100 Portage Street Houghton, MI 49931
906-482-4810 • 800-562-7684 • Fax: 906-482-9799
Offices also in:
Iron Mountain
Ishpeming Marinette
Sault Ste Marie
U.P. Engineers & Architects, Inc. www.UPEA.com
[U28-17435] July 26, 2017
Ms. Debra K. Brinn, Contract Specialist USDA Forest Service Huron Shores Ranger Station 5761 N. Skeel Oscoda, MI 48750-1595
RE: ASBESTOS SURVEY AND LEAD & CADMIUM CONTAINING PAINT SAMPLING –
MONDEAUX RECREATION SITE LOCATED AT W7969 PARK RD., WESTBORO, WI
54490
Dear Debra K. Brinn:
Thank you for selecting U.P. Engineers & Architects, Inc. (UPEA) to conduct the asbestos survey and lead & cadmium containing paint sampling. As authorized, UPEA completed the survey and sampling on July 11th, 2017. UPEA has enclosed an asbestos survey, and a lead and cadmium containing paint sampling report, which includes procedures and methodologies, analytical laboratory results, and applicable conclusions and recommendations.
If you have any questions, please do not hesitate to contact me at (906) 482-4810 or erbjorn@upea.com. We appreciate the opportunity to be of service.
Sincerely, U.P. ENGINEERS & ARCHITECTS, INC.
Emmett Bjorn WI Asbestos Inspector License: AII-234953 WI Lead Risk Assessor License: LRA-234953
Cc: TSPurdy/UPEA w/enclosures
12569R19B0005 Attachment C - Asbestos Survey and Paint Sampling Report 79 Pages
MONDEAUX SITE RECREATION
BUILDINGS LOCATED AT
W7969 PARK RD.
WESTBORO, WI 54490
ASBESTOS SURVEY & LEAD
AND CADMIUM CONTAINING PAINT
SAMPLING REPORT
Prepared for:
USDA Forest Service Huron Shores Ranger Station
5761 N. Skeel Oscodo, MI 48750-1595
Prepared By:
U.P. ENGINEERS & ARCHITECTS, INC.
100 Portage Street Houghton, Michigan 49931
July 2017
TABLE OF CONTENTS
Page
I. PURPOSE AND SCOPE
II. ASBESTOS CONTAINING MATERIAL SURVEY
III. LEAD AND CADMIUM CONTAINING PAINT SAMPLING
IV. CONCLUSIONS AND RECOMMENDATION
V. LIMITATIONS
LIST OF APPENDICES
APPENDIX A INSPECTOR ACCREDITATION
APPENDIX B BUILDING FLOOR PLANS
APPENDIX C ANALYTICAL RESULTS - ASBESTOS
APPENDIX D LABORATORY ACCREDITATION
APPENDIX E ANALYTICAL RESULTS – LEAD & CADMIUM CONTAINING PAINT
APPENDIX F MOLD TESTING – LIVING QUARTERS BUILDING
1 UPEA
I. PURPOSE AND SCOPE
The purpose of this project was to conduct an asbestos survey and lead & cadmium containing paint sampling at the buildings located at W7969 Park Rd., Westboro, WI 54490. The survey and sampling will identify asbestos containing material (ACM), presumed ACM (PACM), and lead and cadmium containing paint throughout the building. The survey and sampling should be referred to by staff and personnel during demolition operations. Material or items not comprised of ACM or PACM may be removed, repaired or replaced by general maintenance staff or contractors. However, ACM or PACM items must be handled and disposed of by properly trained personnel.
Lead and cadmium containing paint may be disposed of as demolition debris, if the proper procedures are followed.
The scope of this project includes:
1. Building walk through
2. Identification of suspect ACM
3. Collection and analysis of bulk samples of suspect ACM
4. Collection of suspect Lead & Cadmium Containing Paint Samples
5. Quantification of ACM and PACM
6. Assess current condition of ACM and PACM, and identify the potential for disturbance of ACM and PACM.
II. ASBESTOS CONTAINING MATERIAL SURVEY
An asbestos survey was conducted for the buildings located at W7969 Park Rd., Westboro, WI 54490. The asbestos survey was performed by Emmett Bjorn; a State of Wisconsin licensed Asbestos Inspector (License # AII-234953) on July 11, 2017.
The asbestos survey consisted of five phases: 1) conduct a visual inspection of the building; 2) identify homogeneous areas; 3) sample selected suspect ACM from different homogeneous areas; 4) quantify ACM and PACM; 5) assess current conditions of sampled suspect ACM and the potential for disturbance of the ACM identified.
Prior to collecting any samples, a sampling strategy was developed based on the layout of the building and the construction periods associated with each section of the building.
Based on the sampling strategy, the building was divided into different homogeneous areas, from which samples would be collected. A homogeneous area can be described as one or more areas of material that are similar in appearance and that have the same construction/installation date and function. Bulk samples of identified suspect asbestos containing material (ACM) were collected in individual containers and sent to a National Voluntary Lab Accreditation Program (NVLAP)/American Industrial Hygiene Association (AIHA) accredited laboratory for analysis. The number of samples collected from each homogeneous area may vary depending on the professional judgment of the inspector and the type of material present.
2 UPEA
A. SAMPLING STRATEGY
In planning the asbestos survey, the approach was taken to test and catalog all visible areas of the building presumed to be asbestos containing. The building is scheduled to be renovated, so any materials presumed to be asbestos containing must be removed prior to any construction.
The asbestos survey was conducted according to AHERA guidelines utilizing a minimum number of samples collected from each homogeneous area. The number of samples collected depends on the category that the suspect asbestos containing building material (ACBM) falls under and the amount of suspect material present. The following table outlines the AHERA sampling Guidelines:
Bulk Sampling Requirements Type of Material Samples Required
Friable Surfacing Material:
Area ≤ 1,000 sq. feet 3 Area > 1,000 sq. feet but ≤ 5,000 sq. feet 5 Area > 5,000 sq. feet 7 Thermal System Insulation (TSI) TSI not assumed to be ACBM 3 Patched TSI not assumed to be ACBM (if patched section < 6 linear or sq. feet)
Miscellaneous Materials Each insulated mechanical system not assumed to be ACBM where cement or plaster is used on fittings such as tees, elbows, or valves
Samples in a manner sufficient to determine if material is or is not ACBM*
Friable Miscellaneous Material not Assumed to be ACBM
Samples in a manner sufficient to determine if material is or is not ACBM*
Nonfriable Suspected ACBM not assumed to be ACSM
Samples in a manner sufficient to determine if material is or is not ACBM*
* EPA recommends that three samples be taken to meet this requirement.
Miscellaneous materials require sufficient sampling, which requires at least one sample per homogeneous material, with three samples typically collected. The number of samples collected is determined by the building inspector, typically based on observations such as quantity, condition, and friability of material present.
B. SUSPECT ASBESTOS CONTAINING MATERIAL
Forty Six (46) samples (29-Lodge, 14-Living Quarters, 3-Garage) of suspect ACM were collected from the building and analyzed by Polarized Light Microscopy (PLM). Table 1 shows any confirmed ACMs. Table 2 presents the sample analysis results. The confirmed ACMs, if any, are reported in bold text.
Appendix B contains a copy of the building floor plans. Copies of the analytical results are included in Appendix C. Appendix D contains a copy of the laboratory accreditation.
3 UPEA
This asbestos survey was completed with limited destructive testing. Therefore, hidden materials may be discovered in walls or ceilings that contain asbestos. If such materials are encountered, all work shall stop immediately until proper testing is conducted to determine the content of the material.
TABLE 1
CONFIRMED ASBESTOS CONTAINING MATERIALS
FLOOR LOCATION MATERIAL QUANTITY FRIABLE
Lodge - Roof Chimney
Penetration Black Tar/Caulk 12 LF No
III. LEAD AND CADMIUM CONTAINING PAINT SAMPLING
Six (6) samples (3-Lodge, 2-Living Quarters, 1-Garage) of suspect lead and cadmium containing paint from the building were collected and submitted for analysis by an accredited laboratory. The following tables (Table 3 & Table 4) present the sample analysis results. The confirmed lead-containing and cadmium-containing paint samples are reported in bold text. Copies of the lead and cadmium analytical results are included in Appendix E.
IV. CONCLUSIONS AND RECOMMENDATIONS
Asbestos:
The results of the asbestos survey conducted on 7/11/2017 for the buildings located at W7969 Park Rd., Westboro, WI 54490 indicate that the building DOES contain asbestos at the Lodge Chimney Roof Penetration. Of the tested materials, asbestos WAS found in one (1) sample collected from the site.
Material or items not comprised of ACM or PACM may be removed, repaired or replaced by general maintenance staff or contractors. However, ACM or PACM items must be handled and disposed of by properly trained personnel. Subcontractors and employees working in the building should be instructed to report any hidden suspect ACM immediately upon discovery.
Lead and Cadmium-Containing Paint:
The results of the lead and cadmium-containing paint sampling conducted on 7/11/2017, indicate that the building sampled DOES contain lead containing paint. Of the tested materials, lead containing paint was identified in the Lodge Windows, Lodge Exterior Trims, Garage Windows, Living Quarters Interior Trims & Living Quarters Interior Walls.
Of the tested materials, cadmium containing paint was NOT identified in any samples.
Since lead paint is present, air monitoring and or proper personal protective equipment will be required during demolition, dependent upon worse-case scenario.
4 UPEA
V. LIMITATIONS
Identification and testing of PACM was conducted by a trained professional licensed in the State of Wisconsin. Professional judgment was used in the selection of materials to be tested and the number of samples of each homogeneous material tested.
This report documents testing of ACM or PACM based on sampling strategies and priorities as described herein, and on the dates and at locations identified in this report.
Modifications to the building or its interior through renovations, remodeling, building additions or changes to fixtures, facilities or furnishings that occur subsequent to the date of this report may add or remove ACM or PACM not identified in this report.
This report was completed to aid the building Owner, general contractors, and potential asbestos abatement contractors in locating ACM. Under no circumstances should this report be utilized as a bidding document or as a project specification document.
This report was completed with limited destructive testing. Therefore, materials may be discovered in walls or ceilings that contain asbestos. If such materials are encountered, all work shall stop immediately until proper testing may be conducted to determine the content of the material.
SAMPLE LOCATION
SAMPLE
NUMBER
MATERIAL
(CLASSIFICATION) DESCRIPTION OF MATERIAL
ESTIMATED
QUANTITY
FRIABLE
YES / NO
ASBESTOS
CONTENT
Drywall White ~1000 SF NO None
Roofing Underlayment Black ~2500 SF NO None
Lodge 28 Roof Penetration Tar Black, Bituminous ~15 LF NO None
Ceiling Plaster White ~1000 SF
Wall Plaster White ~1000 SF NO None
Lodge 23 Drywall White ~1000 SF NO None
Drywall White ~1000 SF NO None
Lodge 21 Ceiling Plaster White ~1000 SF NO None
Grout Brown, between 6"x6" tiles 100 SF NO None
Lodge 19 Ceiling Tile 2'x2', White, Kit. #1 only 200 SF NO None
Baseboard Trim Vinyl, White 60 LF NO None
Lodge 17 Floor Tile 6"x6", Brown 100 SF NO None
Glue Tan, behind wood base board in Open
Space & Kit. #2 100 LF NO None
Lodge 15 Floor Tile 8"x8", grey, ceramic 400 SF NO None
NO None
Lodge 26 Roofing Shingles Brown ~2500 SF NO None
NO None
Lodge 13 Gypcrete Red, in Kit. #1 & Kit. #2 400 SF NO None
NO
Caulk
Caulk White, around windows of Kit. #1 &
Mech. Rm.
50 LF NO
Clear, vertical seams between column
& wall
50 LF NO7
Lodge 11
Lodge 12
Lodge 25
Lodge 27
Lodge 14
Lodge 16
Lodge 18
Lodge 20
Lodge 22
Lodge 24
Lodge
Lodge
Lodge
Lodge
None
Caulk White, around window sashes 20 LF None
Floor Underlayment
Lodge
Living Quarters
Lodge
None
Lodge 1 Caulk Brown, corner of chimney & wall 40 LF
TABLE 2 ‐ PG. 1 OF 2
SUMMARY OF ASBESTOS ANALYTICAL RESULTS
W7969 PARK RD.
WESTBORO, WI 54490
NO None
500 SF NO6
Lodge 2 Door Stop Cushion Grey, on inside of chimney door 5 LF NO
Lodge
Lodge
NO None
Caulk Dark Brown, outside of Open Space &
Mech. Rm.
200 LF
None
Lodge 3 Grout Grey, on floor near chimney 12 SF
Grout Light Grey, 2nd Layer outside of chimney 100 SF NO None
None
NO None
Grout Grey, on outside of chimney between bricks
100 SF NO
Black
None
Caulk White/Grey, around window sashes
(original) 200 LF NO None
Caulk Tan, in crawl space along block border 80 LF NO None
Chimney Penetration Tar on
Roof Black, Bituminous ~12 LF NO 1.25% CHRYSOTILE
Caulk Tan, outside of Restroom & shower windows and outside wall trim
200 LF
NOTE: Material containing less than 1 percent asbestos is not classified as ABM Asbestos Containing Material.
Living Quarters 38 Wall Plaster White 2500 SF NO None
Living Quarters 39 Wall Plaster White, on chimney 100 SF NO None
NO None
Living Quarters 37 Ceiling Tile & Drywall White 150 SF NO None
Garage 43 Caulk White, on window sashes 80 LF NO None
Living Quarters 32 Caulk White, around tub/shower 25 LF NO None
Living Quarters 33 Drywall White 2000 SF NO None
Living Quarters 34 Ceiling Tile & Plaster
Living Quarters 41 Roofing Shingles Tan 800 SF NO None
Living Quarters 42 Roofing Underlayment Black 800 SF NO None
WESTBORO, WI 54490
Living Quarters 40 Grout Trowled surface, grey, over rigid insulation near ground 100 SF NO None
12"x12" Ceiling Tile 100 SF NO None
Living Quarters 35 Caulk White, @ electrical conduit penetration in kit. Ceiling 1 LF NO None
Living Quarters 36 Wall Plaster White 2500 SF
TABLE 2 ‐ PG. 2 OF 2
SUMMARY OF ASBESTOS ANALYTICAL RESULTS
None
Roofing Underlayment
Floor Tile 12"x12", under carpeting 100 SF NO
Caulk Chimney Penetration Tar, Black 12 LF NO
Roofing Shingles Tan 800 SF45 NO
Garage
Garage
46 Black 800 SF NO None
W7969 PARK RD.
Living Quarters
Living Quarters None
None44
TABLE 3
SUMMARY OF LEAD‐CONTAINING PAINT ANALYTICAL RESULTS
LOCATION
SAMPLE
NUMBER
SAMPLE
DESCRIPTION COLOR
TOTAL
LEAD
(mg/kg)
LEAD
CONC
(% by wt)
LODGE –
EXTERIOR
L‐1 WINDOWS BROWN 1380 0.138
LODGE –
EXTERIOR
L‐2 WALLS TAN <29.6 <0.00296
LODGE –
EXTERIOR
L‐3 SOFFIT, FASCIA
& TRIM
BROWN 67.9 0.00679
GARAGE –
EXTERIOR
L‐4 WINDOWS BROWN 1010 0.101
LIVING QTRS –
INTERIOR
L‐5 BASEBOARD &
TRIM
WHITE/PEACH 416 0.0416
LIVING QTRS –
INTERIOR
L‐6 WALLS BEIGE 220 0.022
NOTE: BOLD INDICATES LEAD CONCENTRATION ABOVE ACTION LIMIT
TABLE 4
SUMMARY OF CADMIUM‐CONTAINING PAINT ANALYTICAL RESULTS
LOCATION
SAMPLE
NUMBER
SAMPLE
DESCRIPTION COLOR
TOTAL
CADMIUM
(mg/kg)
CADMIUM
CONC
(% by wt)
LODGE –
EXTERIOR
L‐1 WINDOWS BROWN <5.87 <0.000587
LODGE –
EXTERIOR
L‐2 WALLS TAN <5.92 <0.000592
LODGE –
EXTERIOR
L‐3 SOFFIT, FASCIA
& TRIM
BROWN <6.58 <0.000658
GARAGE –
EXTERIOR
L‐4 WINDOWS BROWN <6.14 <0.000614
LIVING QTRS –
INTERIOR
L‐5 BASEBOARD &
TRIM
WHITE/PEACH <5.94 <0.000594
LIVING QTRS –
INTERIOR
L‐6 WALLS BEIGE <6.12 <0.000612
NOTE: BOLD INDICATES CADMIUM CONCENTRATION ABOVE ACTION LIMIT
APPENDIX A
INSPECTOR ACCREDIATION
APPENDIX B
BUILDING FLOOR PLANS
& SAMPLE LOCATIONS
APPENDIX C
ANALYTICAL RESULTS ‐ ASBESTOS
APPENDIX E
ANALYTICAL RESULTS – LEAD & CADMIUM
CONTAINING PAINT
APPENDIX F
MOLD TESTING – LIVING QUARTERS
BUILDING
100 Portage Street Houghton, MI 49931
906-482-4810 • 800-562-7684 • Fax: 906-482-9799
Offices also in:
Iron Mountain
Ishpeming Marinette
Sault Ste Marie
U.P. Engineers & Architects, Inc. www.UPEA.com
[U28-17435] July 26, 2017
Ms. Debra K. Brinn, Contract Specialist USDA Forest Service Huron Shores Ranger Station 5761 N. Skeel Oscoda, MI 48750-1595
RE: LIMITED MOLD SAMPLING IN LIVING QUARTERS BUILDING AT THE MONDEAUX
RECREATION SITE
Dear Debra K. Brinn, A mold sample was taken from the Living Quarters Building on the kitchen ceiling near the chimney on July 11th, 2017. The inside of the building had a strong moldy odor before it was aired out by keeping the doors open for about 15 minutes. The sample was taken from a dark brown stain (~1 SF) in the white ceiling tile.
The results show that a “low” amount of Ascospores is present in the brown ceiling tile.
Ascospores fungal is a common fungal that is commonly found in interior damp locations and even outdoors. Ascospores may cause allergic reactions to certain individuals, so care should be taken when working around and removing the stained/moldy ceiling tile. Also, the cause of the mold, which is most likely water penetrating the chimney flashing on the roof should be addressed immediately to stop any further damage.
If you have any questions, please do not hesitate to contact me at (906) 482-4810 or erbjorn@upea.com. We appreciate the opportunity to be of service.
Sincerely, U.P. ENGINEERS & ARCHITECTS, INC.
Emmett Bjorn Engineer
Cc: TSPurdy/UPEA