This federal contract opportunity solicitation requests proposals for water heater repair, water softener, and water filter services. The Department of Agriculture Forest Service's INRC Supervisor Office and Dispatch Center requires on-call repair and maintenance of existing water heaters, water softeners, and water filters. Offerors should submit proposals by July 15th, 2023 for an award period of one base year with four option years. Pricing should be quoted as fixed hourly rates for repair labor and equipment parts. This is a small business set-aside reserved for small business concerns only.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Installation & Service Manual
Models: SWR125, SWR150, SWR200, SWR285, SWR400, SWA150, SWA200, SWA285, SWA400 and SWA500
This manual must only be used by a qualified heating installer / service technician. Read all instructions in this manual before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.
⚠ WARNING
Save this manual for future reference.
-- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
-- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a near by phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
-- Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
100329111_2000585724_Rev_H
Contents
PLEASE READ BEFORE PROCEEDING
Hazard Definitions
THE SHIELD -- HOW IT WORKS ............................. 4-6
RATINGS
1. DETERMINE WATER HEATER LOCATION
Closet and Alcove Installations Provide Clearances Flooring and Foundation Remove Water Heater from Wood Pallet Prevent Combustion Air Contamination Using an Existing Vent System to Install a New Water Heater Removing Water Heater From Existing Common Vent . 11 Combustion & Ventilation Air Requirements ............ 12-14
2. GENERAL VENTING
Direct Venting Options Install Vent and Combustion Air Piping Requirements for Installation in Canada Sizing Min./Max. Combustion Air & Vent Piping Lengths Materials Optional Room Air
PVC/CPVC
Polypropylene Stainless Steel Vent
3. SIDEWALL DIRECT VENTING .................... 23-32
4. VERTICAL DIRECT VENTING ............................ 33-36
5. SYSTEM PIPING
General Piping Scalding Water Chemistry Piping Components Piping Diagrams .................................................. 39-41
6. GAS CONNECTIONS
Connecting Gas Supply Piping Natural Gas Pipe Sizing for Natural Gas Natural Gas Supply Pressure Requirements Propane Gas Pipe Sizing for Propane Gas Propane Supply Pressure Requirements Check Inlet Gas Supply ............................................ 44-45 Gas Pressure Gas Valve Replacement
7. FIELD WIRING
Low Voltage Connections Enable Switch Louver Relay Output / Louver Proving Switch Input Power Cord Connection Runtime Contacts Alarm Contacts
8. CONDENSATE DISPOSAL
Condensate Drain
9. START-UP
Check for Gas Leaks Inspect/fill Condensate System Final Checks Before Starting the Water Heater .......... 51-54 Shield Control Module Setup Wizard
10. OPERATING INFORMATION
How the Water Heater Operates Temperature Control Protection Features Water Heater Temperature Regulation Adjustable Control Parameters Installer Adjustable Parameters General SubMenu ........................................................59-60 Service Mode Building Management System (BMS) ..........................61-62
11. MAINTENANCE
Maintenance and Annual Startup Address Reported Problems Inspect Water Heater Interior Clean Condensate Trap Check All Piping for Leaks Flue Vent System and Air Piping Check Water System Check Expansion Tank Check Water Heater Relief Valve Inspect Ignition & Flame Sense Electrodes Check Ignition Ground Wiring Check All Water Heating Wiring Check Control Settings Perform Startup & Checks Check Burner Flames Check Flame Signal Review with Owner Handling Ceramic Fiber Materials Cleaning Heat Exchanger ...................................... 66-67 Oiled Bearing Circulators Magnesium Anode Rod Inspection
12. TROUBLESHOOTING
Before Troubleshooting Troubleshooting Chart - No Display Checking Temperature Sensors Troubleshooting Chart - Noisy System Troubleshooting Chart - Fault Messages Displayed ............................................................... 72-77 Combustion Analysis Procedure Gas Valve Adjustment Procedure
13. DIAGRAMS
Ladder Diagram Wiring Diagram
Please read before proceeding
Installer – Read all instructions, in this manual before installing. Perform steps in the order given.
Have this water heater serviced/inspected by a qualified service technician, at least annually.
Failure to comply with the above could result in severe personal injury, death or substantial property damage.
Failure to adhere to the guidelines on this page can result in severe personal injury, death, or substantial property damage. Water heater operation –
• Do not block flow of combustion or ventilation air to the water heater.
• Should overheating occur or gas supply fail to shut off, do not turn off or disconnect electrical supply to circulator. Instead, shut off the gas supply at a location external to the appliance.
• Do not use this water heater if any part has been under water. The possible damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
When calling or writing about the water heater – Please have the water heater model and serial number from the water heater rating plate.
Consider piping and installation when determining water heater location.
Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
Factory warranty (shipped with unit) does not apply to units improperly installed or improperly operated.
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death -- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
-- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a near by phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
-- Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
⚠ WARNING
NOTICE
⚠ WARNING
⚠ WARNING
Hazard definitions The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
⚠ DANGER
⚠ WARNING
⚠ CAUTION
CAUTION
NOTICE
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not related to personal injury or property damage.
When servicing the water heater –
• To avoid electric shock, disconnect electrical supply before performing maintenance.
• To avoid severe burns, allow the water heater to cool before performing maintenance.
Installation & Service Manual
⚠ WARNING DO NOT install units in rooms or environments that contain corrosive contaminants (see Table 1A on page 10).
Failure to comply could result in severe personal injury, death, or substantial property damage.
The Shield - How it works...
1. Access cover - front Provides access to the gas train, heat exchanger and controls.
2. Air intake adapter Allows for the connection of the PVC air intake pipe to the water heater.
3. Air pressure switch The air pressure switch detects blocked inlet conditions.
4. Burner door temperature switch (285 --500 Models Only) An electrical switch designed to shut down water heater operation in the event the combustion chamber access cover exceeds 500°F (260°C). This switch may only be reset by a qualified service technician AFTER the underlying cause has been identified and corrected. Check the integrity of the front refractory on the inside of the combustion chamber access cover if the switch opens.
5. Blower The blower pulls in air and gas through the venturi (item 32). Air and gas mix inside the blower and are pushed into the burner, where they burn inside the combustion chamber.
6. Burner (not shown) Made with metal fiber and stainless steel construction, the burner uses pre-mixed air and gas and provides a 5 to 1 firing rate.
7. Condensate drain connection Connects the condensate drain line to 1/2" PVC.
8. Electronic Control Module The electronic control responds to internal and external signals and controls the blower, gas valve, and pump to meet the demand.
9. Electronic display The electronic display consists of 4 buttons, and a liquid crystal display. The display is used to make adjustments and read water heater status.
10. Flame inspection window (not shown) The quartz glass window provides a view of the burner surface and flame.
11. Flame sensor Used by the control module to detect the presence of burner flame.
12. Flue gas sensor (not shown) This sensor monitors the flue gas exit temperature. The control module will modulate and shut down the water heater if the flue gas temperature gets too hot. This protects the flue pipe from overheating.
13. Gas connection pipe Threaded pipe connection, either 1/2", 3/4", or 1", depending on the model. This pipe should be connected to the incoming gas supply for the purpose of delivering gas to the water heater.
14. Gas shutoff switch An electrical switch designed to cut power from the gas valve to prevent gas flow to the burner.
15. Gas shutoff valve (400 -- 500 Models Only) Manual valve used to isolate the gas valve from the gas supply.
16. Gas valve The gas valve senses the negative pressure created by the blower, allowing gas to flow only if the gas valve is powered and combustion air is flowing.
17. Heat exchanger access cover Allows access to the combustion side of the heat exchanger coils.
18. Heat exchanger inlet temperature sensor This sensor monitors the inlet water temperature to the heat exchanger.
19. Heat exchanger outlet temperature sensor (not shown) This sensor monitors heat exchanger outlet water temperature.
20. Ignition electrode Provides direct spark for igniting the burner.
21. Line voltage junction box The junction box contains the connection points for the line voltage power.
22. Low voltage connection board The connection board is used to connect external low voltage devices.
23. Low voltage wiring connections (plugs) Conduit entryway for the low voltage connection board.
24. Power cord (not shown) The power cord allows for quick connection to 120V supply.
25. Pump Circulates water between the tank and the heat exchanger.
26. Pump relay Switches power to the pump.
27. Relief valve Protects the heat exchanger from over pressure and temperature conditions. The relief valve is set at 150 PSI.
28. Stainless steel heat exchanger Allows water to flow through specially designed coils for maximum heat transfer, while providing protection against flue gas corrosion. The coils are encased in a jacket that contains the combustion process.
29. Tank sensor Used by the control to monitor the temperature of the tank.
30. Pump access panel Panel used to gain access to the pump and condensate trap;
also used to gain access to the outlet water sensor.
31. Vent pipe connection Allows for the connection of the vent pipe system to the water heater.
32. Venturi The venturi controls air and gas flow into the burner.
33. Water heater drain valve Location from which the water heater can be drained.
34. Water inlet Copper sweat 1-1/2" connection for cold water supply that returns water from the system to the heat exchanger.
35. Water outlet Copper sweat 1-1/2" connection that supplies hot water to the system.
36. Over-temp switch (285 --500 Models Only) An electrical switch designed to shut down water heater operation in the event the outer back of the heat exchanger, directly above the flue connection exceeds 604°F (318°C).
This is a one time switch and could warrant a heat exchanger replacement. Check the integrity of the rear refractory at the back of the upper coil if the switch opens.
Installation & Service Manual
DIR# 2000577867
Front View - Models SWR125 - 200
DIR #2000586061
Left Side (inside unit) -- Models SWR125 - 200
25 3
DIR #2000586061
Right Side (inside unit) -- Models SWR125 - 200
The Shield - How it works... (continued)
DIR #2000586061
Rear View - Models SWR125 - 200
Models SWR125 -- 200
The Shield - How it works...
DIR #2000586074
34 31
Rear View - Models SWA285
DIR #2000586092
Rear View - Model SWA400 - 500 Right Side (inside unit) - Model SWA400 - 500
Right Side (inside unit) - Models SWA285
Models SWA285
Model SWA400 - 500
DIR #2000586074
DIR #2000586092
Ratings
Maximum allowed working pressure is located on the rating plate.
Model Number
Note: Change “N” to “L” for L.P. gas models.
CSA
Input Modulation Btu/hr
(Note 2)
Water Content Gallons
Water Connections
Gas Connections
Vent/Air Size
Min Max (Note 1)
SWR125(N,L) 25,000 - 125,000 65 1-1/2" 1/2" 3"
SWR150(N,L) 30,000 - 150,000 90 1-1/2" 1/2" 3"
SWA150(N,L) 30,000 - 150,000 91 1-1/2" 1/2" 3"
SWR200(N,L) 39,800 - 199,000 91 1-1/2" 1/2" 3"
SWA200(N,L) 39,800 - 199,000 91 1-1/2" 1/2" 3"
SWR285(N,L) 57,000 - 285,000 110 1-1/2" 1/2" 4"
SWA285(N,L) 57,000 - 285,000 110 1-1/2" 1/2" 4"
SWR400(N,L) 79,800 - 399,000 110 1-1/2" 1" 4"
SWA400(N,L) 79,800 - 399,000 110 1-1/2" 1" 4"
SWA500(N,L) 100,000 - 500,000 110 1-1/2" 1" 4"
NOTICE
Installation & Service Manual
HLW LOW LEAD CONTENT
Notes:
1. Shield water heaters require special gas venting.
Use only the vent materials and methods specified in the Shield Installation and Service Manual.
2. For US installations above 2,000 feet elevation, reference NFPA 54 for derate information.
Standard Shield water heaters are equipped to operate from sea level to 4500 feet only with no adjustments. Above 2,000 feet elevation, the water heater will de-rate by 4% for each 1,000 feet above sea level up to 4,500 feet.
De-rate values are based on proper combustion calibration and CO2’s adjusted to the recommended levels.
3. High altitude Shield water heaters are equipped to operate from 3,000 to 9,600 feet only. The water heater will de-rate by 2% up to 5,200 feet and will de-rate by 3.6% for each 1,000 feet above 5,400 feet up to 9,600 feet. High altitude models are manufactured with a different control module for altitude operation, but the operation given in this manual remains the same as the standard models. A high altitude label is also affixed to the unit. De-rate values are based on proper combustion calibration and CO2's adjusted to the recommended levels.
4. For Canadian installations above 2,000 feet elevation, follow all applicable local codes and regulations.
The Shield water heater gas manifold and controls met safe lighting and other performance under tests specified in ANSI Z21.10.3 – latest edition.
Failure to keep water heater area clear and free of combustible materials, gasoline, and other flammable liquids and vapors can result in severe personal injury, death, or substantial property damage.
Installation must comply with:
• Local, state, provincial, and national codes, laws, regulations, and ordinances.
• National Fuel Gas Code, ANSI Z223.1 – latest edition.
• National Electrical Code.
• For Canada only: B149.1 Installation Code, CSA C22.1
Canadian Electrical Code Part 1 and any local codes.
Before locating the water heater, check:
1. Check for nearby connection to:
• Water piping
• Venting connections
• Gas supply piping
• Electrical power
2. Locate the appliance so that if water connections should leak, water damage will not occur. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance. Under no circumstances is the manufacturer to be held responsible for water damage in connection with this appliance, or any of its components.
3. Check area around the water heater. Remove any combustible materials, gasoline and other flammable liquids.
4. The Shield water heater must be installed so that gas control system components are protected from dripping or spraying water or rain during operation or service.
⚠ WARNING
Provide clearances:
Clearances from combustible materials
1. Hot water pipes—at least 1/4" from combustible materials.
2. Vent pipe – at least 1" from combustible materials.
3. See FIG.’s 1-1 and 1-2 on page 9 for other clearance minimums.
Clearances for service access
1. See FIG.’s 1-1 and 1-2 on page 9 for recommended service clearances. If you do not provide the minimum clearances shown, it may not be possible to service the water heater without removing it from the space.
Closet and alcove installations
This appliance requires a special venting system. The vent connection to the appliance must be made with the CPVC pipe section provided with the appliance.
The field provided vent fittings must be cemented to the CPVC pipe section.
Use only the vent materials, primer and cement specified in this manual to make the vent connections. Failure to follow this warning could result in fire, personal injury, or death.
For closet and alcove installations as shown in FIG.’s 1-1 and 1-2, CPVC or stainless steel vent material must be used inside the structure. The ventilating air openings shown in FIG.’s 1-1 and 1-2 are required for this arrangement. Failure to follow this warning could result in fire, personal injury, or death.
⚠ WARNING
⚠ WARNING
NOTICE
⚠ WARNING
1 Determine water heater location
Installation & Service Manual
A closet is any room the water heater is installed in which is less than 433 cubic feet for 125 through 200 models and 638 cubic feet for the 285 through 500 models.
An alcove is any room which meets the criteria for a closet with the exception that it does not have a door.
Example: Room dimensions = 6 feet long, 6 feet wide, and 9 foot ceiling = 6 x 6 x 9 = 324 cubic feet. This would be considered a closet for a Shield Water Heater.
This appliance is certified as an indoor appliance. Do not install the appliance outdoors or locate where the appliance will be exposed to freezing temperatures or to temperatures that exceed 100°F.
Do not install the appliance where the relative humidity may exceed 93%. Do not install the appliance where condensation may form on the inside or outside of the appliance, or where condensation may fall onto the appliance.
Failure to install the appliance indoors could result in severe personal injury, death, or substantial property damage.
FLOOR COMBUSTIBLE
OPEN FRONT
1" (25.4 MM)
MINIMUM CLEARANCE
AROUND VENT PIPE
1/4" (6.35MM)
MINIMUM CLEARANCE
AROUND HOT WATER PIPES
RIGHT
0"
LEFT
0"
0"
FRONT
REAR
0"
0"
DIR #2000586144
PUMP ACCESS
COVER
Figure 1-2 Alcove Installation - Minimum Required Clearances
6"
6"
1/4" (6.35MM)
MINIMUM CLEARANCE
AROUND HOT WATER PIPES
1/4" (6.35MM)
MINIMUM CLEARANCE
AROUND HOT WATER PIPES
VENTILATING
AIR OPENING
VENTILATING
AIR OPENING
CLOSED DOOR
FLOOR COMBUSTIBLE
REAR
FRONT LEFT
RIGHT
0"
0" 0"
0"
0"
DIR #2000586144
PUMP ACCESS
COVER
Figure 1-1 Closet Installation - Minimum Required Clearances
⚠ WARNING
1 Determine water heater location (continued)
RECOMMENDED SERVICE
CLEARANCES:
Top - 18" (457 mm) Left/Right Side - 24" (610 mm) Front - 24" (610 mm)
RECOMMENDED SERVICE
CLEARANCES:
Top - 18" (457 mm) Left/Right Side - 24" (610 mm) Front - 24" (610 mm)
Installation & Service Manual
⚠ WARNING
For closet installations, CPVC, polypropylene or stainless steel vent material MUST BE used in a closet structure due to elevated temperatures. Failure to follow this warning could result in fire, personal injury, or death.
For alcove installations, CPVC, polypropylene or stainless steel vent material MUST BE used in an alcove structure due to elevated temperatures. Failure to follow this warning could result in fire, personal injury, or death.
Do not install the water heater on carpeting even if foundation is used. Fire can result, causing severe personal injury, death, or substantial property damage.
When local codes require compliance with NSF 5, the heater must be sealed to the floor with a food grade silicone to prevent debris and harborage of vermin under the heater.
If flooding is possible, elevate the water heater sufficiently to prevent water from reaching the water heater.
Flooring and foundation
Flooring
The Shield water heater is approved for installation on combustible flooring, but must never be installed on carpeting.
Prevent combustion air contamination
Install air inlet piping for the Shield water heater as described in this manual. Do not terminate vent/air in locations that can allow contamination of combustion air. Refer to Table 1A, for products and areas which may cause contaminated combustion air.
Ensure that the combustion air will not contain any of the contaminants in Table 1A. Contaminated combustion air will damage the water heater, resulting in possible severe personal injury, death or substantial property damage. Do not pipe combustion air near a swimming pool, for example. Also, avoid areas subject to exhaust fumes from laundry facilities. These areas will always contain contaminants.
⚠ WARNING
⚠ WARNING
1 Determine water heater location
Remove water heater from wood pallet
1. Remove the sides and the top of the crate.
2. Remove the blocks on the base of the crate to allow for easier removal.
3. The water heater can then be slid off the base of the crate for installation.
Do not drop the water heater or bump the jacket on the floor or pallet. Damage to the water heater can result.
NOTICE
Installation & Service Manual
Products to avoid:
Spray cans containing chloro/fluorocarbons
Permanent wave solutions
Chlorinated waxes/cleaners
Chlorine-based swimming pool chemicals
Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Hydrochloric acid/muriatic acid
Cements and glues
Antistatic fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms Adhesives used to fasten building products and other similar products
Areas likely to have contaminants
Dry cleaning/laundry areas and establishments
Swimming pools
Metal fabrication plants
Beauty shops
Refrigeration repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Furniture refinishing areas and establishments
New building construction
Remodeling areas
Garages with workshops
Table 1A Corrosive Contaminants and Sources
When removing a water heater from existing common vent system:
Do not install the Shield water heater into a common vent with any other appliance. This will cause flue gas spillage or appliance malfunction, resulting in possible severe personal injury, death, or substantial property damage.
Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death.
At the time of removal of an existing water heater, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
a. Seal any unused openings in the common venting system.
b. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion, or other deficiencies, which could cause an unsafe condition.
c. Test vent system – Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
d. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
e. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe.
f. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined herein, return doors, windows, exhaust fans, fireplace dampers, and any other gas-burning appliance to their previous conditions of use.
g. Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1, Natural Gas and Propane Installation Code. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part 11 of the National Fuel Gas Code, ANSI Z223.1/NFPA and/or CAN/CSA B149.1, Natural Gas and Propane Installation Code.
⚠ DANGER
⚠ WARNING
1 Determine water heater location (continued)
Installation & Service Manual
Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death.
⚠ WARNING
When using an existing vent system to install a new water heater:
Check the following venting components before installing:
• Material - For materials listed for use with this appliance, see Section 2 - General Venting. For polypropylene or stainless steel venting, an adapter of the same manufacturer must be used at the flue collar connection.
• Size - To ensure proper pipe size is in place, see Table 2A.
Check to see that this size is used throughout the vent system.
• Manufacturer - For a stainless steel or polypropylene application, you must use only the listed manufacturers and their type product listed in Tables 2D and 2F for CAT IV positive pressure venting with flue producing condensate.
• Supports - Non-combustible supports must be in place allowing a minimum 1/4" rise per foot. The supports should adequately prevent sagging and vertical slippage, by distributing the vent system weight. For additional information, consult the vent manufacturer’s instructions for installation.
• Terminations - Carefully review Sections 2 through 4 to ensure requirements for the location of the vent and air terminations are met and orientation of these fit the appropriate image from the Sidewall or Vertical options listed in the General Venting Section. For stainless steel vent, only use terminations listed in Table 2G for the manufacturer of the installed vent.
• Seal - With prior requirements met, the system should be tested to the procedure listed in parts (c) through (f) of the Removal of an Existing Water Heater Section, this page.
With polypropylene and stainless steel vent, seal and connect all pipe and components as specified by the vent manufacturer used; with PVC/CPVC vent, see the Installing Vent or Air Piping Section on page 20.
⚠ WARNING
If any of these conditions are not met, the existing system must be updated or replaced for that concern. Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death.
1 Determine water heater location
Combustion and ventilation air requirements for appliances drawing air from the equipment room
Provisions for combustion and ventilation air must be in accordance with Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes.
The equipment room MUST be provided with properly sized openings to assure adequate combustion air and proper ventilation.
Maintain minimum specified clearances for adequate operation. All installations must allow sufficient space for servicing the vent connections, water pipe connections, piping and other auxiliary equipment, as well as the appliance.
Multiple appliances may be installed in a modular water heater installation. Multiple appliances may be installed side by side with no clearance between adjacent appliances because this appliance is approved for zero clearance from combustible surfaces; however, service access will be limited from the sides. Do not block the pump access cover.(see FIG's 1-1 and 1-2.
Consult the Venting section of this manual for specific installation instructions for the appropriate type of venting system that you will be using.
DIR# 2000586334
Figure 1-3_Combustion Air Direct from Outside
1. If air is taken directly from outside the building with no duct, provide two permanent openings to the equipment room (see FIG. 1-3):
(a) Combustion air opening, with a minimum free area of one square inch per 4000 Btu/hr input (5.5 cm2 per KW). This opening must be located within 12" (30 cm) of the bottom of the enclosure.
(b) Ventilation air opening, with a minimum free area of one square inch per 4000 Btu/hr input (5.5 cm2 per kW). This opening must be located within 12" (30 cm) of the top of the enclosure.
DIR# 2000586335
Figure 1-4_Combustion Air Through Ducts
2. If combustion and ventilation air is taken from the outdoors using a duct to deliver the air to the equipment room, each of the two openings should be sized based on a minimum free area of one square inch per 2000 Btu/hr (11 cm2 per kW) of input (see FIG. 1-4).
1 Determine water heater location (continued)
DIR# 2000586337
Figure 1-6_Combustion Air from Outside - Single Opening
3. If air is taken from another interior space, each of the two openings specified above should have a net free area of one square inch for each 1000 Btu/hr (22 cm2 per kW) of input, but not less than 100 square inches (645 cm2) (see FIG. 1-5).
4. If a single combustion air opening is provided to bring combustion air in directly from the outdoors, the opening must be sized based on a minimum free area of one square inch per 3000 Btu/hr (7 cm2 per kW). This opening must be located within 12" (30 cm) of the top of the enclosure (see FIG. 1-6).
DIR# 2000586336IF NECESSARY FOR
TIGHT CONSTRUCTION
Figure 1-5_Combustion Air from Interior Space
Installation & Service Manual
TABLE - 1B
MINIMUM RECOMMENDED COMBUSTION
AIR SUPPLY TO EQUIPMENT ROOM
Model Number
FIG. 1-3 FIG. 1-4 FIG. 1-5 FIG. 1-6
*Outside Air from
2 Openings Directly from Outdoors
*Outside Air from 2 Ducts Delivered from Outdoors
**Inside Air from 2 Ducts Delivered from Interior
Space *Outside Air from 1 Opening Directly from Outdoors, in2Top
Opening, in2
Bottom Opening, in2
Top Opening, in2
Bottom Opening, in2
Top Opening, in2
Bottom Opening, in2
125 32 (207 cm2)
(207 cm2)
(407 cm2)
(407 cm2)
(807 cm2)
(807 cm2)
(271 cm2)
150 38 (246 cm2)
(246 cm2)
(484 cm2)
(484 cm2)
(968 cm2)
(968 cm2)
(323 cm2)
200 50 (323 cm2)
(323 cm2)
(646 cm2)
(646 cm2)
(1,291 cm2)
(1,291 cm2)
(433 cm2)
285 72 (465 cm2)
(465 cm2)
(923 cm2)
(923 cm2)
(1,839 cm2)
(1,839 cm2)
(613 cm2)
400 100 (646 cm2)
(646 cm2)
(1,291 cm2)
(1,291 cm2)
(2,581 cm2)
(2,581 cm2)
(865 cm2)
500 125 (807 cm2)
(807 cm2)
(1,613 cm2)
(1,613 cm2)
(3,226 cm2)
(3,226 cm2)
(1,078 cm2)
*Outside air openings shall directly communicate with the outdoors. When combustion air is drawn from the outside through a duct, the net free area of each of the two openings must have twice (2 times) the free area required for Outside Air/2 Openings.
The above requirements are for the water heater only; additional gas fired appliances in the equipment room will require an increase in the net free area to supply adequate combustion air for all appliances.
**Combined interior space must be 50 cubic feet per 1,000 Btu/hr input. Buildings MUST NOT be of *“Tight Construction”. For buildings of *“Tight Construction”, provide air openings into the building from outside.
*No combustion air openings are needed when the water heater is installed in a space with a volume NO LESS than 50 cubic feet per 1,000 Btu/hr of all installed gas fired appliances. Buildings MUST NOT be of *“Tight Construction”.
*“Tight Construction” is defined as a building with less than 0.40 ACH (air changes per hour).
1 Determine water heater location
The result is improper combustion and a non-warrantable, premature appliance failure.
EXHAUST FANS: Any fan or equipment which exhausts air from the equipment room may deplete the combustion air supply and/or cause a downdraft in the venting system. Spillage of flue products from the venting system into an occupied living space can cause a very hazardous condition that must be immediately corrected. If a fan is used to supply combustion air to the equipment room, the installer must make sure that it does not cause drafts which could lead to nuisance operational problems with the appliance.
Combustion air requirements are based on the latest edition of the National Fuel Gas Code, ANSI Z223.1; in Canada refer to the latest edition of CGA Standard CAN B149.1. Check all local code requirements for combustion air.
All dimensions based on net free area in square inches. Metal louvers or screens reduce the free area of a combustion air opening a minimum of approximately 25%. Check with louver manufacturers for exact net free area of louvers.
Where two openings are provided, one must be within 12" (30cm) of the ceiling and one must be within 12" (30cm) of the floor of the equipment room. Each opening must have net free area as specified in Table 1B. Single openings shall commence within 12" (30cm) of the ceiling.
⚠ CAUTION Under no circumstances should the equipment room ever be under negative pressure. Particular care should be taken where exhaust fans, attic fans, clothes dryers, compressors, air handling units, etc., may take away air from the unit.
The combustion air supply must be completely free of any flammable vapors that may ignite or chemical fumes which may be corrosive to the appliance. Common corrosive chemical fumes which must be avoided are fluorocarbons and other halogenated compounds, most commonly present as refrigerants or solvents, such as Freon, trichlorethylene, perchlorethylene, chlorine, etc. These chemicals, when burned, form acids which quickly attack the stainless steel heat exchanger, headers, flue collectors, and the vent system.
DIR #2000586391
Figure 2-1 Two-Pipe Sidewall Termination
Direct venting options - Sidewall Vent
2 General venting
Installation & Service Manual
DIR #2000586391
Figure 2-2 PVC/CPVC Concentric Sidewall Termination
DIR #2000586468
Figure 2-3 Two-Pipe Vertical Termination
DIR #2000586468
Figure 2-4 PVC/CPVC Concentric Vertical Termination
DIR #2000586468
Figure 2-5 Vertical Vent, Sidewall Air
Direct venting options - Vertical Vent
2 General venting
Installation & Service Manual
This appliance requires a special venting system. Use only approved stainless steel, PVC, CPVC or polypropylene pipe and fittings listed in Tables 2C, 2D, and 2F for vent pipe, and fittings. Failure to comply could result in severe personal injury, death, or substantial property damage.
Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian installations.
Install vent and combustion air piping
⚠ DANGER The Shield water heater must be vented and supplied with combustion and ventilation air as described in this section. Ensure the vent and air piping and the combustion air supply comply with these instructions regarding vent system, air system, and combustion air quality. See also Section 1 of this manual.
Inspect finished vent and air piping thoroughly to ensure all are airtight and comply with the instructions provided and with all requirements of applicable codes.
Failure to provide a properly installed vent and air system will cause severe personal injury or death.
⚠ WARNING
NOTICE
⚠ WARNING For closet and alcove installations, CPVC, polypropylene or stainless steel material MUST BE used in a closet/alcove structure.
Failure to follow this warning could result in fire, personal injury, or death.
Air intake/vent connections
1. Combustion Air Intake Connector (FIG. 2-6) - Used to provide combustion air directly to the unit from outdoors. A fitting is provided on the unit for final connection.
Combustion air piping must be supported per guidelines listed in the National Mechanical Code, Section 305, Table
305.4 or as local codes dictate.
2. Vent Connector (FIG.'s 2-7 thru 2-10) - Used to provide a passageway for conveying combustion gases to the outside. A transition fitting is provided on the unit for final connection. Vent piping must be supported per the National Building Code, Section 305, Table 305.4 or as local codes dictate.
The Shield water heater vent and air piping can be installed through the roof or through a sidewall. Follow the procedures in this manual for the method chosen. Refer to the information in this manual to determine acceptable vent and air piping length.
You may use any of the vent/air piping methods covered in this manual. Do not attempt to install the Shield water heater using any other means.
You must also install air piping from outside to the water heater air intake adapter unless following the Optional Room Air instructions on page 19 of this manual. The resultant installation is direct vent (sealed combustion).
⚠ WARNING DO NOT mix components from different systems. The vent system could fail, causing leakage of flue products into the living space. Mixing of venting materials will void the warranty and certification of the appliance.
⚠ WARNING Do not connect any other appliance to the vent pipe or multiple water heaters to a common vent pipe. Failure to comply could result in severe personal injury, death, or substantial property damage.
Improper installation of venting systems may result in injury or death.⚠ CAUTION
Follow the instructions in Section 1, page 11 of this manual when removing a water heater from an existing vent system.
NOTICE
AIR
DIR #2000586184
Figure 2-6 Near Water Heater Air Piping
Vent system must be pitched a 1/4" minimum per foot back to the appliance to allow drainage of condensate.
NOTICE
2 General venting (continued)
Installation & Service Manual
Requirements for installation in Canada
1. Installations must be made with a vent pipe system certified to ULC-S636.
2. The first three (3) feet of plastic vent pipe from the appliance flue outlet must be readily accessible for visual inspection.
3. The components of the certified vent system must not be interchanged with other vent systems or unlisted pipe/fittings. For concentric vent installations, the inner vent tube must be replaced with field supplied certified vent material to comply with this requirement.
4. The 3" Concentric Vent Kit available from Lochinvar (see Section 3 – Sidewall Termination – Optional Concentric Vent) and the 3" Concentric Vent Kit available from IPEX are both approved for use on the Shield water heater. Both kits are listed to the ULC-S636 standard for use in Canada.
Minimum / Maximum allowable combustion air and vent piping lengths are as follows:
Combustion Air = 12 equivalent feet minimum / 150 equivalent feet maximum
Vent = 12 equivalent feet minimum / 150 equivalent feet maximum
The appliance output rating will reduce by up to 1.0% for each 25 feet of vent length.
NOTICE
Table 2B Concentric Vent Kit Equivalent Vent Lengths Sizing The Shield water heater uses model specific combustion air intake and vent piping sizes as detailed in Table 2A-1 below.
Table 2A Air Intake/Vent Piping Sizes
NOTICE
Model Air Intake Vent 125 -- 200 3 inches 3 inches 285 -- 500 4 inches 4 inches
Model Kit Number Equivalent Vent Length
125 -- 200 100140480 3 feet
285 100140484 3 feet
400 100140484 5 feet
500 100140484 30 feet
Increasing or decreasing combustion air or vent piping sizes is not authorized.
When determining equivalent combustion air and vent length, add 5 feet for each 90° elbow and 3 feet for each 45° elbow.
EXAMPLE: 20 feet of PVC pipe + (4) 90° elbows + (2) 45° elbows + (1) concentric vent kit (100140480) = 49 equivalent feet of piping.
Installation & Service Manual
Materials Air inlet pipe materials:
The air inlet pipe(s) must be sealed. Choose acceptable combustion air inlet pipe materials from the following list:
PVC, CPVC, Polypropylene or ABS Dryer Vent or Sealed Flexible Duct (not recommended for rooftop air inlet) Galvanized steel vent pipe with joints and seams sealed as specified in this section.
Type “B” double-wall vent with joints and seams sealed as specified in this section.
AL29-4C, stainless steel material to be sealed to specification of its manufacturer.
*Plastic pipe may require an adapter (not provided) to transition between the air inlet connection on the appliance and the plastic air inlet pipe.
⚠ WARNING Using air intake materials other than those specified can result in personal injury, death or property damage.
NOTICE The use of double-wall vent or insulated material for the combustion air inlet pipe is recommended in cold climates to prevent the condensation of airborne moisture in the incoming combustion air.
Sealing of Type “B” double-wall vent material or galvanized vent pipe material used for air inlet piping on a sidewall or vertical rooftop Combustion Air Supply System:
a. Seal all joints and seams of the air inlet pipe using either Aluminum Foil Duct Tape meeting UL Standard 723 or 181A-P or a high quality UL Listed silicone sealant such as those manufactured by Dow Corning or General Electric.
b. Do not install seams of vent pipe on the bottom of horizontal runs.
c. Secure all joints with a minimum of three (3) sheet metal screws or pop rivets. Apply Aluminum Foil Duct Tape or silicone sealant to all screws or rivets installed in the vent pipe.
d. Ensure that the air inlet pipes are properly supported.
The PVC, CPVC, or ABS air inlet pipe should be cleaned and sealed with the pipe manufacturer’s recommended solvents and standard commercial pipe cement for the material used.
The PVC, CPVC, ABS, Dryer Vent or Flex Duct air inlet pipe should use a silicone sealant to ensure a proper seal at the appliance connection and the air inlet cap connection. Dryer vent or flex duct should use a screw type clamp to seal the vent to the appliance air inlet and the air inlet cap. Proper sealing of the air inlet pipe ensures that combustion air will be free of contaminants and supplied in proper volume.
Follow the polypropylene manufacturer’s instructions when using polypropylene material as an inlet pipe.
When a sidewall or vertical rooftop combustion air supply system is disconnected for any reason, the air inlet pipe must be resealed to ensure that combustion air will be free of contaminants and supplied in proper volume.
⚠ DANGER Failure to properly seal all joints and seams as required in the air inlet piping may result in flue gas recirculation, spillage of flue products and carbon monoxide emissions causing severe personal injury or death.
Supports Vent system must be supported horizontally to prevent sagging. Methods and intervals for support vary by vent manufacturer and vent material. Vent support methods and intervals shall adhere to vent manufacturer's instructions, where applicable. Vent piping must be supported per the National Building Code, Section 305, Table 305.4 or as local codes dictate.
Installation & Service Manual
Air contamination
Pool and laundry products and common household and hobby products often contain fluorine or chlorine compounds. When these chemicals pass through the water heater, they can form strong acids. The acid can eat through the water heater wall, causing serious damage and presenting a possible threat of flue gas spillage or water heater water leakage into the building.
Please read the information given in Table 1A, page 10, listing contaminants and areas likely to contain them. If contaminating chemicals will be present near the location of the water heater combustion air inlet, have your installer pipe the water heater combustion air and vent to another location, per this manual.
If the water heater combustion air inlet is located in a laundry room or pool facility, for example, these areas will always contain hazardous contaminants.
To prevent the potential of severe personal injury or death, check for areas and products listed in Table 1A, page 10 before installing the water heater or air inlet piping.
If contaminants are found, you MUST:
• Remove contaminants permanently.
—OR—
• Relocate air inlet and vent terminations to other areas.
⚠ WARNING
⚠ WARNING
Optional room air
⚠ WARNING When utilizing the single pipe method, provisions for combustion and ventilation air must be in accordance with Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes.
Commercial applications utilizing the Shield water heater may be installed with a single pipe carrying the flue products to the outside while using combustion air from the equipment room. In order to use the room air venting option the following conditions and considerations must be followed.
• The unit MUST be installed with the appropriate room air provisions.
• The equipment room MUST be provided with properly sized openings to assure adequate combustion air. Please refer to instructions provided with the room air kit (100157615 - Models 125 -- 200 and 100157616 - Models 285 -- 500).
• There will be a noticeable increase in the noise level during normal operation from the inlet air opening.
• Using the room air configuration makes the unit vulnerable to combustion air contamination from within the building. Please review Section 1, Prevent Combustion Air Contamination, to ensure proper installation.
• Vent system and terminations must comply with the standard venting instructions set forth in this manual.
NOTICE Optional room air is intended for commercial applications. Combustion air piping to the outside is recommended for residential applications.
Installation & Service Manual
Installing vent and air piping
Use only cleaners, primers, and solvents that are approved for the materials which are joined together.
NOTICE
1. Work from the water heater to vent or air termination.
Do not exceed the lengths given in this manual for the air or vent piping.
2. Cut pipe to the required lengths and deburr the inside and outside of the pipe ends.
3. Chamfer outside of each pipe end to ensure even cement distribution when joining.
4. Clean all pipe ends and fittings using a clean dry rag.
(Moisture will retard curing and dirt or grease will prevent adhesion.)
5. Dry fit vent or air piping to ensure proper fit up before assembling any joint. The pipe should go a third to two-thirds into the fitting to ensure proper sealing after cement is applied.
6. Priming and Cementing:
a. Handle fittings and pipes carefully to prevent contamination of surfaces.
b. Apply a liberal even coat of primer to the fitting socket and to the pipe end to approximately 1/2" beyond the socket depth.
c. Apply a second primer coat to the fitting socket.
d. While primer is still wet, apply an even coat of approved cement to the pipe equal to the depth of the fitting socket along with an even coat of approved cement to the fitting socket.
e. Apply a second coat of cement to the pipe.
f. While the cement is still wet, insert the pipe into the fitting, if possible twist the pipe a 1/4 turn as you insert it. NOTE: If voids are present, sufficient cement was not applied and joint could be defective.
g. Wipe excess cement from the joint removing ring or beads as it will needlessly soften the pipe.
PVC/CPVC
Table 2C PVC/CPVC Vent Pipe, and Fittings
All CPVC and PVC vent pipes must be glued, properly supported, and the exhaust must be pitched a minimum of a 1/4 inch per foot back to the water heater (to allow drainage of condensate). Horizontal runs shall have supports suitable for non-metallic vent piping that do not clamp tightly onto vent, allowing for vent expansion or contraction.
Supports shall be as close to joints and fittings as practical and no more than 5 feet apart.
NOTICE
⚠ WARNING The vent connection to the appliance must be made with the starter CPVC pipe section provided with the 285-500 models (starter piece is factory installed on the 125-200 models) if PVC/CPVC vent is to be used.
The field provided vent fittings must be cemented to the CPVC pipe section using an “All Purpose Cement” suitable for PVC and CPVC pipe. Use only the vent materials, primer, and cement specified in Table 2C to make the vent connections. Failure to follow this warning could result in fire, personal injury, or death.
⚠ WARNING Insulation shall not be used on PVC or CPVC venting materials. The use of insulation will cause increased vent wall temperatures, which could result in vent pipe failure.
Approved PVC/CPVC Vent Pipe and Fittings Item Material Standard
Vent pipe PVC Schedule 40, 80 ANSI/ASTM D1785
PVC - DWV ANSI/ASTM D2665
CPVC Schedule 40, 80 ANSI/ASTM F441
Vent fittings
PVC Schedule 40 ANSI/ASTM D2466 PVC Schedule 80 ANSI/ASTM D2467 CPVC Schedule 80 ANSI/ASTM F439
PVC - DWV ANSI/ASTM D2665
Pipe Cement / Primer
PVC ANSI/ASTM D2564
CPVC ANSI/ASTM F493
NOTICE: DO NOT USE CELLULAR (FOAM) CORE PIPE
Figure 2-7 Near Water Heater PVC/CPVC Venting
This product has been approved for use with the PVC/CPVC vent materials listed in Table 2C.
NOTE: In Canada, CPVC and PVC vent pipe, fittings and cement/ primer must be ULC-S636 certified.
VENT
CPVC STARTER PIECE
(FACTORY INSTALLED)
DIR #2000586184
CPVC STARTER PIECE
(FACTORY SUPPLIED)
MODELS 125 - 200 MODELS 285 - 500
When available, follow all vent manufacturer’s installation instructions. NOTICE
Installation & Service Manual
The installer must use a specific vent starter adapter at the flue collar connection.