This is a Questions and Answers document for federal contract opportunity 142040-26-0050, concerning UPS Battery Replacements for five National Weather Service (NWS) offices. The document provides clarifications on existing battery systems and site conditions for the replacement project.
The existing battery systems are located at five NWS facilities: Elko, Pendleton, Spokane, Eureka, and Las Vegas. All batteries are Eaton PWHR series units (PWHR1234W2FR at four locations and PWHR1227W2FR at Las Vegas) that came as original equipment from the Eaton factory. Battery quantities range from 108 to 160 units per location, organized into either 3 or 4 strings. The Las Vegas location has 4 strings with 160 batteries, while the other four locations have 3 strings each with quantities of 108 to 120 batteries. Date codes range from October 2021 to March 2022. Regarding logistics and site conditions, all UPS systems are located on the first floor with exterior doors providing direct access to the UPS rooms. Each site has parking available near the facility entrance with an average walkway distance of approximately 30 feet from parking to the UPS room. A ramp is available at each location to facilitate movement of batteries over the exterior door threshold. There are no receiving docks, forklifts, or pallet jacks available at any location. NOAA staff will not stage or move batteries; the contractor must arrange for battery delivery to coincide with work schedules and is responsible for all battery handling and removal from the facilities.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_1333MH26Q0014_Amd_0001.pdf | ||
| Humboldt_WD_2015-5673_Rev_26_5_13_26.pdf | ||
| Spokane_WD_2015-5537_Rev_28_5_13_26.pdf | ||
| Clark_WD_2015-5593_Rev_31_5_13_26.pdf | ||
| Elko_WD_2015-5601_Rev_28_5_13_26.pdf | ||
| Umatilla_WD_2015-5589_Rev_31_5_13_26.pdf | ||
| Sol_1333MH26Q0014.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions/Clarifications & Responses – 142040-26-0050 UPS Battery Replacements for 5 NWS Offices
The following questions and or clarifications requests were received from various interested parties. All questions and clarifications have been consolidated. Questions are denoted by “Q” and the response is denoted by “R.”
Q1: What is the battery cabinet CTO and Serial number for each system.
R1:
Elko
BAT-ER060UXX05
Eaton PWHR1234W2FR (Internal)
QTY 120
3 strings Date Code 10/2021
Pendleton
BAT-ER060UXX04
Eaton PWHR1234W2FR (Internal)
QTY 108
3 strings Date Code 10/2021
Spokane
BAT-ER060UXX06
Eaton PWHR1234W2FR (Internal)
QTY 108
3 strings Date Code 12/2021
Eureka
BAT-ER072UXX09
Eaton PWHR1234W2FR (Internal)
QTY 108
3 strings Date Code 03/2022
Las Vegas
BAT-ER282UJJ09
Eaton PWHR1227W2FR (Internal)
QTY 160
4 strings Date Code 12/2021
Q2: Could you please provide, for each of the five locations:
• Existing battery manufacturer and part/model number
• Number of batteries installed
• Photographs of the existing battery labels and battery cabinets, if available
R2:
See info above. These are original batteries that came in the equipment from the Eaton factory.
Photographs from one of the sites is below. No other site photos available.
Q3: Does each location have a receiving dock and/or forklift, or are there any special delivery restrictions/requirements (like short truck or liftgate)?
R3: No dock or forklift. The contractor is responsible for receiving the batteries.
Q4: Will NOAA staff move the new batteries from the receiving area and stage them near the UPS System(s)?
R4: No. Arrange for the batteries to arrive when the work is being done.
Q5: How far from the entrance/exit (where we will be removing the old batteries out of the facility) can we park our truck(s)?
R5: Yes. Parking is available. There is an exterior door that opens right into the UPS room. A walkway connects the parking lot to this door.
Q6. How far is the UPS System(s) from where the new batteries will be located when we arrive onsite?
R6: The walkway distance varies at each site. Average is around 30 feet.
Q7: Are there any stairs or obstructions that would prevent our technicians from easily transporting the batteries from the UPS system out of the facility to our trucks?
R7: No. Each site has a ramp that can be connected at the door to help move the batteries.
Q8: Is there a pallet jack available for use?
R8: No
Q9: What floor is the UPS system on? Is there a freight elevator available for use if applicable?
R9: On the first floor at each site. Has its own entrance from the outside
Q10: What obstructions/obstacles are present (narrow doorways/stairs, protected floors, etc.) between the drop off point, etc. and the UPS room R10: Only one which is the door threshold from the exterior door going into the UPS room. We have a ramp available to use for this purpose.
Q11: How many strings of batteries are installed in each UPS?
R11: All sites have 3 strings with the exception of Las Vegas which has 4.
Q12: Are there any external battery cabinets connected to the systems? If so, how many battery cabinets are connected to each UPS and how many strings?
R12: Only one battery cabinet is connected to the UPS at each site.
File details come from the government source that posted it. Updated .