The solicitation has a construction value between $100,000 and $250,000. A mandatory site visit was held on August 7, 2024, and all questions were due by 10:00 am Central Time on August 14, 2024. Proposals are due by 5:00 pm Central Time on August 30, 2024. Bid bond guarantees are required for proposals over $150,000, and performance and payment bonds will be required after award for proposals over the respective thresholds. The specific details related to the ASME standards and weld testing requirements are not provided in the solicitation, and the contractor is responsible for acquiring those documents. The agency conducting this procurement is the USDA Agricultural Research Service, Pacific West Area.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions/Responses 12905B24Q0157
8-14-2024 – 9:00am PDT Waste Piping Vault Upgrade
QUESTIONS ARE CLOSED
NO FURTHER QUESTIONS
WILL BE ENTERTAINED
1. Can we get copies of the associated verbiage with the ASME numbers in the contract documents?
No, we are unable to share these documents. The contractor is responsible for acquiring them.
These are the original specifications from when this PPW system was first installed.
2. Can you clarify the x rays of the welds, is it to be 10% or 100% of the welds?
On page 10, section 3.4.1 "Random NDE Testing", It states: "If random testing reveals that a weld fails to meet minimum quality requirements, examine an additional 10 percent of the welds in that same group. If the additional welds examined meet the quality requirements, the entire group of welds represented shall be accepted and the defective welds shall be repaired. If any of the additional welds examined also fail to meet the quality requirements, that entire group of welds shall be rejected. Remove and re-weld rejected welds or examine rejected welds 100 percent and remove and re-weld defects."
In other words, if the additional welds (the second 10% examined within a group) fail, all welds shall be removed and defects re-welded. If a weld within this group is reviewed 100% and passes, it does not need to be removed and re-welded.