13292_-_Approved_Drawings_with_Issue_Date_R2.pdf

PDF 16 MB Posted

Attached to
CONTRACT NUMBER: 23-203110, DSH CENTRAL UTILITY PLANT INTERCONNECT, PROJECT NUMBER: 13292
Solicitation number
0000032336
Issued by
Los Angeles County, California

About this file

This document is an advertisement for bids for the Central Utility Plant Interconnect project at the Department of State Hospitals (DSH) Metropolitan State Hospital in Norwalk, Los Angeles County, California. The project involves the demolition of an existing 66kV outdoor substation and 12kV switchgear, and the installation of new 5kV switchgear, a battery system, and related electrical infrastructure. The bid is being advertised by the California Department of General Services (DGS) Real Estate Services Division, with a bid due date of September 5, 2024 and a public bid opening on September 6, 2024. A mandatory pre-bid site inspection is scheduled for August 21, 2024. The project has an estimated cost of $2,064,800 and a contract term of 909 calendar days.

The project requires a contractor's license classification of C-10 or B. Bidders must also provide copies of valid Certificates of Reported Compliance for any fleet vehicles used on the project that are subject to the California Air Resources Board In-Use Off-Road Diesel Fueled Fleet Regulations. The contract will require payment and performance bonds, each in the amount of 100 percent of the contract price. The project includes Disabled Veteran Business Enterprise (DVBE) participation requirements.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

11401 BLOOMFIELD AVENUE, NORWALK, CALIFORNIA 90650

PROJECT ADDRESS :

PREPARED FOR:

DEPARTMENT OF STATE HOSPITALS

DEMOLISH THE EXISTING 66KV OUTDOOR SUBSTATION INCLUDING ALL

ANCILLARIES AND THE 12KV SWITCHGEAR INSIDE THE CO-GENERATION PLANT.

PROVIDE NEW 5KV SWITCHGEAR AND UTILITY METERING SECTION. NEW 5KV

SWITCHGEAR SHALL HAVE PROVISION FOR FUTURE AUTOMATION AND CONTROLS.

PROVIDE BATTERY, BATTERY CHARGER, ENCLOSURE, AND BATTERY

CALCULATION.

PROVIDE FROM SPARE CIRCUIT BREAKER OF NEW SWITCHGEAR TEMPORARY

POWER SUPPLY TO FEED THE EXISTING "MCC-A" LOCATED IN CO-GEN BUILDING

WHILE THE NEW FEED IS ON CONSTRUCTION.

PROVIDE EQUIPMENT PAD FOR SCE EQUIPMENT AND NEW 5KV SWITCHGEAR

EQUIPMENT, AND UNDERGROUND CONDUIT.

DEMOLISH THE EXISTING TRANSFORMER "A" LOCATED OUTDOOR AND INTERCEPT

THE EXISTING PATHWAY AND PROVIDE NEW 5KV CONDUCTOR TO RE-FEED THE

EXISTING 5KV "MCC-A".

PROVIDE METHODS AND SCHEDULE OF SHUTDOWN TO DSH- METROPOLITAN

STATE HOSPITAL (MSH) FOR APPROVAL. THE SCHEDULE OF SHUTDOWN SHALL

HAVE MINIMAL IMPACT TO THE OPERATION OF THE FACILITY.

1. 2022 BUILDING STANDARDS ADMINISTRATIVE CODE, TITLE 24 C.C.R.

2. 2022 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 C.C.R.

3. 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R.

4. 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R.

5. 2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R.

6. 2022 CALIFORNIA ENERGY CODE (CEC), PART 6, TITLE 24 C.C.R.

7. 2022 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R.

8. 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN), PART 11,

TITLE 24 C.C.R.

9. 2022 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R.

10. TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.

11. HCAI/OSHPD LEVEL 5 - ACUTE PSYCHIATRIC HOSPITAL

N N

NOT TO SCALEN NOT TO SCALE

NOT TO SCALE

Imperial Hwy

NORWALK

Bloom field Ave

Norwalk Blvd

Telegraph Rd.

Studebaker Rd

Florence Ave. Telegraph Rd.

Rosecrans Ave.

SANTA ANA FW

Y N

Pioneer Blvd

G reenstone Ave

Firestone Blvd

NORWALK

STA FE

SPRING

WHITTIERBELL

DOWNEY

BELLFLOWER

GARDENS

PROJECT

LOCATION

PROJECT

LOCATION

SCOPE OF WORKAPPLICABLE CODES

SITE MAP

PROJECT INFORMATION

LOCATION MAP VICINITY MAP

DSH - METROPOLITAN

CUP INTERCONNECT - CENTRAL PLANT

PROJECT LOCATION

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

DateIssue

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

FI

LE

: L :\2

3\

3-

C U

P In te rc on ne ct , D

SH

-M

\C

AD

\2

5_

T1

C O

VE

R

S H

EE

T

- C

EN

TR

AL

P

LA

N T.

dw g

D

AT

E/

TI

M E:

Au g

, 0 4:

PM

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

PROJECT SUMMARY

THE PROJECT CONSISTS OF THE INSTALLATION OF AN ELECTRICAL INTERCONNECT

TO PROVIDE POWER TO CENTRAL UTILITY PLANT (CUP). THE CUP CURRENTLY

UTILIZES A 66KV SUPPLY FROM SOUTHERN CALIFORNIA EDISON. DSH RECENTLY

ACQUIRED THE CUP FROM PREVIOUS LEASE AND IS OPERATING THE CUP ON A

LIMITED BASIS. DSH-METROPOLITAN DOES NOT PLAN TO GENERATING ELECTRICITY

NOR SEND POWER TO THE GRID, THERE IS NO LONGER ANY NEED FOR THE 66KV

SUPPLY NOR SOUTHERN CALIFORNIA EDISON SIGGEN SUBSTATION.

DEPARTMENT OF STATE HOSPITALS

11401 South Bloomfield Avenue Norwalk, California 90650

JOSHUA KAISER

Chief Construction Officer

(916) 248-0015 Email: joshua.kaiser@dsh.ca.gov.

BRIAN HUDSON

DSH Overall CM Lead

(682) 777-0906 Email: Brian.Hudson@dsh.ca.gov.

ALEX VAN ELDEN

(949) 391-5066 Email: Alexander.VanElden@dsh.ca.gov.

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE, NORWALK,

CALIFORNIA 90650 LOS ANGELES COUNTY

TITLE SHEET,

APPLICABLE CODES

AND SCOPE OF WORK

T1.0

OSFM PERMIT#: 23-6278

HCAI COMPLIANCE

NEW EQUIPMENT SHALL COMPLY WITH HCAI REQUIREMENT.

METAL CLAD SWITCHGEAR OSP-0046

METAL ENCLOSED SWITCHGEAR OSP-0037

BATTERY CHARGER OSP-0131

BATTERY RACK OSP-0264

PANG HER

Assoc. Construction Analyst

(916) 915-8293 Email: Pang.Her@dsh.ca.gov.

PAUL SMITH

Chief of Plant Operations

(562) 651-4376 EXT. 8094

Cell: (562) 292-4755 Email: Paul.Smith@dsh.ca.gov.

NATALIE GARCIA

Assistant Hospital Administrator

(562) 521-1417 Main Office: (562) 651-4376 Email: Natalie.Garcia@dsh.ca.gov.

J.C. Chang & Associates, Inc. Engineers, Architects and Planners 385 Van Ness Way, Suite 208 Torrance, California 90501

(310) 212-7644

PREPARED BY:

(REFER TO OSFM PERMIT#: 24-0864 FOR SWITCHGEAR BUILDING)

1 08/05/24 OSHPD AND OSP#

ISSUE DATE: August 5, 2024

AREA OF WORK - CUP BUILDING

IM

P E R

IA

L H

W Y

BLOOMFIELD AVENUE BLOOMFIELD AVENUE

COGENERATIONCO-GEN.

TRANSPORTATIONTRANS.

VOCATIONAL REHABILITATION

HOUSEKEEPING

ADMINISTRATION

OFFICE OF STATE ARCHITECT

GARAGE

RESIDENCE NUMBER

EMPLOYEE

BUILDING

OCCUPATIONAL THERAPY

WAREHOUSE

SHELTER

VOC. REHAB.

HSEKP.

ADMIN.

OSA

G R#

EMP.

BLDG.

O.T.

W S

ABBREVIATIONS & SYMBOLS

PATIENT SUPPORT MODULESP.S.M.

10,274 10,274

9,0009,000

9,371 9,371

2,695 2,439

10,501

8,200

7,933

8,977

8,977

7,933

8,200

10,501

10,501

8,200

7,933

8,977 10,501

8,200

7,933

8,977

17,235

17,235 17,235

17,235

(L

RZ

e U)

WATER TANKS

IRRIGATION PUMP HOUSE

WATER SOFTENER BUILDING DOMESTIC PUMP HOUSE

DEVICE

BACKFLOW

COMMINUTOR

BUILDING

CTE CHILLER

P.S.M.

COURT

TENNIS

DOM.IRR.

M

ET

A L

P R

O P E R

T Y

L

IN

E

P R

O P E R

T Y

L

IN

E

PROPERTY LINE

FD. SERV. WHSE.

LUMBER SHED

GAS PUMP

EN

G

IN

S

SS

S

S

S

D C

U

TRANS.

G A

R A

G E

PLUMBER

OFFICES

PLANT OP'S.

RECEIVING

STORES /

CAR PORT

CARPENTER

PA

IN

T

MASON

ST

O

R

SH

EE

T

EL

EC

T.

W

EL

D

O .T

O .T

O.T. SOUTH

O.T. NORTH

EM

P.

B

LD

G . 4

EMP. BLDG. 3

R

EC

YC

LI

N G

S

S

G

#18

G

#19

#16

G

#14

#13

313/315

G

G

EM

P.

B

LD

G . 2

EMP. BLDG. 1

#1

#15 S

LA

U

N D

R Y

KITCHEN

OFFICE

TRUST

S

201/203

2/

5/

0/

9/

3/

STORAGE

CHILL WATERBARBER/

W3

COOLING TOWER

#6

#8#7

HSEKP. WHSE 1

PROPERTY

HALL

JAMES

306-308

HOUSE

BOILER

E1

309-311 (CPS)

W2NORTH YARD

PCB SHED

HOMES

#10

G

G

G

#11

#12

#20

PUMP HOUSE

(ABANDONED)

C O

N D

O M

IN

IU

M C

O M

PL

EX

FASHION CNT.

STORAGE

PROPERTY LINE

PROPERTY LINE

P R

O P E R

T Y

L

IN

E

PROPERTY LINE

P R

O P E R

T Y

L

IN

E

OASIS

P.S.M.

#17

VOLLEYBALL

BASKETBALL

G R

A

SS

A R

EA

SALLYPORT

VISITOR CENTER

ADMIN.

CLINICAL

BLDG.

C

EN

TE

R

STUDIO

ART

WAREHOUSE

REHAB.

HOMES

HOMES

CENTER

305/307

BIRCH GROVE

CEDAR STREET

ELM STREET

POST

WELLNESS

G R

N D

LOCK

WASH.

WAREHOUSE

KITCHEN

CENTRAL

(Omitted)

CLINIC

D-57 (USSeU)

BEAUTY SHOP

C

EN

TE

R

FA

SH

IO

N

FSHN. CNT.

STORE

RELIGIOUS

CENTER

NORWALK BOULEVARD

80 Stalls

S ta lls

1 8 Stalls

58 Stalls

S ta lls

S ta lls

#5

BUILDING

CO-GEN.

S.N.F.

TRAILER

10110

HOSP.

OFFICE

POLICE

407/415

405/413

CTE

BLDG.

401/409

408/416

406/414

402/410

417 419

418 420

YOUTH

ADMINISTRATION

BUILDING

CTW

BLDG.

A

A

A

BLDG.

S.N.F.

TRUST

OFFICE

BLDG.

LIBRARY

404/412

403/411

/2

P.S.M.

AREA OF WORK - SWITCHGEAR BUILDING

MAIN ENTRANCE TO SITE

258'-5"

297'-0"

AREA OF WORK - EXTERIOR

SCALE: 1" = 200'

FIRE ACCESS SITE

PLAN

T2.0

FIRE ACCESS SITE PLAN

TRUE

NORTH

PLAN

NORTH1

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

F

IL

E L \2

-5

C U

P I n te rc o n n e c t, D

S H

-M \C

A D \2

T F

IR

E A

C C E S S S

IT

E P

L A N

.d w g

D A T E /T

IM

E J a n

:2

P M

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

LEGEND

FIRE ACCESS LANE

FIRE HYDRANT

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

03/04/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-6278 l l

EXISTING CONCRETE SLAB

OVER UNDERGROUND #2

FUEL OIL STORAGE TANK

(E) MANHOLE "MHAA"

SWITCHGEAR ROOM

1,528 SF

U OCCUPANCY

OL 300 = 6 OCC

BOLLARD (TYP)

(E) TUNNEL EXHAUST FAN TO REMAIN

BALSAM STREET

GENERATOR ROOM

1,528 SF

U OCCUPANCY

OL 300 = 6 OCC

T Y P

T Y P

30'-0" TYP.

30'-0" TYP.

105'-7"

/1

51'-0"

20'-4"

IMAGINARY PL

BETWEEN BUILDINGS

36'-7"

SWITCHGEAR

BUILDING

CODE ANALYSES

FLOOR PLAN

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

F

IL

E L \2

-5

C U

P I n te rc o n n e c t, D

S H

-M \C

A D \2

T S

W

IT

C H

G E A R

B U

IL

D

IN

G

C O

D E A

N A L Y S

IS

.d w g

D A T E /T

IM

E J a n

:3

P M

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

CODE ANALYSES:

SCALE

SWITCHGEAR BUILDING CODE ANALYSES FLOOR PLAN

TRUE

NORTH

PLAN

NORTH1

EXISTING BUILDING TYPE: II-B (8" CMU BLOCK WALLS WITH STEEL DECK/ROOF)

OCCUPANCY: F-1 OCCUPANCY

HEIGHT: EXISTING 24' AFG

SPRINKLERED: NO

NUMBER OF STORIES: 1

PER CHAPTER 5 CBC

II-B/F-1 OCC NON SPRINKLERED 15,500 SF ALLOWED > 2,964 SF OK

II-B/F-1 OCC NON SPRINKLERED 2 STORIES (55 FEET) ALLOWED > 1 STORY (24 FEET) OK

PER CHAPTER 6 CBC

II-B BEARING WALL: 0 RATING REQUIRED = OK

II-B INTERIOR WALLS AND, ROOF 0 RATING REQUIRED = OK

II-B/F-1 OCCUPANCY DISTANCE TO FIRE SEPARATION BETWEEN 10 FEET AND 30 FEET = 0 RATING = OK

1. CLOSEST IMAGINARY PL IS 21'-8" FEET TO EAST.

0 FEET8

1/8" = 1'-0"

4 16

CODE ANALYSES CONT:

PER CHAPTER 9 CBC

F-1 OCCUPANCY NOT REQUIRED TO BE SPRINKLERED

PER CHAPTER 10 CBC

FUNCTION OF SPACE: MECH/ELECTRICAL ROOM OL = 300

1. OCCUPANCY = 10 PER PLAN

2. 10 < 49 OCC. ONE EXIT DOOR REQUIRED (PER CEC AND NEC SWITCHGEAR > 800A 2 DOORS REQUIRED (3 PROVIDED OK)

3. F-1 OCC W/O SPRINKLER SYSTEM TO EXIT ACCESS < 200 FT PER PLAN = OK.

FIRE SEPERATION DISTANCE LINE

CODE ANALYSIS NOTES:

30 FEET FIRE SEPARATION DISTANCE UNLESS NOTED

OTHERWISE.

LEGEND:

NOTE:

THIS IS SHOWN FOR REFERENCE ONLY. NO

CHANGE IS PROPOSED FOR BUILDING LOCATION OR

EXISTING FIRE SEPARATION DISTANCE.

IM

P E R

IA

L H

W Y

BLOOMFIELD AVENUEBLOOMFIELD AVENUE

COGENERATIONCO-GEN.

TRANSPORTATIONTRANS.

VOCATIONAL REHABILITATION

HOUSEKEEPING

ADMINISTRATION

OFFICE OF STATE ARCHITECT

GARAGE

RESIDENCE NUMBER

EMPLOYEE

BUILDING

OCCUPATIONAL THERAPY

WAREHOUSE

SHELTER

VOC. REHAB.

HSEKP.

ADMIN.

OSA

G R#

EMP.

BLDG.

O.T.

W S

ABBREVIATIONS & SYMBOLS

PATIENT SUPPORT MODULESP.S.M.

10,274 10,274

9,0009,000

9,371 9,371

2,695 2,439

10,501

8,200

7,933

8,977

8,977

7,933

8,200

10,501

10,501

8,200

7,933

8,977 10,501

8,200

7,933

8,977

17,235

17,235 17,235

17,235

(L RZe

U)

WATER TANKS

IRRIGATION PUMP HOUSE

WATER SOFTENER BUILDING DOMESTIC PUMP HOUSE

DEVICE

BACKFLOW

COMMINUTOR

BUILDING

CTE CHILLER

P.S.M.

COURT

TENNIS

DOM.IRR.

M

ET

A L

P R

O P E R

T Y

L

IN

E

P R

O P E R

T Y L

IN

E

PROPERTY LINE

FD. SERV. WHSE.

LUMBER SHED

GAS PUMP

EN

G

IN

S

SS

S

S

S

D C

U

TRANS.

G A

RA

G

E

PLUMBER

OFFICES

PLANT OP'S.

RECEIVING

STORES /

CAR PORT

CARPENTER

PA

IN

T

MASON

ST

O

R

SH

EE

T

EL

EC

T.

W

EL

D

O .T

O .T

O.T. SOUTH

O.T. NORTH

EM

P.

B

LD

G . 4

EMP. BLDG. 3

R

EC

YC

LI

N G

S

S

G

#1 8

G

#19

#16

G

#14

#13

31 3/315

G

G

EM

P.

B

LD

G . 2

EMP. BLDG. 1

#1

#15 S

LA

U

N D

RY

KITCHEN

OFFICE

TRUST

S

201/203

2/

9/

STORAGE

CHILL WATERBARBER/

W3

COOLING TOWER

#6

#8#7

HSEKP. WHSE 1

PROPERTY

HALL

JAMES

306-308

HOUSE

BOILER

E1

309-31 1 (CPS)

W2NORTH YARD

PCB SHED

HOMES

#1 0

G

G

G

#1 1

#1 2

#20

PUMP HOUSE

(ABANDONED)

C O

N D

O M

IN

IU

M C

O M

PL

EX

FASHION CNT.

STORAGE

PROPERTY LINE

PROPERTY LINE

P R

O P E R

T Y

L

IN

E

PROPERTY LINE

P R

O P E R

T Y L

IN

E

OASIS

P.S.M.

#1 7

VOLLEYBALL

BASKETBALL

G R

A

SS

A R

EA

SALLYPORT

VISITOR CENTER

ADMIN.

CLINICAL

BLDG.

C

EN

TE

R

STUDIO

ART

WAREHOUSE

REHAB.

HOMES

HOMES

CENTER

305/307

BIRCH GROVE

CEDAR STREET

ELM STREET

POST

WELLNESS

G

RN

D

LOCK

WASH.

WAREHOUSE

KITCHEN

CENTRAL

(Omitted)

CLINIC

D-57 (USSeU)

BEAUTY SHOP

C

EN

TE

R

FA

SH

IO

N

FSHN. CNT.

STORE

RELIGIOUS

CENTER

NORWALK BOULEVARD

80 Stalls

S ta lls

1 8 Stalls

58 Stalls

S ta lls

S

CO-GEN.

S.N.F.

TRAILER

10110

HOSP.

OFFICE

POLICE

407/415

405/41 3

CTE

BLDG.

401 /409

408/416

406/414

402/410

417 419

418 420

YOUTH

ADMINISTRATION

BUILDING

CTW

BLDG.

A

A

A

BLDG.

S.N.F.

TRUST

OFFICE

BLDG.

LIBRARY

404/412

403/41 1

/2

KEY PLAN

SCALE:N.T.S.

EXIT PATH < 250'

T3.0

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

03/04/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans l

TRANSFORMER

PIPE

BRIDGE

(E) MANHOLE "MHAA"

BOLLARD

(TYP)

(E)TUNNEL EXHAUST FAN TO REMAIN

30'-0" TYP.

4.7

4.4

101F

102F

107J-A

107J-B

J- A

DRAINAGE

SUMP WITH

PUMP

104L A&B

104LJ2 A&B 104LJ1 A&B

112J

104F 103F

109-J

105F

105F

ADMINISTRATION,

MAINTENANCE, &

CONTROL ROOM

BLOCK

106L-B

106L-A

LUBE OIL

COOLER

J- B

HYDRAULIC

STARTER

SKID

110J A&B

110JD1

110JL1

TURBINE

LUBE OIL

COOLER

SKID

101L

120J-A

120J-B

119J-A 119J-B

101D

111L-C

CHILLER

WASTER WATER CLARIFIER

101J-A&B

101JD1

101JD2

111L-A

MOTOR

111L-B

MOTOR

CHILLER SHELL

103J

105J-B

105J-A

LUBE OIL

CONSOLE

SPACE RESERVED FOR SWITCHGEAR

101L

FLUE GAS

ANALYZER PANEL

EJECTOR, GLAND CONDENSER,

EXTRACTION VALVE PLATFORM

OIL

RETURN

101LD3

101LD2

101LD1

102D

104J-B

104J-A

105LJ1

105LF1

105LJ2

105LF2

105LJ3

105LF3

101C

BALSAM STREET

30'-0" TYP.

T Y P

T Y P

105'-7"

32'-9"

35'-0"

32'-3"

FUTURE

ABOVEGROUND

TANK

FUEL

POLISHER

FUTURE

DAYTANK

FUTURE

2,500KW

FUTURE

NGR NGR

FUTURE SWITCHGEAR

WITH MASTER

CONTROLLER

FUTURE GENERATOR

AREA NOT PART OF THIS

CONTRACT

SCALE

1" = 150'

75 0 15 300FEET 150

CUP BUILDING CODE ANALYSES FLOOR PLAN

TRUE

NORTH

PLAN

NORTH1

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

F

IL

E L \2

-5

C U

P I n te rc o n n e c t, D

S H

-M \C

A D

\2 T C

O -G

E N

B U

IL

D

IN

G

C O

D E A

N A L Y S

IS

.d w g

D A T E /T

IM

E J a n

:3

P M

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

CODE ANALYSES CUP BUILDING:

EXISTING BUILDING TYPE: II-B (8" CMU BLOCK WALLS WITH STEEL DECK/ROOF)

OCCUPANCY: F-1 OCCUPANCY

HEIGHT: EXISTING 46' AFG

SPRINKLERED: YES

NUMBER OF STORIES: 1

AREA: F-1 OCC = 19,147 SF (1ST LEVEL)

AREA: B OCC = 2,260 SF (2ND LEVEL)

PER CHAPTER 5 CBC

II-B/F-1 OCC SPRINKLERED 62,000 SF ALLOWED > 19,147 SF OK

II-B/F-1 OCC SPRINKLERED 92,000 SF ALLOWED > 2,260 SF OK

II-B/B AND F-1 OCC SPRINKLERED 3 STORIES (75 FEET) ALLOWED > 1 STORY (46 FEET) OK

PER CHAPTER 6 CBC

II-B BEARING WALL: 0 RATING REQUIRED = OK

II-B INTERIOR WALLS AND, ROOF 0 RATING REQUIRED = OK

II-B/F-1 OCCUPANCY DISTANCE TO FIRE SEPARATION BETWEEN 10 FEET AND

30 FEET = 0 RATING = OK

1. CLOSEST IMAGINARY PL IS 15 FT.

CODE ANALYSES CONT:

PER CHAPTER 10 CBC

FUNCTION OF SPACE: MECH/ELECTRICAL ROOM OL = 78

1. OCCUPANCY F-1 = 19147/300 = 63 PER PLAN. B OCCUPANCY = 2260/150 = 15 OCC

2. 63 > 49 OCC. TWO EXIT DOOR REQUIRED WITH PANIC HARDWARE (5 DOORS PROVIDED)

3. 15 OCC < 49 HOWEVER, OFFICE ON 2ND FLOOR THEREFORE TWO EXITS REQUIRED (2 EXITS PROVIDED)

4. F-1 OCC W/ SPRINKLER SYSTEM MAX.100 FT TO EXIT ACCESS. EXIT ACCESS < 250 FT = OK

5. B OCC W/ SPRINKLER SYSTEM 30 FT TO EXIT ACCESS. EXIT ACCESS < 300 FT = OK.

FIRE SEPERATION DISTANCE LINE

CODE ANALYSIS NOTES:

30 FEET FIRE SEPARATION DISTANCE UNLESS NOTED

OTHERWISE.

IM

P E R

IA

L H

W Y

BLOOMFIELD AVENUEBLOOMFIELD AVENUE

10,274 10,274

9,0009,000

9,371 9,371

2,695 2,439

10,501

8,200

7,933

8,977

8,977

7,933

8,200

10,501

10,501

8,200

7,933

8,977 10,501

8,200

7,933

8,977

17,235

17,235 17,235

17,235

NORWALK BOULEVARD

80 Stalls

S ta lls

1 8 Stalls

58 Stalls

S ta lls

S

10110

408/416

406/414

402/410

417 419

418 420

CTW

BLDG.

A

A

BLDG.

S.N.F.

404/412

KEY PLAN

SCALE:N.T.S.

EXIT PATH < 250'

NOTE:

THIS IS SHOWN FOR REFERENCE ONLY. NO

CHANGE IS PROPOSED FOR BUILDING LOCATION OR

EXISTING FIRE SEPARATION DISTANCE.

LEGEND:

CUP BUILDING

CODE ANALYSES

FLOOR PLAN

T4.0

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

03/04/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

THIS SYMBOLOGY TO BE USED BY ELECTRICAL AND LAYOUT FOR

ALL FLOOR PLANS, EQUIPMENT, DEVICES, UTILITIES, ETC...,

SHOWN ON DRAWINGS.

LIGHT, THIN LINES INDICATE EXISTING.

HEAVY, THICK LINES INDICATE NEW

HEAVY, SHORT DASHED LINES INDICATE

DEMOLITION OR REMOVAL

TYPICAL PLAN LEGEND

LIGHT, THIN LINES INDICATE EXISTING.

HEAVY, THICK LINES INDICATE NEW

HEAVY, SHORT DASHED LINES INDICATE

DEMOLITION OR REMOVAL

ABBREVIATIONS

NEGLIGIBLENEGL

DISTANCE

DENOTES EXISTING(E)

CB CIRCUIT BREAKER

EA. EACH

COPPERCU

G, GND GROUND

MIN. MINIMUM

AMP./A AMPERE

FIN FINISHED

CIRCUITCKT

LOW VOLTAGE

AMPERE

INTERRUPTING

CAPACITY

AIC

ABOVE FINISHED

FLOOR

AFF

BKR BREAKER

NTS NOT TO SCALE

WEATHER PROOFWP

SWITCHBOARDSWBD

TYP. TYPICAL

UG UNDERGROUND

SWITCHSW

PULL BOXPB

SLD SINGLE LINE DIAGRAM

POLEP

PANELBOARDPNL

(R) RELOCATED

SUB SUBSTATION

NEW(N)

TIME DELAY

UNLESS

OTHERWISE

NOTED

UON

TRANSFORMERXFMR,

TRANSF.

VD VOLTAGE DROP

UL LISTING

ALL ELECTRICAL EQUIPMENT SHALL BE UL LISTED OR APPROVED BY NATIONALLY

RECOGNIZED TESTING LABORATORY.

1. CONTRACTOR SHALL PROVIDE SEQUENCE OF CONSTRUCTION TO MINIMIZE

DOWNTIME/POWER OUTAGE.

2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE TEMPORARY

POWER SUPPLY IN PERFORMING THEIR WORK TO AVOID DISRUPTION ON

CLIENT OPERATION INCLUDING SECURING PERMIT FOR TEMPORARY

POWER SUPPLY.

SEQUENCE OF CONSTRUCTION

VOLTAGE DROP NOTE

APPLICABLE FOR ALL NEW, ALTERED, OR RELOCATED FEEDER AND BRANCH

CIRCUIT CONDUCTORS.

"130.5(C) VOLTAGE DROP: THE MAXIMUM COMBINED VOLTAGE DROP ON BOTH

INSTALLED FEEDER CONDUCTORS AND BRANCH CIRCUIT CONDUCTORS TO THE

FARTHEST CONNECTED LOAD OR OUTLET SHALL NOT EXCEED 5 PERCENT."

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

F

IL

E L \2

-5

C U

P I n te rc o n n e c t, D

S H

-M \C

A D

\2 E A

B B S Y M

B L

IS

T .d w g

D A T E /T

IM

E J a n

:3

P M

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

MOTOR

GROUNDING

SWITCHBOARD 480/277, 3Ø, 4W

MOTOR

GROUNDING

FUSE W/DISCONNECT SWITCH

PROVIDE IS DEFINED TO MEAN THAT THE CONTRACTOR SHALL FURNISH,

INSTALL, ADJUST, TEST AND INTEGRATE INTO A COMPLETE SYSTEM THE ITEM

INDICATED INCLUDING ALL HARDWARE, WIRING, AND MISCELLANEOUS ITEMS

AS NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEM.

DEFINITION

E0.0

E0.1

E1.0

E1.1

E3.0

E3.1

TITLE SHEET, APPLICABLE CODES AND SCOPE OF WORK

FIRE ACCESS SITE PLAN

SWITCHGEAR BUILDING CODE ANALYSES FLOOR PLAN

CUP BUILDING CODE ANALYSES FLOOR PLAN

ELECTRICAL SYMBOL LIST, ABBREVIATIONS, LEGEND,

DEFINITION AND UL LISTING

ELECTRICAL SPECIFICATION NOTES

OVERALL ELECTRICAL SITE PLAN

ELECTRICAL SITE PLAN - DEMOLITION

ELECTRICAL SITE PLAN - ENLARGED

ELECTRICAL SITE PLAN - UNDERGROUND NEW WORK

ENLARGED PLAN

CO-GENERATION-ASSOCIATED CONDUCTOR DEMOLITION

SINGLE LINE DIAGRAM DEMOLITION

SINGLE LINE DIAGRAM NEW WORK

ELECTRICAL DETAILS

ELECTRICAL DETAILS

ELECTRICAL DETAILS

ELECTRICAL DETAILS

SCE DRAWING

ELECTRICAL

DRAWING INDEX

T1.0

ELECTRICAL SYMBOL LIST

E4.0

E2.0

E2.1

E4.1

D

E1.2

E1.3

E4.2

52 DRAW-OUT MV CIRCUIT BREAKER

TRANSFORMER

CURRENT TRANSFORMER (CT)

G

LA LIGHTNING ARRESTER

GENERATOR

M

FEEDER RELAY

METER

DISCONNECT SWITCH

DRAW-OUT POTENTIAL TRANSFORMER (PT)

A AMMETER WITH SELECTOR SWITCH

LOCAL FIRE AUTHORITY - ACCESS APPROVAL

T2.0

T3.0

T4.0

E4.3

ELECTRICAL SYMBOL

LIST, ABBREVIATIONS,

LEGEND, DEFINITION

AND UL LISTING

E0.0

DEMOLISH(D)

GR GENERATOR RELAY

FR

V VOLTMETER WITH SELECTOR SWITCH

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

03/04/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-6278

ISSUE DATE: August 5, 2024

JoEnriqu Text Box Jan. 12, 2024

A. SCOPE

1. FURNISH AND INSTALL ALL REQUIRED MATERIALS AND

EQUIPMENT FOR COMPLETE OPERATING SYSTEMS AS

SHOWN AND AS SPECIFIED.

B. ALL WORK AND MATERIALS SHALL COMPLY WITH THE

LATEST APPLICABLE EDITION OF THE FOLLOWING CODES:

1. 2022 CALIFORNIA BUILDING STANDARDS

ADMINISTRATIVE CODE, TITLE 24 C.C.R.

2. 2019 CALIFORNIA BUILDING CODE, TITLE 24 C.C.R. (2021

INTERNATIONAL BUILDING CODE OF THE INTERNATIONAL

CODE COUNCIL, WITH CALIFORNIA AMENDMENTS).

3. 2022 CALIFORNIA ELECTRICAL CODE, TITLE 24 C.C.R.

(2020 NATIONAL ELECTRICAL CODE OF THE NATIONAL

FIRE PROTECTION ASSOCIATION, NFPA).

4. 2022CALIFORNIA MECHANICAL CODE, TITLE 24 C.C.R.

(2018 UNIFORM MECHANICAL CODE OF THE

INTERNATIONAL ASSOCIATION OF PLUMBING AND

MECHANICAL OFFICIALS, IAPMO).

5. 2022 CALIFORNIA ENERGY CODE, TITLE 24 C.C.R.

6. 2022 BUILDING ENERGY EFFICIENCY STANDARDS.

7. 2022 CALIFORNIA FIRE CODE, TITLE 24 C.C.R.

(2021 INTERNATIONAL FIRE CODE OF THE

INTERNATIONAL CODE COUNCIL).

8. 2022 CALIFORNIA GREEN BUILDING STANDARD CODE

(CALGREEN CODE), TITLE 24 C.C.R.

C. PERMITS AND INSPECTIONS

1. OBTAIN AND PAY FOR ALL REQUIRED PERMITS AND

INSPECTIONS FOR THE INSTALLATION OF THE

ELECTRICAL WORK. DELIVER CERTIFICATES OF

INSPECTION AND APPROVAL TO THE OWNER.

D. SITE VISIT

1. CONTRACTOR SHALL VISIT THE JOB SITE AND BECOME

FAMILIAR WITH THE EXISTING CONDITIONS THAT WILL

AFFECT HIS WORK AND MAKE THE NECESSARY

ALLOWANCES IN HIS BID TO COMPENSATE FOR THESE

CONDITIONS. BY THE ACT OF SUBMITTING A BID FOR

THIS PROJECT, THE CONTRACTOR ACCEPTS ALL

CONDITIONS AT THE SITE. NO REQUEST FOR ADDITIONAL

PAYMENT SHALL BE CONSIDERED AS VALID, DUE TO

FAILURE TO ALLOW FOR CONDITIONS WHICH MAY EXIST.

E. CLEANING PREMISES

1. KEEP JOB SITE, BUILDING AND SITE FREE FROM RUBBISH

AND WASTE MATERIALS, REMOVE SAME FROM SITE ON A

DAILY BASIS.

F. EXAMINATION OF DRAWINGS

1. CONTRACTOR SHALL STUDY ALL DRAWINGS AND

SPECIFICATIONS. SHOULD ANY OF THE WORK SHOWN

OR INDICATED BY THE DRAWINGS BE CONTRARY TO OR

IN CONFLICT WITH ANY CODE REQUIREMENTS, THE SAME

SHALL BE REPORTED TO THE OWNER BEFORE

SUBMITTING A BID. CONTRACTOR WILL BE ADVISED AS

TO HOW TO PROCEED.

G. COORDINATION

1. COORDINATE ALL WORK WITH OTHER TRADES. OBTAIN

ALL DRAWINGS THAT WILL REQUIRE COORDINATION AND

PROVIDE ALL ELECTRICAL CONNECTIONS REQUIRED

WHETHER SHOWN ON ELECTRICAL DRAWINGS OR NOT.

2. ELECTRICAL EQUIPMENT LOCATIONS INDICATED ARE

SHOWN DIAGRAMMATICALLY, EXACT LOCATION SHALL

BE VERIFIED AND DETERMINED IN FIELD, AND APPROVED

BY THE OWNER.

H. SHOP DRAWINGS

1. ALL EQUIPMENT TO BEAR U.L. LABEL OR CERTIFIED BY

NATIONALLY RECOGNIZED TESTING LABORATORY. SHOP

DRAWINGS MUST BE STAMPED BY THE CONTRACTOR

FOR CONFORMANCE PRIOR TO SUBMITTAL. SUBMIT

SHOP DRAWINGS FOR REVIEW PRIOR TO PURCHASING.

SHOP DRAWINGS ARE REQUIRED FOR ALL PANEL

BOARDS, RECEPTACLES, DISCONNECT SWITCHES,

GENERATOR, ATS, LOAD BANK SWITCHGEAR AND

TRANSFORMERS.

2. SERVICE ENTRANCE EQUIPMENT (NEW SWITCHGEAR

WITH METERING SECTION) SHALL BE SUBMITTED TO SCE

BY THE CONTRACTOR FOR APPROVAL.

I. CONTRACTOR BID

1. CONTRACTOR'S BID SHALL BE BASED ON ALL WORK

SHOWN ON THE PLANS AND AS SPECIFIED. ALL PREMIUM,

TIME COSTS REQUIRED SHALL BE INCLUDED IN THE BID.

ALL WORKS SHALL BE GUARANTEE FOR A PERIOD OF

ONE YEAR. IF CONTRACTOR PROPOSES TO SUBSTITUTE

THE SPECIFIED EQUIPMENT, HE SHALL SUBMIT HIS

REQUEST FOR CONSIDERATION TO THE OWNER AND

ENGINEER PRIOR TO THE BID IN WRITING. NO OBSOLETE

OR OUT OF MANUFACTURING EQUIPMENT SHALL BE

ACCEPTED. ALL SUBSTITUTIONS MUST BE REVIEWED BY

THE ENGINEER IN WRITING. SUCH A REVIEW SHALL NOT

RELIEVE THE CONTRACTOR FROM COMPLYING WITH THE

REQUIREMENTS OF THE DRAWINGS AND SPECIFICATION,

THE CONTRACTOR SHALL BE RESPONSIBLE, AT HIS OWN

EXPENSE, FOR ANY CHANGES RESULTING FROM HIS

PROPOSED SUBSTITUTIONS WHICH AFFECT OTHER

PARTS OF HIS OWN WORK OR THE WORK OF OTHER

CONTRACTORS.

J. "AS-BUILT" DRAWINGS

1. CONTRACTOR SHALL KEEP A SET OF PRINTS WHICH

SHALL BE CORRECTED DAILY TO SHOW EVERY CHANGE

FROM THE ORIGINAL DRAWINGS AND SPECIFICATIONS.

UNDERGROUND RUNS SHALL BE ACCURATELY

DIMENSIONED ON THESE PRINTS (REFERENCED TO

BUILDING WALLS OR COLUMNS). ADDENDA AND CHANGE

ORDERS SHALL ALSO BE INCLUDED ON THESE PRINTS.

DELIVER "AS- BUILT" PRINTS TO OWNER PRIOR TO

ACCEPTANCE OF THE JOB. "AS-BUILT" PRINTS SHALL BE

SIGNED AND DATED BY CONTRACTOR.

2. THESE DRAWINGS SHALL BE SUBMITTED TO THE OWNER

FOR APPROVAL. AFTER APPROVAL, THEY SHALL BECOME

THE PROPERTY OF THE OWNER. FINAL PAYMENT WILL BE

WITHHELD UNTIL RECEIPT OF THE APPROVED

DRAWINGS.

K. DEMOLITION

1. PERFORM ALL DEMOLITION WORK AS NOTED ON THE

DRAWINGS AND/OR AS REQUIRED TO CLEAR THE AREA

FOR THE NEW WORK. DELIVER ALL SALVABLE

EQUIPMENT TO THE OWNER AS DIRECTED.

2. FOR ALL EQUIPMENT TO BE REMOVED, REMOVE ALL

WIRING BACK TO THE POWER SUPPLY OR TO THE LAST

DEVICE TO REMAIN. MAINTAIN CIRCUIT CONTINUITY TO

ALL DEVICES AND EQUIPMENT TO REMAIN. REMOVE ALL

UNUSED CONDUIT AND WIRES.

3. OVERCURRENT PROTECTIVE DEVICES VACATED SHALL

BE LABELED "SPARE". UPDATE ALL PANEL AND

SWITCHBOARD DIRECTORIES TO CLEARLY REFLECT NEW

CONDITIONS.

L. PROTECTION & SAFEGUARDS

1. THE CONTRACTOR SHALL ERECT AND MAINTAIN

SUITABLE BARRIERS, PROTECTIVE DEVICES, LIGHT AND

WARNING SIGNS WHERE REQUIRED FOR THE

PROTECTION OF THE PUBLIC AND EMPLOYEES ABOUT

THE BUILDING. HE SHALL BE FULLY RESPONSIBLE FOR

ANY LOSS OR INJURY TO PERSON OR PROPERTY

RESULTING FROM HIS NEGLECT OF THESE

PRECAUTIONS, HIS OWN CARELESSNESS, OR THE

CARELESSNESS OR NEGLECT OF HIS EMPLOYEES, OR

HIS SUB-CONTRACTOR AND/OR THEIR EMPLOYEES.

M. POWER SHUTDOWN

1. POWER SHUTDOWN WHEN REQUIRED FOR THE

EXECUTION OF NEW WORK SHALL BE DONE AFTER

NORMAL WORKING HOURS, AND SHALL BE PROPERLY

COORDINATED IN ADVANCE. CONTRACTOR SHALL

INCLUDE IN HIS BID ALL COST TO COVER OVERTIME.

2. ANY POWER OUTAGES SHALL BE APPROVED BY THE

USER OF THE FACILITY. A ONE WEEK WRITTEN NOTICE

SHALL BE GIVEN FOR ANY OUTAGE REQUEST.

N. EQUIPMENT AND DEVICES

1. THE ELECTRICAL CONSTRUCTION DRAWINGS PROVIDED

HEREIN ARE DIAGRAMMATIC AND SYMBOLIC IN

REPRESENTATION. LOCATIONS DEPICTED ON THE

DRAWINGS FOR ELECTRICAL EQUIPMENT/DEVICES

(MOTORS, STARTERS, DISCONNECT SWITCHES,

RECEPTACLES, JUNCTION/OUTLET BOXES, CONTROL

SWITCHES, ETC.. ARE ONLY APPROXIMATE.

FURTHERMORE, THE EQUIPMENT/DEVICE DEPICTIONS

ARE GENERALLY SYMBOLIC AND NOT DRAWN TO SCALE.

2. ELECTRICAL DRAWINGS INDICATE NEW MATERIALS AND

NEW WORK, UNLESS OTHERWISE NOTED. EXISTING

ELECTRICAL SYSTEMS ARE NOT SHOWN EXCEPT WHERE

INTERFACE IS REQUIRED.

3. ALL NEW BOXES, PANELS, OUTLET COVERS,

ENCLOSURES, ETC. MOUNTED ON THE EXTERIOR OF ANY

STRUCTURE SHALL BE WEATHERPROOF (NEMA 3R MIN) &

ALSO PAINTED TO MATCH THE EXISTING

BUILDING/STRUCTURE.

4. USE "DYMO" LABEL ON FACE OF RECEPTACLE AND

SWITCH COVER PLATE AND JUNCTION BOXES

INDICATING THE SOURCE PANEL AND CIRCUIT USED.

DYMO LABEL TAPE SHALL MATCH THE COLOR OF THE

COVER PLATE ON RECEPTACLES AND SWITCHES.

5. ALL DEVICE SHALL BE WHITE U.O.N.

O. RACEWAYS AND WIRING

1. ALL CABLE/WIRE, CONDUIT RUNS ARE SHOWN

DIAGRAMMATICALLY & THEY SHALL BE ROUTED TO SUIT

ACTUAL FIELD CONDITIONS, EXCEPT WHERE LOCATION

ARE EXPLICITLY DIMENSIONED ON THE DWGS.

2. CONTRACTOR TO LIMIT THE NUMBER OF 90° BENDS

BETWEEN PULL POINTS TO COMPLY WITH THE

REQUIREMENTS OF THE CALIFORNIA ELECTRICAL

SAFETY ORDERS, THE N.E.C.

3. FLEXIBLE CONDUIT SHALL BE USED ONLY FOR SHORT

CONNECTIONS TO LIGHT FIXTURES OR IN EXISTING

WALLS.

4. WATERTIGHT FLEXIBLE CONDUIT (TYPE "UA") SHALL BE

USED FOR CONNECTIONS TO MOTORS, TRANSFORMERS

OR OTHER EQUIPMENT THAT MAY VIBRATE DURING

OPERATION.

5. MAXIMUM LENGTH OF FLEXIBLE CONDUIT SHALL BE

LIMITED TO 6 FT.

6. PVC COATED RIGID GALVANIZED STEEL (RGS) SHALL BE

USED FOR OUTDOOR WIRING.

7. EMT MAYBE USED INDOOR AND WITH COMPRESSION

COUPLING CONNECTIONS.

8. MINIMUM SIZE OF EMT SHALL BE 3/4".

9. THE MINIMUM SIZE OF CONDUITS INSTALLED BELOW

GRADE SHALL BE 1", UON. THE MINIMUM SIZE OF ALL

HOME RUN CONDUITS SHALL BE 3/4", UON. 1/2" CONDUIT

SHALL ONLY BE ALLOWED AT FINAL INDIVIDUAL

CONNECTIONS EQUIPMENT/DEVICES.

10.ALL CONDUITS PENETRATING SLABS SHALL BE

WATERPROOF.

11.THE CONTRACTOR SHALL BE RESPONSIBLE FOR

PROVIDING ALL SLEEVES & OPENINGS REQUIRED FOR

THE PASSAGE OF ELECTRICAL RACEWAYS EVEN WHEN

THESE OPENINGS OR SLEEVES ARE NOT SPECIFICALLY

SHOWN ON THE DRAWINGS. ALL EXCESS OPENINGS

SHALL BE PROPERLY SEALED WITH EQUIVALENT FIRE

RATING. CONDUITS SHALL NOT REQUIRED SLEEVES IF IT

IS APPROVED FOR THROUGH PENETRANTS.

12.CONDUITS TERMINATED AT PANEL BOARDS, CONTROL

CABINETS, ETC. SHALL BE EQUIPPED WITH GROUNDING

BUSHINGS AND SHALL BE EFFECTIVELY BONDED TO

THEIR SOURCE GROUND BUS.

13.ALL BENDS IN CABLES SHALL BE MADE SO THAT THE

PROTECTIVE COVERING ON THE CABLE WILL NOT BE

INJURED. NO BEND SHALL HAVE A RADIUS LESS THAN

THE MINIMUM RECOMMENDED BY THE CABLE

MANUFACTURER.

P. CONDUCTORS

1. UL LISTED. CONDUCTORS SHALL BE COPPER, 600 VOLT,

"THHN/THWN-2" INSULATION, STRANDED, MINIMUM SIZE

#12 EXCEPT FOR CONTROLS.

CONTRACTOR TO VERIFY ROTATION AND PHASING.

COLOR CODES

NEUTRAL - WHITE

a) 208/120VOLT SYSTEM

PHASE A - BLACK

PHASE B - RED

PHASE C - BLUE

b) 480/277VOLT SYSTEM

PHASE A - BROWN

PHASE B - ORANGE

PHASE C - YELLOW

Q. BOXES

1. OUTLET, JUNCTION AND PULL BOXES SHALL BE SIZED

PER APPLICABLE VERSION OF CALIFORNIA ELECTRICAL

CODE ARTICLE 314, TABLES 314.16 (a) AND (b) AND 214.28.

R. GROUNDING AND BONDING

1. ALL NEW (ADDITIONAL) METALLIC STRUCTURES AND

EQUIPMENT FABRICATED WITH METALLIC MATERIALS

SUCH AS MOTOR FRAMES, ENCLOSURES, CABINETS,

MISC. ELECTRIC EQUIPMENT, METALLIC RACEWAYS,

STAIRS, FENCES & HANDRAILS ETC.. SHALL ALL BE

PERMANENTLY & EFFECTIVELY GROUNDED.

2. ALL ABOVE GROUNDING CONDUCTORS SHALL BE

INSULATED STRANDED SOFT DRAWN COPPER, CLASS B,

UON. THE GROUNDING CONDUCTORS WHEREVER

POSSIBLE, SHALL BE ROUTED BENEATH SLABS,

ATTACHED TO THE BUILDING STEEL, OR RUN IN

RACEWAYS AS SHOWN.

3. CONDUIT RUNS AND EQUIPMENT/DEVICE ENCLOSURES

SHALL BE BONDED TOGETHER TO FORM A CONTINUOUS

ELECTRICAL CONDUCTOR. NON-METALLIC RACEWAYS &

ENCLOSURES SHALL INCLUDE BONDING JUMPERS,

4. ALL SYSTEM GROUNDING CONDUCTORS SHALL BE

COPPER. ALL GROUND CONNECTIONS SHALL BE

ACCESSIBLE AND MADE WITH COPPER ALLOY FITTINGS.

5. A GROUND WIRE IS REQUIRED FOR ALL CONDUITS.

S. FEEDERS AND BRANCH CIRCUITS IDENTIFICATION

1. IDENTIFY FEEDERS WITH THE CORRESPONDING CIRCUIT

DESIGNATION AT THE OVER-CURRENT DEVICE, LOAD

END, AND IN PULL BOXES WITH E-Z CODE OR OTHER

APPROVED WIRE MARKER.

2. IDENTIFY BRANCH CIRCUITS WITH I.D. MARKERS, THE

CORRESPONDING CIRCUIT DESIGNATION AT THE

OVER-CURRENT DEVICE, AT ALL SPLICES, AND IN

JUNCTION BOXES, AND IN OUTLETS. USE PLASTIC

COATED SELF-STICKING MARKERS SUCH AS THOMAS &

BETTS E-Z CODE FOR IDENTIFICATION OF CONDUCTORS.

3. CIRCUIT DESIGNATION MEANS PANEL AND CIRCUIT

NUMBER, I.E. 4ALR-3.

4. ALL EQUIPMENT SHALL BE LABELED WITH PHENOLIC

PERMANENT MARKER ENGRAVED LABEL AND MOUNT

WITH SCREWS. ADHESIVE MOUNTING IS NOT

ACCEPTABLE.

5. LARGER DISTRIBUTION PANELS SHALL HAVE PHENOLIC

NAMEPLATES MADE FOR EACH BREAKER. BLACK

BACKGROUND WITH WHITE LETTERS.

6. CHECK PANEL SCHEDULES IDENTIFICATION FOR

VALIDITY. REIDENTIFY ANY OR ALL CHANGES IN PANEL

ON PANEL SCHEDULE CARD. WHILE PANEL COVER IS

REMOVED TURN OFF ANY SPARE BREAKERS AND VERIFY

SPARES ARE INDICATED ON PANEL SCHEDULE CARD.

T. EXECUTION

1. CAREFULLY PROTECT ALL WALLS, TRIM, FLOORS,

EQUIPMENT, UTILITY LINES AND MATERIALS. WHEN

WORKING ON FINISHED SURFACES, LIMIT DAMAGE TO

THE CONFINED SPACE AS POSSIBLE AND RESTORE TO

THE ORIGINAL CONDITION ALL SURFACES WHICH ARE

DAMAGED BECAUSE OF THE INSTALLATION OF THIS

WORK.

2. EQUIPMENT, MATERIALS AND SUPPLIES REMOVED FOR

PROTECTION SHALL BE REPLACED IN ORIGINAL

LOCATIONS. ANY MATERIALS DAMAGED SHALL BE

REPLACED WITH NEW MATERIALS OF LIKE KIND AND

QUALITY.

3. DO ALL DRILLING, CUTTING, CHANNELING AND PATCHING

REQUIRED TO INSTALL ELECTRICAL WORK, AS INDICATED

OR HEREIN SPECIFIED. ALL HOLES, CURBS, ETC., IN

FLOORS, CEILINGS AND WALLS SHALL BE PATCHED TO

MATCH ADJACENT SURFACE, UNLESS INDICATED

OTHERWISE. PAINT ALL NEW ELECTRICAL RACEWAYS,

CABINETS, ENCLOSURES AND FITTINGS TO MATCH

COLOR OF ADJACENT SURFACES.

4. SEAL ALL PENETRATIONS THROUGH FIRE RATED WALLS,

CEILINGS, FLOORS, ETC., TO MAINTAIN THE FIRE RATING.

FURNISH AND INSTALL FIRE RATED ENCLOSURES FOR

ALL EQUIPMENT PENETRATING INTO FIRE RATED

ENVELOPES, SPACES, ETC.

5. ALL DISCONNECT AND TRANSFORMERS SHALL BE

LABELED WITH PERMANENT ENGRAVED LABELS WITH

PANEL DESIGNATION FED FROM AND ROOM LOCATION.

6. CHECK PANEL SCHEDULES IDENTIFICATION FOR

VALIDITY. REIDENTIFY ANY OR ALL CHANGES IN PANEL

ON PANEL SCHEDULE CARD. WHILE PANEL COVER IS

REMOVED TURN OFF ANY SPARE BREAKERS AND VERIFY

SPARES ARE INDICATED ON PANEL SCHEDULE CARD.

U. MISCELLANEOUS

1. CONTRACTOR SHALL PROVIDE ALL MATERIAL UNLESS

NOTED OTHERWISE IN THE CONTRACT AND/OR

CONSTRUCTION DOCUMENT. ALL MATERIAL SHALL BE

NEW AND NOTED BY UNDERWRITER'S LABORATORIES,

FACTORY MUTUAL, OR TESTED BY THE APPROVED THIRD

PARTY TESTING FACILITY.

2. CONVENIENCE OUTLET RECEPTACLES SHALL BE

INSTALLED AS CLOSE AS POSSIBLE TO LOCATIONS

SHOWN ON PLANS. CONTRACTOR RESPONSIBLE FOR

EXACT LOCATION BASED ON FIELD CONDITIONS.

3. CONTRACTOR SHALL NOT PERFORM ANY WORK UNTIL

HE OR HIS REPRESENTATIVE HAS SIGNED THE

CONTRACT.

4. DURING CONSTRUCTION, DO NOT INTERRUPT OR IMPEDE

OPERATION AND WORK IN ADJACENT AREAS.

5. UPON COMPLETION OF WORK, REPLACE SURFACE

MATERIAL, PAVING AND PAVING BASE, COURSE TO

MATCH ORIGINAL. ALL CONDUIT PENETRATIONS SHALL

BE SEALED WITH AN APPROPRIATE RATED SEALANT.

PENETRATIONS EXPOSED TO WEATHER AND THROUGH

ROOF SHALL BE FLASHED AND CAULKED TO FORM A FIRE

RATED AND WATERTIGHT PENETRATION.

6. UPON COMPLETION OF ALL WORK, THOROUGHLY CLEAN

ALL EQUIPMENT AND DUCTS FROM INSIDE AND OUTSIDE

OF EQUIPMENT. REMOVE ALL TRACES OF SOIL, DUST,

LABELS, GREASE, OIL AND FOREIGN MATERIALS.

CLEANUP AND REMOVE FROM THE PREMISES ALL

DEBRIS AND SURPLUS MATERIAL CAUSED BY THIS

WORK.

7. ALL EXISTING SURFACES DAMAGED BY NEW

CONSTRUCTION, SHALL BE PATCHED, OR REPAINTED TO

MATCH EXISTING CONDITIONS, PAINTED SURFACE SHALL

BE PAINTED FROM BREAK TO BREAK. IT SHALL BE THE

CONTRACTORS RESPONSIBILITY TO PATCH & REPAIR ALL

DAMAGE TO EXISTING SURFACES AND FINISHES

FURTHERMORE, THE AFFECTED AREA(S) OF WORK

SHALL BE REPAIRED TO MATCH THE FINISH THAT WAS

PREVIOUSLY EXISTING, PRIOR TO THE COMMENCEMENT

OF WORK.

8. THE CONTRACTOR SHALL VERIFY ALL LOCATIONS,

WHICH REQUIRE PENETRATIONS, SUCH AS ROOFS,

HAZARDOUS AREAS, MASONRY AND FIRE RATED WALLS,

ETC.. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED

OPENINGS & CORE DRILL AS REQUIRED FOR NEW

ELECTRICAL WORK. THE CONTRACTOR SHALL PATCH &

FIRE STOP (SEAL) ALL PENETRATIONS (BOTH SIDES) PER

SPECIFICATIONS.

9. WHERE THERE IS A CONFLICT BETWEEN THE DRAWINGS

& ANY RELEVANT CODES, THE CODES SHALL GOVERN,

EXCEPT WHERE THE DRAWINGS INDICATE A QUALITY

LEVEL SUPERIOR TO THAT SPECIFIED BY THE CODES.

10.IN THE EVENT OF CONFLICT OR DISCREPANCY IN

DRAWINGS/PLANS, IN SPECIFICATIONS, BETWEEN

DRAWINGS AND SPECIFICATIONS, BETWEEN SITE

CONDITIONS AND DRAWINGS, THE CONTRACTOR SHALL

PROVIDE THE MORE STRINGENT REQUIREMENTS.

W. ACCEPTANCE TESTING AND COMMISSIONING.

1. THE CONTRACTOR SHALL PROVIDE A THIRD PARTY

TESTING

2. CONTRACTOR SHALL PROVIDE DOCUMENTATION THAT

THE CONDUCTOR, SWITCHBOARDS, SWITCHGEAR, AND

DEVICES HAVE BEEN COMMISSIONED AND PASSED THE

ACCEPTANCE TESTING AND READY FOR OPERATION

PRIOR TO HANDOVER TO END USER.

3. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO

REQUEST FROM UTILITY COMPANY THEIR PROTECTION

SETTINGS.

4. PERFORM SHORT CIRCUIT AND COORDINATION STUDY.

SET CIRCUIT BREAKERS AND RELAYS ACCORDING TO

STUDY.

5. PERFORM ARC FLASH STUDY AND PROVIDE LABELS.

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

F

IL

E L \2

-5

C U

P I n te rc o n n e c t, D

S H

-M \C

A D

\2 E S

P E C

S .d w g

D A T E /T

IM

E J a n

:3

P M

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

ELECTRICAL SPECIFICATION NOTES

ELECTRICAL

SPECIFICATION

NOTES

E0.1

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

03/04/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-6278

ISSUE DATE: August 5, 2024

JoEnriqu

OH OH OH OH OH OH

O H

O H

66KV 66KV 66KV 66KV 66KV 66KV

K V

66KV

K V

12K V

DEMOLISH OVERHEAD LINES INCLUDING POLES.

SEE DETAIL E4.0, DET. 5 COORDINATE WITH SCE

(E) 12KV OVERHEAD LINE

(D)66KV POLE

H

H

O H

OH

O H

O H

OH

IM

P E R

IA

L H

W Y

BLOOMFIELD AVENUE BLOOMFIELD AVENUE

COGENERATIONCO-GEN.

TRANSPORTATIONTRANS.

VOCATIONAL REHABILITATION

HOUSEKEEPING

ADMINISTRATION

OFFICE OF STATE ARCHITECT

GARAGE

RESIDENCE NUMBER

EMPLOYEE

BUILDING

OCCUPATIONAL THERAPY

WAREHOUSE

SHELTER

VOC. REHAB.

HSEKP.

ADMIN.

OSA

G R#

EMP.

BLDG.

O.T.

W S

ABBREVIATIONS & SYMBOLS

PATIENT SUPPORT MODULESP.S.M.

10,274 1 0,274

9,0009,000

9,371 9,371

2,695 2,439

10,501

8,200

7,933

8,977

8,977

7,933

8,200

10,501

10,501

8,200

7,933

8,977 10,501

8,200

7,933

8,977

17,235

1 7,235 1 7,235

17,235

(L

RZ

e U)

WATER TANKS

IRRIGATION PUMP HOUSE

WATER SOFTENER BUILDING DOMESTIC PUMP HOUSE

DEVICE

BACKFLOW

COMMINUTOR

BUILDING

CTE CHILLER

P.S.M.

COURT

TENNIS

DOM.IRR.

M

ET

A L

P R

O P E R

T Y

L

IN

E

P R

O P E R

T Y L

IN

E

PROPERTY LINE

FD. SERV. WHSE.

LUMBER SHED

GAS PUMP

EN

G

IN

S

SS

S

S

S

D C

U

TRANS.

G A

R A

G E

PLUMBER

OFFICES

PLANT OP'S.

RECEIVING

STORES /

CAR PORT

CARPENTER

PA

IN

T

MASON

ST

O

R

SH

EE

T

EL

EC

T.

W

EL

D

O .T

O .T

O.T. SOUTH

O.T. NORTH

EM

P.

B

LD

G . 4

EMP. BLDG. 3

R

EC

YC

LI

N G

S

S

G

#18

G

#19

#16

G

#14

#13

313/315

G

G

EM

P.

B

LD

G . 2

EMP. BLDG. 1

#1

#15 S

LA

U

N D

R Y

KITCHEN

OFFICE

TRUST

S

201/203

2/

9/

STORAGE

CHILL WATERBARBER/

W3

COOLING TOWER

#6

#8#7

HSEKP. WHSE 1

PROPERTY

HALL

JAMES

306-308

HOUSE

BOILER

E1

309-31 1 (CPS)

W2NORTH YARD

PCB SHED

HOMES

#10

G

G

G

#1 1

#12

#20

PUMP HOUSE

(ABANDONED)

C O

N D

O M

IN

IU

M C

O M

PL

EX

FASHION CNT.

STORAGE

PROPERTY LINE

PROPERTY LINE

P R

O P E R

T Y L

IN

E

PROPERTY LINE

P R

O P E R

T Y L

IN

E

OASIS

P.S.M.

#17

VOLLEYBALL

BASKETBALL

G R

A

SS

A R

EA

SALLYPORT

VISITOR CENTER

ADMIN.

CLINICAL

BLDG.

C

EN

TE

R

STUDIO

ART

WAREHOUSE

REHAB.

HOMES

HOMES

CENTER

305/307

BIRCH GROVE

CEDAR STREET

ELM STREET

POST

WELLNESS

G R

N D

LOCK

WASH.

WAREHOUSE

KITCHEN

CENTRAL

(Omitted)

CLINIC

D-57 (USSeU)

BEAUTY SHOP

C

EN

TE

R

FA

SH

IO

N

FSHN. CNT.

STORE

RELIGIOUS

CENTER

NORWALK BOULEVARD

80 Stalls

S ta lls

1 8 Stalls

58 Stalls

S ta lls

S

CO-GEN.

S.N.F.

TRAILER

10110

HOSP.

OFFICE

POLICE

407/415

405/413

CTE

BLDG.

401/409

408/416

406/414

402/410

417 419

418 420

YOUTH

ADMINISTRATION

BUILDING

CTW

BLDG.

A

A

A

BLDG.

S.N.F.

TRUST

OFFICE

BLDG.

LIBRARY

404/412

403/411

/2

(D)12KV POLE

OVERALL ELECTRICAL SITE PLAN

TRUE

NORTH

PLAN

NORTH1

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

F

IL

E L \2

-5

C U P I n te rc o n n e c t, D

S H -M

\C A D

\2 E O

V E R A L L S

IT

E P

L A N .d w g

D A T E /T

IM

E J a n

:3

P M

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

KEYNOTES:

SEE E1.1, E1.2, & E1.3 FOR BUILDING & SUBSTATION LAYOUT SCOPE

OF WORK.

OVERALL

ELECTRICAL

SITE PLAN

E1.0

SCALE: 0 40020 FEET200

1" = 200'

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

03/04/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-6278

ISSUE DATE: August 5, 2024

JoEnriqu

66/12KV ELECTRICAL SUBSTATION

TO BE DEMOLISHED BY SOUTHERN

CALIFORNIA EDISON (SCE)

SEE E4.0 DETAIL 6

(E)

COGENERATION

BUILDING

TRANSFORMER

PIPE

BRIDGE

BALSAM STREET

(E) UNDERGROUND

CONDUIT BETWEEN

12KV SWITCHGEAR

AND OUTDOOR

SUB-STATION

PROTECT (E)GROUND

OF TRANSFORMER "A"

FOR FUTURE USE

(E) UNDERGROUND

GROUNDING

(E) CHW SUPPLY AND RETURN

PIPING AND FUEL PIPE

UNDERGROUND

TUNNEL

(D)SCE TRANSFORMER

(E) SS

(D)BUILDING

(ELECTRIC

GEAR)

EXISTING CONCRETE SLAB

OVER UNDERGROUND #2 FUEL

OIL STORAGE TANK

(E) MANHOLE "MHAA"

(E)12KV OVERHEAD LINE

(D)12KV POLE WITH AIR

BREAK SWITCH, REFER

TO SCE DRAWING

(D)SCE PAD-MOUNTED

GEAR, PMU-5

(E) HV2-1, HV1-1, HV3-1, HV4-1

(E) HV1-15, CK-2, HV2-2, HV1-2,

HV3-2, HV4-2

(E) CK-3, F4-2

(E)CK-1 AND FUTURE CONDUITS

PROTECT IN PLACE

(E)

MANHOLE

"MHA"

(E)CUP 200KW EMERGENCY

GENERATOR LOCATION

(E)A/G PULLBOX2

TR-A

TR-3TR-2

(E)GROUNDING

CONNECTION NOT

VERIFIED (TYP)

SCALE

1" = 150'

75 0 15 300FEET150

ELECTRICAL SITE PLAN - DEMOLITION PLAN

TRUE

NORTH

PLAN

NORTH1

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

F

IL

E L \2

-5

C U

P I n te rc o n n e c t, D

S H

-M \C

A D \2

E E

L E C

T R

IC

A L S

IT

E P

L A N

.d w g

D A T E /T

IM

E J a n

:3

P M

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

SEE ENLARGED PLAN ON

SHEET E2.0 DETAIL 1 & 2

COORDINATE WITH SCE FOR THE DEMOLITION OF EXISTING GUY.

COORDINATE WITH SCE FOR THE DEMOLITION OF (E) SCE

EQUIPMENT. REFER TO SCE DRAWING. PROVIDE COVER PLATE

ON THE OPENINGS AFTER THE REMOVAL OF EQUIPMENT.

DEMOLISHED EXISTING SWITCHGEAR BUILDING INCLUDING THE

ABANDONED SWITCHGEAR EQUIPMENT.

(E)MV PULLBOX TO PROTECT AND REMAIN IN PLACE.

DEMO WORK KEYNOTES:

ELECTRICAL

SITE PLAN

DEMOTION PLAN

E1.1

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

03/04/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-6278

ISSUE DATE: August 5, 2024

JoEnriqu

(E) SS

EXISTING CONCRETE SLAB OVER

UNDERGROUND #2 FUEL OIL

STORAGE TANK

BALSAM STREET

G

(E) MANHOLE "MHAA"

12KV OVERHEAD LINE

(E)UNDERGROUND CONDUIT

BETWEEN 12KV SWITCHGEAR

AND OUTDOOR SUB-STATION

(E) UNDERGROUND CONDUIT

(E) HV1-15, CK-2, HV2-2, HV1-2, HV3-2, HV4-2

(E) CK-3, F4-2

(E)CK-1 AND SPARE CONDUITS.

ROUTING ARE NOT VERIFIED.

(E)MANHOLE "MHA"

(E) CHW SUPPLY AND RETURN

PIPING AND FUEL PIPE

UNDERGROUND

TUNNEL

(TYP)

(E) TUNNEL EXHAUST FAN TO REMAIN

(E) 5KV, NEMA 3R

SPLICE BOX TO

REMAIN

(E) UNDERGROUND

CONDUIT

(N)(4)4"C - ABOVEGROUND CONDUITS

5 6

"MHAA-1"

4'x6'-6"x5'-6"

13 14

(8)5"C

(E)75KVA TRANSFORMER

(E)MV PB

(E)MCC

(E)MV DISCONNECT SWITCHES

(E)TRANSFORMER "TGB"

(E)45KVA TRANSFORMER

(E)LIGHTING PANEL "A"

(E)PANEL "B"

(E)BATTERY &

BATTERY CHARGER

(E)LOCAL DIST. PANEL (LDP)

(E)ALARMTRONICS

FUTURE PARALLELING

SWITCHGEAR WITH MASTER

CONTROLLER(4) 5"C

(4)2"C (2)2"C

(2)2"C3

3 3

Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

F

IL

E L \2

-5

C U

P I n te rc o n n e c t, D

S H -M

\C A D

\2 E E

L E C T R

IC

A L S

IT

E P

L A N

N

E W

W O

R K E N

L A R

G E D .d w g

D A T E /T

IM

E J a n

:4

P M

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

KEYNOTES:

GENERAL NOTES: (APPLICABLE TO EXTERIOR WORK)

1. THE EXISTING CONDITIONS OF BELOW GROUND PIPING AND UTILITIES SUCH AS GAS

MAINS, WATER MAINS, SANITARY SEWERS, POWER AND COMMUNICATIONS CONDUITS

AND OTHER UTILITIES ARE TAKEN FROM EXISTING RECORD DRAWINGS AND VERIFIED

BY FIELD OBSERVATION. THE LOCATION OF THESE UTILITIES IS APPROXIMATE ONLY.

IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY THE EXACT

LOCATION AND DEPTH OF BELOW GROUND PIPING AND UTILITIES IN THE IMMEDIATE

VICINITY OF SUBSURFACE WORK, WHETHER SHOWN ON THE DRAWING OR NOT.

CONTRACTOR SHALL RETAIN THE SERVICES OF AN UNDERGROUND UTILITY

LOCATING COMPANY. UTILIZE GROUND PENETRATING RADAR AND OTHER UTILITY

LOCATING DEVICES TO DETERMINE THE LOCATION AND DEPTH OF ALL

UNDERGROUND IMPROVEMENTS WITHIN APPROXIMATELY 20' OF ALL NEW WORK.

PAINT MARK ALL UTILITY LOCATIONS ON THE PAVEMENT SURFACE. THIS TASK SHALL

BE COMPLETED PRIOR TO ANY EXCAVATING.

2. PRIOR TO STARTING TRENCHING, POTHOLE TO VERIFY THE DEPTH OF EXISTING

PIPES WHICH ARE TO JOIN OR CROSS NEW PIPING OR CONDUITS. ADJUST DEPTH OF

NEW PIPE CONDUIT AS REQUIRED TO CROSS EXISTING UTILITIES. NOTIFY ENGINEER

OF ANY DISCREPANCIES OR INTERFERENCES PRIOR TO LAYING ANY PIPE.

3. PRIOR TO STARTING TRENCHING, VERIFY LOCATION AND WORKING CONDITION OF

THE ASSOCIATED WATER VALVES WHICH NEED TO BE EXERCISED DUE TO THE

WATER SHUTDOWN ASSOCIATED WITH THE SCOPE OF WORK. NOTIFY ENGINEER IF

THERE ARE ANY DISCREPANCIES WITH THE VALVES.

4. EXISTING UNDERGROUND UTILITIES SHOWN HEREIN HAVE BEEN LOCATED FROM

VARIOUS SOURCES OF VARYING RELIABILITY, INCLUDING SURFACE EVIDENCE AND

AVAILABLE RECORDS, AND ARE SHOWN FOR INFORMATION ONLY. THE CONTRACTOR

IS RESPONSIBLE FOR DETERMINING THE EXACT LOCATION OF ALL EXISTING UTILITIES

AND FOR THE PROTECTION OF AND REPAIR OF DAMAGE TO THEM.

5. ALL WORK RELATED TO SCE EQUIPMENT AND UNDERGROUND WORK SHALL BE

INSTALLED IN ACCORDANCE WITH SCE ESR AND UGS MANUAL. IT SHOULD BE

ACCEPTED BY SCE INSPECTION TEAM. SEE ATTACHED SCE DRAWING FOR

ADDITIONAL INFORMATION.

6. CONTACT DIG ALERT (811) 48 HOURS PRIOR TO EXCAVATION.

SCALE

TRUE

NORTH

PLAN

NORTH1

3,750KVA TRANSFORMER PAD, SEE DETAIL 6/E4.1

PROVIDE ONE ROUND OF SLACK CONDUCTOR.

REMOVE AND REPLACE AC PAVING FOR ELECTRICAL CONDUIT TRENCH.

SEE DETAIL 2/E4.0, 2/E4.1

VACUUM FAULT INTERRUPTER (VFI) EQUIPMENT PAD, SEE DETAIL 7/E4.1.

BYPASS EQUIPMENT PAD, SEE DETAIL 5/E4.1.

3-WAY RAG EQUIPMENT PAD, SEE DETAIL 5/E4.1.

CAPACITOR EQUIPMENT PAD, SEE DETAIL 8/E4.1.

(E) EQUIPMENT PAD TO REMAIN. COVER TRENCH SIMILAR TO EXISTING

COVER PLATE ONCE THE REMOVAL OF (E)EQUIPMENT IS COMPLETED.

(E)SCE 12KV UNDERGROUND CONDUIT NOT VERIFIED. CONDUIT SHALL

BE ABANDONED IN PLACE ONCE THE UPGRADE IS COMPLETED.

NEW 5KV, 1200A, 3Ø, SCE METERING EQUIPMENT SHALL BE IN

COMPLIANCE WITH ESR REQUIREMENT. SUBMIT SHOP DRAWING TO SCE

FOR APPROVAL. SEE DETAIL #2, E4.2 FOR EQUIPMENT PAD DETAIL.

18" X 18" X 6" NEMA 3R PULL BOX (LOW VOLTAGE - POWER).

18" X 18" X 6" NEMA 3R PULL BOX (SIGNAL).

1 1/2"Ø AND 2"Ø PVC (POWER), SEE DETAIL 5/E4.2.

(2)2"Ø PVC (SIGNAL), SEE DETAIL 5/E4.2.

SEE DETAIL 2/E4.2 EXCEPT CONDUIT IS 4" DIAMETER.

(E)SCE 5KV UNDERGROUND CONDUITS AND THE ROUTING ARE NOT

VERIFIED. CONDUITS SHALL BE PLUG AND ABANDONED IN PLACE ONCE

THE UPGRADE IS COMPLETED.

(1)5"C, SEE DETAIL 4/E4.2

(2)5"C, SEE DETAIL 9/E4.2

(4)5"C, SEE DETAIL 8/E4.2

24"D X 36"W X 48"H HV PULL BOX

REPAIR DAMAGE ASPHALT WALKWAY DUE TO NEW UNDERGROUND

CONDUIT. EXTEND WIDTH OF ASPHALT WALKWAY FOR 48".

REFER WITH SCE DRAWING FOR ADDITIONAL INFORMATION ON POLE

RISER REQUIREMENT.

12" X 22" UNDERGROUND PULLBOX, SEE DETAIL 4/E4.3. PROVISION FOR

FUTURE GENERATOR AREA INTERFACE.

REMOVE AND REPLACE AC PAVING FOR ELECTRICAL CONDUIT TRENCH.

SEE DETAIL 2/E4.0 BUT 8 CONDUITS.

SEE DETAIL 8/E4.2 BUT 10 CONDUITS

REMOVABLE BOLLARD, TYPICAL OF 2, SEE DETAIL 2/E4.3

FIXED BOLLARD, DETAIL 4/E4.1, NOT TO EXCEED 4'-6" APART, TYPICAL.

REMOVE AND REPLACE AC PAVING FOR ELECTRICAL CONDUIT TRENCH.

FUTURE GENERATOR POWER CONDUITS, SEE DETAIL 2/E4.0.

0 FEET8

1/8" = 1'-0"

4 16

ELECTRICAL SITE

PLAN - ENLARGED

E1.2

ELECTRICAL SITE PLAN - ENLARGED

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

03/04/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-6278

ISSUE DATE: August 5, 2024

JoEnriqu

(E) SS

(E)

COGENERATION

BUILDING

EXISTING CONCRETE SLAB OVER

UNDERGROUND #2 FUEL OIL

STORAGE TANK

TRANSFORMER

PIPE

BRIDGE

BALSAM STREET

G

(E) MANHOLE "MHAA"

R=5'-0" (TYP)

"MHAA-2"

DETAIL#1/E4.0

(4)5"C

12KV OVERHEAD LINE

G10D

(E)UNDERGROUND CONDUIT

BETWEEN 12KV

SWITCHGEAR AND OUTDOOR

SUB-STATION

VERIFY ON SITE THE DEPTH

AND ROUTING

(E) GROUND OF

TRANSFORMER "A"

TO RE-USE

(E)UNDERGROUND

GROUNDING

(E) UNDERGROUND CONDUIT(E)HV1-15, CK-2, HV2-2,

HV1-2, HV3-2, HV4-2

(E)CK-3, F4-2

(E)MV PB

(E)MANHOLE "MHA"

(E) CHW SUPPLY AND RETURN

PIPING AND FUEL PIPE

UNDERGROUND

TUNNEL

"5

(E)TUNNEL EXHAUST FAN TO REMAIN

(E)5KV, NEMA

3R SPLICE

BOX TO

REMAIN

(E)UNDERGROUND

CONDUIT

"MHAA-1"

DETAIL#5/E4.3

3'-0"

(8)5"C

5 6

1 8

4'-0"

29 (TYP.)

FUTURE

ABOVEGROUND

TANK

FUEL

POLISHER

FUTURE

FUTURE

DAYTANK

NGR NGR

FUTURE PARALLELING

SWITCHGEAR WITH MASTER

CONTROLLER

2,500KW

FUTURE

2,500KW

FUTURE

(4)5"C

FUTURE GENERATOR

AREA NOT PART OF THIS

CONTRACT

11'-8"

5'-9"

4'-7"

4'-0"

SCALE

1" = 150'

75 0 15 300FEET150

ELECTRICAL SITE PLAN - UNDERGROUND NEW WORK

TRUE

NORTH

PLAN

NORTH1 Checked

Vault File Number

Project Number

Reference North Sheet Scale

Sheet Number

Designed

Sheet Title

Supervisor

Issue Date

Drawn

Project

Description

No.

Date Issue

JCCA #: 23793-5

00000000000XXXX

METROPOLITAN STATE HOSPITAL

11401 BLOOMFIELD AVENUE

NORWALK, CALIFORNIA 90650

DEPARTMENT OF

STATE HOSPITALS

(DSH)

AS SHOWN

DSA STAMP

DSH-M CUP

INTERCONNECT

DSH

01/12/2024

SA

F

IL

E L \2

-5

C U

P I n te rc o n n e c t, D

S H

-M \C

A D \2

E E

L E C

T R

IC

A L S

IT

E P

L A N

N

E W

W O

R K .d w g

D A T E /T

IM

E J a n

:4

P M

JCCA

V2 PLAN CHECK SUBMITTAL

Client Agency

DEPARTMENT OF STATE HOSPITALS

385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501

P: 310.212.7644 F:310.212.5272I

HJL ZML RN

SEE ENLARGED PLAN ON

SHEET DETAIL 3/E2.0

SEE ENLARGED PLAN ON

SHEET E2.0 DETAIL 4 & 5.

SEE ENLARGED PLAN ON

SHEET DETAIL 1 & 2/E2.0

KEYNOTES:

3,750KVA TRANSFORMER PAD, SEE DETAIL 6/E4.1.

PROVIDE ONE ROUND OF SLACK CONDUCTOR.

REMOVE AND REPLACE AC PAVING FOR ELECTRICAL

CONDUIT TRENCH. SEE DETAIL 2/E4.0, 2/E4.1.

VACUUM FAULT INTERRUPTER EQUIPMENT PAD, SEE DETAIL

7/E4.1

BYPASS EQUIPMENT PAD, SEE DETAIL 5/E4.1

3-WAY RAG EQUIPMENT PAD, SEE DETAIL 5/E4.1

CAPACITOR EQUIPMENT PAD, SEE DETAIL 8/E4.1

(E)EQUIPMENT PAD TO REMAIN. COVER TRENCH SIMILAR TO

EXISTING COVER PLATE ONCE THE REMOVAL OF

(E)EQUIPMENT IS COMPLETED.

GROUNDING TEST WELL, SEE DETAIL 4/E4.0.

#4/0 BARE COPPER CONDUCTOR BURIED 48" BELOW FINISH

GRADE.

5/8"Ø X 8' GROUNDING ROD, SEE DETAIL 4/E4.0 WITHOUT TEST

WELL

CONNECTION TO REBARS AND MAIN GROUNDING SHALL BE

BY EXOTHERMIC WELDING, USE #2/0 BARE COPPER WIRE

E1.3

ELECTRICAL

SITE PLAN -

UNDERGROUND

NEW WORK

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

03/04/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

23-6278

ISSUE DATE: August 5, 2024

JoEnriqu

DEMOLISH POWER AND CONTROL CONDUCTOR

FROM 12KV SWITCHGEAR. CONDUIT SHALL BE

PLUG & FLUSH IN CONCRETE PAD.

(E) GROUNDING

DEMOLISH TRANSFORMER

TR-A…

This is the start of the file's text. The full file is on GovTribe.