13292_-_Approved_Drawings_with_Issue_Date_R2.pdf
PDF 16 MB Posted
- Attached to
- CONTRACT NUMBER: 23-203110, DSH CENTRAL UTILITY PLANT INTERCONNECT, PROJECT NUMBER: 13292
- Solicitation number
- 0000032336
- Issued by
- Los Angeles County, California
About this file
This document is an advertisement for bids for the Central Utility Plant Interconnect project at the Department of State Hospitals (DSH) Metropolitan State Hospital in Norwalk, Los Angeles County, California. The project involves the demolition of an existing 66kV outdoor substation and 12kV switchgear, and the installation of new 5kV switchgear, a battery system, and related electrical infrastructure. The bid is being advertised by the California Department of General Services (DGS) Real Estate Services Division, with a bid due date of September 5, 2024 and a public bid opening on September 6, 2024. A mandatory pre-bid site inspection is scheduled for August 21, 2024. The project has an estimated cost of $2,064,800 and a contract term of 909 calendar days.
The project requires a contractor's license classification of C-10 or B. Bidders must also provide copies of valid Certificates of Reported Compliance for any fleet vehicles used on the project that are subject to the California Air Resources Board In-Use Off-Road Diesel Fueled Fleet Regulations. The contract will require payment and performance bonds, each in the amount of 100 percent of the contract price. The project includes Disabled Veteran Business Enterprise (DVBE) participation requirements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
11401 BLOOMFIELD AVENUE, NORWALK, CALIFORNIA 90650
PROJECT ADDRESS :
PREPARED FOR:
DEPARTMENT OF STATE HOSPITALS
DEMOLISH THE EXISTING 66KV OUTDOOR SUBSTATION INCLUDING ALL
ANCILLARIES AND THE 12KV SWITCHGEAR INSIDE THE CO-GENERATION PLANT.
PROVIDE NEW 5KV SWITCHGEAR AND UTILITY METERING SECTION. NEW 5KV
SWITCHGEAR SHALL HAVE PROVISION FOR FUTURE AUTOMATION AND CONTROLS.
PROVIDE BATTERY, BATTERY CHARGER, ENCLOSURE, AND BATTERY
CALCULATION.
PROVIDE FROM SPARE CIRCUIT BREAKER OF NEW SWITCHGEAR TEMPORARY
POWER SUPPLY TO FEED THE EXISTING "MCC-A" LOCATED IN CO-GEN BUILDING
WHILE THE NEW FEED IS ON CONSTRUCTION.
PROVIDE EQUIPMENT PAD FOR SCE EQUIPMENT AND NEW 5KV SWITCHGEAR
EQUIPMENT, AND UNDERGROUND CONDUIT.
DEMOLISH THE EXISTING TRANSFORMER "A" LOCATED OUTDOOR AND INTERCEPT
THE EXISTING PATHWAY AND PROVIDE NEW 5KV CONDUCTOR TO RE-FEED THE
EXISTING 5KV "MCC-A".
PROVIDE METHODS AND SCHEDULE OF SHUTDOWN TO DSH- METROPOLITAN
STATE HOSPITAL (MSH) FOR APPROVAL. THE SCHEDULE OF SHUTDOWN SHALL
HAVE MINIMAL IMPACT TO THE OPERATION OF THE FACILITY.
1. 2022 BUILDING STANDARDS ADMINISTRATIVE CODE, TITLE 24 C.C.R.
2. 2022 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 C.C.R.
3. 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R.
4. 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R.
5. 2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R.
6. 2022 CALIFORNIA ENERGY CODE (CEC), PART 6, TITLE 24 C.C.R.
7. 2022 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R.
8. 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN), PART 11,
TITLE 24 C.C.R.
9. 2022 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R.
10. TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.
11. HCAI/OSHPD LEVEL 5 - ACUTE PSYCHIATRIC HOSPITAL
N N
NOT TO SCALEN NOT TO SCALE
NOT TO SCALE
Imperial Hwy
NORWALK
Bloom field Ave
Norwalk Blvd
Telegraph Rd.
Studebaker Rd
Florence Ave. Telegraph Rd.
Rosecrans Ave.
SANTA ANA FW
Y N
Pioneer Blvd
G reenstone Ave
Firestone Blvd
NORWALK
STA FE
SPRING
WHITTIERBELL
DOWNEY
BELLFLOWER
GARDENS
PROJECT
LOCATION
PROJECT
LOCATION
SCOPE OF WORKAPPLICABLE CODES
SITE MAP
PROJECT INFORMATION
LOCATION MAP VICINITY MAP
DSH - METROPOLITAN
CUP INTERCONNECT - CENTRAL PLANT
PROJECT LOCATION
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
DateIssue
JCCA #: 23793-5
00000000000XXXX
METROPOLITAN STATE HOSPITAL
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
DSH-M CUP
INTERCONNECT
DSH
01/12/2024
SA
FI
LE
: L :\2
3\
3-
C U
P In te rc on ne ct , D
SH
-M
\C
AD
\2
5_
T1
C O
VE
R
S H
EE
T
- C
EN
TR
AL
P
LA
N T.
dw g
D
AT
E/
TI
M E:
Au g
, 0 4:
PM
JCCA
V2 PLAN CHECK SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
HJL ZML RN
PROJECT SUMMARY
THE PROJECT CONSISTS OF THE INSTALLATION OF AN ELECTRICAL INTERCONNECT
TO PROVIDE POWER TO CENTRAL UTILITY PLANT (CUP). THE CUP CURRENTLY
UTILIZES A 66KV SUPPLY FROM SOUTHERN CALIFORNIA EDISON. DSH RECENTLY
ACQUIRED THE CUP FROM PREVIOUS LEASE AND IS OPERATING THE CUP ON A
LIMITED BASIS. DSH-METROPOLITAN DOES NOT PLAN TO GENERATING ELECTRICITY
NOR SEND POWER TO THE GRID, THERE IS NO LONGER ANY NEED FOR THE 66KV
SUPPLY NOR SOUTHERN CALIFORNIA EDISON SIGGEN SUBSTATION.
DEPARTMENT OF STATE HOSPITALS
11401 South Bloomfield Avenue Norwalk, California 90650
JOSHUA KAISER
Chief Construction Officer
(916) 248-0015 Email: joshua.kaiser@dsh.ca.gov.
BRIAN HUDSON
DSH Overall CM Lead
(682) 777-0906 Email: Brian.Hudson@dsh.ca.gov.
ALEX VAN ELDEN
(949) 391-5066 Email: Alexander.VanElden@dsh.ca.gov.
METROPOLITAN STATE HOSPITAL
11401 BLOOMFIELD AVENUE, NORWALK,
CALIFORNIA 90650 LOS ANGELES COUNTY
TITLE SHEET,
APPLICABLE CODES
AND SCOPE OF WORK
T1.0
OSFM PERMIT#: 23-6278
HCAI COMPLIANCE
NEW EQUIPMENT SHALL COMPLY WITH HCAI REQUIREMENT.
METAL CLAD SWITCHGEAR OSP-0046
METAL ENCLOSED SWITCHGEAR OSP-0037
BATTERY CHARGER OSP-0131
BATTERY RACK OSP-0264
PANG HER
Assoc. Construction Analyst
(916) 915-8293 Email: Pang.Her@dsh.ca.gov.
PAUL SMITH
Chief of Plant Operations
(562) 651-4376 EXT. 8094
Cell: (562) 292-4755 Email: Paul.Smith@dsh.ca.gov.
NATALIE GARCIA
Assistant Hospital Administrator
(562) 521-1417 Main Office: (562) 651-4376 Email: Natalie.Garcia@dsh.ca.gov.
J.C. Chang & Associates, Inc. Engineers, Architects and Planners 385 Van Ness Way, Suite 208 Torrance, California 90501
(310) 212-7644
PREPARED BY:
(REFER TO OSFM PERMIT#: 24-0864 FOR SWITCHGEAR BUILDING)
1 08/05/24 OSHPD AND OSP#
ISSUE DATE: August 5, 2024
AREA OF WORK - CUP BUILDING
IM
P E R
IA
L H
W Y
BLOOMFIELD AVENUE BLOOMFIELD AVENUE
COGENERATIONCO-GEN.
TRANSPORTATIONTRANS.
VOCATIONAL REHABILITATION
HOUSEKEEPING
ADMINISTRATION
OFFICE OF STATE ARCHITECT
GARAGE
RESIDENCE NUMBER
EMPLOYEE
BUILDING
OCCUPATIONAL THERAPY
WAREHOUSE
SHELTER
VOC. REHAB.
HSEKP.
ADMIN.
OSA
G R#
EMP.
BLDG.
O.T.
W S
ABBREVIATIONS & SYMBOLS
PATIENT SUPPORT MODULESP.S.M.
10,274 10,274
9,0009,000
9,371 9,371
2,695 2,439
10,501
8,200
7,933
8,977
8,977
7,933
8,200
10,501
10,501
8,200
7,933
8,977 10,501
8,200
7,933
8,977
17,235
17,235 17,235
17,235
(L
RZ
e U)
WATER TANKS
IRRIGATION PUMP HOUSE
WATER SOFTENER BUILDING DOMESTIC PUMP HOUSE
DEVICE
BACKFLOW
COMMINUTOR
BUILDING
CTE CHILLER
P.S.M.
COURT
TENNIS
DOM.IRR.
M
ET
A L
P R
O P E R
T Y
L
IN
E
P R
O P E R
T Y
L
IN
E
PROPERTY LINE
FD. SERV. WHSE.
LUMBER SHED
GAS PUMP
EN
G
IN
S
SS
S
S
S
D C
U
TRANS.
G A
R A
G E
PLUMBER
OFFICES
PLANT OP'S.
RECEIVING
STORES /
CAR PORT
CARPENTER
PA
IN
T
MASON
ST
O
R
SH
EE
T
EL
EC
T.
W
EL
D
O .T
O .T
O.T. SOUTH
O.T. NORTH
EM
P.
B
LD
G . 4
EMP. BLDG. 3
R
EC
YC
LI
N G
S
S
G
#18
G
#19
#16
G
#14
#13
313/315
G
G
EM
P.
B
LD
G . 2
EMP. BLDG. 1
#1
#15 S
LA
U
N D
R Y
KITCHEN
OFFICE
TRUST
S
201/203
2/
5/
0/
9/
3/
STORAGE
CHILL WATERBARBER/
W3
COOLING TOWER
#6
#8#7
HSEKP. WHSE 1
PROPERTY
HALL
JAMES
306-308
HOUSE
BOILER
E1
309-311 (CPS)
W2NORTH YARD
PCB SHED
HOMES
#10
G
G
G
#11
#12
#20
PUMP HOUSE
(ABANDONED)
C O
N D
O M
IN
IU
M C
O M
PL
EX
FASHION CNT.
STORAGE
PROPERTY LINE
PROPERTY LINE
P R
O P E R
T Y
L
IN
E
PROPERTY LINE
P R
O P E R
T Y
L
IN
E
OASIS
P.S.M.
#17
VOLLEYBALL
BASKETBALL
G R
A
SS
A R
EA
SALLYPORT
VISITOR CENTER
ADMIN.
CLINICAL
BLDG.
C
EN
TE
R
STUDIO
ART
WAREHOUSE
REHAB.
HOMES
HOMES
CENTER
305/307
BIRCH GROVE
CEDAR STREET
ELM STREET
POST
WELLNESS
G R
N D
LOCK
WASH.
WAREHOUSE
KITCHEN
CENTRAL
(Omitted)
CLINIC
D-57 (USSeU)
BEAUTY SHOP
C
EN
TE
R
FA
SH
IO
N
FSHN. CNT.
STORE
RELIGIOUS
CENTER
NORWALK BOULEVARD
80 Stalls
S ta lls
1 8 Stalls
58 Stalls
S ta lls
S ta lls
#5
BUILDING
CO-GEN.
S.N.F.
TRAILER
10110
HOSP.
OFFICE
POLICE
407/415
405/413
CTE
BLDG.
401/409
408/416
406/414
402/410
417 419
418 420
YOUTH
ADMINISTRATION
BUILDING
CTW
BLDG.
A
A
A
BLDG.
S.N.F.
TRUST
OFFICE
BLDG.
LIBRARY
404/412
403/411
/2
P.S.M.
AREA OF WORK - SWITCHGEAR BUILDING
MAIN ENTRANCE TO SITE
258'-5"
297'-0"
AREA OF WORK - EXTERIOR
SCALE: 1" = 200'
FIRE ACCESS SITE
PLAN
T2.0
FIRE ACCESS SITE PLAN
TRUE
NORTH
PLAN
NORTH1
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 23793-5
00000000000XXXX
METROPOLITAN STATE HOSPITAL
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
DSH-M CUP
INTERCONNECT
DSH
01/12/2024
SA
F
IL
E L \2
-5
C U
P I n te rc o n n e c t, D
S H
-M \C
A D \2
T F
IR
E A
C C E S S S
IT
E P
L A N
.d w g
D A T E /T
IM
E J a n
:2
P M
JCCA
V2 PLAN CHECK SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
HJL ZML RN
LEGEND
FIRE ACCESS LANE
FIRE HYDRANT
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-6278 l l
EXISTING CONCRETE SLAB
OVER UNDERGROUND #2
FUEL OIL STORAGE TANK
(E) MANHOLE "MHAA"
SWITCHGEAR ROOM
1,528 SF
U OCCUPANCY
OL 300 = 6 OCC
BOLLARD (TYP)
(E) TUNNEL EXHAUST FAN TO REMAIN
BALSAM STREET
GENERATOR ROOM
1,528 SF
U OCCUPANCY
OL 300 = 6 OCC
T Y P
T Y P
30'-0" TYP.
30'-0" TYP.
105'-7"
/1
51'-0"
20'-4"
IMAGINARY PL
BETWEEN BUILDINGS
36'-7"
SWITCHGEAR
BUILDING
CODE ANALYSES
FLOOR PLAN
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 23793-5
00000000000XXXX
METROPOLITAN STATE HOSPITAL
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
DSH-M CUP
INTERCONNECT
DSH
01/12/2024
SA
F
IL
E L \2
-5
C U
P I n te rc o n n e c t, D
S H
-M \C
A D \2
T S
W
IT
C H
G E A R
B U
IL
D
IN
G
C O
D E A
N A L Y S
IS
.d w g
D A T E /T
IM
E J a n
:3
P M
JCCA
V2 PLAN CHECK SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
HJL ZML RN
CODE ANALYSES:
SCALE
SWITCHGEAR BUILDING CODE ANALYSES FLOOR PLAN
TRUE
NORTH
PLAN
NORTH1
EXISTING BUILDING TYPE: II-B (8" CMU BLOCK WALLS WITH STEEL DECK/ROOF)
OCCUPANCY: F-1 OCCUPANCY
HEIGHT: EXISTING 24' AFG
SPRINKLERED: NO
NUMBER OF STORIES: 1
PER CHAPTER 5 CBC
II-B/F-1 OCC NON SPRINKLERED 15,500 SF ALLOWED > 2,964 SF OK
II-B/F-1 OCC NON SPRINKLERED 2 STORIES (55 FEET) ALLOWED > 1 STORY (24 FEET) OK
PER CHAPTER 6 CBC
II-B BEARING WALL: 0 RATING REQUIRED = OK
II-B INTERIOR WALLS AND, ROOF 0 RATING REQUIRED = OK
II-B/F-1 OCCUPANCY DISTANCE TO FIRE SEPARATION BETWEEN 10 FEET AND 30 FEET = 0 RATING = OK
1. CLOSEST IMAGINARY PL IS 21'-8" FEET TO EAST.
0 FEET8
1/8" = 1'-0"
4 16
CODE ANALYSES CONT:
PER CHAPTER 9 CBC
F-1 OCCUPANCY NOT REQUIRED TO BE SPRINKLERED
PER CHAPTER 10 CBC
FUNCTION OF SPACE: MECH/ELECTRICAL ROOM OL = 300
1. OCCUPANCY = 10 PER PLAN
2. 10 < 49 OCC. ONE EXIT DOOR REQUIRED (PER CEC AND NEC SWITCHGEAR > 800A 2 DOORS REQUIRED (3 PROVIDED OK)
3. F-1 OCC W/O SPRINKLER SYSTEM TO EXIT ACCESS < 200 FT PER PLAN = OK.
FIRE SEPERATION DISTANCE LINE
CODE ANALYSIS NOTES:
30 FEET FIRE SEPARATION DISTANCE UNLESS NOTED
OTHERWISE.
LEGEND:
NOTE:
THIS IS SHOWN FOR REFERENCE ONLY. NO
CHANGE IS PROPOSED FOR BUILDING LOCATION OR
EXISTING FIRE SEPARATION DISTANCE.
IM
P E R
IA
L H
W Y
BLOOMFIELD AVENUEBLOOMFIELD AVENUE
COGENERATIONCO-GEN.
TRANSPORTATIONTRANS.
VOCATIONAL REHABILITATION
HOUSEKEEPING
ADMINISTRATION
OFFICE OF STATE ARCHITECT
GARAGE
RESIDENCE NUMBER
EMPLOYEE
BUILDING
OCCUPATIONAL THERAPY
WAREHOUSE
SHELTER
VOC. REHAB.
HSEKP.
ADMIN.
OSA
G R#
EMP.
BLDG.
O.T.
W S
ABBREVIATIONS & SYMBOLS
PATIENT SUPPORT MODULESP.S.M.
10,274 10,274
9,0009,000
9,371 9,371
2,695 2,439
10,501
8,200
7,933
8,977
8,977
7,933
8,200
10,501
10,501
8,200
7,933
8,977 10,501
8,200
7,933
8,977
17,235
17,235 17,235
17,235
(L RZe
U)
WATER TANKS
IRRIGATION PUMP HOUSE
WATER SOFTENER BUILDING DOMESTIC PUMP HOUSE
DEVICE
BACKFLOW
COMMINUTOR
BUILDING
CTE CHILLER
P.S.M.
COURT
TENNIS
DOM.IRR.
M
ET
A L
P R
O P E R
T Y
L
IN
E
P R
O P E R
T Y L
IN
E
PROPERTY LINE
FD. SERV. WHSE.
LUMBER SHED
GAS PUMP
EN
G
IN
S
SS
S
S
S
D C
U
TRANS.
G A
RA
G
E
PLUMBER
OFFICES
PLANT OP'S.
RECEIVING
STORES /
CAR PORT
CARPENTER
PA
IN
T
MASON
ST
O
R
SH
EE
T
EL
EC
T.
W
EL
D
O .T
O .T
O.T. SOUTH
O.T. NORTH
EM
P.
B
LD
G . 4
EMP. BLDG. 3
R
EC
YC
LI
N G
S
S
G
#1 8
G
#19
#16
G
#14
#13
31 3/315
G
G
EM
P.
B
LD
G . 2
EMP. BLDG. 1
#1
#15 S
LA
U
N D
RY
KITCHEN
OFFICE
TRUST
S
201/203
2/
9/
STORAGE
CHILL WATERBARBER/
W3
COOLING TOWER
#6
#8#7
HSEKP. WHSE 1
PROPERTY
HALL
JAMES
306-308
HOUSE
BOILER
E1
309-31 1 (CPS)
W2NORTH YARD
PCB SHED
HOMES
#1 0
G
G
G
#1 1
#1 2
#20
PUMP HOUSE
(ABANDONED)
C O
N D
O M
IN
IU
M C
O M
PL
EX
FASHION CNT.
STORAGE
PROPERTY LINE
PROPERTY LINE
P R
O P E R
T Y
L
IN
E
PROPERTY LINE
P R
O P E R
T Y L
IN
E
OASIS
P.S.M.
#1 7
VOLLEYBALL
BASKETBALL
G R
A
SS
A R
EA
SALLYPORT
VISITOR CENTER
ADMIN.
CLINICAL
BLDG.
C
EN
TE
R
STUDIO
ART
WAREHOUSE
REHAB.
HOMES
HOMES
CENTER
305/307
BIRCH GROVE
CEDAR STREET
ELM STREET
POST
WELLNESS
G
RN
D
LOCK
WASH.
WAREHOUSE
KITCHEN
CENTRAL
(Omitted)
CLINIC
D-57 (USSeU)
BEAUTY SHOP
C
EN
TE
R
FA
SH
IO
N
FSHN. CNT.
STORE
RELIGIOUS
CENTER
NORWALK BOULEVARD
80 Stalls
S ta lls
1 8 Stalls
58 Stalls
S ta lls
S
CO-GEN.
S.N.F.
TRAILER
10110
HOSP.
OFFICE
POLICE
407/415
405/41 3
CTE
BLDG.
401 /409
408/416
406/414
402/410
417 419
418 420
YOUTH
ADMINISTRATION
BUILDING
CTW
BLDG.
A
A
A
BLDG.
S.N.F.
TRUST
OFFICE
BLDG.
LIBRARY
404/412
403/41 1
/2
KEY PLAN
SCALE:N.T.S.
EXIT PATH < 250'
T3.0
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans l
TRANSFORMER
PIPE
BRIDGE
(E) MANHOLE "MHAA"
BOLLARD
(TYP)
(E)TUNNEL EXHAUST FAN TO REMAIN
30'-0" TYP.
4.7
4.4
101F
102F
107J-A
107J-B
J- A
DRAINAGE
SUMP WITH
PUMP
104L A&B
104LJ2 A&B 104LJ1 A&B
112J
104F 103F
109-J
105F
105F
ADMINISTRATION,
MAINTENANCE, &
CONTROL ROOM
BLOCK
106L-B
106L-A
LUBE OIL
COOLER
J- B
HYDRAULIC
STARTER
SKID
110J A&B
110JD1
110JL1
TURBINE
LUBE OIL
COOLER
SKID
101L
120J-A
120J-B
119J-A 119J-B
101D
111L-C
CHILLER
WASTER WATER CLARIFIER
101J-A&B
101JD1
101JD2
111L-A
MOTOR
111L-B
MOTOR
CHILLER SHELL
103J
105J-B
105J-A
LUBE OIL
CONSOLE
SPACE RESERVED FOR SWITCHGEAR
101L
FLUE GAS
ANALYZER PANEL
EJECTOR, GLAND CONDENSER,
EXTRACTION VALVE PLATFORM
OIL
RETURN
101LD3
101LD2
101LD1
102D
104J-B
104J-A
105LJ1
105LF1
105LJ2
105LF2
105LJ3
105LF3
101C
BALSAM STREET
30'-0" TYP.
T Y P
T Y P
105'-7"
32'-9"
35'-0"
32'-3"
FUTURE
ABOVEGROUND
TANK
FUEL
POLISHER
FUTURE
DAYTANK
FUTURE
2,500KW
FUTURE
NGR NGR
FUTURE SWITCHGEAR
WITH MASTER
CONTROLLER
FUTURE GENERATOR
AREA NOT PART OF THIS
CONTRACT
SCALE
1" = 150'
75 0 15 300FEET 150
CUP BUILDING CODE ANALYSES FLOOR PLAN
TRUE
NORTH
PLAN
NORTH1
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 23793-5
00000000000XXXX
METROPOLITAN STATE HOSPITAL
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
DSH-M CUP
INTERCONNECT
DSH
01/12/2024
SA
F
IL
E L \2
-5
C U
P I n te rc o n n e c t, D
S H
-M \C
A D
\2 T C
O -G
E N
B U
IL
D
IN
G
C O
D E A
N A L Y S
IS
.d w g
D A T E /T
IM
E J a n
:3
P M
JCCA
V2 PLAN CHECK SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
HJL ZML RN
CODE ANALYSES CUP BUILDING:
EXISTING BUILDING TYPE: II-B (8" CMU BLOCK WALLS WITH STEEL DECK/ROOF)
OCCUPANCY: F-1 OCCUPANCY
HEIGHT: EXISTING 46' AFG
SPRINKLERED: YES
NUMBER OF STORIES: 1
AREA: F-1 OCC = 19,147 SF (1ST LEVEL)
AREA: B OCC = 2,260 SF (2ND LEVEL)
PER CHAPTER 5 CBC
II-B/F-1 OCC SPRINKLERED 62,000 SF ALLOWED > 19,147 SF OK
II-B/F-1 OCC SPRINKLERED 92,000 SF ALLOWED > 2,260 SF OK
II-B/B AND F-1 OCC SPRINKLERED 3 STORIES (75 FEET) ALLOWED > 1 STORY (46 FEET) OK
PER CHAPTER 6 CBC
II-B BEARING WALL: 0 RATING REQUIRED = OK
II-B INTERIOR WALLS AND, ROOF 0 RATING REQUIRED = OK
II-B/F-1 OCCUPANCY DISTANCE TO FIRE SEPARATION BETWEEN 10 FEET AND
30 FEET = 0 RATING = OK
1. CLOSEST IMAGINARY PL IS 15 FT.
CODE ANALYSES CONT:
PER CHAPTER 10 CBC
FUNCTION OF SPACE: MECH/ELECTRICAL ROOM OL = 78
1. OCCUPANCY F-1 = 19147/300 = 63 PER PLAN. B OCCUPANCY = 2260/150 = 15 OCC
2. 63 > 49 OCC. TWO EXIT DOOR REQUIRED WITH PANIC HARDWARE (5 DOORS PROVIDED)
3. 15 OCC < 49 HOWEVER, OFFICE ON 2ND FLOOR THEREFORE TWO EXITS REQUIRED (2 EXITS PROVIDED)
4. F-1 OCC W/ SPRINKLER SYSTEM MAX.100 FT TO EXIT ACCESS. EXIT ACCESS < 250 FT = OK
5. B OCC W/ SPRINKLER SYSTEM 30 FT TO EXIT ACCESS. EXIT ACCESS < 300 FT = OK.
FIRE SEPERATION DISTANCE LINE
CODE ANALYSIS NOTES:
30 FEET FIRE SEPARATION DISTANCE UNLESS NOTED
OTHERWISE.
IM
P E R
IA
L H
W Y
BLOOMFIELD AVENUEBLOOMFIELD AVENUE
10,274 10,274
9,0009,000
9,371 9,371
2,695 2,439
10,501
8,200
7,933
8,977
8,977
7,933
8,200
10,501
10,501
8,200
7,933
8,977 10,501
8,200
7,933
8,977
17,235
17,235 17,235
17,235
NORWALK BOULEVARD
80 Stalls
S ta lls
1 8 Stalls
58 Stalls
S ta lls
S
10110
408/416
406/414
402/410
417 419
418 420
CTW
BLDG.
A
A
BLDG.
S.N.F.
404/412
KEY PLAN
SCALE:N.T.S.
EXIT PATH < 250'
NOTE:
THIS IS SHOWN FOR REFERENCE ONLY. NO
CHANGE IS PROPOSED FOR BUILDING LOCATION OR
EXISTING FIRE SEPARATION DISTANCE.
LEGEND:
CUP BUILDING
CODE ANALYSES
FLOOR PLAN
T4.0
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
THIS SYMBOLOGY TO BE USED BY ELECTRICAL AND LAYOUT FOR
ALL FLOOR PLANS, EQUIPMENT, DEVICES, UTILITIES, ETC...,
SHOWN ON DRAWINGS.
LIGHT, THIN LINES INDICATE EXISTING.
HEAVY, THICK LINES INDICATE NEW
HEAVY, SHORT DASHED LINES INDICATE
DEMOLITION OR REMOVAL
TYPICAL PLAN LEGEND
LIGHT, THIN LINES INDICATE EXISTING.
HEAVY, THICK LINES INDICATE NEW
HEAVY, SHORT DASHED LINES INDICATE
DEMOLITION OR REMOVAL
ABBREVIATIONS
NEGLIGIBLENEGL
DISTANCE
DENOTES EXISTING(E)
CB CIRCUIT BREAKER
EA. EACH
COPPERCU
G, GND GROUND
MIN. MINIMUM
AMP./A AMPERE
FIN FINISHED
CIRCUITCKT
LOW VOLTAGE
AMPERE
INTERRUPTING
CAPACITY
AIC
ABOVE FINISHED
FLOOR
AFF
BKR BREAKER
NTS NOT TO SCALE
WEATHER PROOFWP
SWITCHBOARDSWBD
TYP. TYPICAL
UG UNDERGROUND
SWITCHSW
PULL BOXPB
SLD SINGLE LINE DIAGRAM
POLEP
PANELBOARDPNL
(R) RELOCATED
SUB SUBSTATION
NEW(N)
TIME DELAY
UNLESS
OTHERWISE
NOTED
UON
TRANSFORMERXFMR,
TRANSF.
VD VOLTAGE DROP
UL LISTING
ALL ELECTRICAL EQUIPMENT SHALL BE UL LISTED OR APPROVED BY NATIONALLY
RECOGNIZED TESTING LABORATORY.
1. CONTRACTOR SHALL PROVIDE SEQUENCE OF CONSTRUCTION TO MINIMIZE
DOWNTIME/POWER OUTAGE.
2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE TEMPORARY
POWER SUPPLY IN PERFORMING THEIR WORK TO AVOID DISRUPTION ON
CLIENT OPERATION INCLUDING SECURING PERMIT FOR TEMPORARY
POWER SUPPLY.
SEQUENCE OF CONSTRUCTION
VOLTAGE DROP NOTE
APPLICABLE FOR ALL NEW, ALTERED, OR RELOCATED FEEDER AND BRANCH
CIRCUIT CONDUCTORS.
"130.5(C) VOLTAGE DROP: THE MAXIMUM COMBINED VOLTAGE DROP ON BOTH
INSTALLED FEEDER CONDUCTORS AND BRANCH CIRCUIT CONDUCTORS TO THE
FARTHEST CONNECTED LOAD OR OUTLET SHALL NOT EXCEED 5 PERCENT."
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 23793-5
00000000000XXXX
METROPOLITAN STATE HOSPITAL
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
DSH-M CUP
INTERCONNECT
DSH
01/12/2024
SA
F
IL
E L \2
-5
C U
P I n te rc o n n e c t, D
S H
-M \C
A D
\2 E A
B B S Y M
B L
IS
T .d w g
D A T E /T
IM
E J a n
:3
P M
JCCA
V2 PLAN CHECK SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
HJL ZML RN
MOTOR
GROUNDING
SWITCHBOARD 480/277, 3Ø, 4W
MOTOR
GROUNDING
FUSE W/DISCONNECT SWITCH
PROVIDE IS DEFINED TO MEAN THAT THE CONTRACTOR SHALL FURNISH,
INSTALL, ADJUST, TEST AND INTEGRATE INTO A COMPLETE SYSTEM THE ITEM
INDICATED INCLUDING ALL HARDWARE, WIRING, AND MISCELLANEOUS ITEMS
AS NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEM.
DEFINITION
E0.0
E0.1
E1.0
E1.1
E3.0
E3.1
TITLE SHEET, APPLICABLE CODES AND SCOPE OF WORK
FIRE ACCESS SITE PLAN
SWITCHGEAR BUILDING CODE ANALYSES FLOOR PLAN
CUP BUILDING CODE ANALYSES FLOOR PLAN
ELECTRICAL SYMBOL LIST, ABBREVIATIONS, LEGEND,
DEFINITION AND UL LISTING
ELECTRICAL SPECIFICATION NOTES
OVERALL ELECTRICAL SITE PLAN
ELECTRICAL SITE PLAN - DEMOLITION
ELECTRICAL SITE PLAN - ENLARGED
ELECTRICAL SITE PLAN - UNDERGROUND NEW WORK
ENLARGED PLAN
CO-GENERATION-ASSOCIATED CONDUCTOR DEMOLITION
SINGLE LINE DIAGRAM DEMOLITION
SINGLE LINE DIAGRAM NEW WORK
ELECTRICAL DETAILS
ELECTRICAL DETAILS
ELECTRICAL DETAILS
ELECTRICAL DETAILS
SCE DRAWING
ELECTRICAL
DRAWING INDEX
T1.0
ELECTRICAL SYMBOL LIST
E4.0
E2.0
E2.1
E4.1
D
E1.2
E1.3
E4.2
52 DRAW-OUT MV CIRCUIT BREAKER
TRANSFORMER
CURRENT TRANSFORMER (CT)
G
LA LIGHTNING ARRESTER
GENERATOR
M
FEEDER RELAY
METER
DISCONNECT SWITCH
DRAW-OUT POTENTIAL TRANSFORMER (PT)
A AMMETER WITH SELECTOR SWITCH
LOCAL FIRE AUTHORITY - ACCESS APPROVAL
T2.0
T3.0
T4.0
E4.3
ELECTRICAL SYMBOL
LIST, ABBREVIATIONS,
LEGEND, DEFINITION
AND UL LISTING
E0.0
DEMOLISH(D)
GR GENERATOR RELAY
FR
V VOLTMETER WITH SELECTOR SWITCH
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-6278
ISSUE DATE: August 5, 2024
JoEnriqu Text Box Jan. 12, 2024
A. SCOPE
1. FURNISH AND INSTALL ALL REQUIRED MATERIALS AND
EQUIPMENT FOR COMPLETE OPERATING SYSTEMS AS
SHOWN AND AS SPECIFIED.
B. ALL WORK AND MATERIALS SHALL COMPLY WITH THE
LATEST APPLICABLE EDITION OF THE FOLLOWING CODES:
1. 2022 CALIFORNIA BUILDING STANDARDS
ADMINISTRATIVE CODE, TITLE 24 C.C.R.
2. 2019 CALIFORNIA BUILDING CODE, TITLE 24 C.C.R. (2021
INTERNATIONAL BUILDING CODE OF THE INTERNATIONAL
CODE COUNCIL, WITH CALIFORNIA AMENDMENTS).
3. 2022 CALIFORNIA ELECTRICAL CODE, TITLE 24 C.C.R.
(2020 NATIONAL ELECTRICAL CODE OF THE NATIONAL
FIRE PROTECTION ASSOCIATION, NFPA).
4. 2022CALIFORNIA MECHANICAL CODE, TITLE 24 C.C.R.
(2018 UNIFORM MECHANICAL CODE OF THE
INTERNATIONAL ASSOCIATION OF PLUMBING AND
MECHANICAL OFFICIALS, IAPMO).
5. 2022 CALIFORNIA ENERGY CODE, TITLE 24 C.C.R.
6. 2022 BUILDING ENERGY EFFICIENCY STANDARDS.
7. 2022 CALIFORNIA FIRE CODE, TITLE 24 C.C.R.
(2021 INTERNATIONAL FIRE CODE OF THE
INTERNATIONAL CODE COUNCIL).
8. 2022 CALIFORNIA GREEN BUILDING STANDARD CODE
(CALGREEN CODE), TITLE 24 C.C.R.
C. PERMITS AND INSPECTIONS
1. OBTAIN AND PAY FOR ALL REQUIRED PERMITS AND
INSPECTIONS FOR THE INSTALLATION OF THE
ELECTRICAL WORK. DELIVER CERTIFICATES OF
INSPECTION AND APPROVAL TO THE OWNER.
D. SITE VISIT
1. CONTRACTOR SHALL VISIT THE JOB SITE AND BECOME
FAMILIAR WITH THE EXISTING CONDITIONS THAT WILL
AFFECT HIS WORK AND MAKE THE NECESSARY
ALLOWANCES IN HIS BID TO COMPENSATE FOR THESE
CONDITIONS. BY THE ACT OF SUBMITTING A BID FOR
THIS PROJECT, THE CONTRACTOR ACCEPTS ALL
CONDITIONS AT THE SITE. NO REQUEST FOR ADDITIONAL
PAYMENT SHALL BE CONSIDERED AS VALID, DUE TO
FAILURE TO ALLOW FOR CONDITIONS WHICH MAY EXIST.
E. CLEANING PREMISES
1. KEEP JOB SITE, BUILDING AND SITE FREE FROM RUBBISH
AND WASTE MATERIALS, REMOVE SAME FROM SITE ON A
DAILY BASIS.
F. EXAMINATION OF DRAWINGS
1. CONTRACTOR SHALL STUDY ALL DRAWINGS AND
SPECIFICATIONS. SHOULD ANY OF THE WORK SHOWN
OR INDICATED BY THE DRAWINGS BE CONTRARY TO OR
IN CONFLICT WITH ANY CODE REQUIREMENTS, THE SAME
SHALL BE REPORTED TO THE OWNER BEFORE
SUBMITTING A BID. CONTRACTOR WILL BE ADVISED AS
TO HOW TO PROCEED.
G. COORDINATION
1. COORDINATE ALL WORK WITH OTHER TRADES. OBTAIN
ALL DRAWINGS THAT WILL REQUIRE COORDINATION AND
PROVIDE ALL ELECTRICAL CONNECTIONS REQUIRED
WHETHER SHOWN ON ELECTRICAL DRAWINGS OR NOT.
2. ELECTRICAL EQUIPMENT LOCATIONS INDICATED ARE
SHOWN DIAGRAMMATICALLY, EXACT LOCATION SHALL
BE VERIFIED AND DETERMINED IN FIELD, AND APPROVED
BY THE OWNER.
H. SHOP DRAWINGS
1. ALL EQUIPMENT TO BEAR U.L. LABEL OR CERTIFIED BY
NATIONALLY RECOGNIZED TESTING LABORATORY. SHOP
DRAWINGS MUST BE STAMPED BY THE CONTRACTOR
FOR CONFORMANCE PRIOR TO SUBMITTAL. SUBMIT
SHOP DRAWINGS FOR REVIEW PRIOR TO PURCHASING.
SHOP DRAWINGS ARE REQUIRED FOR ALL PANEL
BOARDS, RECEPTACLES, DISCONNECT SWITCHES,
GENERATOR, ATS, LOAD BANK SWITCHGEAR AND
TRANSFORMERS.
2. SERVICE ENTRANCE EQUIPMENT (NEW SWITCHGEAR
WITH METERING SECTION) SHALL BE SUBMITTED TO SCE
BY THE CONTRACTOR FOR APPROVAL.
I. CONTRACTOR BID
1. CONTRACTOR'S BID SHALL BE BASED ON ALL WORK
SHOWN ON THE PLANS AND AS SPECIFIED. ALL PREMIUM,
TIME COSTS REQUIRED SHALL BE INCLUDED IN THE BID.
ALL WORKS SHALL BE GUARANTEE FOR A PERIOD OF
ONE YEAR. IF CONTRACTOR PROPOSES TO SUBSTITUTE
THE SPECIFIED EQUIPMENT, HE SHALL SUBMIT HIS
REQUEST FOR CONSIDERATION TO THE OWNER AND
ENGINEER PRIOR TO THE BID IN WRITING. NO OBSOLETE
OR OUT OF MANUFACTURING EQUIPMENT SHALL BE
ACCEPTED. ALL SUBSTITUTIONS MUST BE REVIEWED BY
THE ENGINEER IN WRITING. SUCH A REVIEW SHALL NOT
RELIEVE THE CONTRACTOR FROM COMPLYING WITH THE
REQUIREMENTS OF THE DRAWINGS AND SPECIFICATION,
THE CONTRACTOR SHALL BE RESPONSIBLE, AT HIS OWN
EXPENSE, FOR ANY CHANGES RESULTING FROM HIS
PROPOSED SUBSTITUTIONS WHICH AFFECT OTHER
PARTS OF HIS OWN WORK OR THE WORK OF OTHER
CONTRACTORS.
J. "AS-BUILT" DRAWINGS
1. CONTRACTOR SHALL KEEP A SET OF PRINTS WHICH
SHALL BE CORRECTED DAILY TO SHOW EVERY CHANGE
FROM THE ORIGINAL DRAWINGS AND SPECIFICATIONS.
UNDERGROUND RUNS SHALL BE ACCURATELY
DIMENSIONED ON THESE PRINTS (REFERENCED TO
BUILDING WALLS OR COLUMNS). ADDENDA AND CHANGE
ORDERS SHALL ALSO BE INCLUDED ON THESE PRINTS.
DELIVER "AS- BUILT" PRINTS TO OWNER PRIOR TO
ACCEPTANCE OF THE JOB. "AS-BUILT" PRINTS SHALL BE
SIGNED AND DATED BY CONTRACTOR.
2. THESE DRAWINGS SHALL BE SUBMITTED TO THE OWNER
FOR APPROVAL. AFTER APPROVAL, THEY SHALL BECOME
THE PROPERTY OF THE OWNER. FINAL PAYMENT WILL BE
WITHHELD UNTIL RECEIPT OF THE APPROVED
DRAWINGS.
K. DEMOLITION
1. PERFORM ALL DEMOLITION WORK AS NOTED ON THE
DRAWINGS AND/OR AS REQUIRED TO CLEAR THE AREA
FOR THE NEW WORK. DELIVER ALL SALVABLE
EQUIPMENT TO THE OWNER AS DIRECTED.
2. FOR ALL EQUIPMENT TO BE REMOVED, REMOVE ALL
WIRING BACK TO THE POWER SUPPLY OR TO THE LAST
DEVICE TO REMAIN. MAINTAIN CIRCUIT CONTINUITY TO
ALL DEVICES AND EQUIPMENT TO REMAIN. REMOVE ALL
UNUSED CONDUIT AND WIRES.
3. OVERCURRENT PROTECTIVE DEVICES VACATED SHALL
BE LABELED "SPARE". UPDATE ALL PANEL AND
SWITCHBOARD DIRECTORIES TO CLEARLY REFLECT NEW
CONDITIONS.
L. PROTECTION & SAFEGUARDS
1. THE CONTRACTOR SHALL ERECT AND MAINTAIN
SUITABLE BARRIERS, PROTECTIVE DEVICES, LIGHT AND
WARNING SIGNS WHERE REQUIRED FOR THE
PROTECTION OF THE PUBLIC AND EMPLOYEES ABOUT
THE BUILDING. HE SHALL BE FULLY RESPONSIBLE FOR
ANY LOSS OR INJURY TO PERSON OR PROPERTY
RESULTING FROM HIS NEGLECT OF THESE
PRECAUTIONS, HIS OWN CARELESSNESS, OR THE
CARELESSNESS OR NEGLECT OF HIS EMPLOYEES, OR
HIS SUB-CONTRACTOR AND/OR THEIR EMPLOYEES.
M. POWER SHUTDOWN
1. POWER SHUTDOWN WHEN REQUIRED FOR THE
EXECUTION OF NEW WORK SHALL BE DONE AFTER
NORMAL WORKING HOURS, AND SHALL BE PROPERLY
COORDINATED IN ADVANCE. CONTRACTOR SHALL
INCLUDE IN HIS BID ALL COST TO COVER OVERTIME.
2. ANY POWER OUTAGES SHALL BE APPROVED BY THE
USER OF THE FACILITY. A ONE WEEK WRITTEN NOTICE
SHALL BE GIVEN FOR ANY OUTAGE REQUEST.
N. EQUIPMENT AND DEVICES
1. THE ELECTRICAL CONSTRUCTION DRAWINGS PROVIDED
HEREIN ARE DIAGRAMMATIC AND SYMBOLIC IN
REPRESENTATION. LOCATIONS DEPICTED ON THE
DRAWINGS FOR ELECTRICAL EQUIPMENT/DEVICES
(MOTORS, STARTERS, DISCONNECT SWITCHES,
RECEPTACLES, JUNCTION/OUTLET BOXES, CONTROL
SWITCHES, ETC.. ARE ONLY APPROXIMATE.
FURTHERMORE, THE EQUIPMENT/DEVICE DEPICTIONS
ARE GENERALLY SYMBOLIC AND NOT DRAWN TO SCALE.
2. ELECTRICAL DRAWINGS INDICATE NEW MATERIALS AND
NEW WORK, UNLESS OTHERWISE NOTED. EXISTING
ELECTRICAL SYSTEMS ARE NOT SHOWN EXCEPT WHERE
INTERFACE IS REQUIRED.
3. ALL NEW BOXES, PANELS, OUTLET COVERS,
ENCLOSURES, ETC. MOUNTED ON THE EXTERIOR OF ANY
STRUCTURE SHALL BE WEATHERPROOF (NEMA 3R MIN) &
ALSO PAINTED TO MATCH THE EXISTING
BUILDING/STRUCTURE.
4. USE "DYMO" LABEL ON FACE OF RECEPTACLE AND
SWITCH COVER PLATE AND JUNCTION BOXES
INDICATING THE SOURCE PANEL AND CIRCUIT USED.
DYMO LABEL TAPE SHALL MATCH THE COLOR OF THE
COVER PLATE ON RECEPTACLES AND SWITCHES.
5. ALL DEVICE SHALL BE WHITE U.O.N.
O. RACEWAYS AND WIRING
1. ALL CABLE/WIRE, CONDUIT RUNS ARE SHOWN
DIAGRAMMATICALLY & THEY SHALL BE ROUTED TO SUIT
ACTUAL FIELD CONDITIONS, EXCEPT WHERE LOCATION
ARE EXPLICITLY DIMENSIONED ON THE DWGS.
2. CONTRACTOR TO LIMIT THE NUMBER OF 90° BENDS
BETWEEN PULL POINTS TO COMPLY WITH THE
REQUIREMENTS OF THE CALIFORNIA ELECTRICAL
SAFETY ORDERS, THE N.E.C.
3. FLEXIBLE CONDUIT SHALL BE USED ONLY FOR SHORT
CONNECTIONS TO LIGHT FIXTURES OR IN EXISTING
WALLS.
4. WATERTIGHT FLEXIBLE CONDUIT (TYPE "UA") SHALL BE
USED FOR CONNECTIONS TO MOTORS, TRANSFORMERS
OR OTHER EQUIPMENT THAT MAY VIBRATE DURING
OPERATION.
5. MAXIMUM LENGTH OF FLEXIBLE CONDUIT SHALL BE
LIMITED TO 6 FT.
6. PVC COATED RIGID GALVANIZED STEEL (RGS) SHALL BE
USED FOR OUTDOOR WIRING.
7. EMT MAYBE USED INDOOR AND WITH COMPRESSION
COUPLING CONNECTIONS.
8. MINIMUM SIZE OF EMT SHALL BE 3/4".
9. THE MINIMUM SIZE OF CONDUITS INSTALLED BELOW
GRADE SHALL BE 1", UON. THE MINIMUM SIZE OF ALL
HOME RUN CONDUITS SHALL BE 3/4", UON. 1/2" CONDUIT
SHALL ONLY BE ALLOWED AT FINAL INDIVIDUAL
CONNECTIONS EQUIPMENT/DEVICES.
10.ALL CONDUITS PENETRATING SLABS SHALL BE
WATERPROOF.
11.THE CONTRACTOR SHALL BE RESPONSIBLE FOR
PROVIDING ALL SLEEVES & OPENINGS REQUIRED FOR
THE PASSAGE OF ELECTRICAL RACEWAYS EVEN WHEN
THESE OPENINGS OR SLEEVES ARE NOT SPECIFICALLY
SHOWN ON THE DRAWINGS. ALL EXCESS OPENINGS
SHALL BE PROPERLY SEALED WITH EQUIVALENT FIRE
RATING. CONDUITS SHALL NOT REQUIRED SLEEVES IF IT
IS APPROVED FOR THROUGH PENETRANTS.
12.CONDUITS TERMINATED AT PANEL BOARDS, CONTROL
CABINETS, ETC. SHALL BE EQUIPPED WITH GROUNDING
BUSHINGS AND SHALL BE EFFECTIVELY BONDED TO
THEIR SOURCE GROUND BUS.
13.ALL BENDS IN CABLES SHALL BE MADE SO THAT THE
PROTECTIVE COVERING ON THE CABLE WILL NOT BE
INJURED. NO BEND SHALL HAVE A RADIUS LESS THAN
THE MINIMUM RECOMMENDED BY THE CABLE
MANUFACTURER.
P. CONDUCTORS
1. UL LISTED. CONDUCTORS SHALL BE COPPER, 600 VOLT,
"THHN/THWN-2" INSULATION, STRANDED, MINIMUM SIZE
#12 EXCEPT FOR CONTROLS.
CONTRACTOR TO VERIFY ROTATION AND PHASING.
COLOR CODES
NEUTRAL - WHITE
a) 208/120VOLT SYSTEM
PHASE A - BLACK
PHASE B - RED
PHASE C - BLUE
b) 480/277VOLT SYSTEM
PHASE A - BROWN
PHASE B - ORANGE
PHASE C - YELLOW
Q. BOXES
1. OUTLET, JUNCTION AND PULL BOXES SHALL BE SIZED
PER APPLICABLE VERSION OF CALIFORNIA ELECTRICAL
CODE ARTICLE 314, TABLES 314.16 (a) AND (b) AND 214.28.
R. GROUNDING AND BONDING
1. ALL NEW (ADDITIONAL) METALLIC STRUCTURES AND
EQUIPMENT FABRICATED WITH METALLIC MATERIALS
SUCH AS MOTOR FRAMES, ENCLOSURES, CABINETS,
MISC. ELECTRIC EQUIPMENT, METALLIC RACEWAYS,
STAIRS, FENCES & HANDRAILS ETC.. SHALL ALL BE
PERMANENTLY & EFFECTIVELY GROUNDED.
2. ALL ABOVE GROUNDING CONDUCTORS SHALL BE
INSULATED STRANDED SOFT DRAWN COPPER, CLASS B,
UON. THE GROUNDING CONDUCTORS WHEREVER
POSSIBLE, SHALL BE ROUTED BENEATH SLABS,
ATTACHED TO THE BUILDING STEEL, OR RUN IN
RACEWAYS AS SHOWN.
3. CONDUIT RUNS AND EQUIPMENT/DEVICE ENCLOSURES
SHALL BE BONDED TOGETHER TO FORM A CONTINUOUS
ELECTRICAL CONDUCTOR. NON-METALLIC RACEWAYS &
ENCLOSURES SHALL INCLUDE BONDING JUMPERS,
4. ALL SYSTEM GROUNDING CONDUCTORS SHALL BE
COPPER. ALL GROUND CONNECTIONS SHALL BE
ACCESSIBLE AND MADE WITH COPPER ALLOY FITTINGS.
5. A GROUND WIRE IS REQUIRED FOR ALL CONDUITS.
S. FEEDERS AND BRANCH CIRCUITS IDENTIFICATION
1. IDENTIFY FEEDERS WITH THE CORRESPONDING CIRCUIT
DESIGNATION AT THE OVER-CURRENT DEVICE, LOAD
END, AND IN PULL BOXES WITH E-Z CODE OR OTHER
APPROVED WIRE MARKER.
2. IDENTIFY BRANCH CIRCUITS WITH I.D. MARKERS, THE
CORRESPONDING CIRCUIT DESIGNATION AT THE
OVER-CURRENT DEVICE, AT ALL SPLICES, AND IN
JUNCTION BOXES, AND IN OUTLETS. USE PLASTIC
COATED SELF-STICKING MARKERS SUCH AS THOMAS &
BETTS E-Z CODE FOR IDENTIFICATION OF CONDUCTORS.
3. CIRCUIT DESIGNATION MEANS PANEL AND CIRCUIT
NUMBER, I.E. 4ALR-3.
4. ALL EQUIPMENT SHALL BE LABELED WITH PHENOLIC
PERMANENT MARKER ENGRAVED LABEL AND MOUNT
WITH SCREWS. ADHESIVE MOUNTING IS NOT
ACCEPTABLE.
5. LARGER DISTRIBUTION PANELS SHALL HAVE PHENOLIC
NAMEPLATES MADE FOR EACH BREAKER. BLACK
BACKGROUND WITH WHITE LETTERS.
6. CHECK PANEL SCHEDULES IDENTIFICATION FOR
VALIDITY. REIDENTIFY ANY OR ALL CHANGES IN PANEL
ON PANEL SCHEDULE CARD. WHILE PANEL COVER IS
REMOVED TURN OFF ANY SPARE BREAKERS AND VERIFY
SPARES ARE INDICATED ON PANEL SCHEDULE CARD.
T. EXECUTION
1. CAREFULLY PROTECT ALL WALLS, TRIM, FLOORS,
EQUIPMENT, UTILITY LINES AND MATERIALS. WHEN
WORKING ON FINISHED SURFACES, LIMIT DAMAGE TO
THE CONFINED SPACE AS POSSIBLE AND RESTORE TO
THE ORIGINAL CONDITION ALL SURFACES WHICH ARE
DAMAGED BECAUSE OF THE INSTALLATION OF THIS
WORK.
2. EQUIPMENT, MATERIALS AND SUPPLIES REMOVED FOR
PROTECTION SHALL BE REPLACED IN ORIGINAL
LOCATIONS. ANY MATERIALS DAMAGED SHALL BE
REPLACED WITH NEW MATERIALS OF LIKE KIND AND
QUALITY.
3. DO ALL DRILLING, CUTTING, CHANNELING AND PATCHING
REQUIRED TO INSTALL ELECTRICAL WORK, AS INDICATED
OR HEREIN SPECIFIED. ALL HOLES, CURBS, ETC., IN
FLOORS, CEILINGS AND WALLS SHALL BE PATCHED TO
MATCH ADJACENT SURFACE, UNLESS INDICATED
OTHERWISE. PAINT ALL NEW ELECTRICAL RACEWAYS,
CABINETS, ENCLOSURES AND FITTINGS TO MATCH
COLOR OF ADJACENT SURFACES.
4. SEAL ALL PENETRATIONS THROUGH FIRE RATED WALLS,
CEILINGS, FLOORS, ETC., TO MAINTAIN THE FIRE RATING.
FURNISH AND INSTALL FIRE RATED ENCLOSURES FOR
ALL EQUIPMENT PENETRATING INTO FIRE RATED
ENVELOPES, SPACES, ETC.
5. ALL DISCONNECT AND TRANSFORMERS SHALL BE
LABELED WITH PERMANENT ENGRAVED LABELS WITH
PANEL DESIGNATION FED FROM AND ROOM LOCATION.
6. CHECK PANEL SCHEDULES IDENTIFICATION FOR
VALIDITY. REIDENTIFY ANY OR ALL CHANGES IN PANEL
ON PANEL SCHEDULE CARD. WHILE PANEL COVER IS
REMOVED TURN OFF ANY SPARE BREAKERS AND VERIFY
SPARES ARE INDICATED ON PANEL SCHEDULE CARD.
U. MISCELLANEOUS
1. CONTRACTOR SHALL PROVIDE ALL MATERIAL UNLESS
NOTED OTHERWISE IN THE CONTRACT AND/OR
CONSTRUCTION DOCUMENT. ALL MATERIAL SHALL BE
NEW AND NOTED BY UNDERWRITER'S LABORATORIES,
FACTORY MUTUAL, OR TESTED BY THE APPROVED THIRD
PARTY TESTING FACILITY.
2. CONVENIENCE OUTLET RECEPTACLES SHALL BE
INSTALLED AS CLOSE AS POSSIBLE TO LOCATIONS
SHOWN ON PLANS. CONTRACTOR RESPONSIBLE FOR
EXACT LOCATION BASED ON FIELD CONDITIONS.
3. CONTRACTOR SHALL NOT PERFORM ANY WORK UNTIL
HE OR HIS REPRESENTATIVE HAS SIGNED THE
CONTRACT.
4. DURING CONSTRUCTION, DO NOT INTERRUPT OR IMPEDE
OPERATION AND WORK IN ADJACENT AREAS.
5. UPON COMPLETION OF WORK, REPLACE SURFACE
MATERIAL, PAVING AND PAVING BASE, COURSE TO
MATCH ORIGINAL. ALL CONDUIT PENETRATIONS SHALL
BE SEALED WITH AN APPROPRIATE RATED SEALANT.
PENETRATIONS EXPOSED TO WEATHER AND THROUGH
ROOF SHALL BE FLASHED AND CAULKED TO FORM A FIRE
RATED AND WATERTIGHT PENETRATION.
6. UPON COMPLETION OF ALL WORK, THOROUGHLY CLEAN
ALL EQUIPMENT AND DUCTS FROM INSIDE AND OUTSIDE
OF EQUIPMENT. REMOVE ALL TRACES OF SOIL, DUST,
LABELS, GREASE, OIL AND FOREIGN MATERIALS.
CLEANUP AND REMOVE FROM THE PREMISES ALL
DEBRIS AND SURPLUS MATERIAL CAUSED BY THIS
WORK.
7. ALL EXISTING SURFACES DAMAGED BY NEW
CONSTRUCTION, SHALL BE PATCHED, OR REPAINTED TO
MATCH EXISTING CONDITIONS, PAINTED SURFACE SHALL
BE PAINTED FROM BREAK TO BREAK. IT SHALL BE THE
CONTRACTORS RESPONSIBILITY TO PATCH & REPAIR ALL
DAMAGE TO EXISTING SURFACES AND FINISHES
FURTHERMORE, THE AFFECTED AREA(S) OF WORK
SHALL BE REPAIRED TO MATCH THE FINISH THAT WAS
PREVIOUSLY EXISTING, PRIOR TO THE COMMENCEMENT
OF WORK.
8. THE CONTRACTOR SHALL VERIFY ALL LOCATIONS,
WHICH REQUIRE PENETRATIONS, SUCH AS ROOFS,
HAZARDOUS AREAS, MASONRY AND FIRE RATED WALLS,
ETC.. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED
OPENINGS & CORE DRILL AS REQUIRED FOR NEW
ELECTRICAL WORK. THE CONTRACTOR SHALL PATCH &
FIRE STOP (SEAL) ALL PENETRATIONS (BOTH SIDES) PER
SPECIFICATIONS.
9. WHERE THERE IS A CONFLICT BETWEEN THE DRAWINGS
& ANY RELEVANT CODES, THE CODES SHALL GOVERN,
EXCEPT WHERE THE DRAWINGS INDICATE A QUALITY
LEVEL SUPERIOR TO THAT SPECIFIED BY THE CODES.
10.IN THE EVENT OF CONFLICT OR DISCREPANCY IN
DRAWINGS/PLANS, IN SPECIFICATIONS, BETWEEN
DRAWINGS AND SPECIFICATIONS, BETWEEN SITE
CONDITIONS AND DRAWINGS, THE CONTRACTOR SHALL
PROVIDE THE MORE STRINGENT REQUIREMENTS.
W. ACCEPTANCE TESTING AND COMMISSIONING.
1. THE CONTRACTOR SHALL PROVIDE A THIRD PARTY
TESTING
2. CONTRACTOR SHALL PROVIDE DOCUMENTATION THAT
THE CONDUCTOR, SWITCHBOARDS, SWITCHGEAR, AND
DEVICES HAVE BEEN COMMISSIONED AND PASSED THE
ACCEPTANCE TESTING AND READY FOR OPERATION
PRIOR TO HANDOVER TO END USER.
3. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO
REQUEST FROM UTILITY COMPANY THEIR PROTECTION
SETTINGS.
4. PERFORM SHORT CIRCUIT AND COORDINATION STUDY.
SET CIRCUIT BREAKERS AND RELAYS ACCORDING TO
STUDY.
5. PERFORM ARC FLASH STUDY AND PROVIDE LABELS.
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 23793-5
00000000000XXXX
METROPOLITAN STATE HOSPITAL
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
DSH-M CUP
INTERCONNECT
DSH
01/12/2024
SA
F
IL
E L \2
-5
C U
P I n te rc o n n e c t, D
S H
-M \C
A D
\2 E S
P E C
S .d w g
D A T E /T
IM
E J a n
:3
P M
JCCA
V2 PLAN CHECK SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
HJL ZML RN
ELECTRICAL SPECIFICATION NOTES
ELECTRICAL
SPECIFICATION
NOTES
E0.1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-6278
ISSUE DATE: August 5, 2024
JoEnriqu
OH OH OH OH OH OH
O H
O H
66KV 66KV 66KV 66KV 66KV 66KV
K V
66KV
K V
12K V
DEMOLISH OVERHEAD LINES INCLUDING POLES.
SEE DETAIL E4.0, DET. 5 COORDINATE WITH SCE
(E) 12KV OVERHEAD LINE
(D)66KV POLE
H
H
O H
OH
O H
O H
OH
IM
P E R
IA
L H
W Y
BLOOMFIELD AVENUE BLOOMFIELD AVENUE
COGENERATIONCO-GEN.
TRANSPORTATIONTRANS.
VOCATIONAL REHABILITATION
HOUSEKEEPING
ADMINISTRATION
OFFICE OF STATE ARCHITECT
GARAGE
RESIDENCE NUMBER
EMPLOYEE
BUILDING
OCCUPATIONAL THERAPY
WAREHOUSE
SHELTER
VOC. REHAB.
HSEKP.
ADMIN.
OSA
G R#
EMP.
BLDG.
O.T.
W S
ABBREVIATIONS & SYMBOLS
PATIENT SUPPORT MODULESP.S.M.
10,274 1 0,274
9,0009,000
9,371 9,371
2,695 2,439
10,501
8,200
7,933
8,977
8,977
7,933
8,200
10,501
10,501
8,200
7,933
8,977 10,501
8,200
7,933
8,977
17,235
1 7,235 1 7,235
17,235
(L
RZ
e U)
WATER TANKS
IRRIGATION PUMP HOUSE
WATER SOFTENER BUILDING DOMESTIC PUMP HOUSE
DEVICE
BACKFLOW
COMMINUTOR
BUILDING
CTE CHILLER
P.S.M.
COURT
TENNIS
DOM.IRR.
M
ET
A L
P R
O P E R
T Y
L
IN
E
P R
O P E R
T Y L
IN
E
PROPERTY LINE
FD. SERV. WHSE.
LUMBER SHED
GAS PUMP
EN
G
IN
S
SS
S
S
S
D C
U
TRANS.
G A
R A
G E
PLUMBER
OFFICES
PLANT OP'S.
RECEIVING
STORES /
CAR PORT
CARPENTER
PA
IN
T
MASON
ST
O
R
SH
EE
T
EL
EC
T.
W
EL
D
O .T
O .T
O.T. SOUTH
O.T. NORTH
EM
P.
B
LD
G . 4
EMP. BLDG. 3
R
EC
YC
LI
N G
S
S
G
#18
G
#19
#16
G
#14
#13
313/315
G
G
EM
P.
B
LD
G . 2
EMP. BLDG. 1
#1
#15 S
LA
U
N D
R Y
KITCHEN
OFFICE
TRUST
S
201/203
2/
9/
STORAGE
CHILL WATERBARBER/
W3
COOLING TOWER
#6
#8#7
HSEKP. WHSE 1
PROPERTY
HALL
JAMES
306-308
HOUSE
BOILER
E1
309-31 1 (CPS)
W2NORTH YARD
PCB SHED
HOMES
#10
G
G
G
#1 1
#12
#20
PUMP HOUSE
(ABANDONED)
C O
N D
O M
IN
IU
M C
O M
PL
EX
FASHION CNT.
STORAGE
PROPERTY LINE
PROPERTY LINE
P R
O P E R
T Y L
IN
E
PROPERTY LINE
P R
O P E R
T Y L
IN
E
OASIS
P.S.M.
#17
VOLLEYBALL
BASKETBALL
G R
A
SS
A R
EA
SALLYPORT
VISITOR CENTER
ADMIN.
CLINICAL
BLDG.
C
EN
TE
R
STUDIO
ART
WAREHOUSE
REHAB.
HOMES
HOMES
CENTER
305/307
BIRCH GROVE
CEDAR STREET
ELM STREET
POST
WELLNESS
G R
N D
LOCK
WASH.
WAREHOUSE
KITCHEN
CENTRAL
(Omitted)
CLINIC
D-57 (USSeU)
BEAUTY SHOP
C
EN
TE
R
FA
SH
IO
N
FSHN. CNT.
STORE
RELIGIOUS
CENTER
NORWALK BOULEVARD
80 Stalls
S ta lls
1 8 Stalls
58 Stalls
S ta lls
S
CO-GEN.
S.N.F.
TRAILER
10110
HOSP.
OFFICE
POLICE
407/415
405/413
CTE
BLDG.
401/409
408/416
406/414
402/410
417 419
418 420
YOUTH
ADMINISTRATION
BUILDING
CTW
BLDG.
A
A
A
BLDG.
S.N.F.
TRUST
OFFICE
BLDG.
LIBRARY
404/412
403/411
/2
(D)12KV POLE
OVERALL ELECTRICAL SITE PLAN
TRUE
NORTH
PLAN
NORTH1
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 23793-5
00000000000XXXX
METROPOLITAN STATE HOSPITAL
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
DSH-M CUP
INTERCONNECT
DSH
01/12/2024
SA
F
IL
E L \2
-5
C U P I n te rc o n n e c t, D
S H -M
\C A D
\2 E O
V E R A L L S
IT
E P
L A N .d w g
D A T E /T
IM
E J a n
:3
P M
JCCA
V2 PLAN CHECK SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
HJL ZML RN
KEYNOTES:
SEE E1.1, E1.2, & E1.3 FOR BUILDING & SUBSTATION LAYOUT SCOPE
OF WORK.
OVERALL
ELECTRICAL
SITE PLAN
E1.0
SCALE: 0 40020 FEET200
1" = 200'
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-6278
ISSUE DATE: August 5, 2024
JoEnriqu
66/12KV ELECTRICAL SUBSTATION
TO BE DEMOLISHED BY SOUTHERN
CALIFORNIA EDISON (SCE)
SEE E4.0 DETAIL 6
(E)
COGENERATION
BUILDING
TRANSFORMER
PIPE
BRIDGE
BALSAM STREET
(E) UNDERGROUND
CONDUIT BETWEEN
12KV SWITCHGEAR
AND OUTDOOR
SUB-STATION
PROTECT (E)GROUND
OF TRANSFORMER "A"
FOR FUTURE USE
(E) UNDERGROUND
GROUNDING
(E) CHW SUPPLY AND RETURN
PIPING AND FUEL PIPE
UNDERGROUND
TUNNEL
(D)SCE TRANSFORMER
(E) SS
(D)BUILDING
(ELECTRIC
GEAR)
EXISTING CONCRETE SLAB
OVER UNDERGROUND #2 FUEL
OIL STORAGE TANK
(E) MANHOLE "MHAA"
(E)12KV OVERHEAD LINE
(D)12KV POLE WITH AIR
BREAK SWITCH, REFER
TO SCE DRAWING
(D)SCE PAD-MOUNTED
GEAR, PMU-5
(E) HV2-1, HV1-1, HV3-1, HV4-1
(E) HV1-15, CK-2, HV2-2, HV1-2,
HV3-2, HV4-2
(E) CK-3, F4-2
(E)CK-1 AND FUTURE CONDUITS
PROTECT IN PLACE
(E)
MANHOLE
"MHA"
(E)CUP 200KW EMERGENCY
GENERATOR LOCATION
(E)A/G PULLBOX2
TR-A
TR-3TR-2
(E)GROUNDING
CONNECTION NOT
VERIFIED (TYP)
SCALE
1" = 150'
75 0 15 300FEET150
ELECTRICAL SITE PLAN - DEMOLITION PLAN
TRUE
NORTH
PLAN
NORTH1
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 23793-5
00000000000XXXX
METROPOLITAN STATE HOSPITAL
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
DSH-M CUP
INTERCONNECT
DSH
01/12/2024
SA
F
IL
E L \2
-5
C U
P I n te rc o n n e c t, D
S H
-M \C
A D \2
E E
L E C
T R
IC
A L S
IT
E P
L A N
.d w g
D A T E /T
IM
E J a n
:3
P M
JCCA
V2 PLAN CHECK SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
HJL ZML RN
SEE ENLARGED PLAN ON
SHEET E2.0 DETAIL 1 & 2
COORDINATE WITH SCE FOR THE DEMOLITION OF EXISTING GUY.
COORDINATE WITH SCE FOR THE DEMOLITION OF (E) SCE
EQUIPMENT. REFER TO SCE DRAWING. PROVIDE COVER PLATE
ON THE OPENINGS AFTER THE REMOVAL OF EQUIPMENT.
DEMOLISHED EXISTING SWITCHGEAR BUILDING INCLUDING THE
ABANDONED SWITCHGEAR EQUIPMENT.
(E)MV PULLBOX TO PROTECT AND REMAIN IN PLACE.
DEMO WORK KEYNOTES:
ELECTRICAL
SITE PLAN
DEMOTION PLAN
E1.1
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-6278
ISSUE DATE: August 5, 2024
JoEnriqu
(E) SS
EXISTING CONCRETE SLAB OVER
UNDERGROUND #2 FUEL OIL
STORAGE TANK
BALSAM STREET
G
(E) MANHOLE "MHAA"
12KV OVERHEAD LINE
(E)UNDERGROUND CONDUIT
BETWEEN 12KV SWITCHGEAR
AND OUTDOOR SUB-STATION
(E) UNDERGROUND CONDUIT
(E) HV1-15, CK-2, HV2-2, HV1-2, HV3-2, HV4-2
(E) CK-3, F4-2
(E)CK-1 AND SPARE CONDUITS.
ROUTING ARE NOT VERIFIED.
(E)MANHOLE "MHA"
(E) CHW SUPPLY AND RETURN
PIPING AND FUEL PIPE
UNDERGROUND
TUNNEL
(TYP)
(E) TUNNEL EXHAUST FAN TO REMAIN
(E) 5KV, NEMA 3R
SPLICE BOX TO
REMAIN
(E) UNDERGROUND
CONDUIT
(N)(4)4"C - ABOVEGROUND CONDUITS
5 6
"MHAA-1"
4'x6'-6"x5'-6"
13 14
(8)5"C
(E)75KVA TRANSFORMER
(E)MV PB
(E)MCC
(E)MV DISCONNECT SWITCHES
(E)TRANSFORMER "TGB"
(E)45KVA TRANSFORMER
(E)LIGHTING PANEL "A"
(E)PANEL "B"
(E)BATTERY &
BATTERY CHARGER
(E)LOCAL DIST. PANEL (LDP)
(E)ALARMTRONICS
FUTURE PARALLELING
SWITCHGEAR WITH MASTER
CONTROLLER(4) 5"C
(4)2"C (2)2"C
(2)2"C3
3 3
Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 23793-5
00000000000XXXX
METROPOLITAN STATE HOSPITAL
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
DSH-M CUP
INTERCONNECT
DSH
01/12/2024
SA
F
IL
E L \2
-5
C U
P I n te rc o n n e c t, D
S H -M
\C A D
\2 E E
L E C T R
IC
A L S
IT
E P
L A N
N
E W
W O
R K E N
L A R
G E D .d w g
D A T E /T
IM
E J a n
:4
P M
JCCA
V2 PLAN CHECK SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
HJL ZML RN
KEYNOTES:
GENERAL NOTES: (APPLICABLE TO EXTERIOR WORK)
1. THE EXISTING CONDITIONS OF BELOW GROUND PIPING AND UTILITIES SUCH AS GAS
MAINS, WATER MAINS, SANITARY SEWERS, POWER AND COMMUNICATIONS CONDUITS
AND OTHER UTILITIES ARE TAKEN FROM EXISTING RECORD DRAWINGS AND VERIFIED
BY FIELD OBSERVATION. THE LOCATION OF THESE UTILITIES IS APPROXIMATE ONLY.
IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY THE EXACT
LOCATION AND DEPTH OF BELOW GROUND PIPING AND UTILITIES IN THE IMMEDIATE
VICINITY OF SUBSURFACE WORK, WHETHER SHOWN ON THE DRAWING OR NOT.
CONTRACTOR SHALL RETAIN THE SERVICES OF AN UNDERGROUND UTILITY
LOCATING COMPANY. UTILIZE GROUND PENETRATING RADAR AND OTHER UTILITY
LOCATING DEVICES TO DETERMINE THE LOCATION AND DEPTH OF ALL
UNDERGROUND IMPROVEMENTS WITHIN APPROXIMATELY 20' OF ALL NEW WORK.
PAINT MARK ALL UTILITY LOCATIONS ON THE PAVEMENT SURFACE. THIS TASK SHALL
BE COMPLETED PRIOR TO ANY EXCAVATING.
2. PRIOR TO STARTING TRENCHING, POTHOLE TO VERIFY THE DEPTH OF EXISTING
PIPES WHICH ARE TO JOIN OR CROSS NEW PIPING OR CONDUITS. ADJUST DEPTH OF
NEW PIPE CONDUIT AS REQUIRED TO CROSS EXISTING UTILITIES. NOTIFY ENGINEER
OF ANY DISCREPANCIES OR INTERFERENCES PRIOR TO LAYING ANY PIPE.
3. PRIOR TO STARTING TRENCHING, VERIFY LOCATION AND WORKING CONDITION OF
THE ASSOCIATED WATER VALVES WHICH NEED TO BE EXERCISED DUE TO THE
WATER SHUTDOWN ASSOCIATED WITH THE SCOPE OF WORK. NOTIFY ENGINEER IF
THERE ARE ANY DISCREPANCIES WITH THE VALVES.
4. EXISTING UNDERGROUND UTILITIES SHOWN HEREIN HAVE BEEN LOCATED FROM
VARIOUS SOURCES OF VARYING RELIABILITY, INCLUDING SURFACE EVIDENCE AND
AVAILABLE RECORDS, AND ARE SHOWN FOR INFORMATION ONLY. THE CONTRACTOR
IS RESPONSIBLE FOR DETERMINING THE EXACT LOCATION OF ALL EXISTING UTILITIES
AND FOR THE PROTECTION OF AND REPAIR OF DAMAGE TO THEM.
5. ALL WORK RELATED TO SCE EQUIPMENT AND UNDERGROUND WORK SHALL BE
INSTALLED IN ACCORDANCE WITH SCE ESR AND UGS MANUAL. IT SHOULD BE
ACCEPTED BY SCE INSPECTION TEAM. SEE ATTACHED SCE DRAWING FOR
ADDITIONAL INFORMATION.
6. CONTACT DIG ALERT (811) 48 HOURS PRIOR TO EXCAVATION.
SCALE
TRUE
NORTH
PLAN
NORTH1
3,750KVA TRANSFORMER PAD, SEE DETAIL 6/E4.1
PROVIDE ONE ROUND OF SLACK CONDUCTOR.
REMOVE AND REPLACE AC PAVING FOR ELECTRICAL CONDUIT TRENCH.
SEE DETAIL 2/E4.0, 2/E4.1
VACUUM FAULT INTERRUPTER (VFI) EQUIPMENT PAD, SEE DETAIL 7/E4.1.
BYPASS EQUIPMENT PAD, SEE DETAIL 5/E4.1.
3-WAY RAG EQUIPMENT PAD, SEE DETAIL 5/E4.1.
CAPACITOR EQUIPMENT PAD, SEE DETAIL 8/E4.1.
(E) EQUIPMENT PAD TO REMAIN. COVER TRENCH SIMILAR TO EXISTING
COVER PLATE ONCE THE REMOVAL OF (E)EQUIPMENT IS COMPLETED.
(E)SCE 12KV UNDERGROUND CONDUIT NOT VERIFIED. CONDUIT SHALL
BE ABANDONED IN PLACE ONCE THE UPGRADE IS COMPLETED.
NEW 5KV, 1200A, 3Ø, SCE METERING EQUIPMENT SHALL BE IN
COMPLIANCE WITH ESR REQUIREMENT. SUBMIT SHOP DRAWING TO SCE
FOR APPROVAL. SEE DETAIL #2, E4.2 FOR EQUIPMENT PAD DETAIL.
18" X 18" X 6" NEMA 3R PULL BOX (LOW VOLTAGE - POWER).
18" X 18" X 6" NEMA 3R PULL BOX (SIGNAL).
1 1/2"Ø AND 2"Ø PVC (POWER), SEE DETAIL 5/E4.2.
(2)2"Ø PVC (SIGNAL), SEE DETAIL 5/E4.2.
SEE DETAIL 2/E4.2 EXCEPT CONDUIT IS 4" DIAMETER.
(E)SCE 5KV UNDERGROUND CONDUITS AND THE ROUTING ARE NOT
VERIFIED. CONDUITS SHALL BE PLUG AND ABANDONED IN PLACE ONCE
THE UPGRADE IS COMPLETED.
(1)5"C, SEE DETAIL 4/E4.2
(2)5"C, SEE DETAIL 9/E4.2
(4)5"C, SEE DETAIL 8/E4.2
24"D X 36"W X 48"H HV PULL BOX
REPAIR DAMAGE ASPHALT WALKWAY DUE TO NEW UNDERGROUND
CONDUIT. EXTEND WIDTH OF ASPHALT WALKWAY FOR 48".
REFER WITH SCE DRAWING FOR ADDITIONAL INFORMATION ON POLE
RISER REQUIREMENT.
12" X 22" UNDERGROUND PULLBOX, SEE DETAIL 4/E4.3. PROVISION FOR
FUTURE GENERATOR AREA INTERFACE.
REMOVE AND REPLACE AC PAVING FOR ELECTRICAL CONDUIT TRENCH.
SEE DETAIL 2/E4.0 BUT 8 CONDUITS.
SEE DETAIL 8/E4.2 BUT 10 CONDUITS
REMOVABLE BOLLARD, TYPICAL OF 2, SEE DETAIL 2/E4.3
FIXED BOLLARD, DETAIL 4/E4.1, NOT TO EXCEED 4'-6" APART, TYPICAL.
REMOVE AND REPLACE AC PAVING FOR ELECTRICAL CONDUIT TRENCH.
FUTURE GENERATOR POWER CONDUITS, SEE DETAIL 2/E4.0.
0 FEET8
1/8" = 1'-0"
4 16
ELECTRICAL SITE
PLAN - ENLARGED
E1.2
ELECTRICAL SITE PLAN - ENLARGED
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-6278
ISSUE DATE: August 5, 2024
JoEnriqu
(E) SS
(E)
COGENERATION
BUILDING
EXISTING CONCRETE SLAB OVER
UNDERGROUND #2 FUEL OIL
STORAGE TANK
TRANSFORMER
PIPE
BRIDGE
BALSAM STREET
G
(E) MANHOLE "MHAA"
R=5'-0" (TYP)
"MHAA-2"
DETAIL#1/E4.0
(4)5"C
12KV OVERHEAD LINE
G10D
(E)UNDERGROUND CONDUIT
BETWEEN 12KV
SWITCHGEAR AND OUTDOOR
SUB-STATION
VERIFY ON SITE THE DEPTH
AND ROUTING
(E) GROUND OF
TRANSFORMER "A"
TO RE-USE
(E)UNDERGROUND
GROUNDING
(E) UNDERGROUND CONDUIT(E)HV1-15, CK-2, HV2-2,
HV1-2, HV3-2, HV4-2
(E)CK-3, F4-2
(E)MV PB
(E)MANHOLE "MHA"
(E) CHW SUPPLY AND RETURN
PIPING AND FUEL PIPE
UNDERGROUND
TUNNEL
"5
(E)TUNNEL EXHAUST FAN TO REMAIN
(E)5KV, NEMA
3R SPLICE
BOX TO
REMAIN
(E)UNDERGROUND
CONDUIT
"MHAA-1"
DETAIL#5/E4.3
3'-0"
(8)5"C
5 6
1 8
4'-0"
29 (TYP.)
FUTURE
ABOVEGROUND
TANK
FUEL
POLISHER
FUTURE
FUTURE
DAYTANK
NGR NGR
FUTURE PARALLELING
SWITCHGEAR WITH MASTER
CONTROLLER
2,500KW
FUTURE
2,500KW
FUTURE
(4)5"C
FUTURE GENERATOR
AREA NOT PART OF THIS
CONTRACT
11'-8"
5'-9"
4'-7"
4'-0"
SCALE
1" = 150'
75 0 15 300FEET150
ELECTRICAL SITE PLAN - UNDERGROUND NEW WORK
TRUE
NORTH
PLAN
NORTH1 Checked
Vault File Number
Project Number
Reference North Sheet Scale
Sheet Number
Designed
Sheet Title
Supervisor
Issue Date
Drawn
Project
Description
No.
Date Issue
JCCA #: 23793-5
00000000000XXXX
METROPOLITAN STATE HOSPITAL
11401 BLOOMFIELD AVENUE
NORWALK, CALIFORNIA 90650
DEPARTMENT OF
STATE HOSPITALS
(DSH)
AS SHOWN
DSA STAMP
DSH-M CUP
INTERCONNECT
DSH
01/12/2024
SA
F
IL
E L \2
-5
C U
P I n te rc o n n e c t, D
S H
-M \C
A D \2
E E
L E C
T R
IC
A L S
IT
E P
L A N
N
E W
W O
R K .d w g
D A T E /T
IM
E J a n
:4
P M
JCCA
V2 PLAN CHECK SUBMITTAL
Client Agency
DEPARTMENT OF STATE HOSPITALS
385 VAN NESS AVE., SUITE 208, TORRANCE, CA 90501
P: 310.212.7644 F:310.212.5272I
HJL ZML RN
SEE ENLARGED PLAN ON
SHEET DETAIL 3/E2.0
SEE ENLARGED PLAN ON
SHEET E2.0 DETAIL 4 & 5.
SEE ENLARGED PLAN ON
SHEET DETAIL 1 & 2/E2.0
KEYNOTES:
3,750KVA TRANSFORMER PAD, SEE DETAIL 6/E4.1.
PROVIDE ONE ROUND OF SLACK CONDUCTOR.
REMOVE AND REPLACE AC PAVING FOR ELECTRICAL
CONDUIT TRENCH. SEE DETAIL 2/E4.0, 2/E4.1.
VACUUM FAULT INTERRUPTER EQUIPMENT PAD, SEE DETAIL
7/E4.1
BYPASS EQUIPMENT PAD, SEE DETAIL 5/E4.1
3-WAY RAG EQUIPMENT PAD, SEE DETAIL 5/E4.1
CAPACITOR EQUIPMENT PAD, SEE DETAIL 8/E4.1
(E)EQUIPMENT PAD TO REMAIN. COVER TRENCH SIMILAR TO
EXISTING COVER PLATE ONCE THE REMOVAL OF
(E)EQUIPMENT IS COMPLETED.
GROUNDING TEST WELL, SEE DETAIL 4/E4.0.
#4/0 BARE COPPER CONDUCTOR BURIED 48" BELOW FINISH
GRADE.
5/8"Ø X 8' GROUNDING ROD, SEE DETAIL 4/E4.0 WITHOUT TEST
WELL
CONNECTION TO REBARS AND MAIN GROUNDING SHALL BE
BY EXOTHERMIC WELDING, USE #2/0 BARE COPPER WIRE
E1.3
ELECTRICAL
SITE PLAN -
UNDERGROUND
NEW WORK
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
03/04/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
23-6278
ISSUE DATE: August 5, 2024
JoEnriqu
DEMOLISH POWER AND CONTROL CONDUCTOR
FROM 12KV SWITCHGEAR. CONDUIT SHALL BE
PLUG & FLUSH IN CONCRETE PAD.
(E) GROUNDING
DEMOLISH TRANSFORMER
TR-A…