONNECTIONS WITH
MANUFACTURER'S INSTALLATION MANUAL.
Ia+
VIN
Ia-
CT-1
DMM CT INPUT TERMINALS
Ib+ Ib- Ic+ Ic-
FU
S
E
O
FF
O
FF
O N
O N
FU
S
E 3/4"C - 3 #12
& 1 #12 GRD.
EVCS
PANELBOARD
3/4"C - (6) CT
WIRING
ON ON ON
OFF OFF OFF
SPACE
O
FF
O
FF
O N
O N
O
FF
O
FF
O N
O N
O
FF
O
FF
O N
O N
O
FF
O
FF
O N
O N
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
O
FF
O
FF
O N
O N
O
FF
O
FF
O N
O N
O
FF
O
FF
O N
O N
SPACE
SPACE
SPACE
SPACE
O N
O N
O N
O
FF
O
FF
O
FF
(TYP.)
(TYP.)
CT-2 CT-3
CT-3
CT-2
CT-1
ØCØBØA
PROVIDE LABEL
IDENTIFYING SHUT-OFF
LOCATION. LABEL SHALL
CORRESPOND TO
CHARGER NUMBER.
REFER TO DETAIL #4
ON THIS SHEET.
Drawn by:
Job No.:
PA / PM:
Description of RevisionsByDate#
Sheet Title/Number
Scale:
Date:
REVISIONS
La ke H ug he s R oa d, Ca st ai c, C
A
E. Torres
E. Burtch
As Noted
D ep ar tm en t o f W at er R es ou rc es
C as ta ic
O
M C en te r E
V S
E In st al la tio n
124-01-02.64
12/18/2025
V1
255 East Rincon St., Suite 301 Corona, CA 92879 P 951.340.1977 | F 951.340.1090 www.gossengineering.com
DSA IDENTIFICATION STAMP:
CALOF I
G I
RE
NG
A
E
S
No. E17083
T E
ET
S
AT L CE A
F R I C
L
ORNI
E
PR
RAET
RE
D D.D
OF ONA
B R L
SSI
NE
RE
IWD
U
T
HC
E
CSFM APPLICATION NUMBER: 26-S-0457-C
95% CD SUBMITTALEB12/18/20251
100% CD SUBMITTALEB02/06/20262
ELECTRICAL
DETAILS
E4.00
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
4/21/2026
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
26-0457
DWR - Electric Vehicle Supply Equipment - Castaic O&M Center
PROJECT NUMBER: 000000000013643; ISSUE DATE 07/10/26
AutoCAD SHX Text O
GROUND RING DETAIL 4N.T.S.
SCALE
UNDERGROUND CONDUIT BURIAL DETAIL 1N.T.S.
1'-0"
MIN.
2'-0"
MIN.
ELECTRICAL
WARNING TAPE
3" CLEAN SAND
BEDDING
3" CLEAN SAND
BEDDING
NATIVE BACKFILL
90% COMPACTION
CONDUIT/S PER PLAN
SCALE
GROUND ROD DETAIL 5N.T.S.
SCALE
GROUND WELL DETAIL 6N.T.S.
SCALE
UNDERGROUND PULLBOX DETAIL 2N.T.S.
SCALE
GROUND CONNECTION - EXOTHERMIC WELD DETAIL 7N.T.S.
SCALE
BOLLARD DETAIL 3N.T.S.
NOTE:
THE GROUND RING SHALL BE INSTALLED
12" FROM THE EDGE OF THE EQUIPMENT PAD,
AND NOT LESS THAN 30" BELOW FINISH
SURFACE PER CEC 250.53.
4'-0"
CONCRETE
BOLLARD CAP
STEEL PIPE AND FOOTING
PER STRUCTURAL
DRAWINGS
FIELD PRIME STEEL BOLLARDS WITH
2 COATS OF ZINC-RICH PRIMER.
PAINT BOLLARDS WITH 2 COATS OF
INDUSTRIAL YELLOW ENAMEL.
TOP OF EXISTING GRADE
1'-0"
MIN.
2'-0"
MIN.
3" CLEAN SAND
BEDDINGDETAIL NOTE:
1. PER CEC 300.5 NO CONCRETE CASING IS
REQUIRED IF SCHEDULE 80 PVC IS USED 2'-0"
BELOW GRADE LEVEL. SEE POWER PLAN
FOR MORE INFORMATION.
1" MINIMUM.
FOR MULTIPLE CONDUIT RUNS,
SPACING SHALL BE EQUAL TO THE
LARGEST CONDUIT SIZE.
3" CLEAN SAND
BEDDING
EXISTING BASE
CRUSHED AGGREGATE BASE
RECOMPACTED TO 95%
RELATIVE COMPACTION
MATCH
EXISTING +1"
MATCH
EXISTING
+1"
ELECTRICAL
WARNING TAPE
NATIVE BACKFILL
95% COMPACTION
CONDUIT/S PER PLAN
TOP OF EXISTING GRADE (ASPHALT)
NEW ASPHALT
PAVEMENT
ASPHALT PAVEMENT
APPLICATION
NATIVE SOIL
APPLICATION
TOP OF EXISTING GRADE
1" MINIMUM.
FOR MULTIPLE CONDUIT RUNS,
SPACING SHALL BE EQUAL TO THE
LARGEST CONDUIT SIZE.
NATIVE SOIL
APPLICATION
GRAVEL
BASE
ELECTRICAL
CONDUIT/S
(OUT)
ELECTRICAL
CONDUIT/S
(IN)
2'-0"
MIN.
CONCRETE STEEL
REINFORCED
BOLT DOWN LID
(TRAFFIC RATED)NATIVE BACKFILL
95% COMPACTION
12" DEEP
STEEL REINFORCED
CONCRETE PULLBOX
(TRAFFIC RATED)
(EXTEND AS REQUIRED)
BASE
(TYPICAL)
AC PAVEMENT
(TYPICAL)
ASPHALT PAVEMENT
APPLICATION
TOP OF EXISTING GRADE
NOTE:
REFER TO SHEET NOTES ON
POWER PLANS FOR SPECIFIC
PULLBOX SIZES OR DIMENSIONS.
GRAVEL
BASE
ELECTRICAL
CONDUIT/S
(OUT)
ELECTRICAL
CONDUIT/S
(IN)
2'-0"
MIN.
CONCRETE STEEL
REINFORCED
BOLT DOWN LID
(TRAFFIC RATED)NATIVE BACKFILL
95% COMPACTION
12" DEEP
STEEL REINFORCED
CONCRETE PULLBOX
(TRAFFIC RATED)
(EXTEND AS REQUIRED)
TOP OF EXISTING GRADE
3/4"Ø x 10'-0"L
COPPER
GROUND ROD
(SEE DETAIL #5)
GROUND-WELL
WITH
3/4"Ø x 10'-0"L
COPPER
GROUND ROD
(SEE DETAIL #6)
DIGITAL
MULTI-METER
ELECTRICAL
EQUIPMENT
PER PLANS
EQUIPMENT PAD.
REFER TO STRUCTURAL
DRAWINGS FOR
INFORMATION
EQUIPMENT
GROUNDING
CONNECTION
PAD MOUNTED
TRANSFORMER
#4 BARE COPPER
GROUND RING
CONDUCTOR
(TYP.)
#4 BARE COPPER
GROUND RING
CONDUCTOR
(TYP.)
EXOTHERMIC
WELD
(SEE DETAIL 7)
EQUIPMENT GROUNDING
CONDUCTOR
(SIZE AS SHOWN ON THE PLANS)
GROUND LOOP/GRID
EXOTHERMIC WELD CADWELD
TYPE TA MOLD MODEL NO.
MD-4109-9
NOTE:
ALL GROUNDING SHALL BE IN
ACCORDANCE WITH
CALIFORNIA ELECTRICAL CODE,
CEC 2022, ARTICLE 250
NOTE:
ALL GROUNDING SHALL BE IN
ACCORDANCE WITH
CALIFORNIA…