Attachment 4 - Plans Drawings.pdf
PDF 19 MB Posted
- Attached to
- New Farm Storage Building (Kimberly, ID) Federal contract opportunity
- Solicitation number
- 12905B25R0005
About this file
This file is a detailed architectural and engineering design set for a new farm storage building at the USDA Agricultural Research Service's Northwest Irrigation & Soils Research Laboratory in Kimberly, Idaho. The base bid involves constructing a 40 ft by 60 ft pre-engineered steel building with a heated and insulated interior, featuring two 24 ft wide overhead sectional doors for drive-through capability, two insulated personnel doors, a ventilation system, forced air unit heaters, and concrete floors. An optional bid item includes a 20 ft x 60 ft lean-to structure with additional concrete foundation work, electrical power and lighting, bird netting, and one additional insulated personnel door.
The comprehensive design documents include detailed specifications for structural elements, mechanical systems, electrical infrastructure, and plumbing, with specific requirements for materials, installation, and performance standards. The project is planned as a Total Small Business Set-Aside under NAICS Code 236220 with a size standard of $45M, with an estimated project value between $500,000 and $1,000,000. The Request for Proposal (RFP #12905B25R0005) is anticipated to be issued around March 26, 2025, and will be accessible via SAM.gov. Potential contractors must be registered in the System for Award Management and will be responsible for providing all labor, equipment, materials, and supervision to complete the construction according to the detailed specifications.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 3 - Technical Specifications.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NEW FARM STORAGE BUILDING
NORTHWEST IRRIGATION & SOILS RESEARCH LAB
AGRICULTURAL RESEARCH SERVICE
U.S. DEPARTMENT OF AGRICULTURE
KIMBERLY, ID
USDA
LOCATION MAPVICINITY MAP NO SCALE
N N
NO SCALE
GENERAL NOTE:
THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO PERFORMING WORK OR FABRICATION OR PURCHASE OF EQUIPMENT, MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS SHALL BE BROUGHT TO THE CONTRACTING OFFICER'S ATTENTION FOR RESOLUTION
BEFORE PROCEEDING WITH ANY CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.
LOCATION
PROJECT
POCATELLO
IDAHO FALLS
KIMBERLY
BOISE
NEW FARM STORAGE
BUILDING LOCATION
BUILDING 2
BUILDING 1
BU
ILD
IN
G
N
E
NORTHWEST IRRIGATION &
SOILS RESEARCH LAB
3793 N. 3600 E.
KIMBERLY, ID
BU
ILD
IN
G
BU
ILD
IN
G
SHOP
U
D A
S
KIMBERLY, ID
TITLE SHEET
T101
BID DESCRIPTION:
BASE BID: PROVIDE A HEATED, INSULATED PRE-ENGINEERED STEEL BUILDING WITH CONCRETE FLOORS. THE BUILDING WILL BE APPROXIMATELY 40 FT BY 60 FT AND WILL HAVE TWO 24 FT WIDE OVERHEAD SECTIONAL DOORS FOR DRIVE-THRU CAPABILITY WITH EXTERIOR GRAVEL TO OVERHEAD DOORS. IT WILL ALSO INCLUDE TWO INSULATED HOLLOW METAL MAN-DOORS PER THE DRAWINGS. INSTALLATION OF VENTILATION SYSTEM AND FORCED AIR UNIT HEATERS. PRE-ENGINEERED METAL BUILDING MANUFACTURER WILL ALSO INCLUDE ALL NECESSARY COMPONENTS FOR A COMPLETE BUILDING SYSTEM, INCLUDING WALL AND ROOF METAL PANELS AND INSULATION, INTERIOR METAL LINER PANELS, FASCIAS, TRIM, GUTTERS AND DOWNSPOUTS (WEST AND EAST SIDES). THIS BUILDING WILL REQUIRE EXCAVATION OF SOILS AT EXISTING SITE, CONNECTION TO EXISTING
ELECTRICAL AND WATER UTILITIES LOCATED ON PROJECT SITE.
BID OPTION: PROVIDE A COMPLETE LEAN-TO STRUCTURE AS PART OF THE PRE-ENGINEERED METAL BUILDING MANUFACTURER'S PACKAGE AS INDICATED IN DRAWINGS. THE LEAN-TO WILL BE 20' X 60' AND INCLUDE ADDITIONAL CONCRETE FOUNDATION WORK FOR STEEL COLUMNS, ELECTRICAL POWER AND LIGHTING, BIRD NETTING AND CONTROL SYSTEM AS INDICATED IN DRAWINGS AND SPECIFICATIONS. THE LEAN-TO SHALL BE A CONTINUATION OF THE METAL ROOF PANELS AND ALL ASSOCIATED METAL FASCIAS, TRIMS, GUTTERS AND DOWNSPOUTS SHALL BE INCORPORATED TO PROVIDE A SEAMLESS LOOK BETWEEN THE BUILDING AND THE LEAN-TO. IT WILL ALSO INCLUDE ONE INSULATED HOLLOW METAL MAN-DOOR
ACCESSING THE LEAN-TO PER THE DRAWINGS.
U
D A
S
KIMBERLY, ID
DRAWING INDEX
T102
DRAWING NO.
INDEX OF DRAWINGS
SHEET NO. TITLE
T101 T102 C100 C101 C102 C103 C200 C201 S001 S100 S101 A101 A201 A301 A501 A601 M001 M101 M501 P001 P101 E001 E101 E102 E103 E104 E600
TITLE SHEET
DRAWING INDEX
EXISTING SITE PLAN
DEMO SITE PLAN
NEW SITE/UTILITY PLAN
GRADING PLAN
CIVIL/SITE DETAILS
CIVIL/SITE DETAILS
STRUCTURAL NOTES
STRUCTURAL DETAILS
STRUCTURAL DETAILS
FLOOR PLAN
ELEVATIONS
BUILDING SECTIONS
DETAILS
SCHEDULES
ABBREVIATIONS AND GENERAL NOTES
HVAC FLOOR PLAN
HVAC SCHEDULES AND DETAILS
ABBREVIATIONS AND GENERAL NOTES
PLUMBING FLOOR PLAN
ABBREVIATIONS AND GENERAL NOTES
POWER PLAN
RECEPTACLE PLAN
LIGHTING PLAN
FIRE ALARM PLAN
LIGHTING SLIDES
EP
EP
EP
EP
EGEGEGEGEG
EP TOPTOP TOPTOP
XXXXXXXX
EP
EP
EP
EP
EPEPEPEPEP
EP
EP
EPEPEP
EP
EP
EP
EP
X
XXXXXXXX
X X
X X
X X
EG
EG
EG
EG
EG
EGEGEG
EG
EG
XXXXXXX
X X
X X
X
EG
EG
EG
EG
EGEG
EG
EG
EG
EG EG
EG
EG
EG
EG
UP
UP UP UP UP
OHP OHP OHP OHP OHP
W
G
SS
SS
SS
SS
SS SS SS SS
SS
SS
SS
SS
SS
SS
TOP TOP TOP
EP EP
EG EG
EDGE OF BUILDING
TOP OF WALL
EDGE OF PAVEMENT
EDGE OF CONCRETE
EDGE OF GRAVEL
FENCE
EXISTING WATER PIPE
EXISTING GAS PIPE
EXISTING SEWER PIPE
UNDERGROUND POWER
MAJOR CONTOUR
MINOR CONTOUR
YARD HYDRANT
VERTICAL PIPE
SEWER MANHOLE
ABANDONED GREASE TRAP
POWER POLE
GUY WIRE
BOLLARD
POST
JUNCTION BOX
FUEL TANK
PUMP
IRRIGATION VALVE
FF FINISH FLOOR
SPOT ELEVATION
GREASE TRAP
X X X
W W W
G G G
SS SS SS
UP UP
SS
SS
SS
SS
SS
SS
SS
SS
SS
EP
W
WG
SS SS SS
SCALE: 1" =
020 2010
20'
ABANDONED GREASE TRAP
RIM EL 3912.58
E INV 6" METAL 3908.44
SEWER MH
RIM EL 3913.24
SEWER LEACH FIELD
RIM ELEV 3912.71
S INV 6" RCP 3909.22
N INV 4" PVC 3909.23
E INV 4" PVC 3909.10
W INV 4" PVC 3909.10
TREES/BUSHES
TREES/BUSHES
SV-1 THE PLANS ARE BASED ON A SURVEY THAT WAS PERFORMED BY J.U.B.
ENGINEERS, INC ON JUNE 24-27, 2019. HORIZONTAL DATUM IS BASED ON IDAHO
STATE PLANE COORDINATE SYSTEM, CENTRAL ZONE NAD83 IN U.S. SURVEY
FEET. VERTICAL DATUM AND ELEVATIONS SHOWN HEREON BASED ON NAVD88.
EXISTENCE OF WETLANDS, ENVIRONMENTAL HAZARDS, CEMETERIES OR ANY
UNDERGROUND STRUCTURE WAS NOT OBSERVED DURING THE COURSE OF THE
SURVEY.
GN-1 REVIEW ALL PROJECT DOCUMENTS PRIOR TO START OF CONSTRUCTION.
REPORT ANY DISCREPANCIES TO CONTRACTING OFFICER PRIOR TO
PROCEEDING WITH WORK. DIMENSIONS RELATING TO EXISTING
CONSTRUCTION ARE TO BE FIELD VERIFIED. THE CONTRACTOR SHALL
IMMEDIATELY COMMUNICATE, IN WRITING TO THE CONTRACTING
OFFICER, CONCERNS WHERE THEY BELIEVE DESIGN DOCUMENTS ARE
INSUFFICIENT, INADEQUATE OR INCORRECT FOR PERFORMING THE
CONSTRUCTION WORK.
GN-2 EXISTING UTILITIES ARE SHOWN IN THEIR APPROXIMATE LOCATIONS AS
LOCATED AT THE TIME OF THE DESIGN SITE VISIT. THE CONTRACTOR
SHALL VERIFY THE LOCATION OF ALL UTILITIES, NOTE EXISTING
CONDITIONS AND NOTE ANY VARIANCES TO THE CONTRACTING OFFICER
PRIOR TO BEGINNING CONSTRUCTION AND PROTECT ALL EXISTING
UTILITIES.
GN-3 COORDINATE CIVIL WORKS AND OTHER TRADES.
GN-4 ALL DETAILS AND SECTIONS ON THE DRAWINGS ARE INTENDED TO BE
TYPICAL AND SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR
SITUATION ELSEWHERE ON THE PROJECT EXCEPT WHERE A SEPARATE
DETAIL IS SHOWN.
GN-5 VERIFY EXISTING CONDITIONS. WHEN SPECIFIC INFORMATION IS
INCORRECT, MISSING OR IS IN CONFLICT, BRING THE CONFLICT TO THE
ATTENTION OF THE CONTRACTING OFFICER PRIOR TO BEGINNING WORK
RELATED TO THAT ITEM.
GN-6 THE CONTRACTOR SHALL TAKE CARE, BY THE USE OF GRADING,
DIVERSION AND DEWATERING, TO PREVENT PONDING OF WATER ON SITE
IN AREAS OF STRUCTURAL, UTILITIES AND PAVEMENT SUBGRADES.
GN-7 THE CONTRACTOR SHALL PROVIDE AS-BUILT DRAWINGS OF ALL OF THE
NEW UTILITIES AND SERVICE.
GN-8 PRODUCTS SHALL BE INSTALLED PER MORE STRINGENT REQUIREMENTS
OF THE DESIGN DOCUMENTS OR THE MANUFACTURER'S PRINTED
INSTRUCTIONS FOR THE INDICATED APPLICATION. THESE INSTRUCTIONS
SHALL BE MAINTAINED ON SITE FOR THE DURATION OF THE INSTALLATION
AT A MINIMUM.
1. EXISTING GRAVEL THICKNESS IS ESTIMATED TO BE 6" IN DEPTH.
2. EXISTING ASPHALT SECTION IS ESTIMATED TO BE 6" ASPHALT AND 6" OF GRAVEL.
6" SEWER:
CLAY, CEMENT
ASBESTOS OR
CONCRETE
114" CAST IRON WATER
CAPPED WITH 114" GATE
VALVE IN VALVE BOX
114" (1#) GAS LINE
INVERT = 3909±
SCALE: 1" =
010 10
10'
EXISTING SITE PLAN1
SCALE: 1" = 20'C100
NORTH
U
D A
S
KIMBERLY, ID
EXISTING SITE PLAN
C100
EXISTING PAVEMENT NOTES:
SURVEY NOTES:
GENERAL NOTES:
LEGEND:
DETAIL A
SCALE 1" = 10'
DETAIL B
SCALE 1" = 10'
lhenderson kimberly
EGEGEGEGEG
XXXXXX
EP
EP
EP
EP
EPEPEPEPEP
EP
EP
EPEPEP
EP
EP
EP
EP
EG
EG
EG
EG
EG
EGEGEG
EG
EG
XXXXXXX
X X
X X
X X
X X
X X
X
EG
EG
EG
EG
EGEG
EG
EG
EG
EG EG
EG
EG
EG
EG
UP
UP UP UP UP
OHP OHP OHP
W
G
SS
SS
SS
SS
SS SS SS SS
SS
SS
SS
SS
SS
SS
X X
X X
X
X X X X X
EXISTING SHOP BLDG EXISTING BLDG 2
EX
IS
TI
NG
B
LD
G
X X X X X X X
FENCE TO BE REMOVED (BY OTHERS -NOT IN THIS CONTRACT).
CLEAR AND GRUB BUILDING LOCATION.
TREE AND BRUSH TO BE REMOVED (BY OTHERS - NOT IN THIS CONTRACT).
LOCATE AND PROTECT EXISTING UNDERGROUND ELECTRICAL SERVICE AND ALL OTHER
UTILITIES.
SAWCUT, REMOVE AND DISPOSE OF EXISTING ASPHALT PAVEMENT AND GRAVEL.
SALVAGE CLEAN GRAVEL AND STOCK ON SITE WHERE DIRECTED BY THE CONTRACTING
OFFICER.
3LINEAR DEMOLITION
DEMOLITION AND SITE PREP AREA
SAWCUT
LIMITS OF ANTICIPATED DISTURBANCE (APPROX 17,000
SF OR 13 ACRE)
BEG
END
SOIL SAMPLE LOCATION
SEE SOIL LOG SHEET C200
D-1 PROTECT ASSETS AND FINISHES NOT SHOWN TO BE REMOVED. ANY DAMAGE
CAUSED BY CONSTRUCTION OPERATIONS SHALL BE REPAIRED TO MATCH THE
EXISTING CONDITIONS AT NO COST TO THE GOVERNMENT.
D-2 AT A MINIMUM, PROVIDE 4' TALL, TEMPORARY ORANGE HIGH DENSITY POLYETHYLENE
SAFETY FENCE TO ISOLATE HAZARD AND CONSTRUCTION FROM UNAUTHORIZED
ACCESS.
D-3 CARE SHALL BE TAKEN IN ALL OPEN SUBGRADES TO PREVENT DETERIORATION
CAUSED BY WEATHER. DEWATER ALL OPEN SUBGRADES AS REQUIRED TO MAINTAIN
STABILITY.
D-4 THE CONTRACTOR SHALL CONTROL THE SPREAD OF DUST AND IRRITANTS TO OTHER
SPACES, ADJACENT BUILDINGS AND OUTSIDE OF DESIGNATED WORK AREAS.
D-5 THE CONTRACTOR SHALL PROVIDE CLEAN, STRAIGHT, NEAT CUTS FOR DEMOLITION
THAT MINIMIZE IMPACTS AND ADVERSE AFFECTS ON EXISTING FINISHES.
COORDINATE THE LOCATION OF THE CUTS TO ACCOMMODATE FINAL FINISHES.
D-6 THE REPAIR IS DESIGNED TO BE VIABLE IN ITS FULLY CONSTRUCTED, FINAL
CONFIGURATION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THE SAFETY
AND STABILITY OF ALL COMPONENTS DURING CONSTRUCTION.
D-7 PRIOR TO THE THE CONSTRUCTION CONTRACT AWARD, THE USDA WILL RELOCATE
ALL MOBILE ASSETS AND INVENTORY TO A LOCATION THAT WILL NOT INHIBIT
CONSTRUCTION OPERATIONS.
D-8 ITEMS NOTED AS "NOT IN CONTRACT" WILL BE REMOVED PRIOR TO THE AWARD OF
THE CONSTRUCTION CONTRACT
D-9 BELOW THE NEW BUILDING, NEW PAVEMENT AND NEW GRAVEL FOOTPRINT, THE
CONTRACTOR SHALL STRIP ALL ORGANIC MATERIAL AND STOCKPILE (FOR USE AS
TOPSOIL). SCARIFY, STABILIZE AND COMPACT ALL BUILDING, PAVEMENT AND GRAVEL
PRIOR TO PLACING ANY ADDITIONAL FILL.
LIMITS OF ASPHALT PAVEMENT REMOVAL
PROPOSED
CONTRACTOR LAYDOWN
AREA
ALL WORK THIS SHEET IS PART OF THE BASE BID
TH1
U
D A
S
KIMBERLY, ID
SCALE: 1" =
020 2010
20'
DEMO SITE PLAN1
SCALE: 1" = 20'C101
NORTH
DEMO SITE PLAN
C101
KEYED NOTES:
DEMOLITION NOTES:
LEGEND:
TH2
EP
EP
EPEPEPEPEP
EP
EP
EPEPEP
EP
EP
EP
EP
EG
EG
EG
EG
EG
EG
EG
EG
EG
EG EG
EG
UP
UP UP UP UP
W
G
SS
SS
SS
SS
SS SS SS SS
SS
SS
SS
SS
SS
SS
EXISTING SHOP BLDG EXISTING BLDG 2
EX
IS
TI
NG
B
LD
G
NE
W
B
LD
G
EP
EPEPEPEPEP
EP
EP
EPEPEP
EP
EP
EP
EP
EG
EG
EG
EG
UP
UP UP UP UP
W
G
SS
SS
SS
SS
SS SS SS SS
SS
SS
SS
SS
SS
SS
EX
IS
TI
NG
B
LD
G
NE
W
B
LD
G
SCALE: 1" =
020 2010
20'
BUILDING ADDITION
NEW FENCE (BY OTHERS - NOT IN THIS CONTRACT).
PROVIDE NEW PRE-ENGINEERED METAL BUILDING. (SEE ARCHITECTURAL).
PROVIDE NEW PRE-ENGINEERED METAL LEAN-TO. (BID OPTION - BO)
PROVIDE NEW 24' WIDE OVERHEAD DOOR (SEE ARCHITECTURAL).
PROVIDE NEW 114" WATERLINE. REDUCE AT BUILDING TO MATCH PLUMBING. (2/C201 & 5/C201).
PROVIDE WATER VALVE (4/C201).
EXISTING WATER VALVE WITH CAPPED 114" TERMINATION. ANTICIPATED POINT OF WATER CONNECTION. (FIELD
VERIFY MATERIAL AND LOCATION PRIOR TO BEGINNING WORK).
PROVIDE GAS SERVICE VALVE IN VALVE BOX.
PROVIDE A NATURAL GAS LOCKING WING COCK, PRESSURE REGULATOR.
PROVIDE NEW 1-1/4" POLYETHYLENE GAS PIPE. ANTICIPATED TIE TO EXISTING 4" (1#) GAS LINE (FIELD VERIFY
MATERIAL AND LOCATION PRIOR TO BEGINNING WORK).
PROVIDE NEW GRAVEL PAVEMENT FROM BUILDING FACE TO TIE TO SURROUNDING PAVEMENT SURFACES/GRADE.
PROVIDE NEW BOLLARDS AT LOCATIONS INDICATED. (3/C201).
BEG
END
BEG
END
GRAVEL
NEW WATER VALVE VW
NEW WATER LINE
12 12
BO
VW
TIE (END)
BEG
NEW GAS LINE
U-1 THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE LOCAL UTILITY COMPANY, OBTAIN ALL REQUIRED PERMITS AND PAY ALL ASSOCIATED FEES.
U-2 WORK PERFORMED ON THE SERVICE SHALL BE PERFORMED BY AN APPROVED UTILITY CONTRACTOR FOR THE RELATED WORK. WHERE IN CONFLICT, THE
CONTRACTOR SHALL COMPLY WITH THE MORE STRINGENT OF THE UTILITY OR DESIGN DOCUMENT REQUIREMENTS.
U-3 SEE MECHANICAL AND ELECTRICAL PLANS FOR ADDITIONAL DETAILS ON NATURAL GAS AND ELECTRICAL SERVICE.
U-4 THE CONTRACTOR SHALL PROVIDE AN ACCURATE AS-BUILT DRAWING OF ALL UNDERGROUND INSTALLED UTILITIES TO THE OWNER ON A 24"X36" PLAN SHEET.
DETAILS SHALL INCLUDE, AT A MINIMUM; SIZES, DIMENSIONS FROM VISIBLE SITE FEATURES AND DEPTH OF BURY.
U-5 NEW GAS AND WATER LINES CAN BE LOCATED ADJACENT IN TRENCH AT CONTRACTOR'S OPTION.
VG
VGNEW GAS VALVE
VW
ALL WORK THIS SHEET IS PART OF THE BASE BID
G-1 AT THE COMPLETION OF GRADING, THE CONTRACTOR SHALL SPREAD 4" TOPSOIL ON ALL DISTURBED UNIMPROVED AREAS AS REQUIRED TO ESTABLISH
VEGETATIVE COVER. AT THE COMPLETION OF THE PROJECT, HAUL EXCESS MATERIAL OFF SITE.
G-2 TEMPORARY SEED OR STABILIZE ALL AREAS OF EXPOSED EARTH THAT ARE PLANNED TO BE UNFINISHED OR UNWORKED FOR A PERIOD EXCEEDING 14 DAYS.
NOTE:
SEE 2/C102 FOR REQUIRED PAVEMENT
IMPROVEMENTS
TH2
SOIL BORING
EP EP
EG EG
EDGE OF PAVEMENT
EDGE OF GRAVEL
BO
BO
U
D A
S
KIMBERLY, ID
NEW SITE/UTILITY PLAN
C102
NEW SITE/UTILITY PLAN1
SCALE: 1" = 20'C102
NORTH
PAVEMENT SURFACING PLAN2
SCALE: 1" = 20'C102
NORTH
KEYED NOTES:LEGEND (PROPOSED):
GENERAL NOTES:
UTILITY NOTES:
TH1
TH1
EP
EP
EP
EGEGEGEGEG
EP TOPTOP TOPTOP
XXXXXXXX
EP
EP
EP
EP
EPEPEPEPEP
EP
EP
EPEPEP
EP
EP
EP
EP
EG
EG
EG
EG
EG
EGEGEG
EG
EG
XXXXXXX
X X
X X
X X
X X
X X
X
EG
EG
EG
EG
EGEG
EG
EG
EG
EG EG
EG
EG
EG
EG
UP
UP UP UP UP
OHP OHP OHP OHP OHP
W
G
SS
SS
SS
SS
SS SS SS SS
SS
SS
SS
SS
SS
SS
X X
X X
X
X X X X X X X X X
EXISTING SHOP BLDG EXISTING BLDG 2
EX
IS
TI
NG
B
LD
G
X X X X X X X
SCALE: 1" =
020 2010
20'
PROP FF =
3913.8
3913NEW CONTOUR
SPOT ELEVATION 3913.8
FE =
3913.5
FE =
3913.5
GRADE TO
DRAIN
GRADE TO
DRAIN
ALL WORK THIS SHEET IS PART OF THE BASE BID
GRADE SWALE
PAVEMENT
LIMITS
U
D A
S
KIMBERLY, ID
GRADING PLAN
C103
GRADING PLAN1
SCALE: 1" = 20'C103
NORTH
LEGEND (GRADING):
TH1
TH2
GT-1 RECOMMENDATIONS FOR THIS DESIGN ARE BASED ON: 'GEOTECHNICAL INVESTIGATION,
PROPOSED FARM SHOP BUILDING' DATED: JULY 2, 2019. HLE, INC.
GT-2 GROUNDWATER WAS NOT ENCOUNTERED IN THE BORINGS AT THE TIME OF AUGERING.
GROUNDWATER LEVEL OBSERVATIONS PROVIDE AN INDICATION OF GROUNDWATER
CONDITIONS PRESENT AT THE TIME THE BORINGS WERE DRILLED. GROUNDWATER LEVEL
FLUCTUATIONS OCCUR DUE TO SEASONAL VARIATIONS IN THE AMOUNT OF RAINFALL,
RUNOFF AND OTHER FACTORS NOT EVIDENT AT THE TIME.
GT-3 SITE PREPARATION SHALL INCLUDE REMOVAL OF ASPHALT, GRAVEL AND ORGANIC
MATERIAL BELOW THE FOOTPRINT FOR THE PLACEMENT OF ALL IMPROVEMENTS AND
STRUCTURES. STRIP AND STORE TOPSOIL FOR REUSE AT THE COMPLETION OF SITE
GRADING.
GT-4 COMPACTION EFFORTS:
ALL SUBGRADES SHALL BE STABLE.
BACKFILL MATERIAL MUST BE WITHIN THE RANGE OF -2 TO +2 PERCENT OF OPTIMUM
MOISTURE CONTENT AT THE TIME OF COMPACTION.
S-1 SLABS/PAVEMENTS - AREAS OF THE SITE WITHIN THE BUILDING AREA SHALL BE
EXCAVATED TO SUFFICIENT DEPTHS TO REMOVE EXISTING ASPHALT AND ORGANIC
MATERIAL. THE EXPOSED SUBGRADE MATERIAL SHOULD BE RE-COMPACTED TO A
MINIMUM OF 95% OF THE MAXIMUM DENSITY AS OF ASTM D-1557.
S-2 FOOTING - SPREAD FOOTINGS BEARING ON RE-COMPACTED SILT (MINIMUM 95% OF THE
MAXIMUM DENSITY AS DETERMINED BY ASTM D-1557) FOR AN ALLOWABLE LOAD
BEARING CAPACITY OF 1,300 PSF.
S-3 THE CONTRACTOR SHALL PROVIDE A QUALIFIED INSPECTOR APPROVED BY THE
CONTRACTING OFFICER TO VERIFY THE COMPACTION.
ALL WORK THIS SHEET IS PART OF THE BASE BID
U
D A
S
KIMBERLY, ID
CIVIL/SITE DETAILS
C200
SOIL LOGS1
SCALE: NONEC200
GEOTECHNICAL NOTES:
STRUCTURAL NOTES:
DIA.
8" MIN. NEW WORK
NEW COMPACTED BASE
COURSE TO MATCH EXISTING
COMPACTED FILL
PLACE IN 6" LOOSE LIFT AND COMPACTED
TO A MINIMUM OF 95% OF THE MAXIMUM
DENSITY AS OF ASTM D-1557
EXISTING GRAVEL SURFACING
SLOPE TO FACILITATE
CONSTRUCTION
12"
LOCAL MATERIAL/EXECUTION REQUIREMENTS:
MATERIAL AND EXECUTION SHALL MEET THE FOLLOWING REQUIREMENTS OF
THE IDAHO TRANSPORTATION DEPARTMENT'S "2018 STANDARD
SPECIFICATIONS FOR HIGHWAY CONSTRUCTION":
1. SECTION 303 AGGREGATE BASE (GRADATION "3 4 IN A" OR "3 4 IN
B").
2. SECTION 210 STRUCTURE EXCAVATION AND BACKFILL.
3. SECTION 205 EXCAVATION AND EMBANKMENT.
4. SECTION 409 PORTLAND CEMENT CONCRETE PAVEMENT.
3000 PSI CONCRETE ENCASEMENT W/ 4-#4 BARS
LONGITUDINAL 10' EITHER SIDE CROSSING
WHEN
<18" VERTICAL SEPARATION (ABOVE OR BELOW)
WATER MAIN SHALL BE LAID AT LEAST 10' HORIZONTALLY AND 18" VERTICALLY FROM ANY SEWER OR MANHOLE.
WHERE WATERLINES MUST CROSS SEWER LINES, THE JOINTS SHALL BE CENTERED TO PROVIDE THE MAXIMUM SPACING BETWEEN THE JOINTS OF THE SEWER LINE AND WATER LINE AND A VERTICAL SEPARATION OF AT LEAST
18" SHALL BE MAINTAINED.
6" 6"
CONCRETE
SLAB
VALVE BOX
VALVE
" M
IN
(T
YP
6"
FINISHED
GRADE
LETTERS "WATER" CAST
IN METAL COVER
S 1/2"S 1/2"
PIPING SIZE / VALVE TYPES
< 2" GLOBE VALVE
> OS&Y GATE
VALVES SHALL BE CERTIFIED PER AMERICAN WATER WORKS ASSOCIATION C509
MIN MIN
NOTE: WHEN 18" VERTICAL SEPARATION CANNOT BE
MAINTAINED, JOINTS SHALL BE LOCATED SUCH THAT THEY
ARE EQUAL DISTANCE BEFORE AND AFTER CROSSING.
STABILIZED SUBGRADE. 12" MINIMUM
THICKNESS (COMPACT TO A MINIMUM 95%
ASTM D6987).
6" BASE COURSE
GRAVEL SURFACING
NEW GRAVEL SURFACING (TO MATCH
EXISTING W/ MINIMUM THICKNESS OF 6")
FINISHED GRADE
6" TYP.
3 4" AT GRAVEL
RAMP TO DOORS
8' MIN. AT 2%SLAB ON GRADE
FOUNDATION (SEE
STRUCTURAL DETAILS)
VAPOR RETARDER AND
CAPILLARY BARRIER
FINISHED FLOOR ELEVATION
MATERIAL VARIES
SMOOTH TRANSITION
TO SEED AREAS AND
OTHER FINISHED
SURFACES
EXTERIOR BUILDING
ENVELOPE
MINIMUM COVER FOR ALL UTILITIES
SHALL BE 30 INCHES UNLESS
OTHERWISE SPECIFIED.
SEWER
LINE
6" TYP.
AROUND PIPE
18" MIN VERTICAL SEPARATION WHERE
WATER AND SEWER LINES INTERSECT.
3'- 4"
4"
2'-4" SQ.
2"
GROUND
SURFACE
60" TYPICAL
ALL WORK THIS SHEET IS PART OF THE BASE BID
U
D A
S
KIMBERLY, ID
CIVIL/SITE DETAILS
C201
BUILDING GRADING DETAIL1
SCALE: NONEC201 WATER AND SEWER DETAIL2
SCALE: NONEC201
BOLLARD DETAIL3
SCALE: NONEC201
TRENCH DETAIL5
SCALE: NONEC201
WATER ISOLATION VALVE DETAIL4
SCALE: NONEC201
TYPICAL PAVEMENT SECTION DETAIL6
SCALE: NONEC201
MOUND CONCRETE
WRAP IN 4" WIDE REFLECTIVE TAPE, ASTM D4956 -
TYPE VII (WHITE)
8" SCH. 40 STEEL BOLLARD
CONCRETE FILLED. PAINT AN
APPROVED WHITE.
PAVE TO MATCH EXISTING. (IF REQ'D) PROVIDE
1/2" FULL DEPTH EXPANSION MATERIAL AT
PAVED SURFACES.
TWO 16" #4 BARS THREADED THROUGH A ≈3/4"
HOLE AND TACK WELDED. ONE EACH WAY.
CONCRETE
12"
11 2 3 4
A
B
C
1. THE BUILDING SHALL BE A PRE-ENGINEERED BUILDING AS SPECIFIED IN SPECIFICATION SECTION 13 34 19, "METAL BUILDING SYSTEMS". THE BUILDING SHALL BE A MANUFACTURER'S STANDARD PREFABRICATED METAL STRUCTURE OF THE INSIDE AREA SHOWN. OVERALL DIMENSIONS AND CONSTRUCTION DETAILS MAY VARY TO
SUIT MANUFACTURER'S STANDARD DESIGN.
2. THE BUILDING SHALL BE DESIGNED AND FABRICATED ACCORDING TO AISC (AMERICAN INSTITUTE OF STEEL CONSTRUCTION) AND AISI (AMERICAN IRON AND STEEL INSTITUTE) LATEST SPECIFICATIONS. THE
DIMENSIONAL TOLERANCES OUTLINED IN THE AWS (AMERICAN WELDING SOCIETY) CODE UNDER
WORKMANSHIP AND THE TOLERANCES APPLICABLE TO ROLL FORM STEEL UNDER THE AISC "STANDARD MILL PRACTICE" SECTION SHALL BE REQUIRED IN THE FABRICATION OF THE STEEL BUILDING FRAMES.
3. DETAILS SHOWN ON THESE CONSTRUCTION DRAWINGS ARE THE ENGINEER OF RECORD'S ESTIMATE OF REQUIREMENTS BASED ON ANTICIPATED METAL SYSTEMS AND CONFIGURATION. THE FINAL SYSTEMS SHALL BE PROVIDED IN A DELEGATED DESIGN PROVIDED BY A LICENSED ENGINEER EMPLOYED BY THE CONTRACTOR/MANUFACTURER. PROVIDE A COMPLETE DESIGN ANALYSIS SHOWING ALL CALCULATIONS FOR THE RIGID FRAMES, GIRTS, AND PURLINS, MODIFIED FOUNDATION REQUIREMENTS, LAYOUT OF ANCHOR BOLTS AND OTHER EMBEDDED ITEMS SHALL BE SUBMITTED FOR APPROVAL WITH THE SHOP DRAWINGS. SHOP DRAWINGS SHALL INCLUDE DETAILS OF ALL MAIN MEMBERS, TYPICAL CONNECTIONS (SHOWING BOLT HOLES
AND WELDS), AND ERECTION DRAWINGS.
4. THE BUILDING SHALL BE DESIGNED TO SUPPORT ALL FLOORS, DOORS, EQUIPMENT AND ALL OTHER DEVICES.
ADDITIONAL STRUCTURAL STEEL, GIRTS OR PURLINS SHALL BE PLACED IN CONVENIENT LOCATIONS FOR
ATTACHMENT OF ALL EQUIPMENT AND DEVICES.
5. CROSS BRACING WILL NOT BE ALLOWED IN THE WALLS OR AT LEAN-TO COLUMNS. USE PORTAL FRAMES FOR
LATERAL LOAD TRANSFER IN VERTICAL STRUCTURAL MEMBERS.
6. THE FOUNDATIONS SHOWN ARE ESTIMATES FOR THE BUILDING TYPE SHOWN ON THE DRAWINGS AND ARE TO BE USED AS A GUIDE FOR THE BUILDING SUPPLIED. THESE FOUNDATIONS ARE SIZED FOR THE VALUES SHOWN IN THE "FOUNDATION REACTION DIAGRAM". THE CONTRACTOR'S ENGINEER SHALL DESIGN THE FOUNDATIONS
FOR THE SPECIFIC LOADS FOR THE BUILDING SUPPLIED.
7. THE CONTRACTOR SHALL USE IN HIS DESIGN THE BASIC CRITERIA SHOWN BY THIS DRAWING, SUCH AS SLAB
THICKNESS, CONTROL JOINTS, DESIGN LOADS AND MINIMUM DEPTH OF FOOTING.
8. FOOTINGS SHALL BE SIZED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 1300 PSF. THE ALLOWABLE SOIL PRESSURE IS BASED UPON A GEOTECHNICAL REPORT PREPARED BY HLE, INC.(BLACKFOOT, ID) DATED JULY 2, 2019.
9. DESIGN THE BUILDING SYSTEM FOR THE LIVE LOADS OR SNOW LOADS (WHICHEVER IS GREATER) INDICATED AND A COLLATERAL LOAD OF 5 PSF IN ADDITION TO THE BUILDING DEAD LOADS, WIND LOADS AND SEISMIC LOADS. PARAMETERS FOR THE DEVELOPMENT OF THE SNOW, WIND AND SEISMIC LOADS ARE LISTED IN THE DESIGN LOAD SUMMARY ON THIS SHEET. ROOF PURLINS SHALL BE DESIGNED FOR AN ADDITIONAL CONCENTRATED LIVE LOAD OF 300 POUNDS LOCATED ANYWHERE ALONG THE LENGTH OF THE PURLIN.
10. ALL CONCRETE SHALL CONFORM TO ACI (AMERICAN CONCRETE INSTITUTE) 301 AND SHALL DEVELOP A
MINIMUM COMPRESSIVE STRENGTH (F'C) OF 3500 PSI @ 28 DAYS.
11. CONCRETE COVER ON REINFORCEMENT SHALL BE AS FOLLOWS:
CONCRETE CAST AGAINST EARTH 3 INCHES
CONCRETE EXPOSED TO EARTH OR WEATHER 2 INCHES CONCRETE SLABS
2 INCHES
12. REINFORCING STEEL SHALL BE ASTM A 615, GRADE 60 FOR BARS OR ASTM A 185 FOR WELDED WIRE FABRIC.
REINFORCING STEEL SHALL BE LAPPED AS SPECIFIED IN ACI 318-02.
13. GROUT SHALL BE NON-SHRINK WITH COMPRESSIVE STRENGTH (F'C) OF 4500 PSI @ 28 DAYS.
14. PROVIDE VAPOR BARRIER (ASTM E1745) OVER A 6 INCH CAPILLARY (WASHED STONE (NO. 57)) BARRIER UNDER
SLABS.
15. PROVIDE A BY-PASS OR OUTSET MOUNTED GIRT SYSTEM TO FACILITATE ARCHITECTURAL FEATURES.
PRE-ENGINEERED METAL BUILDING AND STRUCTURAL NOTES:
HORIZONTAL MIDDLEHM
VALUES WITH (-) SIGN ACT IN OPPOSITE (2)
FOUNDATION REACTION DIAGRAM (MAX. VALUES)
DIRECTION OF ARROWS IN DIAGRAMS
VERTICAL MIDDLE
VERTICAL LEFT
VERTICAL
NOT TO SCALE
V
VL
VM
MAXIMUM ESTIMATED REACTIONS
ALL VALUES ARE IN KIPS (1000 LBS).
-3
VL+
(1) ±1
HL
HL+
HORIZONTAL
HORIZONTAL LEFT
ABBREVIATIONS
7.6
VL
-10.3
HR
±7.6
VR
13.7
H
HL
VR+
HR+
(3) NO MOMENTS SHALL BE TRANSFERRED FROM THE
METAL BUILDING SYSTEM TO THE FOUNDATION
FOR SOIL BORING INFORMATION SEE GEOTECHNICAL ENGINEERING REPORT 'PROPOSED FARM
SHOP BUILDING' PREPARED BY HLE, INC. DATED JULY 2, 2019 INCLUDED WITH SOLICITATION REFERENCE DOCUMENTS. SEE CIVIL SHEET FOR BORING LOCATIONS AND SOIL BORING PROFILES.
ASCE-7 (16)
MINIMUM DESIGN LOAD SUMMARY
RISK CATEGORY 'II'
WIND
WIND SPEED103 VMPH
10-YEAR MRI 72 VMPH
25-YEAR MRI78 VMPH
50-YEAR MRI83 VMPH
100-YEAR MRI88 VMPH
SEISMIC
SOIL CLASS 'D'
SS 0.21
S1 0.081
FA 1.6
FV 2.4
SMS 0.336
SM1 0.195
SDS 0.224
SD1 0.13
TL 6
PGA 0.084
PGAM 0.127
FPGA 1.6
LE 1
CV 0.7
SEISMIC DESIGN CATEGORYB
ICE
THICKNESS 0.25 IN.
CONCURRENT TEMPERATURE 15 F
GUST SPEED40 MPH
SNOW
GROUND SNOW LOAD, PG14 LB/FT2
GROUND SNOW LOAD, PG14 LB/FT2 (3924.0 FT)
ELEVATION 3917.2 FT
RAIN
ANNUAL = APPROX 12 INCHES
5 MIN, 25 YR = 6 INCHES/HR
FLOOD
FLOOD ZONEX (UNSHADED)
STATIC BFE REFER TO MAP 16083C1425C (9/26/2008).
24'
OHD
20'
3'
SLAB ON GRADE
20'-10"
24'
OHD
ANY STRUCTURAL FILL SHALL BE IN ACCORDANCE WITH THE STRUCTURAL FILL PORTION OF THE
GEOTECHNICAL REPORT AND BE COMPACTED TO A MINIMUM 95% OF THE MAXIMUM DENSITY AS
DETERMINED BY ASTM D-1557.
PLACEMENT OF ANY FILL MATERIAL BENEATH THE FOOTING ELEVATION, IF NECESSARY, SHOULD BE ACCOMPLISHED WITH A GW OR GP CLASS SANDY GRAVEL MATERIAL, PLACED IN LIFTS NOT EXCEEDING 8 INCHES AND COMPACTED TO A MINIMUM OF 95% OF OPTIMUM DRY DENSITY AS DETERMINED BY ASTM
D-1557 "MODIFIED PROCTOR."
A QUALIFIED INSPECTOR APPROVED BY THE CONTRACTING OFFICER SHOULD VERIFY THE COMPACTION.
PROVIDE THE CONTRACTING OFFICER WITH THE INSPECTOR'S CREDENTIALS A MINIMUM 7 DAYS PRIOR
TO BEGINNING WORK.
ALL EARTHWORK SHALL BE PERFORMED TO THE MORE STRINGENT REQUIREMENTS OF THE CONTRACT
DOCUMENTS OR THE GEOTECHNICAL REPORT.
SUBSURFACE SOIL
Soil Classification TEST HOLES ENCOUNTERED Depths Encountered Net Allowable Bearing
Capacity(FS=3)
Asphalt/Crushed Gravel TH # 1,2 0.0 - 0.5 feet -
Silt (ML) TH # 1,2 0.5 - 7.5 feet 1,300 lbs/ft²
Caliche Hardpan TH # 1,2 7.5 - 11.0 feet 3,000 lbs/ft²
Basalt TH # 1,2 11.0 - 12.0 feet (refusal) 6,000 lbs/ft²
VM+
HM+
HORIZONTAL RIGHTHR
VERTICAL RIGHTVR
-13.3±8.6
HM
19.3
VM
LEAN-TO
A.B.I.
MAIN
BUILDING
ENCLOSURE
CONTROL
(CONTRACTION) JOINT
TYP.
FOUNDATION MARK,
F3
F3 F3 F3
FINISHED FLOOR
≈ 3913.8'
3/4" 3/4"
BOLLARD, TYP. ( SEE CIVIL)
OVERHEAD
DOOR
RECESS
OVERHEAD DOOR RECESS
LEAN-TO
INTERIOR GRADE BEAM,
SEE 2/S101
GRADE BEAM, SEE
2/S101
TIE BEAM, (SEE
5/S101)
BOLLARD, TYP. (SEE
CIVIL AND 3/C201)
SLOPE FLOOR WITH 1"
FALL TO FLOOR DRAIN
F2 F1 F1 F2
F2 F1 F1 F2
MAIN FAN SUPPORT PROVIDE INSET (2) 8ZS2.25X85
PURLINS FULLY SPANNING BETWEEN CENTER BAY OF
BUILDING FRAME.
PROVIDE INSET (2) 6ZS2.25X65 FOR FAN SUPPORT
BETWEEN 8ZS2.25X85 PURLINS
GUY PER
MANUFACTURER'S
WRITTEN
REQUIREMENTS
(NOT IN CONTRACT)
HIGH SPEED LOW
VOLUME FAN (130#, MAX)
(NOT IN CONTRACT)
BASE BID BASE BID
SEE DETAIL 3/S101
EXTERIOR GRADE BEAM, TYP.
(SEE 1/S101)
SEE DETAIL 3/S101
BID OPTION
BID OPTION
SUPPLEMENTAL ROOF FRAMING - (2)
8ZS2.25X85 ZEE (MAIN) AND (2)
6ZS2.25X65 ZEES (INSET OR FLUSH TO
FRAMING) SEE 2/S001.
4' 4'
U
D A
S
KIMBERLY, ID
STRUCTURAL NOTES
S001
08' 8'
1'-0"
4'
SCALE: 1/8" = 1'-0"
06' 6'3'
SCALE: 3/16" =
APPROXIMATED STRUCTURAL SECTION2
SCALE: 1/8" = 1'-0"S001
GENERAL LAYOUT1
SCALE: 1/8" = 1'-0"S001
GEOTECHNICAL ENGINEERING (SOIL BORING) REPORT:
3"
CLR.
#4 @ 16" OC EW
VAPOR RETARDER
6" CAPILLARY BARRIER
8"
GRADED/STABILE/COMPACTED SUBGRADE
3500 PSI CONCRETE
1. CAPILLARY BARRIER SHALL BE A COARSE AGGREGATE WITH #57 GRADATION OR APPROVED EQUAL.
2. VAPOR RETARDERS SHALL MEET THE REQUIREMENTS OF ASTM E1745. ALL LAPS SHALL BE SEALED IN ACCORDANCE WITH THE
MANUFACTURER'S WRITTEN INSTRUCTIONS AND ACI 360.
3. CONCRETE SHALL OBTAIN A MINIMUM 3500 PSI STRENGTH AT 28 DAYS. CONCRETE SLUMP SHALL NOT EXCEED 5" WITHOUT THE
WRITTEN APPROVAL OF THE CONTRACTING OFFICER.
4. AREAS OF THE SITE WITHIN THE BUILDING AREA SHOULD BE EXCAVATED TO SUFFICIENT DEPTHS TO REMOVE EXISTING
ASPHALT AND ORGANIC MATERIAL. THE EXPOSED SUBGRADE MATERIAL SHOULD BE RE-COMPACTED TO A MINIMUM OF 92% OF THE MAXIMUM DENSITY AS OF ASTM D-1557. A CLEAN, FREE DRAINING GRANULAR MATERIAL SHOULD BE INSTALLED BELOW ALL SLABS ON GRADE. THIS MATERIAL SHOULD BE A MINIMUM OF SIX (6) INCHES AND COMPACTED TO A MINIMUM 95% OF THE
MAXIMUM DENSITY AS DETERMINED BY ASTM D-1557.
JOINT SEALANT
1/8" 'T'
1 1/2"
1/3 'T'
1/6 'T'
L x W
SEE SCHEDULE
3'-0"
8"
COLUMN
1/2" EXPANSION
JOINT
FIN. FLR. ≈
X'X" (ARCH)
3913.8' (CIVIL)
BASE PLATES, ANCHOR RODS, AND COLUMNS SHALL BE
PROVIDED AS REQUIRED PER THE BUILDING
MANUFACTURER'S DRAWINGS. THESE DRAWINGS
SHALL BE STAMPED AND SIGNED BY THE
MANUFACTURERS' PROFESSIONAL ENGINEER AND
APPROVED BY THE CONTRACTING OFFICER PRIOR TO
BEGINNING CONSTRUCTION ON THE FOUNDATION.
(2) #4 HAIRPIN INTO SLAB
- 3" BELOW BASE PLATE
2"
1'-8"
1'-8"
1'-8
JOINT SEALANT
1/8" 'T'
1 1/2"
1/3 'T'
1/4 'T'
FOOTING SCHEDULE
MARK LENGTH
F1 6'-0"
WIDTH THICKNESS
2'-0"
REINFORCEMENT
(7) #6, E.W.6'-0"
NOTE: UNLESS OTHERWISE NOTED, THE TOPS OF ALL FOOTINGS
TO BE 3'-0" BELOW FINISHED FLOOR ELEVATION.
F2 4'-0" 1'-6" (5) #6, E.W.4'-0"
PANEL NOTCH
2" LAP
FOR CLARITY, CAPILLARY BARRIER AND SLAB DETAILS ARE NOT SHOWN.
** COORDINATE FINAL DIMENSIONS WITH METAL BUILDING MANUFACTURER.
COLUMN
LINE
L x W
SEE SCHEDULE
THICKNESS
SEE SCHEDULE
3'-0"
2" NON SHRINK GROUT
F3 4'-0" 1'-6" (5) #6, E.W.4'-0"
SLAB ON GRADE NOTES:
THICKNESS
SEE SCHEDULE
U
D A
S
KIMBERLY, ID
STRUCTURAL DETAILS
S100
SCALE: 1" = 1'-0"
0 1' 2' 2'-6"1' 6" 6"
FOOTING DETAILS3
SCALE: 1" = 1'-0"S100
SLAB ON GRADE1
SCALE: NONES100
SLAB JOINT DETAILS2
SCALE: NONES100
COLUMN
LINE
COLUMN
LINE
COLUMN
LINE
COLUMN
LINE
COLUMN
LINE
CONTROL JOINT DETAIL
CONSTRUCTION JOINT DETAIL
SECTION
F1-FOOTING
SECTION
F2-FOOTING
PLAN
F1-FOOTING
PLAN
F2-FOOTING
(3) #4 HAIRPIN INTO SLAB/GRADE BEAM
(2) 3" BELOW BASE PLATE (1) 6"
ABOVE BOTTOM OF ANCHOR BOLTS
FOOTING, SEE SCHEDULE
EDGE OF SLAB
EDGE OF SLAB
FOOTING, SEE
SCHEDULE
(2) #4 HAIRPIN INTO
GRADE BEAM - 3"
BELOW BASE PLATE
COLUMN
1/2" EXPANSION
JOINT
ANCHOR RODS **
BASE PLATE
1/2" EXP. JOINT MATERIAL
(6) #3 TIES
(8) #5 VERTICAL
COLUMN
EDGE OF SLAB
2% MIN
FOR 10 '
REINFORCING, SEE
SCHEDULE
COLUMN
EDGE OF SLAB
ANCHOR RODS **
BASE PLATE
2" NON SHRINK GROUT
1/2" EXP. JOINT MATERIAL
(6) #3 TIES
(8) #5 VERTICAL
REINFORCING, SEE
SCHEDULE
FINISHED FLOOR ≈
3915.8' (CIVIL)
(1) - SAW JOINTS AS SOON AS CONCRETE SETS AND
PRIOR TO FORMATION OF RANDOM CRACKING
EVERY THIRD BAR SHALL RUN
CONTINUOUS THROUGH THE
JOINT
FORMED KEY JOINT 1
(APPROX 1 X3) 2
EVERY THIRD BAR SHALL RUN
CONTINUOUS THROUGH THE
JOINT
(1)
1'-8"
1'-8"
(3) #5, BOTTOM
(2) #5
(3) #5, TOP
#3, 12" O.C.
(3) #5, BOTTOM
(3) #5, TOP
#3, 12" O.C.
1'-8"
1'-8"
3"
2'-0"
CONTROL (CONTRACTION)
JOINT, TYP
2'-2"
#3 @ 16" O.C.
(2)#5 CONT.
1'-0"
6" 3 4"
0"
2" **
L x W
SEE SCHEDULE
TH
IC
KN
ES
S
SE
E
SC
HE
DU
LE
(6) #3 TIES
(8) #5 VERTICAL
1'-8"
SQ
FOOTING (BEHIND)
REINFORCING,
SEE SCHEDULE
12" EXPANSION MATERIAL
GRAVEL PAVEMENT APRON
(SEE CIVIL)
* OVERHEAD DOOR SEAT (CONFIRM DISTANCE WITH
DOOR MANUFACTURER)
18"
12"
(3) #7 TOP AND BOTTOM
#3 TIES AT 7" OC
COLUMN/PIER - SEE SCHEDULE FOR SIZE AND
REINFORCEMENT
FOOTING - SEE SCHEDULE FOR
SIZE AND REINFORCEMENT
TIE BEAM
U
D A
S
KIMBERLY, ID
STRUCTURAL DETAILS
S101
SCALE: 1" = 1'-0"
0 1' 2' 2'-6"1' 6" 6"
EXTERIOR GRADE BEAM1
SCALE: 1" = 1'-0"S101
COLUMN
LINE
COLUMN
LINE COLUMN
LINE
COLUMN
LINE
INTERIOR GRADE BEAM2
SCALE: 1" = 1'-0"S101
GRADE BEAM @ RAMP3
SCALE: 1" = 1'-0"S101
F3 - FOOTING4
SCALE: 1" = 1'-0"S101
TIE BEAM5
SCALE: 1" = 1'-0"S101
FF=3913.8' ± FF=3913.8' ±
FF=3913.8' ±
FF=3913.8' ±2% GRADE (MIN)
FARM STORAGE
A301
PROVIDE BIRD SCREEN
ON UNDERSIDE OF
LEAN TO (BID OPTION)
A201
40'
20'
37'-4" 20'-10"
1'-10"
EQ
UA
L S
PA
CI
NG
EQ
UA
L S
PA
CI
NG
BASE BID BID OPTION
BASE BID BID OPTION
PROVIDE EYE WASH STATION (SEE PLUMBING)
PERSONNEL DOOR (BID OPTION)
A201
A201
A301
U
D A
S
KIMBERLY, ID
FLOOR PLAN
A101
GRAPHIC SCALE
04' 4'
1'-0"SCALE: 1/4"=
2'
SCALE:
FLOOR PLAN
1/4" = 1'-0"
A101
GENERAL NOTES
A. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS
AND EXISTING CONDITIONS PRIOR TO PERFORMING ANY
WORK OR FABRICATION OR PURCHASE OF EQUIPMENT,
MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS SHALL BE
BROUGHT TO THE CONTRACTING OFFICER'S ATTENTION
FOR RESOLUTION BEFORE PROCEEDING WITH ANY
CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.
B. ALL UTILITIES AFFECTED BY DEMOLITION SHALL BE
REINSTALLED IN THE WORK OR CAPPED AND TERMINATED
IN ACCORDANCE WITH CODES.
C. ALL EXPOSED STRUCTURAL STEEL MUST BE PAINTED, SEE
SPEC SECTION 09 90 00. COLOR TO BE DETERMINED BY
OWNER/USER.
36'H BY 36"W EXHAUST FAN
(SEE DETAIL 1/A501 AND
MECHANICAL DRAWINGS)
PROVIDE BIRD CONTROL SYSTEM @
UNDERSIDE OF LEAN TO, ATTACH TO BOTTOM
OF EXPOSED STEEL STRUCTURE (BID
OPTION) **
METAL OUTSIDE CORNER TRIM
'-8
' E
AV
E
HE
IG
HT
24'
3'
3'
24' BY 16' INSULATED, HEAVY
DUTY OVERHEAD SECTIONAL
STEEL DOOR; BASIS OF DESIGN
IS CLOPAY COMMERCIAL -
MODEL 3724
METAL WALL PANEL
PERSONNEL DOOR AS SCHEDULED
(SEE 2/A501)
20'
BID OPTION BASE BID
GUTTER AND DOWNSPOUT TO
MATCH OPPOSITE SIDE IF BID
OPTION IS NOT EXECUTED
4" BY 5" METAL DOWNSPOUT
(TYP.)
CONCRETE SPLASH BLOCK
TYPICAL AT EACH DOWNSPOUT
' E
AV
E
HE
IG
HT
STANDING SEAM METAL ROOF
METAL OUTSIDE CORNER TRIM
METAL WALL PANEL
METAL GUTTER (TYP.)
' E
AV
E
HE
IG
HT
'-8
3'
4'
24'
METAL WALL PANEL
48'H BY 36"W LOUVERS (SEE DETAIL
1/A501 AND MECHANICAL DRAWINGS)
24' BY 16' INSULATED, HEAVY
DUTY OVERHEAD SECTIONAL
STEEL DOOR; BASIS OF DESIGN
IS CLOPAY COMMERCIAL -
MODEL 3724
METAL OUTSIDE CORNER TRIM
PROVIDE BIRD CONTROL SYSTEM @
UNDERSIDE OF LEAN TO, ATTACH TO
BOTTOM OF EXPOSED STEEL
STRUCTURE (BID OPTION) **
PERSONNEL DOOR AS SCHEDULED
(SEE 2/A501) ** PROVIDE BIRD CONTROL SYSTEM TO UNDERSIDE OF EXPOSED
STRUCTURE TO ENSURE A CLOSED AND SEALED SYSTEM FOR A
BIRD FREE AREA. PROVIDE A BIRD CONTROL NETTING SYSTEM AND
ALL ACCESSORIES AND MOUNTING EQUIPMENT FOR A COMPLETE
SYSTEM. PROVIDE BIRD SPIKES AT LEDGES OF EXPOSED STEEL
STRUCTURE. BASIS OF DESIGN IS "BIRD-B-GONE INC.". SEE SPEC
SECTION 13 34 19.
20'
BID OPTIONBASE BID
GUTTER AND DOWNSPOUT TO
MATCH OPPOSITE SIDE IF BID
OPTION IS NOT EXECUTED
U
D A
S
KIMBERLY, ID
ELEVATIONS
A201
GRAPHIC SCALE
04' 4'
1'-0"SCALE: 1/4"=
2'
SCALE:
NORTH ELEVATION
1/4" = 1'-0"
A201 SCALE:
SOUTH ELEVATION
1/4" = 1'-0"
A201
SCALE:
WEST ELEVATION
1/4" = 1'-0"
A201
INTERIOR
METAL
LINER PANEL
STRAIGHT
SIDEWALL
COLUMNS
8" WALL GIRTS
VINYL FACED R-19
METAL BUILDING
INSULATION
METAL WALL PANEL
VINYL FACED METAL
BUILDING INSULATION
STANDING SEAM METAL ROOF OVER R-25
OPEN FACE BATT INSULATION OVER VINYL
FACED R-9 LINER INSULATION
METAL RIDGE CAP FLASHING
8" CONCRETE SLAB (SEE
STRUCTURAL)
METAL GUTTER (TYP.)
PROVIDE BIRD CONTROL SYSTEM @
UNDERSIDE OF LEAN TO, ATTACH TO
BOTTOM OF EXPOSED STEEL
STRUCTURE (BID OPTION) (**SEE
NOTE ON A201)
' E
AV
E
HE
IG
HT
8" EAVE STRUT
8" ROOF PURLINS TYP.
8" EAVE STRUT
24' BY 16' INSULATED, HEAVY
DUTY OVERHEAD SECTIONAL
STEEL DOOR
METAL GUTTER
WITH SUPPORT
STRAP (BID OPTION)
A501
8" CONCRETE SLAB (SEE
STRUCTURAL)
INTERIOR METAL
LINER PANEL
STRAIGHT
SIDEWALL
COLUMNS
8" WALL GIRTS
VINYL FACED R-19 METAL
BUILDING INSULATION
METAL WALL PANEL
RAKE TRIM FASTENED
WITH STITCH SCREW
SPACED EVERY 12"
WITH CONTINUOUS
TAPE SEAL (TYP.)
COLUMNS BEYOND (SEE
STRUCTURAL)
STANDING SEAM METAL ROOF
VINYL FACED METAL
BUILDING INSULATION
20'
BID OPTION
BID OPTIONBASE BID
GUTTER AND DOWNSPOUT TO
MATCH OPPOSITE SIDE IF BID
OPTION IS NOT EXECUTED
EYE WASH,
SEE PLUMBING
PERSONNEL DOOR
AND FRAME (BID
OPTION)
A501
A501
U
D A
S
KIMBERLY, ID
BUILDING SECTIONS
A301
GRAPHIC SCALE
04' 4'
1'-0"SCALE: 1/4"=
2'
SCALE:
SECTION
1/4" = 1'-0"
A301
SCALE:
SECTION
1/4" = 1'-0"
A301
GENERAL NOTES
A. ALL EXPOSED STRUCTURAL STEEL MUST BE PAINTED, SEE
SPEC SECTION 09 90 00. COLOR TO BE DETERMINED BY
OWNER/USER.
VINYL FACED
INSULATION
8" "C" CHANNEL
METAL WALL PANEL
METAL TRIM
SEALANT W/BACKER ROD
LOUVER (SEE MECHANICAL)
1-1/2"x 1-1/2"x 1/8" ANGLE CONT.
1-1/2"x 1-1/2"x 1/8" ANGLE CONT.
LOUVER (SEE MECHANICAL)
METAL "J" TRIM
8" "C" CHANNEL
VINYL FACED
INSULATION
METAL WALL PANEL
3-1/2" VINYL FACED
INSULATION
8" "C" CHANNEL
METAL WALL PANEL
METAL SILL TRIM
SEALANT W/BACKER ROD
LOUVER (SEE MECHANICAL)
1-1/2"x 1-1/2"x 1/8" ANGLE CONT.
HEAD
SILL
JAMB
1"
5 1/4"
1 1 /2"
7"
PROVIDE METAL WALL PANEL
WITH VINYL FACED INSULATION
8" WALL GIRTMETAL FRAME 2"
SEALANT
DOOR AS SCHEDULED
JAMB ANCHOR
3-5/8" x 24GA. METAL
SILL
DOOR AS SCHEDULED
METAL WALL PANEL
1/2" EXPANSION
MATERIAL
EXISTING
FOUNDATION
THRESHOLD SET IN BED OF
SEALANT W/MIN. (3) 1/4" DIA.
ANCHORS
DOOR SWEEP
RAIN DRIP
HEAD/JAMB
RAKE TRIM
STITCH SCREW AT 12" O.C. (TYP.) CONTINUOUS TAPE SEAL
STANDING SEAM
ROOFING PANEL
STITCH SCREW AT
12" O.C. (TYP.)
CLOSURE
WALL PANEL
METAL RIDGE CAP FLASHING
STANDING SEAM
ROOFING PANEL
8" ROOF
PURLINS TYP.
PANEL CLOSURE
RIDGE ℄
LOCKRIVET AT 12" O.C.
BOTH SIDES
6"x6" METAL
GUTTER (TYP.)
8" EAVE STRUT
METAL WALL PANEL
STANDING SEAM
ROOFING PANEL
U
D A
S
KIMBERLY, ID
DETAILS
A501
GRAPHIC SCALE
SCALE:
LOUVER HEAD/JAMB/SILL DETAILS
3" = 1'-0"
A501
SCALE:
EXTERIOR DOOR HEAD/JAMB/SILL DETAILS
1-1/2" = 1'-0"
A501 SCALE:
RAKE TRIM DETAIL
1-1/2" = 1'-0"
A501
SCALE:
ROOF RIDGE DETAIL
1-1/2" = 1'-0"
A501 SCALE:
GUTTER DETAIL
3" = 1'-0"
A501
08" 8"
1'-0'SCALE: 1-1/2" =
4"
04" 4"
1'-0'SCALE: 3" =
2"
7' 2"
3'2" 2"
2"
24'2" 2"
TINTED
INSULATED
GLASS (TYP.)
U
D A
S
KIMBERLY, ID
SCHEDULES
A601
DOOR SCHEDULE
NUMBER
GALV.
SET
HARDWAREDOOR
THICKNESSMATERIALMARK
PAINT
FINISH
NOTESFRAME
TYPE
GALV.
FINISH
HW-1A
METAL PAINT
05 1 3/4" PAINT PAINT
B METAL
METAL METAL
METAL
METAL
PAINTMETAL
METAL
METAL
- PAINT
1 3/4" PAINT
NOTES:
1. INSULATED DOOR.
2. LOCKS TO BE SCHLAGE TO MATCH EXISTING CAMPUS SYSTEM. KEY/PIN TO MATCH
MASTER KEY. SEE HW-1 IN SPEC SECTION 08 71 00.
3. BID OPTION.
4. PROVIDE MANUFACTURER'S HARDWARE INCLUDING LOCKING HARDWARE.
A B
METAL 1 3/4" PAINT
HW-1
HW-1
A
FINISH SCHEDULE
ROOM
NO ROOM NAME FLOOR BASE
WALLS
CEILING
NOTESEAST WEST NORTH SOUTH
MAT'L MAT'L MAT'L MAT'L MAT'L HEIGHT
101 FARM STORAGE SC - -
DOOR TYPES
LEGEND:
SC STAINED CONCRETE
MLP METAL LINER PANEL
VFI VINYL FACED INSULATION
NOTES:
1. PAINT EXPOSED STRUCTURE.
1, 4 1, 4
1, 2 1, 2, 3
1, 2
A
S
KIMBERLY, ID
M001
ABBREVIATIONS AND GENERAL NOTES
MECHANICAL LEGEND GENERAL NOTES
1. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION OR PURCHASE OF EQUIPMENT, MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS MUST BE BROUGHT TO THE CONTRACTING OFFICERS ATTENTION FOR RESOLUTION BEFORE PROCEEDING WITH ANY CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.
2. PROVIDE SAFETY BARRIERS AND FOLLOW ALL SAFETY REQUIREMENTS OF THE OWNER. TAKE PRECAUTIONS
TO ENSURE THE SAFETY OF ALL PERSONNEL.
3. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS (DO NOT SCALE FOR LOCATIONS). THE CONTRACTOR MUST PROVIDE A COMPLETE AND FUNCTIONAL HEATING, VENTILATING, AND AIR CONDITIONING SYSTEM (HVAC) AS INDICATED WITH ALL NECESSARY
EQUIPMENT, APPURTENANCES AND CONTROLS AS INDICATED.
4. CONTRACTOR MUST EMPLOY WORKMEN WHO ARE TRAINED AND EXPERIENCED IN NECESSARY SKILLS TO
PERFORM THE WORK.
5. PROVIDE AND INSTALL THERMOSTATS OR TEMPERATURE SENSORS WHERE SHOWN ON THE DRAWINGS.
MOUNT DEVICE AT 4'-0" ABOVE THE FINISHED FLOOR UNLESS OTHERWISE NOTED.
6. ALL PENETRATIONS OF THE BUILDING ENVELOPE MUST BE FULLY SEALED WATER TIGHT.
7. UNLESS NOTED OTHERWISE, THE WORD “FURNISH” MEANS ITEM(S) THAT ARE TO BE PROCURED OR
FABRICATED AND INSTALLED BY THE CONTRACTOR.
ABBREVIATIONS
TEMPERATURE SENSORT REFER TO KEYED NOTESOR THERMOSTAT
AFF ABOVE FINISHED FLOOR LB POUND
AI ANALOG INPUT LEF LAB EXHAUST FAN
AO ANALOG OUTPUT MAU MAKEUP AIR UNIT
APPROX APPROXIMATE MAX MAXIMUM
ARCH ARCHITECTURAL MECH MECHANICAL
BI BINARY INPUT MFR MANUFACTURER
BO BINARY OUTPUT MIN MINIMUM OR MINUTE
CD CEILING DIFFUSER NC NORMALLY CLOSED
CFM CUBIC FEET PER MINUTE NO NORMALLY OPENED
CL CENTER LINE NPT NATIONAL PIPE THREAD
CLG CEILING Ø DIAMETER, PHASE
CONC CONCRETE O/A OUTSIDE AIR
DET DETAIL OD OUTSIDE DIMENSION
DIA DIAMETER ODU OUTDOOR UNIT
DIM DIMENSION PH PHASE
DWG DRAWING PSI POUNDS PER SQUARE INCH
E/A EXHAUST AIR R/A RETURN AIR
EA EACH RAD RADIUS
EAG EXHAUST AIR GRILLE RAR RETURN AIR REGISTER
EAT ENTERING AIR TEMPERATURE RED REDUCER
ECC ECCENTRIC REINF REINFORCING
EDH ELECTRIC DUCT HEATER REQ'D REQUIRED
EF EXHAUST FAN RPM REVOLUTIONS PER MINUTE
EFF EFFICIENCY RTU ROOF TOP UNIT
ELEC ELECTRICAL S/A SUPPLY AIR
ELEV ELEVATION SAG SUPPLY AIR GRILLE
F FAHRENHEIT SD SMOKE DETECTOR
FIN FINISHED SEN SENSIBLE
FLR FLOOR SF SQUARE FEET
FPM FEET PER MINUTE SQ SQUARE
FT FOOT SS STAINLESS STEEL
GA GAUGE TA TRANSFER AIR
GALV GALVANIZED TEMP TEMPERATURE
GEN GENERAL TH THERMOMETER
HR HOUR TYP TYPICAL
ID INSIDE DIMENSION UH UNIT HEATER
IDU INDOOR UNIT UNO UNLESS NOTED OTHERWISE
IN INCHES V VOLTS
KW KILOWATT W/ WITH
LAT LEAVING AIR TEMPERATURE WT WEIGHT
X
U
D A
S
KIMBERLY, ID
GRAPHIC SCALE
04' 4'
1'-0"SCALE: 1/4"=
2'
SCALE:
HVAC FLOOR PLAN
1/4" = 1'-0"
M101
GENERAL NOTES
A. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS
AND EXISTING CONDITIONS PRIOR TO PERFORMING ANY
WORK OR FABRICATION OR PURCHASE OF EQUIPMENT,
MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS SHALL BE
BROUGHT TO THE CONTRACTING OFFICER'S ATTENTION
FOR RESOLUTION BEFORE PROCEEDING WITH ANY
CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.
GUH-1
M101
HVAC FLOOR PLAN
EF-1
L-1 L-2
1. PROVIDE NEW LOW PRESSURE OUTPUT GAS REGULATOR
WITH SHUTOFF VALVE. SIZED FOR 560 CFH @ 1 PSI INPUT.
REFER TO SITE UTILITIES PLAN
2. MOUNT UNIT HEATERS PER MANUFACTURER'S WRITTEN
DOCUMENTATION ANGLE TOWARDS CENTER OF BUILDING
AS SHOWN. MAINTAIN RECOMMENDED CLEARANCES.
PROVIDE CONCENTRIC VENT KIT.
3. MOUNT EXHAUST FAN @ 16'-0" AFF. COORDINATE WITH
ARCHITECTURAL PLANS.
4. MOUNT INTAKE LOUVER @ 16'-0" AFF. COORDINATE WITH
ARCHITECTURAL PLANS.
KEYED NOTESX
EF-2
GUH-2
GUH-3
GUH-4
1"Ø GAS PIPING
1"Ø GAS PIPING
1-1/2"Ø GAS PIPING
2"Ø GAS PIPING
EXISTING GAS PIPING. SEE
CIVIL FOR CONTINUATION.
T T
TT
A
S
KIMBERLY, ID
M501
HVAC SCHEDULES AND DETAILS
NOTES
1. SINGLE SPEED, TOTALLY ENCLOSED FAN MOTOR.
2. DIRECT DRIVE PROPELLER FAN.
3. FACTORY INSTALLED 24V CONTROL TRANSFORMER.
4. SEPARATED COMBUSTION WITH ALUMINIZED HEAT EXCHANGER (82% MINIMUM EFFICIENCY).
5. SINGLE STAGE GAS VALVE.
6. DIRECT SPARK IGNITION.
7. PROVIDE FINGER PROOF FAN GUARD.
8. PROVIDE LOW VOLTAGE, SINGLE STAGE WALL THERMOSTAT WITH HEAT/OFF/FAN SWITCH. MOUNT AT 48" AFF.
9. PROVIDE FIELD INSTALLED VERTICAL CONCENTRIC VENT KIT.
GAS UNIT HEATER SCHEDULE
MARK
BASIS OF DESIGN
FUEL
GAS
INPUT
(MBH)
HEAT
OUTPUT
(MBH)
FAN
CFM
HEAT
THROW
(FT)
ELECTRICAL DATA WEIGHT
(LB) NOTESMANUFACTURER MODEL NO. MOTOR
HP
MOTOR
RPM
MOTOR
AMPS
TOTAL
AMPS VOLTAGE
GUH-1, GUH-2,
GUH-3, GUH-4 MODINE HDS125 NATURAL
GAS 30 24.6 505 25 1/15 1550 2.4 3.8 120/1/60 55 ALL
NOTES
1. PROVIDE WITH GRAVITY BACKDRAFT DAMPER
2. PROVIDE WITH GALVANIZED STEE FAN PANEL
3. PROVIDE WITH CAST ALUMINUM AIRFOIL BLADE PROPELLER
4. PROVIDE WITH BALL BEARING DIRECT DRIVE MOTOR
5. PROVIDE SPEED CONTROLLER MOUNTED IN ACCESIBLE SPACE (SHIPPED LOOSE)
6. PROVIDE GALVANIZED STEEL WALL HOUSING WITH OSHA GUARD AND MOUNTING FLANGE (SHIPPED LOOSE)
7. LOCAL ON OFF SWITCH (INTERLOCK WITH INTAKE LOUVER AND FAN MOTOR).
EXHAUST FAN SCHEDULE
MARK
BASIS OF DESIGN
TYPE
FAN DATA ELECTRICAL DATA
NOTESMANUFACTURER MODEL NO. VOLUME
(CFM)
ESP
(IN. WG) RPM MOTOR
POWER VOLTAGE
EF-1, EF-2 GREENHECK AER-E36C-310-VGWALL PROPELLER 2,500 0.05 416 3/4 120/1 ALL
WALL LOUVER SCHEDULE
MARK
BASIS OF DESIGN WIDTH
(IN.)
HEIGHT
(IN.)
CLEAR
AREA (SF)
DESIGN
CFM
VELOCITY
(FPM)
PRESSURE
DROP
(IN, WG)
SERVICE MATERIAL MOTORIZED
ACTUATOR NOTESMANUFACTURER MODEL NO.
L-1, L-2 GREENHECK EAD-601 36 48 5.4 2500 460 0.03 INTAKE ALUMINUM YES - 120V ALL
NOTES
1. PROVIDE WITH BIRD SCREEN.
2. PROVIDE 120V ACTUATOR INTERLOCKED TO WALL MOUNTED EXHAUST FANS.
NEW GAS PRESSURE
REGULATOR
250# UNION
SHUTOFF VALVE
250# UNION
1 PSIG
11" W.C.
VENT PIPE PER MFGR'S INSTALLATION INSTRUCTIONS AND
ALL APPLICABLE CODES
SCALE:
GAS PRESSURE REGULATOR DETAIL
NOT TO SCALE
M501
COMBUSTION AIR
1" CLEARANCE COMBUSTION
AIR INLET VANES TO ROOF
VENT
PROVIDE SECURING STRAP
TO PREVENT MOVEMENT OF
TERMINATION KIT IN ROOF
CONNECT TO UNIT HEATER
PER MFG INSTRUCTIONS
RAIN SHIELD
ROOF
SCALE:
CONCENTRIC VENT DETAIL
NOT TO SCALE
M501
SCALE:
GAS UNIT HEATER DETAIL - GUH-1,2,3,4
NOT TO SCALE
M501
SUPPORT UNIT HEATER FROM
STRUCTURE WITH FOUR-POINT
SUSPENSION. COMPLY WITH
MFGR'S. RECOMMENDATIONS.
UNIT
HEATER
GAS
MAIN
SHUTOFF
VALVE
DIRTLEG
UNION
MAXITROL "RS" REGULATOR
(OR EQUAL)
ROOF
CONCENTRIC VENT KIT
PROVIDED WITH HEATER
(SEE 2/M501)
ACTUATOR
SPEED CONTROL
(MOUNT IN AN ACCESSIBLE LOCATION)
DIRECT DRIVE MOTOR
W/FINGER SAFE GUARD
OPERABLE EXHAUST LOUVER
(INTERLOCK WITH INTAKE
LOUVER AND FAN MOTOR)
OFF ON
LOCAL ON OFF SWITCH
(INTERLOCK WITH INTAKE
LOUVER AND FAN MOTOR)ELECTRICAL SUPPLY
WALL ANGLE
INTERLOCK WIRING TO INTAKE LOUVER
WALL SLEEVE
ACTUATOR
OPERABLE INTAKE LOUVER
(INTERLOCK WITH EXHAUST
LOUVER AND FAN MOTOR)
WALL ANGLE
INTERLOCK WIRING
FROM EXHAUST FAN
SCALE:
SIDEWALL EXHAUST DETAIL - EF-1,2
NOT TO SCALE
M501
SCALE:
INTAKE LOUVER DETAIL - L-1,2
NOT TO SCALE
M501
A
S
KIMBERLY, ID
PLUMBING LEGEND
DIRECTION OF FLOW
PIPE TURNED DOWN
PIPE TURNED UP
RISE OR DROP
BRANCH BOTTOM CONNECTION
TEE OUTLET UP
TEE OUTLET DOWN
CAP ON END OF PIPE
SANITARY WASTE - ABOVE FLOOR OR GRADE
SANITARY WASTE - BELOW FLOOR OR GRADE
VENT PIPING
POTABLE / DOMESTIC COLD WATER PIPING
POTABLE / DOMESTIC HOT WATER SUPPLY PIPING
PLUMBING ABBREVIATIONS
BRANCH TOP CONNECTION
POTABLE / DOMESTIC HOT WATER RETURN PIPING
° DEGREES
Ø DIAMETER
AC AIR COMPRESSOR
AD AIR DRYER
AFF ABOVE FINISHED FLOOR
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
BFP BACKFLOW PREVENTER
BTU BRITISH THERMAL UNIT
CA COMPRESSED AIR
CO CLEANOUT
CW COLD WATER (DOMESTIC)
DWV DRAIN WASTE AND VENT
EMCS ENERGY MANAGEMENT CONTROL SYSTEM
ET EXPANSION TANK
EW EYE WASH
EWC ELECTRIC WATER COOLER
F FARENHEIGHT
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FT FOOT
GAS NATURAL GAS
GCO GROUND CLEANOUT
GPM GALLONS PER MINUTE
GWH GAS WATER HEATER
HP HORSEPOWER
HW HOT WATER (DOMESTIC)
HWCP HOT WATER CIRCULATION PUMP
HWR HOT WATER RETURN (DOMESTIC)
IMB ICE MAKER BOX
IPC INTERNATIONAL PLUMBING CODE
kW KILLOWATT
KS KITCHEN SINK
LV LAVATORY
MAX MAXIMUM
MIN MINIMUM
MS MOP SINK
NPT NATIONAL PIPE TAPER
P PLUMBING
PDI PLUMBING AND DRAINAGE INSTITUTE
PSI POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE
RPZ REDUCED PRESSURE ZONE
S SANITARY SEWER
SH SHOWER
SS SAFETY SHOWER
SSEW SAFETY SHOWER EYE WASH
TYP TYPICAL
U/G UNDERGROUND
UR URINAL
V VENT PIPING
VTR VENT THROUGH ROOF
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WCO WALL CLEANOUT
WH WALL HYDRANT
WHA WATER HAMMER ARRESTOR
NOTE:
UNDERLINED FIXTURE AND EQUIPMENT MARKS (SUCH AS WC) ARE
NOT ABBREVIATIONS. REFER TO THE PLUMBING SCHEDULE SHEETS,
P601 - P699 FOR FIXTURE AND EQUIPMENT DESCRIPTIONS.
GENERAL PLUMBING NOTES
1. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS (DO NOT SCALE FOR LOCATIONS). THE CONTRACTOR WILL PROVIDE A COMPLETE AND FUNCTIONAL PLUMBING SYSTEM AS INDICATED WITH ALL NECESSARY
EQUIPMENT, APPURTENANCES AND CONTROLS AS INDICATED.
2. THE CONTRACTOR MUST REVIEW THE DRAWINGS OF OTHER TRADES AS PART OF THIS CONTRACT FOR ADDITIONAL WORK REQUIRED AND FOR COORDINATION OF PLUMBING WORK FOR OPERATIONS OF OR CONNECTIONS TO OTHER TRADES.
3. CONTRACTOR MUST EMPLOY WORKMEN WHO ARE TRAINED AND EXPERIENCED IN NECESSARY SKILLS TO PERFORM PLUMBING AND
PLUMBING DEMOLITION WORK.
4. MAKE OFFSETS AND TRANSITIONS TO COORDINATE WITH OTHER TRADES WITHOUT ANY ADDITIONAL EXPENSE TO THE OWNER.
CONTRACTOR MUST PROVIDE COORDINATION DRAWINGS OF TRADES.
5. ALL PIPING PENETRATIONS TO THE BUILDING ENVELOPE MUST BE FULLY SEALED WATER TIGHT.
6. CONTRACTOR MUST FIELD VERIFY EXACT LOCATIONS AND POINTS OF CONNECTIONS TO THE EXISTING UTILITIES (DOMESTIC WATER &
SANITARY SEWER, NATURAL GAS, ETCETERA).
7. REFER TO SPECIFICATIONS, SHEET NOTES, DETAILS AND SCHEDULES FOR ADDITIONAL REQUIREMENTS PERTAINING TO THE PLUMBING
WORK.
8. SCHEDULES, NOTES OR SPECIFICATIONS MAY REFERENCE "BASIS OF DESIGN" INFORMATION REGARDING A SPECIFIC MANUFACTURER
OR MODEL NUMBER. SUCH INFORMATION IS PROVIDED SO AS TO ESTABLISH A STANDARD OF PERFORMANCE, QUALITY, FEATURES AND OPTIONS (SEE SCHEDULES AND SPECIFICATIONS). THE INTENT IS NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT OF OTHER MANUFACTURERS MUST BE ACCEPTABLE PROVIDED SUCH EQUIPMENT EQUALS OR EXCEEDS THE BASIS OF DESIGN EQUIPMENT IN PERFORMANCE, QUALITY, FEATURES AND OPTIONS WHETHER SPECIFIED, SCHEDULED OR NOTED.
9. ALL EQUIPMENT FURNISHED FOR THIS PROJECT MUST COMPLY WITH THE "BUY AMERICAN ACT".
10. ALL WORK MUST BE FABRICATED AND/OR ERECTED USING CONTRACTOR'S FIELD MEASUREMENTS FOR PROPER COORDINATION WITH
WORK OF OTHER TRADES.
11. ALL CONTRACT DOCUMENTS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENTS OR GEOMETRICAL RELATIONSHIPS OF
THE WORK. THEY ARE NOT INTENDED TO SPECIFY OR SHOW EVERY OFFSET, SEQUENCE, DEVICE, OPTION, FITTING, OR COMPONENT. DO
NOT SCALE DRAWINGS.
12. INFORMATION AND COMPONENTS SHOWN ON DIAGRAMS OR DETAILS, BUT NOT SHOWN ON PLANS, AND VICE VERSA, MUST BE PROVIDED
AS IF EXPRESSLY REQUIRED BY BOTH.
13. EXCEPT WHERE INDICATED OTHERWISE, THE NOTATION OR DESCRIPTION OF ANY ITEM IN THE CONTRACT DOCUMENTS CARRIES WITH IT THE INSTRUCTION TO FURNISH AND INSTALL THE ITEM, WHETHER OR NOT THIS INSTRUCTION IS EXPLICITLY STATED.
14. ALL WORK MUST BE INSTALLED SO AS MAINTAIN ANY "UL" ASSEMBLY RATINGS, FIRE RATINGS OR SMOKE BARRIER CAPABILITIES OF WALLS, PARTITIONS, FLOORS AND ROOF. SEAL AROUND AND PLACE UL RATED FIRE-STOP MATERIAL AT ANY PENETRATION OR DISTURBANCE OF SUCH ASSEMBLIES. COORDINATE WITH ARCHITECTURAL PLANS AND CONTRACTOR.
15. COORDINATE PLACEMENT OF ALL WORK WITH OTHER TRADES. DO NOT LOCATE, POSITION OR INSTALL ANY WORK IN SUCH A WAY THAT SYSTEM COMPONENTS OR ACCESS DOORS WILL BE INACCESSIBLE, UNUSABLE OR UN-MAINTAINABLE AFTER CONSTRUCTION IS
COMPLETED. COMPLY WITH MANUFACTURER'S MINIMUM RECOMMENDED SERVICE CLEARANCES.
16. UNLESS OTHERWISE INDICATED, ALL WORK MUST BE SUPPORTED FROM STRUCTURE ABOVE, FROM WALLS, FROM COLUMNS, OR FROM THE FLOOR. DO NOT USE THE INSTALLED WORK OF OTHER TRADES, OR WORK RELATED TO ANY SUPPORT SYSTEMS FOR SUPPORT FOR
OTHER TRADES.
17. PROVIDE PIPE TRANSITIONS AS REQUIRED AT FIXTURE CONNECTIONS WHERE PIPE SIZES INDICATED DIFFER FROM THE FIXTURE
CONNECTION SIZE.
18. PROVIDE EQUIPMENT ACCESS PANELS FOR ALL EQUIPMENT AND VALVES THAT ARE LOCATED ABOVE HARD CEILINGS, IN WALLS, OR BEHIND SURFACES THAT ARE NOT REMOVABLE. ACCESS PANELS MUST BE 18"X18" MINIMUM UNLESS OTHERWISE NOTED. LOCATE ACCESS PANELS AS CLOSE AS POSSIBLE TO DEVICE NEEDING ACCESS, BUT NO FARTHER THAN 24" AWAY.
19. INSULATE HOT AND COLD DOMESTIC WATER PIPING WITH 1/2" THICK, BLACK, FLEXIBLE CLOSED-CELL ELASTOMERIC THERMAL INSULATION
COMPLYING WITH ASTM C534.
ABBREVIATIONS AND GENERAL NOTES
P001
PLUMBING FIXTURE SCHEDULE
MARK DESCRIPTION MINIMUM
SUPPLY
MINIMUM
DRAIN
EW EYE AND FACE WASH, STAINLESS STEEL BOWL, WAL MOUNT, PROVIDE 1/2"
STAY OPEN BALL VALVE. EQUAL TO GUARDIAN G1750. PROVIDE
THERMOSTATIC MIXING VALVE EQUAL TO GUARDIAN G6020.
1/2" 1-1/4"
EWH ELECTRIC WATER HEATER, 6 GALLON, WALL MOUNT, 1440 WATTS, 120V1/2" N/A
WH WALL HYDRANT, FREEZELESS, SOLID BRASS BODY AND SEAT, SATIN
NICKEL PLATED BODY, POWDER COATED CAST ALUMINUM HANDLE,
ANTI-SIPHON VACUUM BREAKER, EQUAL TO PRIER P-154.
1/2" N/A
NOTES:
BASIS OF DESIGN SHOWN TO ESTABLISH A STANDARD OF QUALITY AND PERFORMANCE, NOT TO LIMIT
COMPETITION. EQUIVALENT EQUIPMENT FROM OTHER MANUFACTURERS SHALL BE ACCEPTABLE.
U
D A
S
KIMBERLY, ID
GRAPHIC SCALE
04' 4'
1'-0"SCALE: 1/4"=
2'
GENERAL NOTES
A. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS
AND EXISTING CONDITIONS PRIOR TO PERFORMING ANY
WORK OR FABRICATION OR PURCHASE OF EQUIPMENT,
MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS SHALL BE
BROUGHT TO THE CONTRACTING OFFICER'S ATTENTION
FOR RESOLUTION BEFORE PROCEEDING WITH ANY
CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.
EW
P101
PLUMBING FLOOR PLAN
EWH
1-1/4" WASTE PIPE
TO OUTDOORS
STAY OPEN BALL VALVE WITH
PUSH PLATE
EYE WASH ASSEMBLY EQUAL TO HAWS
7260BT-7270BT.
PROVIDE POINT OF USE THERMOSTATIC
MIXING VALVE EQUAL TO HAWS MODEL
9201EFE. SET TO 80°F.
1/2" NPT SUPPLY
1/2" CW & 1/2" HW
1/2" CW & 1/2" HW
1" CW (OVERHEAD)
FINISHED WALL
SCALE:
EMERGENCY EYE-WASH DETAIL - EW
NOT TO SCALE
P101
SCALE:
PLUMBING FLOOR PLAN
1/4" = 1'-0"
P101
SCALE:
POINT OF USE WATER
HEATER DETAIL - EWH
NOT TO SCALE
P101
6 GALLON POINT OF USE WATER
HEATER EQUAL TO AO SMITH EPU-6.
1440 WATTS @ 120/1 VOLTAGE
SHUTOFF VALVE
HOT WATER
TO FIXTURES
COLD WATER TO
WATER HEATER
ROUTE T&P DISCHARGE
TO OUTDOORS
UNDERGROUND COLD WATER PIPING.
SEE CIVIL FOR CONTINUATION.
WH
1/2" CW (OVERHEAD)
FULL PORT BALL VALVE
PROVIDE SHUTOFF VALVE
IN ACCESSIBLE LOCATION
PER IPC SECTION 6.
MOUNT AT 48"
ABOVE GRADE
COLD WATER PIPING.
REFER TO PLANS FOR SIZE.
STRAP PIPING TO
STRUCTURE NON-FREEZE WALL
HYDRANT PER SCHEDULE
90° ELL
PROVIDE WALL HYDRANT
WITH STEM LENGTH TO
PREVENT FREEZING.
SCALE:
WALL HYDRANT DETAIL - WH
NOT TO SCALE
P101
VALVE BOX WITH
SHUTOFF VALVE
7LA
6A
FA
CP
U
D A
S
KIMBERLY, ID
E001
ABBREVIATIONS AND GENERAL NOTESBSN
1. ALL EQUIPMENT AND DEVICES ARE TO BE SURFACE
MOUNTED UNLESS OTHERWISE NOTED.
2. DEVICES NOTED AS "GFI" SHALL BE GROUND FAULT
CIRCUIT INTERRUPTING DEVICES.
3. DEVICES NOTED AS "WP" SHALL BE WEATHERPROOF
WHILE-IN-USE.
4. DEVICES NOTED AS "NL" SHALL BE NIGHT LIGHTS. PROVIDE
UNSWITCHED POWER TO FIXTURE.
5. DEVICES NOTED AS "WG" SHALL BE PROVIDED AND
INSTALLED WITH A WIRE GUARD.
6. PROVIDE UNSWITCHED POWER TO EMERGENCY BATTERY
PACKS.
GENERAL NOTES
LUMINAIRES
GEAR
E
HIGH BAY LED FIXTURE
EXIT SIGN WITH EMERGENCY LIGHTING
WALL MOUNTED FIXTURE
PANELBOARD
TRANSFORMER
? NEMA 3R-SS SAFETY SWITCH, AMPERAGE IDENTIFIED.
RECEPTACLES
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNTED 18"
A.F.F. TO CENTERLINE OF BOX UNLESS NOTED
OTHERWISE.
DUPLEX RECEPTACLE, NEMA 5-20R, GFCI, WPIU,
MOUNTED 18" A.F.F. TO CENTERLINE OF BOX UNLESS
NOTED OTHERWISE.
DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, ONE
COVER PLATE, MOUNTED 18" A.F.F. TO CENTERLINE
OF BOX UNLESS NOTED OTHERWISE.
RECEPTACLE 3P, 4W, 208/120V, 50A, TWIST-LOCK,
MOUNTED 48" A.F.F. TO CENTERLINE OF RECEPTACLE
UNLESS NOTED OTHERWISE.
LIGHT FIXTURES
HIGH BAY LED FIXTURE
WALL MOUNT LED FIXTURE
2X2 LED FIXTURE
EMERGENCY EXIT SIGN/LIGHTE
M
FIRE ALARM SYSTEM
MANUAL PULL STATION. MOUNT 48" A.F.F. TO
CENTERLINE OF BOX.
STROBE. MOUNT 80" A.F.F. TO BOTTOM OF BOX
COMBINATION HORN AND STROBE. MOUNT 80" A.F.F.
TO BOTTOM OF BOX.
SMOKE DETECTOR
THERMAL DETECTOR
FIRE ALARM CONTROL PANEL
Voltage Circuit Length Conductor Size (AWG)
120 < 90' #12
120 > 90' #10
120 > 145' #8
120 > 230' #6
VOLTAGE DROP CHART NOTES:
1) CIRCUIT SIZES INDICATED ON THE DRAWINGS ARE MINIMUM
REQUIREMENTS. REFER TO THIS CHART FOR UPSIZING
CONDUCTORS AS…
This is the start of the file's text. The full file is on GovTribe.