13-08 LAX RSI Program Project Details - Attachment 08.pdf

PDF 7 MB Posted

Attached to
Residential Sound Insulation Program Group 12 (Construction)
Solicitation number
0521-2026-09-RFB-231762
Issued by
Los Angeles County, California

About this file

This is a project details attachment for the Los Angeles World Airports (LAWA) Residential Sound Insulation (RSI) Program at Los Angeles International Airport, prepared by CSDA Design Group with mechanical and electrical engineering by YDG Engineers, Inc. The document provides comprehensive construction details and specifications for sound retrofit modifications to eligible residential dwellings near LAX, including replacement of windows and doors with acoustically-rated assemblies, attic insulation, finish and rough carpentry, exterior and interior plastering and painting, roof equipment platforms, ventilation unit installation, and electrical service upgrades. The project is identified as Bid Group 12, with the detail booklet dated June 26, 2026. The document encompasses 59 detail sheets organized by construction division, covering structural elements, doors, windows, mechanical systems, plumbing, and electrical connections required for the sound insulation retrofit work.

The project details document provides standardized construction specifications and installation methods for all major work categories, including mechanical screens for roof and floor applications, attic access hatches with fire-rating options, window modifications and replacements for various existing conditions, acoustic door installations, HVAC equipment placement and connections, condensate drainage systems, gas piping configurations, and electrical penetrations. The specifications reference manufacturer installation instructions, California Building Code (CBC) compliance requirements, and industry standards such as SMACNA guidelines. Details address site-specific conditions such as sloped versus flat roofs, tile versus wood frame windows, and various wall construction types. The document is intended to serve as a generic guide for contractors, with field verification required for existing conditions and final detailed solutions developed based on actual site conditions encountered during construction.

View the file

Other files

File Type Posted
4-00 LAX RSI Program RFB Bid Group 12.pdf PDF
8-11 LAX RSI Program Lead Asbestos Survey Results - Attachment 11.pdf PDF
2-14 LAX RSI Program ESBS Building Dept. Protocols - Attachment 14.pdf PDF
14-01 LAX RSI Program Administrative Requirements - Attachment 01.pdf PDF
9-05 LAX RSI Program Project Requirements - Attachment 05.pdf PDF
10-10 LAX RSI Program Project Area Map - Attachment 10.pdf PDF
16-07 LAX RSI Program Project Drawings - Attachment 07.pdf PDF
15-09 LAX RSI Program Technical Specifications - Attachment 09.pdf PDF
17-15 LAX RSI Program Davis-Bacon General Wage - Attachment 15.pdf PDF
5-02 LAX RSI Program Bid Form Bid Group 12 - Attachment 02.pdf PDF
6-06 LAX RSI Program Federal Requirements - Attachment 06.pdf PDF
20-17 LAX RSI Program Addendum No. 1.pdf PDF
21-18 LAX RSI Program Pre-Bid Conference Slides.pdf PDF
1-01 LAX RSI Program Administrative Requirements - Attachment 1.pdf PDF
3-04 LAX RSI Program Special Conditions - Attachment 04.pdf PDF
18-16 LAX RSI Program FAA Civil Rights Title VI Assurances - Attachment 16.pdf PDF
12-13 LAX RSI Program Draft Contract - Attachment 13.pdf PDF
19-02 LAX RSI Program Bid Form Bid Group 12 - Attachment 02.xlsx XLSX spreadsheet
7-12 LAX RSI Program Payment Performance Bonds - Attachment 12.pdf PDF
11-03 LAX RSI Program General Conditions - Attachment 03.pdf PDF
Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LAX RESIDENTIAL SOUND INSULATION PROGRAM

ATTACHMENT 8:

Project Details

DETAIL BOOKLET FOR

LOS ANGELES INTERNATIONAL AIRPORT

RESIDENTIAL SOUND INSULATION PROGRAM

610 E. FRANKLIN AVE.

EL SEGUNDO, CA 90245

VERSION 1

June 26, 2026

BID GROUP 12

ARCHITECT:

SIGNATURE PAGE

CSDA DESIGN GROUP

610 E. FRANKLIN AVE.

EL SEGUNDO, CA 90245

TEL: 310-821-9200

MECHANICAL: YDG ENGINEERS, INC.

2930 W. IMPERIAL HIGHWAY, SUITE 516

INGLEWOOD, CA 90303

TEL: 310-912-5008

ELECTRICAL: YDG ENGINEERS, INC.

2930 W. IMPERIAL HIGHWAY, SUITE 516

INGLEWOOD, CA 90303

TEL: 310-912-5008

E

AT

O

TS

F

RO

F CAL I

AI

N

DSE

N

L

CI

E H

TI

T

CE

CRA

No. C-21640

CHRISTOPHER

WARD

NOVEMBER 30, 2025

RENEWAL DATE

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

LAWA SHEET INDEX

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

00 00 00.00

02/20/26

LAX RESIDENTIAL SOUND INSULATION DETAILS

DIVISION 5 - METALS

05 58 00.01 BOLLARD DETAIL

05 58 00.02 NON-REMOVEABLE BOLLARD DETAIL

DIVISION 6 - WOOD & PLASTICS

06 10 53.01 EXTERIOR WALL PATCHING

06 22 00.16 MECHANICAL SCREEN - SLOPED ROOF

06 22 00.18 RECESSED LIGHT FIXTURE (SECTION VIEW)

06 22 00.20 INSULATION BARRIER FOR EAVE VENTS

(SECTION VIEW)

06 22 00.21 RECESSED ATTIC ACCESS HATCH

06 22 00.22 ATTIC ACCESS HATCH FLUSH WITH CEILING

06 22 00.22A FIRE RATED ATTIC ACCESS PANEL IN CEILING

06 22 00.24 MECHANICAL SCREEN/ ROOF

06 22 00.24A ROOF TOP EQUIPMENT SCREEN/ GUARD

06 22 00.25 MECHANICAL SCREEN/ FLOOR

06 22 00.26 MECHANICAL SCREEN ATTACHMENT DETAILS

06 22 00.27 DUCT CHASE WALL (INTERIOR SECTION)

06 22 00.28 1-HOUR FIRE RATED DUCT SHAFT DETAIL

06 22 00.30 VENTILATION UNIT ENCLOSURE/ EXTERIOR

06 22 00.36 FURRED SOFFIT

06 22 00.37 FURRED CEILING/ INTERIOR UNIT ENCLOSURE -

SECTION

06 22 00.39 ACCESS LADDER W/ CAGE AND BASE PLATFORM

06 22 00.45 MECHANICAL DUCT/PIPE VENTILATION THRU

SLOPED ROOF TYP.

06 22 00.46 MECHANICAL VENTILATION THROUGH EXTERIOR

2x WOOD FRAMED WALL

06 22 10.01 ATTIC DORMER VENT - COMPOSITION SHINGLE

06 22 10.02 ATTIC DORMER VENT - CONCRETE TILE

06 22 10.03 ATTIC TURBINE VENT

06 22 10.04 ATTIC GABLE VENT

06 22 10.05 ATTIC EAVE VENT

DIVISION 8 - OPENINGS

08 11 69.01 NEW ACOUSTICAL STORM DOOR

08 14 00.01 NEW METAL ACOUSTIC DOOR

08 14 00.02 NEW DOOR LEAF IN (E) METAL FRAME

08 14 00.03 NEW EXTERIOR ACOUSTICAL DOOR - SINGLE

FAMILY

08 14 00.04 NEW INTERIOR DOOR

08 14 00.05 NEW INTERIOR MECHANICAL CLOSET DOOR

08 14 00.06 NEW EXTERIOR ACOUSTICAL DOOR -

MULTIFAMILY

08 32 13.01 NEW ACOUSTIC SLIDING DOOR

08 50 00.01 SCHEMATIC FRAMING FOR WINDOW WIDENING

08 50 00.02 ALLOWABLE HEADER SPANS

08 50 00.03A FASTENING SCHEDULE I

08 50 00.03B FASTENING SCHEDULE II

08 50 00.04 RETROFIT INSTALLATION AT EXISTING WOOD

FRAME WINDOW WITH LOWERED SILL

08 50 00.05 MODIFICATION OF STEEL PIPE CORNER POST

08 50 00.07 (N) VINYL WINDOW AT (E) WOOD FRAME - TILE

SILL

08 50 00.08 INSTALLATION AT (E) INTERIOR RAISED SILL WITH

TILE OR STONE

08 50 00.09 SECONDARY WINDOW AT GARDEN WINDOW

08 50 00.11 BAY WINDOW MODIFICATION

08 50 00.13 (N) VINYL WINDOW AT (E) ALUMINUM FRAME -

TILE SILL

08 50 00.15 BAY/ BOW WINDOW MODIFICATION - PLAN VIEW

08 50 00.16 BAY/ BOW WINDOW MODIFICATION SECTION VIEW

08 50 00.18 SCHEMATIC FRAMING FOR COMBINED WINDOW

OPENINGS

08 53 13.03 (N) VINYL NAIL-FIN WINDOW

08 53 13.04 RETROFIT VINYL INSTALLATION AT (E) ALUMINUM

FRAME - FLUSH FIN

08 53 13.05 RETROFIT VINYL INSTALLATION AT EXISTING

WOOD FRAME

08 60 00.01 SECONDARY GLAZING AT SKYLIGHT - 4'-0" MAX.

08 60 00.02 SECONDARY GLAZING AT SKYLIGHT - GREATER

THAN 4'-0"

08 81 00.01 REPLACEMENT GLAZING AT EXISTING FIXED LITE

08 81 00.02 INTERIOR SECONDARY GLAZING IN WOOD STOPS

08 81 00.03 EXTERIOR SECONDARY STORM WINDOW

08 81 00.04 INTERIOR SECONDARY STORM WINDOW

08 81 00.05 BOW WINDOW MODIFICATIONS/ DETAILS

W-9 REPLACEMENT GLAZING AT EXISTING FIXED LITE

Grand total: 59

DATE:

VERSION:

06/26/26

Checker

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

LAWA SHEET INDEX

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

00 00 00.00a

06/26/26

LAX RESIDENTIAL SOUND INSULATION DETAILS

DIVISION 22 - PLUMBING

22 00 00.01 FRENCH DRAIN FOR CONDENSATE DRAIN

22 00 00.02 CONDENSATE DRAIN PIPING AND TRAP

22 00 00.03 CONDENSATE DRAIN TO TAILPIECE

22 00 00.04 CONDENSATE PUMP INSTALLATION

22 00 00.05 CONDENSATE DRAIN PIPING SUPPORT

22 00 00.06 GAS PIPING ROUGH-IN SHUT OFF VALVE & DIRT

LEG/ SEDIMENT TRAP

22 00 00.07 GAS PIPING CONNECTION MULTI-FAMILY UNIT

22 00 00.08 GAS PIPING CONNECTION SINGLE FAMILY UNIT

DIVISION 23 - MECHANICAL

23 09 00.01 SPLIT SYSTEM & PACKAGE UNIT CONTROL

23 09 00.02 THERMOSTAT CONTROL WITING SPLIT SYSTEM

23 20 00.01 HVAC AND PLUMBING THROUGH ROOF

23 20 00.02 WALL PENETRATION FOR HVAC & PLUMBING

PIPING

23 20 00.03 UNDERGROUND INSTALLATION OF

REFRIGERATNT PIPING

23 20 00.04 EXTERNAL PIPING COVER

23 20 00.05 WALL PENETRATION FOR MECHANICAL &

PLUMBING PIPING

23 31 00.01 ROUND LOW AND MEDIUM PRESSURE

DUCTWORK

23 31 00.02 MAIN DUCT SUPPORT

23 31 00.03 DUCT ROOF PENETRATION

23 31 00.04 RECTANGULAR DUCT FITTINGS, ELBOW,

OFFSETS AND TRANSITIONS

23 31 00.05 EXTERNAL DUCT ASSEMBLY

23 31 00.06 FLEXIBLE DUCT TO METAL DUCT CONNECTIONS

AND DUCT SUPPORTS

23 31 00.07 ROOF AND WALL DUCT PENETRATION

23 34 00.01 CEILING MOUNTED BATH EXHAUST FAN

23 37 00.02 SUPPLY AIR WALL DIFFUSER

23 37 00.03 CONCENTRIC VENT UP THROUGH ROOF

23 54 00.01 VERTICAL FORCED AIR UNIT DETAIL

23 54 00.02 HORIZONTAL FAU ASSEMBLY IN ATTIC DETAIL

23 54 00.03 CONCENTRIC VENT UP THROUGH ROOF

23 54 00.04 FAU COMBUSTION AIR/ EXHAUST VENT

THROUGH WALL

23 54 00.05 FLUE VENT THRU ROOF

23 54 00.06 COMBUSTION AIR DUCT THRU ROOF

23 54 00.07 RETURN AIR PLENUM DETAIL

23 81 00.01 CONDENSING UNIT ASSEMBLY ON SLOPED

ROOF & GRADE LEVEL

23 81 00.02 CONDENSING UNIT - CLEARANCE REQUIRED

23 81 00.03 ROOF CURB CONNECTION

23 81 00.04 PACKAGED UNIT ON ROOF (DOWN DISCHARGE)

23 81 00.05 PACKAGED UNIT ON ROOF (SIDE DISCHARGE)

23 81 26.01 CONDENSING UNIT MOUNTING ON GROUND

DETAIL

23 81 26.04 PLATFORM DETAIL FOR NEW CONDENSING

UNITS

DIVISION 26 - ELECTRICAL

26 05 00.01 WALL PENETRATION FOR CONDUIT

26 05 00.02 ROOF PENETRATION FOR CONDUIT

26 05 00.04 ELECTRICAL CONNECTION FOR PACKAGED

HVAC UNIT ON ROOF TOP

26 05 00.05 ELECTRICAL CONNECTION FOR CONDENSING

UNIT ON ROOF TOP

26 05 00.06 ELECTRICAL CONNECTION FOR CONDENSING

UNIT AT GRADE LEVEL

26 05 00.07 ELECTRICAL CONNECTION FOR HORIZONTAL

FAU IN ATTIC

26 05 00.08 ELECTRICAL CONNECTION FOR VERITICAL

UPLOW FAU IN A CLOSET

26 05 00.09 ELECTRICAL CONNECTION FOR BATH EXHAUST

FAN

26 05 00.11 KNOB & TUBE WIRING REPLACEMENT IN ATTIC

(OR BASEMENT) SPACE

26 05 26.03 GROUNDING FOR NEW ELECTRICAL SERVICE

PANEL

26 05 43.15 ELECTRICAL TRENCH DETAIL

26 27 13.12 SCE STANDARDS FOR NEW COMBINATION

METER, UNDERGROUND SERVICE

26 27 13.14 SCE STANDARDS FOR NEW COMBINATION

METERS, MULTIPLE-FAMILY DWELLINGS

Grand total: 52

BUILDING WALL

CONDENSING UNIT / HEAT PUMP

NOTES:

1. PROVIDE MIN. 3' CLEAR SPACE FROM COIL SIDE AND COMPRESSOR END.

2. MAINTAIN MIN. 5' CLEARANCE TO ANY OBSTRUCTION ABOVE UNIT.

3. MAINTAIN 8" MIN. CLEARANCE FROM FAN SIDE AND COIL END.

4. ANCHOR CONDENSING UNIT TO PAD PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

5. LOCATE CONDENSING UNIT TO CLEAR ALL (E) ELECTRICAL J-BOX, (E) ELECTRICAL OUTLETS, AND (E) HOUSE BIBS.

LOCATION ON PLAN IS DIAGRAMMATIC; CONTRACTOR SHALL VERIFY SITE CONDITIONS.

6. OBTAIN BUILDING/PLANNING DEPARTMENT APPROVAL WHEN UNIT ENCROACHES ON SIDE YARD SET BACKS.

MORTAR FILLED

ROUNDED AT TOP

4" ⌀ STEEL PIPE NOT

GALVANIZED

24" BELOW GRADE AND

36" ABOVE GRADE

PAINT BRIGHT YELLOW

SLOPE

EXISTING PAVING

12" x 12" x 24"

CONCRETE FOOTING

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1" = 1'-0"

BOLLARD DETAIL

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

05 58 00.01

NOTES:

1. METERS LOCATED ON A WALL ADJACENT TO ANY PARKING AREA, OR AREA ACCESSIBLE TO VEHICULAR TRAFFIC, SHALL BE

PROTECTED BY NON-REMOVABLE BARRIERS. WHEEL STOPS AND REMOVABLE BARRIERS ARE NOT ACCEPTABLE SUBSTITUTES.

MAINTAIN A MINIMUM OF THREE FEET OF CLEAR AND LEVEL WORKING SPACE IN FRONT OF ALL SERVICE EQUIPMENT ENCLOSURES. BARRIERS MUST BE SO POSITIONED AS TO ALLOW ALL SERVICE EQUIPMENT DOORS/ PANELS TO BE OPENED 90

DEGREES.

2. USE FOUR-INCH GALVANIZED STEEL PIPE (1/4" INCH MINIMUM WALL) FILLED WITH CONCRETE.

3. THE CONCRETE ENCASEMENT SHALL BE A MINIMUM OF SIX INCHES THICK IN STABLE SOIL AND 12 INCHES THICK IN SANDY OR

UNSTABLE SOIL.

4. BARRIERS MUST BE INSTALLED IN LINE WITH EACH END OF THE SERVICE EQUIPMENT TO PREVENT VEHICLE CONTACT. THE

DISTANCE BETWEEN BARRIERS SHALL NOT EXCEED 4'-6".

5. BEFORE EXCAVATING FOR THE BARRIERS, CALL DIG ALERT AT 1-811-227-2600 TO MARK-OUT SERVICE. CALL AT LEAST 48

HOURS PRIOR TO EXCAVATING.

CONCRETE CAP

ROUNDED AT TOP

CONCRETE FILLED

SLOPE

FINAL GRADE

6"

E

M B

E D

T O

T A

L L

E N

G T

H

A

B V

G

R A

D E

SEE NOTE 2

SECTION VIEW

PLAN VIEW

3'-0" MIN.

M

A X

SEE

NOTE 4

PULL CAN/ SECTION

OR METERS SEE

NOTE 1

4'-6"

MAX

4'-6"

MAX

PARKING SPACES OR

VEHICULAR TRAFFIC

SEE

NOTE 4

M

IN

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1" = 1'-0"

NON-REMOVEABLE BOLLARD

DETAIL

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

05 58 00.02

2X4 INFILL WALL FRAMING;

PROVIDE TOP PLATE & BOTTOM

SILL AND MIN OF 3 STUDS PER

OPENING

1/2" GYPSUM BOARD ALIGNED W

(E) INTERIOR WALL FINISH.

TEXTURE AND PAINT WALL

SURFACE TO MATCH (E)

ADJACENT WALL SURFACES

(N) EXTERIOR WALL FINISH

MATCHING AND ALIGNED WITH

(E) EXTERIOR WALL FINIS.

TEXTURE AND PAINT WALL

SURFACE TO MATCH (E)

ADJACENT WALL SURFACE

(E) EXTERIOR WALL FINISH

(E) WALL BLOCKING AT

PERIMETER OF OPENING,

VERIFY CONDITION IN FIELD

REMOVE (E) THROUGH-WALL AC UNIT

OR SIMILAR ITEM (I.E., PET DOOR)

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

EXTERIOR WALL PATCHING

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 10 53.01

(N) SCREEN (TYP.).

SEE DETAIL 06 22 00.24 & 24A

(N) POST & BRACE (TYP.)

(N) FLASHING (TYP.)

(N) MECH. EQUIP. OR

DUCTWORK

5'-0" FROM ROOF RIDGE TO

CENTER OF MECH. EQUIP.

(N) ROOF CURB, SEE

MANUF. INSTALLATION

INSTRUCTIONS

SEE DETAIL 23 81 00.03

FOR CURB

CONNECTIONS

CEILING JOIST

(E) 2X4 RAFTERS @ 24"

O.C. (N) BLOCKING (TYP.)

REMOVE & REPLACE (E) WOOD

DECKING AS REQUIRED TO

INSTALL (N) BLOCKING

EXTERIOR WALL

REMOVE (E) ROOFING IN A WORK

AREA, REPLACE W/ (N) ROOFING TO

MATCH (E)

NOTE: OPPOSITE HAND LAYOUT FOR REVERSE ROOF SLOPE

M

IN

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

MECHANICAL SCREEN - SLOPED

ROOF

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.16

ATTIC

ADDITIONAL INSULATION

SHALL BE INSTALLED TO

ACHIEVE MIN. R-49

INSULATION VALUE

17"

14 1/2"

FF 109X DOME

INTUMESCENT

INSERT

FASTENER

2"

R 6 1/2"

/4

5/8"

EXISTING RECESSED

LIGHT FIXTURE

EXISTING CEILING

INTERIOR

AA

WOOD JOITS

TENMAT FF109X COVER OVER FIXTURE

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

RECESSED LIGHT FIXTURE

(SECTION VIEW)

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.18

06/26/26

Checker

NOTE:

Install the TENMAT following manufacturer’s instructions

EXISTING ROOF

STRUCTURE

CLEAR SPACE FOR

VENTILATION

EXISTING EAVE

VENT

EXTERIOR

EXISTING WALL

CONSTRUCTION

INTERIOR 12" LENGTH OF R-19 BATT

INSULATION TO ENSURE

CLEAR VENTILATION SPACE

AT EAVE VENT. FIT TIGHTLY

BETWEEN JOISTS AT EACH

EAVE VENT

ATTIC

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

INSULATION BARRIER FOR EAVE

VENTS (SECTION VIEW)

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.20

PROVIDE (N) DOUBLE HEADERS AS

NECESSARY FOR (N) ATTIC ACCESS

PANEL. CONNECT THE HEADERS TO

ADJACENT CEILING JOIST WITH

FRAMING ANCHORS. (N) HEADERS MUST

BE THE SAME SIZE AS CEILING JOISTS

(E) CEILING JOIST

1/8" GAP ON ALL SIDES

3" RIGID FIBERGLASS

INSULATION BOARD

MECHANICALLY FASTENED TO

PANEL

(E) OR (N) PERIMETER

FRAMING

(N) 5/8" THICK BIRCH VENEER PLYWOOD

PANEL. PAINT PANEL TO MATCH (E)

CEILING FINISH

1"X4" STOP THROUGHOUT INSIDE

PERIMETER

(N) ATTIC OPENING SIZED TO MEET

CODE. NET CLEAR OPENING TO BE

MEASURED FROM INSIDE OF TRIM

PK 22 PEMKOPRENE PRESSURE

SENSITIVE GASKETING ATTACHED TO

TOP OF 1"X4" STOP - TYP., ALL

AROUND

(E) CEILING

(N) 1 5/8" X1/2" PINE CASING W/

MITERED CORNERS SECURED W/

FINISH NAILS. SET NAILS AND

CONCEAL HOLES PRIOR TO THE

APPLICATION OF FINISH

NOTE:

1. PRIME AND PAINT ALL NEW EXPOSED WOOD (STOPS, TRIM, PANEL, ETC.) TO MATCH SURROUNDING SURFACE.

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

RECESSED ATTIC ACCESS HATCH

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.21

1/8" GAP ON ALL SIDES

(N) DOOR PANEL

PK22 PEMKOPRENE PRESSURE

SENSITIVE GASKETING ATTACHED TO

BACK OF CASING TYPICAL ALL AROUND

PROVIDE (N) DOUBLE HEADERS AS NECESSARY

FOR (N) ATTIC ACCESS PANEL CONNECT THE

HEADERS TO ADJACENT CEILING JOISTS WITH

FRAMING ANCHORS. (N) HEADERS MUST BE THE

SAME SIZE AS CEILING JOISTS.

ENLARGED DETAIL

1'-5/8".

1/2".

(E) CEILING JOIST (E) OR (N) PERIMETER FRAMING

(N) 5/8" THICK BIRCH VENEER PLYWOOD

PANEL. FLUSH W/ CEILING, PAINT TO MATCH

(E) CEILING FINISH

(N) ATTIC OPENING SIZED TO MEET CODE

NET CLEAR OPENING TO BE MEASURED

FROM INSIDE EDGE OF TRIM

(E) CEILING

SEE DETAIL BELOW.

(N) 1-5/8" X 1/2" PINE CASING W/ MITERED

CORNERS SECURED W/ FINISH NAILS. SET NAILS

AND CONCEAL HOLES PRIOR TO THE

APPLICATION OF FINISH

3" RIGID FIBERGLASS INSULATION

BOARD MECHANICALLY FASTENED

TO PANEL

NOTE:

1. PRIME AND PAINT ALL NEW EXPOSED WOOD (STOPS, TRIM, PANEL, ETC.) TO MATCH SURROUNDING SURFACE.

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1/2" = 1'-0"

ATTIC ACCESS HATCH FLUSH WITH

CEILING

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.22

NEW 2X FRAMING AT PERIMETER

OF ATTIC ACCESS PANEL

ROUGH OPENING - DOOR SIZE + 0.25"

LATCH-BOLT COVER EXTENDS 1/2" BEYOND OUTSIDE EDGE OF FRAME

LOCK-BOLT COVER

1'' FLANGE

FLUSH PIANO HINGE

SPRING FOR

AUTO-CLOSE

FEATURE

INTERIOR

RELEASE MUST

REMAIN IN PLACE

TO MAINTAIN FIRE

RATING

LOCK-BOLT COVER

1'' FLANGE

NOTE:

RETURN NEW GWB FINISH UP ALL

4-SIDES OF RE-FRAMED OPENING

NOTE:

1. CUT BACK EXISTING CEILING SURFACE TO ALLOW INSTALLATION, PATCH AND FINISH TO MATCH EXISTING.

2. SIZE NEW DOOR AND ENLARGE ROUGH OPENING PER MANUFACTURER'S CALCULATIONS AND

RECOMMENDATIONS TO MEET SPECIFIED CLEAR OPENING, SEE DOOR SCHEDULE.

3. FINISH DOOR TO MATCH CEILING.

4. PROVIDE MANUFACTURER'S RECOMMENDED NUMBER OF LATCHES.

5. REFER TO _____ FOR REQUIRED FRAMING.

1. FRAME: COLD ROLLED STEEL MIN. 16 GA

2. DOOR: COLD ROLLED STEEL MIN. 20 GA

3. HINGE: FLUSH CONTINUOUS HINGE

6. LOCK: KNURLED KNOB/KEYED SLAM LATCH

7. 2" THICK FIRE RATED MINERAL WOOL, 8 R-VALUE

INTERIOR

RELEASE

MECHANISM

SPRING

MOUNT

BRACKET

EXISTING CEILING

ASSEMBLY

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1/2" = 1'-0"

FIRE RATED ATTIC ACCESS PANEL

IN CEILING

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.22A

1. ALL WOOD SHALL BE SEALED AND PRIMED BEFORE INSTALLATION

2. ALL SURFACES EXPOSED TO VIEW SHALL BE PAINTED WITH TWO COATS OF LATEX FLAT, COLOR TO BE SELECTED BY

OWNER (SHALL NOT BE A DARK HUE SO THAT HEAT ABSORPTION IS MINIMIZED).

3. LOCATION OF EQUIPMENT AND SCREEN, MUST BE CONSULTED WITH CONSTRUCTION MANAGER

REAR ELEVATION STREET ELEVATION

GALV. CAP

FLASHING

TEXTURE 1-11

PLYWOOD, SEE NOTE #3

SERVICE PANEL TO

FACE GATE

2"X4" BRACE SLOPED AT

60 DEGREES, TYP.

CONTINUOUS SILL, TWO

SIZES PARALLEL W/ ROOF

SLOPE

SCREEN STRUCTURE FRONT &

BACK SEE ENLARGED DETAILS

ENLARGED PLAN DETAIL

GALV. CAP FLASHING

HINGED GATE 30" MIN.

CLR OPENING-

OUTSWING, CENTERED

ON SCREEN WALL. 3"

(HOT DIP) GALV. HINGES

& BARREL BOLT

TEXTURE 1-11

PLYWOOD.

SEE NOTE #3

CUT BOTTOM OF GATE

TO CLEAR ROOF (WHEN

OPEN)

CLR. FOR DRAINAGE,

TYP.

SECTION A

GALV. CAP FLASHING

2X4 TOP PLATE PRESSURE

TREATED RIPPED FOR DRAINAGE

2X4 STUDS AT 24" O.C.

MAX.

2X4 BRACE SCREWED TO

STUDS W/ 8" WOOD SCREWS.

FACE NAILED GALV. PLATE

CONNECTOR ON FAR SIDE.

2X4 BACKUP ON UNDERSIDE OF

SHEATHING AT EACH SILL PIECE

2 - 8# SCREWS AT TOE BED OF

ASPHALT MASTIC

5/8" A-C MARINE PLYWOOD

2X4X24 TREATED SILL ATTACHED

THROUGH ROOF W/ 3/8" BOLTS -

SET SILL IN BED OF ASPHALT

MASTIC

2X4

STRONG

BACK

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

MECHANICAL SCREEN/ ROOF

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.24

1. ALL WOOD SHALL BE SEALED AND PRIMED BEFORE INSTALLATION.

2. ALL SURFACES EXPOSED TO VIEW SHALL BE PAINTED WITH TWO COATS OF LATEX FLAT. COLOR TO BE SELECTED BY

OWNER (SHALL NOT BE A DARK HUE SO THAT HEAT ABSORPTION IS MINIMIZED.)

3. LOCATION OF EQUIPMENT AND SCREEN, MUST BE CONSULTED WITH CONSTRUCTION MANAGER

4. ANY OTHER SIDE REQUIRING GUARDS SHALL FOLLOW THE SAME DETAILS AS SHOWN IN SECTION A.

STREET ELEVATION REAR ELEVATION

ENLARGED PLAN DETAIL

SECTION A

CLR. FOR

DRAINAGE, TYP

TEXTURE 1-11

PLYWOOD. SEE

NOTE #3

GALV. CAP

FLASHING

SCREEN STRUCTURE

FRONT & BACK, SEE

ENLARGED DETAILS

CONTINUOUS SILL, TWO

SIDES PARALLEL WITH

ROOF SLOPE

2"X4" BRACE SLOPED AT

45° - TYP.

SERVICE PANEL TO

FACE GATE

2"X4"X24" TREATED SILL ATTACHED

THROUGH ROOF WITH 3/8" BOLTS -

SET SILL IN BED OF ASPHALT MASTIC

R O

O F

S L

O P

E

5/8" A-C MARINE PLYWD.

GALV. CAP FLASHING

2"X4" TOP PLATE PRESSURE

TREATED & RIPPED FOR DRAINAGE

2"X4" STUDS AT 21" O.C. MAX

2"X4" BRACE AT MIN. 45° TO THE

STUD, SCREWED TO STUDS W/ #8

WOOD SCREWS

BOTTOM OF STUDS TO BE

ATTACHED TO THE PLATE

BELOW WITH SIMPSON SSP

PLATE

BOTTOM OF BRACES TO BE

ATTACHED TO THE PLATE

BELOW WITH SIMPSON H3

PLATE

2"X4" BACKUP ON UNDERSIDE OF

SHEATHING AT EACH SILL PIECE

BED OF ASPHALT MASTIC

2"X4"

STRONG

BACK

30" MIN. CLR.

ALL AROUND

GUARD SIDE

CLR FOR

DRAINAGE - TYP.

CUT BOTTOM OF GATE TO

CLR ROOF (WHEN OPEN)

TEXTURE 1-11 PLYWOOD

SEE NOTE #3

HINGED GATE 30" MIN CLR

OPENING - OUTSWING,

CENTERED ON SCREEN

WALL. 3" (HOT DIP)

GALVANIZED HINGES &

BARREL BOLT

GALV. CAP FLASHING

MECH.

EQUIP.

/3

L O

R G

R E

A T

E R

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

ROOF TOP EQUIPMENT SCREEN/

GUARD

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.24A

1. FOR DETAILS A, B-1, AND B-2 REFER TO DETAIL 06 22 00.26.

2. PLYWOOD SHALL BE PRIMED AND PAINTED WITH 2 COATS OF SEMI-GLOSS EXTERIOR LATEX - BASE PAINT. COLOR TO

MATCH BUILDING WALL.

SIMPSON MCB-44 IN 12"

DIAMETER BY 12" DEEP

CONCRETE FOOTING

AT TWO CORNERS

3/4" A-FACE MARINE

PLYWOOD ON THREE

SIDES

CONDENSER UNIT OR

HEAT PUMP

BUILDING WALL

EXISTING GRADE

SIDE VIEW

TOP VIEW

PAD

CONDENSER

UNIT OR HEAT

PUMP

BUILDING WALLCORNER BRACE

UNDER TOP

STRONGBACK AND

AT BOTTOM

14" LONG 1 1/2" WIDE

GALV. FLAT BAR WITH

THUMB TURN

FASTENERS. PAINT BAR

WITH RUST RESISTANT

ENAMEL.

HINGED CORNER AT

ACCESS SIDE OF

CONDENSING UNIT/

HEAT PUMP

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

MECHANICAL SCREEN/ FLOOR

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.25

GALV. CAP FLASHING

GALV. DECK SCREWS IN

PRE-DRILLED HOLES.

COUNTER SINK BUT DO

NOT FILL

2"X4" P.T. TOP STRONG

BACK

TOP EDGE

2"X4" P.T. POST

RABETTED CORNER

CORNER DETAIL

GALV. HINGE AT TOP

AND BOTTOM

2"X4" P.T. POST

2"X2" P.T. STIFFENER

PROVIDE HINGED PANEL AT

ACCESS SIDE OF

CONDENSING UNIT/ HEAT

PUMP ONLY

CORNER DETAIL AT ACCESSB2

B1

A

NOTES:

1. REFER TO DETAIL 06 22 00-25

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

MECHANICAL SCREEN

ATTACHMENT DETAILS

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.26

(E) CEILING

(N) 25 GA. 2 1/2" STEEL

BOTTOM TRACK

(N) 25 GA. 2 1/2" STEEL

STUDS @ 24" O.C. MAX.

(N) 1/2" GYP. BD. TAPE,

FILL AND SAND JOINTS.

TEXTURE & PAINT TO

MATCH (E) WALL

ROOM

(N) 25 GA. 2 1/2" STEEL

BOTTOM TRACK

(N) BASE TO MATCH

(E) BASE

FINISH FLOOR

(N) 1/2" ⌀ EXPULSION BOLT @ 18"

O.C. (3" EMBED) TYP.

(N) TEK SCREW

EACH SIDE TYP.

CHASE

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

DUCT CHASE WALL (INTERIOR

SECTION)

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.27

OUTSIDE

AIR DUCTS

(E) ROOF

CONSTRUCTION

(E) CEILING

(E) WALL

20 GA. "J"

RUNNERS

TO

ROOF

TO

ROOF

TO FAN

COIL UNIT

FURRED SOFFIT, SEE

DETAIL 06 22 00.36

1HR SHAFT WALL

ASSEMBLY W/ 2-1/2"

20 GA. C-H STUDS, 1"

GYP LINER AND 5/8"

TYPE X GYP. BD.

FINISH TO MATCH (E)

BASE TO MATCH (E)

PROFILE & FINISH

1HR THRU-PENETRATION

FIRESTOP SYSTEM AT (E)

FLOOR & CLG

PENETRATIONS

TO FAN COIL UNIT

CHASE WALL

AS REQUIRED

FURRED SOFFIT, SEE

DETAIL 06 22 00.36

(E) BASE

(E) FLOOR

(E) CEILING

(E) FIRE RATED WALL

1HR. THRU-PENETRATION

FIRESTOP SYSTEM AT (E)

WALL PENETRATIONS

(E) FLOORING/ CLG.

CONSTRUCTION

NOTES:

1. GALVANIZED STEEL DUCTS RUN THROUGH FIRE RATED STRUCTURE WITHOUT CHASE AND SOFFIT: MAX 16" DIAMETER OR

SMALLER AND MINIMUM OF 24 GA.

2. MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR FIRE-RATED SEALANT ARE TO SUPERSEDE ANY INSTALLATION

REQUIREMENTS OF THIS DETAIL.

3. CONTRACTOR MUST FILL DEPTHS OF GAP WITH SEALANT TO MATCH THICKNESS OF EXISTING WALL MATERIAL (I.E.

DRYWALL) NOT LESS THAN 1/2" DEEP AND SUCH THAT A MINIMUM OF THREE-EIGHTH OF AN INCH (3/8") CROWN IS FORMED

AROUND THE DUCT.

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

1-HOUR FIRE RATED DUCT SHAFT

DETAIL

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.28

1. GENERAL CONTRACTOR SHALL FIELD VERITY ALL EXISTING CONDITIONS AND MEASUREMENTS PRIOR TO THE START OF

THE WORK. REFER TO SPECS FOR ADDITIONAL REQUIREMENTS. THIS DETAIL IS INTENDED AS A GENERIC GUIDE FOR THE CONSTRUCTION OF A VENTILATION UNIT ENCLOSURE. GENERAL CONTRACTOR TO SUBMIT SHOP DRAWINGS FOR

THE ACTUAL ENCLOSURE.

LINE OF EXISTING EXTERIOR WALL

2-1/4" 25 GA. GALVANIZED C SHAPED METAL STUD SECURED TO (E) WOOD FRAMING

WITH 2-1/4" LONG SCREWS @ 16" O.C. TYP. AT ALL METAL STUD TO WOOD FRAME

CONNECTIONS. CONTRACTORS MUST FIELD VERIFY LOCATION OF (E) WOOD

FRAMING

C-SHAPED, 2-1/2" 25 GA GALVANIZED METAL STUDS SECURED TO

SIDE WALL TRACKS WITH PAN HEAD TYPE "S" SCREWS @16" O.C.

(TYP) TO PROVIDE FRAME FOR BUILDING FELT AND WIRE MESH

AND STUCCO. PAINT AND FINISH TO MATCH ADJACENT AREA.

VENTILATION UNIT

ATTACH FACTORY SUPPLIED MOUNTING

BRACKETS AND RUBBER GROMMETS TO THE

BUILDING FRAMING MEMBERS WITH PAN HEAD

NO. 10 SCREWS PER MANUF. WRITTEN

INSTRUCTIONS.

2-1/2" 25 GA. GALVANIZED C SHAPED METAL STUD

SECURED TO EXISTING WOOD FRAMING WITH 2-1/4" LONG

SCREWS @ 16" O.C. TYP. AT ALL METAL STUD TO WOOD

FRAME CONNECTIONS CONTRACTOR MUST FIELD VERIFY

LOCATION OF (E) WOOD FRAMING.

(E) 2" X6" CEILING JOIST @16" O.C. FIELD VERIFICATION

REQUIRED BY CONTRACTOR

(E) STUCCO

CUT (E) STUCCO AS NECESSARY

TO OVERLAP THE NEW BUILDING

PAPER OVER EXISTING BUILDING

PAPER TO PROVIDE APPROPRIATE

FLASHING AND WATER TIGHT

CONDITION. PATCH AND PAINT

STUCCO.

(N) 22"x22" ACCESS DOOR (EXHAUST FAN) AND (N) 30"x30" ACCESS

DOOR (ERV SYSTEM) MANUFACTURED BY KARP (USE MODEL

D5C-214M STAINLESS STEEL TYPE). INSTALL PER

MANUFACTURER'S WRITTEN INSTRUCTIONS.

CONTINUOUS BRACE ANGLE

PORTLAND CEMENT 7/8" THICKNESS. METAL LATH

ATTACH TO STUDS WITH NO. 6-20 SCREWS. "T-NAILS",

OR STAPLES SPACED 6" O.C. MAX. AND DRIVEN

THROUGH GYPSUM SHEATHING.

7'-0" MIN. PER CBC 1208.2.1 TO FIN. FLOOR

BULLNOSE WHERE

EXISTING, TYP.

APPROX.

12"-14" ±

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1" = 1'-0"

VENTILATION UNIT ENCLOSURE/

EXTERIOR

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.30

25 GA. 2 1/2" STEEL

TOP TRACK

DUCT BEYOND

GRILLE BEYOND

CUT AND BLOCK

OPENINGS IN (E) WALL

AS REQUIRED FOR

DUCTS

(E) WALL

GYPSUM BOARD - TAPE AND

FILL JOINTS AND CORNERS.

SAND, TEXTURE AND POINT

TO MATCH (E) CEILING.

PROVIDE ACCESS PANEL AT

DAMPERS.

25 GA. 2 1/2"

STEEL BOTTOM

TRACK

25 GA. 2 1/2" STEEL

STUDS @ 24" O.C.

(E) CEILING

DUCT - SEE PLAN

25 GA. 2 1/2"

STEEL LEDGER

METAL OR VINYL

CORNER BEAD

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1" = 1'-0"

FURRED SOFFIT

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.36

LINE OF (E) 2"X6" CEILING JOIST @16" O.C.

FIELD VERIFICATION REQUIRED BY

CONTRACTOR

(E) WALL

7'-0" MIN. PER CBC 1208.2.1

TO FIN. FLOOR

(E) WALL

ATTACH MECHANICAL EQUIPMENT PER

MANUFACTURER'S WRITTEN

INSTRUCTION.

2-1/2" 25 GA. GALV. C SHAPED METAL

STUD SECURED TO (E) WOOD FRAMING

W/ 2-1/4" LONG SCREWS @ 16" O.C.

TYP. AT ALL METAL STUD TO WOOD

FRAME CONNECTIONS. CONTRACTOR

MUST FIELD VERIFY LOCATION OF (E)

WOOD FRAMING, TYP.

NOTE:

1. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL (E) CONDITIONS AND MEASUREMENTS PRIOR TO THE START OF ANY

WORK. REFER TO SPECS FOR ADDITIONAL REQUIREMENTS. THIS DETAIL IS INTENDED AS A GENERIC GUIDE FOR THE CONSTRUCTION OF FURRED CEILING ENCLOSING MECHANICAL EQUIPMENT/ COMPONENT. GENERAL CONTRACTOR TO

SUBMIT SHOP DRAWINGS FOR THE ACTUAL ENCLOSURE.

2. ANY ROOM WITH A FURRED CEILING SHALL BE REQUIRED TO HAVE THE MINIMUM CEILING HEIGHT IN TWO-THIRDS OF THE AREA THEREOF, BUT IN NO CASE SHALL THE HEIGHT OF THE FURRED CEILING BE LESS THAN 7 FEET FROM THE FINISHED

FLOOR.

3. INSTALL MECHANICAL EQUIPMENT PER MANUFACTURER'S WRITTEN INSTRUCTIONS.

NEW 24" x 36" ELMDOR METAL WALL/CEILING

ACCESS DOOR WITH PATCHING, PAINT, AND

REPAIR TO MATCH ADJACENT SURFACES.

INSTALL PER MANUFACTURER'S WRITTEN

INSTRUCTIONS.

VENTILATION UNIT

ENERGY RECOVERY SYSTEM (ERV)

C-SHAPED, 2-1/2" 25. GA GALV. METAL

STUDS SECURED TO SIDEWALL TRACKS

WITH PAN HEAD TYPE "S" SCREWS @16"

O.C. (TYP) TO PROVIDE FRAME FOR (N)

5/8" DRYWALL AND/OR REPAIR OF (E)

DRYWALL PAINT AND FINISH TO MATCH

ADJACENT AREA

A P

P R

O X

T O

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

FURRED CEILING/ INTERIOR UNIT

ENCLOSURE - SECTION

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.37

11/10/25

DATE: 02/20/26

TOP HOOP BAR 3"

X1/4", TYP.

NOTE: SOME CAGE

VERTICAL BARS

OMITTED FOR

CLARITY

HASP RECEPTOR

WELDED TO RAIL

NOTES:

1. STEEL SHALL BE PRIMED WITH RUST RESISTANT PRIMER. PROVIDE TWO FINISH COATS OF EXTERIOR ENAMEL, COLOR TO

MATCH EXISTING WALL.

FRONT VIEW SECTION VIEW

ATTACHED BRACKET - TYP.

FOUR LOCATIONS

ROOF OVERHANG "NOTCHED"

FOR LADDER - PROVIDE NEW

WATERPROOF FLASHING

(E) SLOPED

ROOF

EXISTING

WALL

4"X4"X1/4" STEEL

BASE PLATE

48"X72"X4"

CONCRETE BASE W/

THICKENED EDGES

6"X2" STRUCTURAL

CHANNEL (ALL

AROUND) COPED &

WELDED AT CORNERS

1" OPEN STEEL

GRATE. WELD TO

FRAME

1/2" RADIUS - TYP.

3/8" X 2 1/2" CROSS

RAILS WELDED TO SIDE

RAILS

3/4" DIA. STEEL RUNGS @ 12"

O.C. WELDED TO RAILS

HOOP BETWEEN TOP AND

BOTTOM BAR 2"X1/4", TYP.

3/8" X 2" STEEL SIDE RAILS,

TYP.

HOOP BAR 3" X1/4", TYP.

WELD SIDE

RAILS TO

CHANNEL

BELOW

TWO DIAGONAL STRAP

BRACES

PROVIDE 6"X6"X1/4"

BEARING PLATE

2"X2"X3/8" LEGS WELDED TO

CHANNEL FRAME W/ 4"x4"x1/4"

BASE PLATE

7"

M a x

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

ACCESS LADDER W/ CAGE AND

BASE PLATFORM

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.39

NEW THRU-ROOF PENETRATION

STAINLESS STEEL CLAMPING RING

METAL FLASHING COLLAR OVER

MEMBRANE FLASHING COLLAR,

OVERLAP COLLAR ONTO

LOWER LAYER OF ROOF

SHINGLES

UPPER LAYER OF ASPHALT

ROOF SHINGLES

UPPER LAYER OF FULLY-CUT

MEMBRANE AROUND PIPE

PENETRATION AND LAP OVER

MEMBRANE COLLAR

EXISTING ROOFING FELT OVER

NEW LEAD FLASHING SLEEVE

3/4" PLYWOOD SHEATHING

WITH H-CLIPS, CUT PLYWOOD

AROUND PIPE PENETRATION

CLOSED CELL FOAM BACKER

ROD AND URETHANE SEALANT

AT PIPE PRIMER (AIR BARRIER)

RIGID INSULATION SURROUNDING

CLOSED CELL FOAM BACKER ROD

AND URETHANE SEALANT AT PIPE

PERIMETER

ROOF RAFTER

LOWER LAYER OF FULLY-ADHERED

ROOF MEMBRANE

LOWER LAYER OF ASPHALT

ROOF SHINGLES

NEW GSW FLASHING SLEEVE FLARED

TOP WITH EDGE WITH STRAP

RE-INSTALLED EXISTING ROOFING

MATERIAL OR PROVIDE NEW

THERMOPLASTIC SPLIT DUCT-SEAL

MEMBRANE FLASHING COLLAR,

OVERLAP COLLAR ON TO LOWER

LAYER OF ROOF MEMBRANE

NEW POLYURETHANE SEALANT

NOTES:

1. CONTRACTOR TO PROVIDE WATER TIGHT ROOF.

2. PENETRATION GAPS GREATER THAN 1/4" REQUIRE BACKER ROD BEFORE APPLICATION OF M-BOND ADHESIVE.

4" MIN.

M

IN

M E

C H

A N

IC

A

L D

U C

T P

IP

E

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

MECHANICAL DUCT/PIPE

VENTILATION THRU SLOPED ROOF

TYP.

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.45

EXISTING SHEATHING

AND WALL INSULATION

INTERIOR WALL FINISHES

REMOVE EXISTING FINISHED

WALL, PATCH AND FINISH GWB

TO MATCH EXISTING

CONTINUOUS SEALANT

2X WOOD FRAMING

CONTINUOUS SEALANT

REMOVE EXISTING FINISHED

WALL, PATCH AND FINISH

GWB TO MATCH EXISTING

EXISTING SHEATHING

AND WALL INSULATION

MECHANICAL

DUCT

EXTERIOR INTERIOR

BAKER ROD AND CONTINUOUS SEALANT

24 GA. GALV. SHEET METAL FLASHING

TUCKED UNDER EXTERIOR WALL

FINISH, EXTEND FLASHING 4" UP WALL

VENTILATION FIXTURE. REFER TO

MECHANICAL DRAWINGS

2X2 P.T. BLOCKING SET IN

CONTINUOUS BEADS OF SEALANT,

4 SIDES

24 GA GALV. SHEET METAL

FLASHING @ SILL AND JAMBS

WEATHER RESISTANT BARRIER (WRB)/ SELF-

ADHERED MEMBRANE OVER (E) BUILDING

PAPER AND FOLD TO INTERIOR (APPLY

BEFORE INSTALLATION OF DUCT WORK)

CUT BACK OR REMOVE (E) EXTERIOR WALL

FINISH FOR INSTALLATION OF NEW VENTING

FIXTURE AND FLASHING; MODIFY AND

REINSTALL/ REPLACE WALL FINISH AS NEEDED

TO MATCH EXISTING, TYP.

EXISTING WALL FINISH

CUT BACK OR CAREFULLY LIFT EXISTING

WALL FINISH, WALL UNDER-LAYMENT/

BUILDING PAPER AND INSTALL TOP EDGE

OF WEATHER RESISTANT BARRIER (WRB)/

SELF-ADHERED MEMBRANE FLASHING

AGAINST EXISTING SHEATHING, LAPPED

OVER METAL FLASHING AND EXTEND

SELF-ADHERED MEMBRANE FLASHING 4"

MIN. UP WALL FROM TOP OF FLASHING

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

MECHANICAL VENTILATION

THROUGH EXTERIOR 2x WOOD

FRAMED WALL

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 00.46

(E) ROOF RAFTERS

(E) ROOF SHINGLES

CUT (E) ROOF TO INSTALL (N)

LOW PROFILE DORMER VENT

(MANUF: O'HAGIN, OR EQ).

(N) SEALANT (AROUND

VENT OPENING)

(N) SEALANT

(AROUND OUTER

FLANGE OF VENT)

NOTE:

1. INSTALL VENT PER MANUFACTURER'S INSTALLATION INSTRUCTION

2. SEAL ALL PENETRATIONS USING LOCALLY-APPROVED SEALANT

3. DISTRIBUTE REQUIRED VENTS BETWEEN UPPER ROOF AND LOWER ROOF WITH MIN 50% AT THE UPPER ROOF (1'-0" FROM

RIDGE) AND REMAINING AT THE LOWER ROOF (1'-0" FROM EAVE).

4. PROVIDE WATERPROOFING ASSEMBLY TO MATCH WITH (E) ROOF ASSEMBLY AND INSTALL PER MFR INSTALLATION

INSTRUCTIONS OR SMACNA WHICHEVER IS MORE STRINGENT

5. PROVIDE "FIRE & ICE" PER MFR IN WUI AREA AND CONTACT MFR FOR INSTALLATION INFORMATION

PROVIDE WIND

DIVERTER AT HIGH

WIND AREA

(70-110MPH) AND

WUI AREA

SECTION VIEW

PLAN VIEW

TYP.

4"

(N) ROOF SCREWS AT 4" O.C..

(N) SEALANT AT ALL

PENETRATIONS AND AROUND

VENT OPENING

(N) ROOF SHINGLES

AROUND VENT, PER

MANUF. INSTALLATION

INSTRUCTION

TYP.

1"

CUT (E) ROOF TO INSTALL (N)

LOW PROFILE DORMER VENT

(MANUF: O'HAGIN, OR EQ).

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

ATTIC DORMER VENT -

COMPOSITION SHINGLE

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 10.01

(E) ROOF RAFTERS

(E) TILE ROOF

REMOVE SURROUNDING ROOF

TILES. CUT (E) ROOF TO INSTALL

(N) CLAY MEDIUM PROFILE

DORMER VENT (MANUF: O'HAGIN,

OR EQ).

NOTE:

1. INSTALL VENT PER MANUFACTURER'S INSTALLATION INSTRUCTION

2. SEAL ALL PENETRATIONS USING LOCALLY-APPROVED SEALANT 3. DISTRIBUTE REQUIRED VENTS BETWEEN UPPER ROOF AND

LOWER ROOF WITH MIN 50% AT THE UPPER ROOF (1'-0" FROM

RIDGE) AND REMAINING AT THE LOWER ROOF (1'-0" FROM EAVE).

4. PROVIDE WATERPROOFING ASSEMBLY TO MATCH WITH (E) ROOF ASSEMBLY AND INSTALL PER MFR INSTALLATION

INSTRUCTIONS OR SMACNA WHICHEVER IS MORE STRINGENT

5. PROVIDE "FIRE & ICE" PER MFR IN WUI AREA AND CONTACT MFR FOR INSTALLATION INFORMATION

SEALANT (AROUND

VENT OPENING)

SEALANT AT GAPS

BETWEEN VENT COVER

AND SURROUNDING TILES

(E) UNDERLAYENT OVER THE VENT FLANGE, OR PROVIDE (N) AS

NEEDED. MATCH WITH (E) AND OVERLAP WITH (E), MIN 4" TYP.

VENT FLANGE OVER (E)

UNDERLAYMENT

SECTION VIEW

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

ATTIC DORMER VENT - CONCRETE

TILE

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 10.02

(N) TURBINE

(E) ROOF STRUCTURE

EXTERIOR

INTERIOR

LATERAL SECTION

(E) ROOF

STRUCTURE

CUT (E) ROOF OPENING

AS NECESSARY TO

INSTALL (N) TURBINE

VENT. SECURE WITH

NAILS AT ALL SIDES AND

SEAL ALL EXPOSED NAILS

WITH ROOFING CEMENT.

CROSS SECTION

FAN WHERE OCCURS

NOTE:

1. INSTALL VENT PER MANUFACTURER'S INSTALLATION INSTRUCTION

2. SEAL ALL PENETRATIONS USING LOCALLY-APPROVED SEALANT

3. PROVIDE BLOCKING AS REQUIRED FOR ATTACHMENT TO ROOF STRUCTURE

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1" = 1'-0"

ATTIC TURBINE VENT

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 10.03

EXISTING WALL

1. PROVIDE BLOCKING AS REQUIRED FOR ATTACHMENT TO STRUCTURE

2. SEAL ALL PENETRATIONS USING LOCALLY-APPROVED SEALANT

3. NEW BAFFEL SHALL BE AT LEAST AS WIDE AS THE NEW VENT OPENING

4. AFTER FABRICATION, BAFFLE SHALL BE SECURELY ATTACHED IN POSITION

5. PROVIDE SAF TO WRAP AROUND THE OPENING AND OVERLAP WITH WRB, MATCH FLASHING AND ALL MATERIALS WITH (E) WALL ASSEMBLY AND INSTALL PER MFR INSTALLATION INSTRUCTIONS.

SEALANT AND

BACKER ROD

SEALANT AND

BACKER ROD

CUT (E) WALL TO

INSTALL (N) GABLE

VENT (MANUF:

AIROLITE OR EQ).

ATTACH TO FRAME.

PATCH PAINT

ADJACENT SURFACES

TO MATCH EXISTING

(N) 2X6 FRAME, SET

PLUMB, SQUARE,

AND LEVEL FOR (N)

GABLE VENT

EXTERIOR INTERIOR

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

ATTIC GABLE VENT

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 10.04

CUT (E) EAVE AS NECESSARY

TO INSTALL (N) 2"X12" MIN

VENT, ATTACH WITH 1/2"

STAINLESS STEEL SMS.

PROVIDE APPROPRIATE

CAULKING FOR AN AIR TIGHT

SEAL. PATCH AND PAINT TO

MATCH (E) SURFACES

(E) WALL

(E) ROOFING AND ROOF

FRAMING

(N) 1/4" x 1/4" GALVANIZED

HARDWARE CLOTH

NOTE:

1. PROVIDE SAF TO WRAP AROUND THE OPENING AND OVERLAP WITH WRB, MATCH FLASHING AND ALL MATERIALS WITH (E) SOFFIT ASSEMBLY AND INSTALL PER MFR INSTALLATION INSTRUCTIONS.

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1 1/2" = 1'-0"

ATTIC EAVE VENT

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

06 22 10.05

(E) WALL

CONSTRUCTION

(E) OR (N) DOOR JAMB

WOOD FILLER AS REQUIRED

(N) SECONDARY DOOR AND

INTEGRAL JAMB

UNEVEN SURFACE

INTERFACE, CAULK GAP

ALL AROUND

CLEAR PINE OR FIR MOUNTING

BLOCK AS REQUIRED, 3/4"

THICK, MINIMUM

PLAN VIEW

NOTES:

1. THIS DETAIL IS INTENDED AS A GENERIC GUIDE TO THE INSTALLATION OF A SECONDARY HINGED DOOR (STORM DOOR).

2. ALL (N) WOOD SHALL BE PRIMED AND PAINTED TO MATCH (E) CONDITIONS.

STUCCO MOLDING, PATCH AND

REPAIR AS REQUIRED

(N) ACOUSTIC STORM DOOR

EXTERIOR INTERIOR

PROPERLY ADJUSTED

DOOR SHOE

ANCHOR PER MANUF.

RECOMMENDATIONS

BOTTOM SEAL

CONDITION VARIES

LEAD SHIELD @ CONCRETE

SLAB COND.

THRESHOLD

(E) FLOORING CONDITIONS

VARY, BUTT THRESHOLD TO

(E) OR PROVIDE ADDITION

TRIM AS REQUIRED

(N) ALUM. THRESHOLD

DOOR SHOE

WEATHER/ SOUND SEAL

(E) DOOR TO REMAIN

MOLDING TO REMAIN

HEAD

PROVIDE SILL NOSING AS

REQUIRED TO MAKE SEAL

WITH STORM DOOR

1/4" MIN (SHIM OUT

STORM DOOR AS

REQUIRED)

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

NEW ACOUSTICAL STORM DOOR

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 11 69.01

1. REMOVE (E) THRESHOLD AND PREPARE FLOOR TO ALLOW INSTALLATION OF (N) THRESHOLD.

2. PROVIDE 4 (N) HINGES.

3. DOOR SWEEP/ WEATHERSTRIPPING PROVIDED BY DOOR MANUFACTURER

HEAD - JAMB

SIMILAR

ACOUSTICAL FILLER BY

INSTALLER

1/8" MAX. CLEARANCE AT

JAMBS AND HEAD TYP.

INTERIOR

SPRING BRONZE SEAL

(N) METAL ACOUSTIC

DOOR

CONTINUOUS

SEALANT

EXTERIOR CASING,

WHERE OCCURS

1/2" FRAME SEAL

INTERIOR TRIM, WHERE

OCCURS

EXTERIOR

1/4" MAX. CLR

1/2" CLR. MAX. TO

TOP OF THRESHOLD

SEE SPEC

FINISHED FLOOR

ADA THRESHOLD;

SUPPLIED BY DOOR

MANUFACTURER

(N) CORNER PAD P112 PS

AT HINGED JAMB

DOOR BOTTOM

SUPPLIED BY DOOR

MANUFACTURER

(N) DRIP COVER

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3" = 1'-0"

NEW METAL ACOUSTIC DOOR

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 14 00.01

2. PROVIDE 4 (N) HINGES.

3. SEAL NUMBERS REFER TO PEMKO PRODUCTS.

HEAD - JAMB

SIMILAR

1/8" MAX. CLEARANCE AT

JAMBS AND HEAD TYP.

INTERIOR

CONTINUOUS

SEALANT

(E) METAL FRAME

EXTERIOR

FINISHED FLOOR

(N) RBP-119 SPRING

BRONZE SEALS

(N) ACOUSTIC DOOR

WEATHER STRIPPING

303 PK

1/4" MAX. CLR

(N) CORNER PAD P112 PS

AT HINGED JAMB

(N) PEMKO 234 APK

RECESSED INTO DOOR

BOTTOM

(N) PEMKO 2005

SET IN

CONTINUOUS BED

OF SEALANT, SEE

SPEC

(N) PEMKO 345

DRIP COVER

(N) CUSTOM

OAK SILL

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3" = 1'-0"

NEW DOOR LEAF IN (E) METAL

FRAME

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 14 00.02

2. PROVIDE 4 (N) HINGES.

3. SEAL NUMBERS REFER TO PEMKO PRODUCTS.

4. KERF SHALL BE .125-.120" WIDE X .375" DEEP.

5. MIN. SPACE BETWEEN DOOR FACE AND FACE OF WOOD STOP TO BE .3125" OR .5" MAX.

FINISHED FLOOR

PEMKO 94518 OR 95518 TO

SUIT JAMB WIDTH

1/4" MAX. CLEARANCE

PEMKO 234 APK

RECESSED INTO

DOOR BOTTOM

(N) ACOUSTIC DOOR

CORNER PAD P112 PS AT

HINGED JAMB

INTERIOR

1/8" MAX. CLEARANCE AT

JAMBS AND HEAD, TYP.

HEAD - JAMB

SIMILAR

KERF-IN SEAL Q103

REFER TO SPEC FOR

COLOR

(N) KERFED FRAME

WEATHER STRIPPING 303 PK

PEMKO 355

ASTRAGAL

ASTRAGAL AT DBL. DOOR

NTS.

EXTERIOR

PEMKO 345

DRIP COVER

1-1/8" TO TOP

OF THRESHOLD

(N) CUSTOM OAK SILL

NEW WOOD TRIM,

FINISH TO MATCH EXISTING

NEW WOOD

FRAME,SHIM

AS REQUIRED

NEW PRE-PRIMED

WOOD TRIM, FINISH

TO MATCH

EXISTING SET IN

SEALANT AT HEAD

SEALANT (TYP.)

SEALANT (TYP.)

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1" = 1'-0"

NEW EXTERIOR ACOUSTICAL

DOOR - SINGLE FAMILY

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 14 00.03

(N) FRAME, TRIM AND STOP

PEMKO KERF-IN Q-103 SOUND

SEAL IN (N) DOOR FRAME

WEATHERSTRIPPING

PROPERLY ADJUSTED

WEATHER SWEEP

ANCHOR PER MANUF.

RECOMMENDATIONS

WEATHERSTRIPPING

(N) FRAME, TRIM AND STOP

EXTERIOR INTERIOR

HEAD - JAMB SIMILAR

JAMB AT HINGE

(N) WOOD TRIM, FINISH TO MATCH (E)

(N) PRE-HUNG DOOR AND FRAME

DOOR SHOE

(N) OR (E) THRESHOLD SET IN SEALANT

(E) FLOORING

LEAD SHIELD @ CONC. SLAB CONDITION

THRESHOLD

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

NEW INTERIOR DOOR

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 14 00.04

HEAD - JAMB SIMILAR

NEW HEADER

NEW WOOD TRIM AT

HEAD AND JAMBS TO

MATCH EXISTING

NEW 1 3/8" DOOR

AUTOMATIC DOOR BOTTOM

(ATTACH METAL STRIKE-

PLATE TO JAMB)

SILL

EXISTING FLOOR OR NEW

RETURN AIR PLENUM

WEATHERSTRIP AT HEAD

AND JAMBS

NEW WOOD FRAME

TYP. WALL: 2X4 FRAMING

WITH 1/2" GYP BOARD,

BOTH SIDES

NOTES:

1. PAINT NEW CONSTRUCTION TO MATCH EXISTING

2. SEE DOOR SCHEDULE FOR SIZE OF NEW DOOR AND HARDWARE

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3" = 1'-0"

NEW INTERIOR MECHANICAL

CLOSET DOOR

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 14 00.05

2. PROVIDE 4 (N) HINGES.

3. SEAL NUMBERS REFER TO PEMKO PRODUCTS.

4. KERF SHALL BE .125-.120" WIDE X .375" DEEP.

5. MIN. SPACE BETWEEN DOOR FACE AND FACE OF WOOD STOP TO BE .3125" OR .5" MAX.

FINISHED FLOOR

PEMKO 2005, OR 181 SET IN

CONTINUOUS BED OF

SEALANT, SEE SPEC

1/4" MAX. CLEARANCE

PEMKO 234 APK

RECESSED INTO

DOOR BOTTOM

(N) ACOUSTIC DOOR

CORNER PAD P112 PS AT

HINGED JAMB

INTERIOR

1/8" MAX. CLEARANCE AT

JAMBS AND HEAD, TYP.

HEAD - JAMB

SIMILARKERF-IN SEAL Q103

REFER TO SPEC FOR

COLOR

(N) KERFED FRAME

REFER TO NOTES FOR KERF

SIZE AND DOOR SPACING

WEATHER STRIPPING 303 PK

PEMKO 355

ASTRAGAL WITH

3/8" VINYL BULB

SEAL INSERT SEE

DETAIL 08 14 00.06

ASTRAGAL AT DBL. DOOR

NTS.

EXTERIOR

DRIP COVER

1/2" MAX. TO TOP

OF THRESHOLD

SEE SPEC

(N) CUSTOM OAK SILL

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1" = 1'-0"

NEW EXTERIOR ACOUSTICAL

DOOR - MULTIFAMILY

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 14 00.06

HEAD

(JAMB SIMILAR)

INTERIOREXTERIOR

EXISTING SLIDING GLASS

DOOR FRAME TO REMAIN AT

HEAD AND JAMBS W/

FASTENER PER MANUF. SPECS.

SEALANT

PERIMETER TRIM WIT

DOUBLE-SIDED ADHESIVE

FOAM TAPE

SEALANT

INSTALL NEW FRAME FLUSH

WITH INTERIOR FACE OF

EXISTING WALL

NEW SLIDING GLASS DOOR

PROVIDE WEEP HOLES AT

ALL SILL FINS TO DRAIN TO

EXTERIOR

3/4" MAX. SILL HEIGHT

FINISHED FLOOR

SILL

SEALANT

EXISTING FINISH

SEALANT

NEW FLUSH FIN CUT AS REQUIRED.

CUT EXISTING FLANGES

NEW SLIDING GLASS DOOR

BEND SHEET METAL SILL

FLASHING TO EXTEND 1-3/4"

MIN. BETWEEN DOOR AND

EXISTING JAMB

NEW 22 GAUGE GALVANIZED

STEEL FLASHING SET IN

FULL BED OF SEALANT

PAINT EXPOSED FLASHING

TO MATCH NEW DOOR

WHEN CONCRETE IS

CLOSER THAN 1/2" TO

FINISHED FLOOR, REMOVE &

REPLACE TO -0'-3/4"

LANDING

(CONDITION VARIES)

NOTES:

1. REMOVE EXISTING DOOR FRAME AT SILL PRIOR TO INSTALLATION OF NEW SLIDING GLASS DOOR.

2. FASTEN SLIDING GLASS DOOR TO EXISTING WALL FRAMING.

3. SHIM AS NECESSARY.

4. WHERE EXTERIOR TRIM OCCURS, SCRIBE FLANGE TO TRIM AND CAULK. CAULK OUTER PERIMETER OF TRIM AND REPAINT TO

MATCH EXISTING.

BLOCKING AT SILL AS REQUIRED.

USE OF FLEXIBLE FLASHING AT SILL

PRIOR TO INSTALLATION OF METAL

FLASHING OR SILL PAN FROM

MANUFACTURER.

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3" = 1'-0"

NEW ACOUSTIC SLIDING DOOR

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 32 13.01

CUT EXISTING KING/ TRIMMER

STUDS AS NECESSARY FOR (N)

WIDENED WINDOW, TYP.

(N) 4" X POST AT (E) SHEAR WALLS

OR (N) 2-2"X STUDS @ NON

SHEARWALLS, TYP

EXISTING WINDOW

EXISTING WALL FRAMING NEW WALL FRAMING

2" X CRIPPLE

STUDS @ 16" O.C.

PROVIDE (N) SOLID WOOD HEADER OVER

EACH OPENING IN THE EXTERIOR

BEARING WALL. (N) HEADER SIZE SHALL

BE AS OUTLINED IN THE ATTACHED CBC

TABLE 2308.8.1.1 OR SHALL BE AS

DESIGNED. NAILING SHALL BE PER CBC

TABLE 2304.10.2

(N) 2"X

ROUGH SILL

(N) WIDEN WINDOW.

REFER TO WINDOW

SCHEDULE FOR

DIMENSIONS

ADD (N) CRIPPLE STUDS

AS NECESSARY

NOTES:

1. CEILING SHALL BE SHORED BEFORE REMOVING (E) HEADER AS NEEDED BASED ON SITE CONDITIONS.

2. IF THE (E) WINDOW WIDENED LESS THAN 3 INCHES, THE (N) WINDOW OPENING CAN BE CREATED THROUGH CUTTING THE (E)

TRIMMER STUD(S). IN THIS CASE CONTRACTOR MUST CONNECT THE (E) HEADER(S) TO ADJACENT KING STUDS WITH HEADER

HANGERS SIMPSON HUC48 AT 2X4 WALLS AND HUC68 AT 2X6 WALLS. VERIFY WITH ENGINEER.

3. REMOVE INTERIOR WALL FINISH AS NECESSARY FOR THE WORK.

4. PROVIDE NEW BASE TRIM BELOW WINDOW OPENING.

5. PATCH & PAINT TO MATCH (E) FOR A (N) LIKE FINISH.

6. FIELD CONDITIONS MAY DICTATE ONLY ONE SIDE OF WINDOW TO BE EXPANDED. VERIFY ON PLANS.

(N) 2" X JACK STUDS

2" X ROUGH SILL

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1" = 1'-0"

SCHEMATIC FRAMING FOR

WINDOW WIDENING

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 50 00.01

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1" = 1'-0"

ALLOWABLE HEADER SPANS

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 50 00.02

02/20/26

Checker

NOTES:

1. THIS DRAWING DEPICTS MINIMUM CODE REQUIREMENTS PER CBC 2025. INFORMATION IS FOR

REFERENCE ONLY AND IS NOT A SUBSTITUTE FOR ACCURATE DRAWINGS PREPARED FOR EACH

PROPOSED CONSTRUCTION PROJECT.

2. FOR OTHER GRADES, SPECIES AND SPAN CONDITIONS, SEE FULL SCHEDULES IN CBC CHAPTER 23.

3. HEADERS BASED ON ROOF LIVE LOAD OF 20 PSF & ROOF DEAD LOAD OF 10 PSF. SEE CHAPTER 23 FOR

OPTIONS.

4. BUILT-UP HEADERS MUST BE FASTENED PER FASTENING SCHEDULE.

5. CONDITIONS SHOWN ARE FOR EXTERIOR WALL. TRIBUTARY WIDTH OF JOIST IS 1/2 BUILDING WIDTH.

DATE:

VERSION:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1" = 1'-0"

FASTENING SCHEDULE I

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 50 00.03A

02/20/26

Checker

TABLE 2304.10.2 CONTINUED ON 08 50 00.03B

DATE:

VERSION:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1" = 1'-0"

FASTENING SCHEDULE II

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 50 00.03B

02/20/26

Checker

NOTES:

1. THIS DRAWING DEPICTS MINIMUM CODE REQUIREMENTS PER CBC 2025. INFORMATION IS FOR

REFERENCE ONLY AND IS NOT A SUBSTITUTE FOR ACCURATE DRAWINGS PREPARED FOR

EACH PROPOSED CONSTRUCTION PROJECT.

2. FOR OTHER GRADES, SPECIES AND SPAN CONDITIONS, SEE FULL SCHEDULES IN CBC

CHAPTER 23.

DATE:

VERSION:

1. THE INTENT OF THIS DETAIL IS TO PROVIDE A FINISHED APPEARANCE THAT IS SIMILAR TO WINDOWS THAT ARE NOT CUT

DOWN.

2. STANDARD WINDOW DETAILS SHALL BE USED IN CONJUNCTION WITH MANUFACTURERS INSTALLATION INSTRUCTIONS.

3. IN THE EVENT THAT PORTIONS OF THE (E) WEATHER RESISTANT BARRIER WERE CUT OUT DURING WINDOW REMOVAL. THE

INSTALLER SHOULD REPLACE THE WEATHER RESISTANT BARRIER THIS CAN BE ACCOMPLISHED BY LAPPING A (N) PIECE OF BUILDING PAPER OVER THE REMAINING WEATHER RESISTANT BARRIER. THE (N) PIECE OF MATERIAL SHOULD OVERLAP THE

(E) BY MINIMUM OF 1". ADDITIONALLY THE OVERLAPPING EDGE SHOULD BE SEALED TO THE (E) MATERIAL.

(E) OR (N) SILL ROUGH FRAMING

(N) SILL AND APRON TO

MATCH (E)

(N) TRIM PIECE, TYP.

FIBREX INSULATION INSTALLED

INT HE CAVITY OF THE WINDOW

FRAME, SILL, JAMBS AND HEAD

INTERIOR

1/4" MAX. GAP BETWEEN (E)

HEADER AND (N) FRAME FILLED

WITH CONTINUOUS WOOD

BLOCKING AT JAMBS AND HEAD

SUB-CASING PIECE

(N) ALUMINUM TRIM, SIZE TO FIT

(TYP), PROVIDE WOOD TRIM

WHEN REQUIRED

NEW CASING TO MATCH (E)

(E) HEAD OR JAMB

ROUGH FRAMING

HEAD/ JAMB

SIMILAR

(E) MEMBRANE

REPLACE STUCCO MOLD

IF DAMAGED

SEALANT, TYP.

(N) ACOUSTICAL

WINDOW

EXTERIOR

PANNING CUT TO

FIT, TYP.

CONTINUOUS

SUPPORT BLOCKING

AT SILL

SEALANT, TYP.

NAIL

(N) SILL PIECE TO

MATCH (E). CUT AS

SHOWN, ATTACH WITH

GALV. FINISH NAILS

AND CONSTRUCTION

ADHESIVE

DRIP

(N) 25 GA (MIN)

GALV. FLASHING

FULL WIDTH OF

WINDOW

SILL

(E) WALL CONSTRUCTION

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1" = 1'-0"

RETROFIT INSTALLATION AT

EXISTING WOOD FRAME WINDOW

WITH LOWERED SILL

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 50 00.04

(E) PIPE COLUMN

EXTERIOR CASING OUT

OF 1" THICK CLEAR D.F.

10d GALV. FINISH NAIL

AT 12" O.C. STAGGERED,

TYP.

CONTINUOUS BED OF

CONSTRUCTION

ADHESIVE, TYP.

PANNING IN BED OF

SEALANT, TYP.

(N) WINDOW UNIT

NOTES:

1. THIS DETAIL REFLECTS AN APPROXIMATION OF (E) CONDITIONS WITH A SUGGESTED MODIFICATION. CONTRACTOR

SHALL BE RESPONSIBLE FOR FINAL DETAILED SOLUTION.

2. ALL EXPOSED WOOD SHALL BE APPEARANCE GRADE CLEAR FIR.

3. ALL (N) WOOD SHALL BE PRIMED ON ALL SIDES BEFORE INSTALLATION

4. FINISH PAINT TO MATCH SURROUNDING SURFACES

WINDOW UNIT

ADHESIVE -

BACKED TRIM

(N) SOLID BLOCKING 2 SIDES

AROUND PIPE COLUMN ATTACHED

W 1/4 - 20 COUNTER SUNK

SCREWS WITH WASHERS IN

DRILLED AND TAPPED HOLES AT

24" O.C., TYP.

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

3/4" = 1'-0"

MODIFICATION OF STEEL PIPE

CORNER POST

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 50 00.05

1. (E) WOOD WINDOW FRAME SHALL REMAIN. REMOVE SASH, PARTING BEADS WEIGHTS, ETC. TO ALLOW (N) WINDOW

INSTALLATIONS

SILL

CONTINUOUS

BLOCKING

(E) CERAMIC TILE OR

APPLIED SURFACE

MATERIAL TO REMAIN

INTERIOR

PERIMETER TRIM

SEALANT

INTERIOR

SEALANT

INTERIOR

PERIMETER TRIM

SEALANT

(E) CERAMIC

TILE TO

REMAIN

CONTINUOUS

BLOCKING

HEAD

JAMB SIMILAR

(E) WALL CONSTRUCTION

EXISTING WOOD TRIM

WHERE OCCURS

GLAZING TAPE OR

SEALANT

EXTERIOR PANNING

CUT AS REQUIRED

BACKER ROD

EXTERIOR

EXTERIOR PANNING

CUT AS REQUIRED

GLAZING TAPE OR

SEALANT; LEAVE

GAPS AT (E) WEEP

HOLES

SEALANT

(E) WOOD SILL

TO REMAIN

(E) WOOD TRIM

WHERE OCCURS (E) WALL CONSTRUCTION

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1" = 1'-0"

(N) VINYL WINDOW AT (E) WOOD

FRAME - TILE SILL

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 50 00.07

EXTERIOR INTERIOR

WOOD FILLER (BY

CONTRACTOR)

(E) RAISED SILL

(E) TILE OR STONE

SEALANT

(N) ACOUSTICAL

WINDOW MAIN FRAME

SILL

WOOD FILLER (BY

CONTRACTOR)

(E) WALL

CONSTRUCTION

(E) OR (N)

REDWOOD SLOPED

SILL - (E) TO

REMAIN

SILL

SNAP ON

PANNING

INSTALLED AND

TRIMMED BY

INSTALLER

SILICONE

SEALANT

/2

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1" = 1'-0"

INSTALLATION AT (E) INTERIOR

RAISED SILL WITH TILE OR STONE

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 50 00.08

(E) WALL

CONSTRUCTION

(E) GARDEN

WINDOW

(E) TILE SURFACE

(WHERE OCCURS)

(N) 2- TRACK WINDOW

HORIZONTAL SLIDER X-X,

1/4-INCH LAMINATED

GLAZING

SCREW NEW WINDOW

TO (E) JAMB + HEAD

(TWO SCREWS PER

SIDE)

TYPICAL

ATTACHMENT

"STICKY" TRIM OR

PANNING (AS REQUIRED)

AT PERIMETER ON

INTERIOR AND EXTERIOR.

CAULK JOINTS

NOTES:

1. DO NOT PENETRATE TILE SILL OR STONE FINISH AT SILL

2. IN CASE OF TILE OR STONE AT ALL SIDES OF WINDOW OPENING, PRE-DRILL WITH MASONRY BIT

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1" = 1'-0"

SECONDARY WINDOW AT GARDEN

WINDOW

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 50 00.09

1. THIS DETAIL REFLECTS AN APPROXIMATION OF (E) CONDITIONS WITH A SUGGESTED MODIFICATION. CONTRACTOR

SHALL BE RESPONSIBLE FOR FINAL DETAILED SOLUTION

(E) WALL FRAMING

5/16" LAG BOLT AND

WASHER AT 16" O.C.

PENETRATION OF (E)

FRAMING SHALL BE AT

LEAST 2"

(N) WINDOWS SHALL BE

SUPPORTED ON (E) PLYWOOD

SHELF REINFORCED AS

SHOWN

RE-FINISH (E) STUCCO

ON THIS WALL SURFACE

SO THAT THE ENTIRE

WALL HAS A MATCHING

APPEARANCE

REMOVE (E) STUCCO AS

REQUIRED TO PROVIDE

A GOOD STRUCTURAL

INTEGRATION OF (N)

AND (E) MATERIALS,

TYP.

(N) BRAKE METAL MULLION

COVER, TYP.

REMOVE (E) WINDOWS

COMPLETELY

PROVIDE FLASHING AND

TRIM AS NECESSARY FOR

COMPLETE INSTALLATION

(N) WOOD FASCIA

STUCCO TO MATCH (E)

SECTION "A"

METAL FLASHING

PERIMETER

(N) CLEAR PINE

FASCIA

(N) 2" X4" AT 16" O.C.

REMOVE (E) STUCCO

(N) LATH AND STUCCO

TO MATCH (E)

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1" = 1'-0"

BAY WINDOW MODIFICATION

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 50 00.11

(E) WALL CONSTRUCTION

HEAD

(JAMB SIMILAR)

(E) WOOD TRIM WHERE

OCCURS

(E) ALUM. FRAME CUT

FLUSH OR COLLAPSED

CUT (E) HINGE OR DRIP TO

BE FLUSH W/ WALL

GLAZING TAPE OR

SEALANT

EXTERIOR PANNING CUT

AS REQUIRED

EXTERIOR PANNING

CUT AS REQUIRED

GLAZING TAPE OR

SEALANT; LEAVE GAPS AT

(E) WEEP HOLES

CUT (E) HINGE OR DRIP

TO BE FLUSH W/ WALL

(E) ALUM. FRAME CUT

FLUSH OR COLLAPSED

(E) WOOD TRIM WHERE

OCCURS

CONTINUOUS

BLOCKING

(E) CERAMIC TILE

OR APPLIED

SURFACE MATERIAL

TO REMAIN

INTERIOR

PERIMETER TRIM

SEALANT

SEALANT

INTERIOR

PERIMETER TRIM

SEALANT

(E) CERAMIC TILE TO

REMAIN

CONTINUOUS

BLOCKING

SILL

(E) WALL CONSTRUCTION

DETAIL NUMBER:

DATE:

610 E. FRANKLIN AVE,

EL SEGUNDO, CA 90245

SCALE:

DETAIL: OWNER:ARCHITECT:

VERSION:

1" = 1'-0"

(N) VINYL WINDOW AT (E)

ALUMINUM FRAME - TILE SILL

LOS ANGELES RESIDENTIAL NOISE INSULATION PROGRAM

08 50 00.13

1. THIS DETAIL IS INTENDED AS A GENERIC GUIDE TO THE REPLACE OF PREFABRICATED BAY/BOW WINDOWS.

2. WINDOW DETAILS MUST BE USED IN CONJUNCTION WITH MANUFACTURERS INSTALLATION INSTRUCTIONS

3. THIS DETAIL REFLECTS AN APPROXIMATION OF EXISTING CONDITIONS WITH SUGGESTED MODIFICATION.

CONTRACTOR SHALL BE RESPONSIBLE FOR FINAL DETAILED SOLUTION.

PANNING TRIMMED TO FIT INSTALLED

WITH CONTINUOUS BACK SEALANT,

TYP.

(N) 2X FRAME AND BLOCKING.

PROVIDE (N) TRIM AND CASING AS

NECESSARY FOR FINISHED

APPEARANCE. FILL IN ANY

REMAINING OPENING WITH BATT

INSULATION.

(N) WINDOW

PROVIDE (N) SEAT

PROVIDE (N) TRIM AND

CASING SIMILAR TO (E)

(E) WALL

CUT BACK (E) STUCCO

FOR PROPER

INSTALLATION OF (N)

WINDOW. PROVIDE (N)

FLASHING AND CASING AS

NECESSARY FOR

COMPLETE INSTALLATION.

PATCH AND PAINT

STUCCO…

This is the start of the file's text. The full file is on GovTribe.