This solicitation requests quotes to construct a concrete pad and install a Government-provided generator and automatic transfer switch for the USDA Agricultural Research Service in Pomeroy, WA. The work includes all labor, materials, equipment, supervision, and transportation to install the pad and equipment in accordance with drawings, a statement of work, and contract terms. Quotes are due within 14 days of award and the project must be completed within 90 days of receiving the notice to proceed. The estimated value is between $25,000 and $100,000. Applicable labor laws and wage determinations are included as attachments.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions and Answers
Q1. Is this single phase or three phase and what is the voltage?
A1. The generator is 120/240VAC three phase 60hz.
Q2. Are permits required?
A2. This is not Federal land so normal exemptions that would be present for a military base for example do not apply.
Q3. Is the contractor responsible for filling the fuel tank and is so what is the capacity?
A3. Yes the contractor must fill the tank, the capacity is 600 gallons. The site normally purchases fuel from Four Star Supply in Pullman. Coleman Oil may be another option in Lewiston.
Q4. The ATS is not service entrance rated but no mention of a disconnect is in the SOW.
A4. Added disconnect to SOW see revised SOW.
Q5. Was startup and load bank testing included in the generator purchase?
A5. No. The contractor is responsible for providing this.