This document is a Request for Services (RFS) from the USDA Forest Service for lead testing and well plumbing services at the Kenton Ranger District Administrative Site in Michigan. The Forest Service is soliciting a State of Michigan certified and licensed well driller to perform the following tasks: remove and reinstall the existing well pump, drop-pipe, and check-valve; temporarily install a peristaltic pump to acquire water samples; replace the drop-pipe, check-valve, and well pump with new components; excavate and verify the materials of the existing water service lines; and properly chlorinate and flush the well upon completion. The RFS includes supplemental information on the well specifications, site utilities, and well log. Questions should be directed to the Government Project Leader, Eric R. Johnson. The contractor will be required to provide deliverables such as data sheets, manuals, instructions, as-builts, warranties, certificates, and reports.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA – FOREST SERVICE – OTTAWA NATIONAL FOREST
2024 KENTON RANGER DISTRICT ADMIN SITE – LEAD TESTING + WELL PLUMBING PROJECT
I. Project: 2024 Kenton Ranger District Admin Site – Lead Testing + Well Plumbing Project
II. Requesting Forest: Ottawa National Forest
E6248 US-2
Ironwood, MI 49938
Phone: 1-906-932-1330 Fax: 1-906-932-0122 Website: https://www.fs.usda.gov/ottawa
III. Government Project Leader: Eric R. Johnson, Civil / Facilities Engineer
E6248 US-2
Ironwood, MI 49938 Phone: 1-906-285-6898 Fax: 1-906-932-0122 E-mail: eric.r.johnson@usda.gov
IV. Description of Services:
The Ottawa National Forest is soliciting a request for and completing the following:
A. A State of Michigan certified and licensed well driller to:
a. Mobilize to the Kenton Ranger District Administrative Site in Kenton, Michigan 49967.
b. Turn the power to well / well pump on and off as needed to safely perform the tasks below.
i. Follow all applicable and salient OSHA requirements.
c. Remove the existing drop-pipe, check-valve and well pump from the well,
d. Temporarily install contractor furnished peristaltic pump into the drinking water well as deep as the approximate pump depth (or deeper if able) for water samples acquisition by Forest Service (FS) personnel:
i. A contract authorized Forest Service staff person(s) will acquire the well water samples via the contractor installed peristaltic pump with aid from the contractor (i.e. for operating the peristaltic pump to acquire the water samples, etc.).
e. Remove the temporarily installed peristaltic pump from the well.
f. Reinstall the existing well pump, drop-pipe, check-valve.
g. Flush the well for 30-minutes (to waste).
h. Remove the existing drop-pipe, check-valve and well pump from the well,
i. Temporarily reinstall contractor furnished peristaltic pump into the drinking water well as deep as the approximate pump depth (or deeper if able) for water samples acquisition:
i. A contract authorized Forest Service staff person(s) will acquire the well water samples via the contractor installed peristaltic pump with aid from the contractor (i.e. for operating the peristaltic pump to acquire the water samples, etc.).
j. Remove the temporarily installed peristaltic pump from the well.
k. Replace the drop-pipe (and associated fittings) with schedule 80 PVC drop-pipe (including fittings and other appurtenances) for a complete job.
https://www.fs.usda.gov/ottawa mailto:eric.r.johnson@usda.gov
i. Comply with NSF 61 standards as applicable and salient.
l. Replace the check-valve with certified “no Lead” check-valve that meets or exceeds the other qualities (i.e. pressures, flow, etc.) of the existing check-valve.
i. Comply with NSF 61 standards as applicable and salient.
m. Replace the existing well pump with a new Myers submersible well pump matching the quality (when the existing well pump was newly purchased & installed) and characteristics (i.e. flow rate, inlet size, maximum head, horsepower, type, etc.) of the existing well pump:
i. F.E. Myers
ii. Model: J1525P-13 (or J1525P-B)
iii. 25-GPM
iv. 1.5HP
v. Discharge Height same as existing
vi. Verify actual in-field
vii. Depth same as existing
viii. Verify actual in-field
ix. Outlet size (probably 1.25” diameter drop-pipe)
1) Verify before installing new.
x. Be prepared for installing larger or smaller schedule 80 PVC drop-pipe diameters, fittings, and associated plumbing appurtenances (i.e. check-valve, etc.).
n. It isn’t anticipated that the FS will salvage any of the materials, supplies or equipment, and thus becomes the property of the contractor.
i. Remove from FS property, and, if disposing, do so in accordance with the laws, regulations, standards, and codes of jurisdictions having authority (for Lead, etc.).
o. Upon completion of working within the “Well”, as necessary, applicable and salient, properly chlorinate (as required by standards, regulations, and codes) and flush the “Well” to comply with all requirements (code, standards, laws, regulations).
p. Excavate (in grass / non-paved locations only; do not disturb or damage paved areas) down to the existing water service lines for the Administrative Office building, and the Warehouse garage to verify (and document; i.e. photos, etc.) the materials of the existing water service lines.
i. A contract authorized Forest Service staff person will determine the excavation locations.
ii. After verification and documentation of pipe materials, backfill with sand near / around pipes (pipe bedding), compact, backfill excavated materials (excluding rocks over 1” diameter), and restore surface to slope, drainage, elevation, and surface turf appearance (“the way it looked”) prior to beginning excavation.
iii. Don’t drive on or damage paved areas with excavating equipment or any heavy equipment used for working on the well, excavating, etc.
V. Location:
The Kenton RD Ad Office Site and associated facilities are located at the following:
4810 E. M28 Kenton, MI 49967
VI. Supplemental Information:
A. See supplemental information (below) titled “19960918-WSSN2007431-KentonRDadSite- WUPDHD-SanSurvey-1.pdf” for information about the well, well casing, depth(s), pump, well seal / cap, check valve, distribution system, different casing diameters at different depths, etc. on pages #5 and #6 below.
VII. Supplemental “Well” photos:
See pages #7, #8, and #9 of 11 pages.
VIII. Supplemental “Site Utilities” map (locations are approximated):
See page #10 of 11 pages.
IX. Supplemental 10/15/1968 Well Log / Record:
See page #11 of 11 pages.
X. Questions regarding this contract should be directed to:
Eric R. Johnson, Civil / Facilities Engineer, – 906-675-9840 or eric.r.johnson@usda.gov mailto:eric.r.johnson@usda.gov
XI. Deliverable(s):
A. For all products, materials, equipment, supplies, and verifications:
i. data sheets / cut-sheets
ii. manuals
iii. instructions
iv. as-builts
v. warranties
vi. certificates
vii. reports (including photos)
B. All documents shall be prepared and submitted using English Units.
XII. End
I. Basic Inlormation
Suppy Namo LUSES Keaton Admuais traon 3:k Supply Address
Counly Hauighha Contact Person
Owner /SDA
Perlod of Operation
Llcense Type:
II. Well
Type of Establishment fice + Maatenane Total Pop. Serod Z5 No. of Employees2O _No. Service Connectlons
Casing,Diamelor
Owner Mailing AddressP.).
Recols ndicete
M-28
Other
X Not Llcensed
(Source of information:
Tolal No., of Wells
Casing Terminatlon:
I|I. Well Installation - Approved:
DavidP:ckford
IV. Well lsolalion - Approved:
Distance to Nearest Sewer
Brand Name:
Focest Service Box /48
Locatlon:
TownshipDJacn Town 47_s Range37_E
(sçhool, reslaur�qt, elc.)
V. Pump Installatlon - Approved:
Type: Shallow Well Jet
Approved Well SeaWCap: X Yes No
Well .D. 70544 " Hboueyrond below ess
Distance to Polential Contaminatlion
X 12 Month
VIl. Distibutlon Syslem
Malerlal:
VIlI, Trealment NA
Distance to Major Source of Coniamination
() Dislance to Underground Slorage Tanks (2)A bwe ground tnks
Pump Salting/Drop Pipe Longth
Meyers
Pitless Adaplor
Yes
Check Valve on Pump Dlscharge LIne:
VI. Slorage Tank Inslallalion - Approved:
Type: Galvanlzed
Approved Sampling Tap Provldad:
Copper
Type:J Sohener
Yes
>75
Well Well House
NONCOMMUNITY PUBLIC WATER SUPPLY
SANITARY SURVEY REPORT
l1 Sewer ls within Isolation Area, is Malerial and Installalion Approved:
Tank Localon: Offue Blda ot hee Tank #1-Brand Name: ell -X- trol
Garaye Tank i2-Brand Name: Jle|l-X trul
Food
Owner
Yes
Year Installed
No
No
Deep Well Jet
>75
No
Chlodnallon
Yes
Title
Galvanlzod
12 In. Above Grade or Floor: X
MakaModal # Meartor
Bladder/Dlaphram
Yos
Seasonal
Measured
Foresty Tech. Type: O la
Campground
DSee Comments page 2
Type of Sewer
Dilling Mthod
No
Source
Source wsSN Z0074 3/ Phone 52-3500
Ciy Keoton _Zip 4443
Depth 83
Well Drilr Johason b See Comments page 2
Well House
Fllrallon
Ciy Keato
Wall log)
No
Slze ol lanks3000
DNo
Burted
I1 Seasonal : From
Plastlc (ype
Phone
O Yes
DSS Facility
Basement Oflset
Yes D No
See Commenls page 2
Turbine
Prolocted Sucllon Line:
DNo
Sedion No. |
852-.3SOo
Phosphale
X Submersible Hand Pump Other
Model No. JTI525P -3Hp2 Pump Capacily Adequale:
Basoment P# (Gravily Draln): DYes No
SlateMI
Check Valve Locallon Approved:
See Comments page 2
Bulk Slorage D other
Operallng Range 20_ 30 psl
Modol # J)X 262_or Capaciy sal or Halgh/engih
Other
Pit (Gravity Drain):
Approved Vent Provided:
(storm, building, sanitary) Type of malerial
Yes
(ile field, surlace water)
(landlill, chemical wasle, sewage lagoon) gallons Compound in Tank
Secud Centamnt
Well or Well Sile Subject to Flooding:
Casing Depth 83
Nontranslent
Pump insialer Sitola 1s5s)
Cast lron
Iron Aomoval
1/4 te
No
Other
Zip 4943_
D other, 1/4
Yes
Yes
(uel oil, gas, etc.)
+ desel
Yes
U+:l:ty siák fauiet near pressure tnk.
Yes No
1/4
Number of Tanks
X Dlameler
XNol Applicable DNo
X Dlameter
Yes XNo
No
USFS Tuly Is, 1482 ope-ehon Maipkn anc e Plen indcaks (2) buried seraye tks o-Ste. Concli tien' sie. locu F cn vnknown.
s37
Dother.
Modal Lak- 252or Capacly Z sal or Halghutangith, ericjohnson Highlight ericjohnson Highlight ericjohnson Highlight ericjohnson Highlight ericjohnson Highlight ericjohnson Highlight ericjohnson Highlight ericjohnson Highlight ericjohnson Highlight ericjohnson Highlight ericjohnson Highlight ericjohnson Highlight ericjohnson Highlight ericjohnson Highlight ericjohnson Highlight ericjohnson Highlight
IV. Cross Connections - Protection Provided?
Toilets Urinals Hose Bibs Boilers Kitchen Fixturcs Cooling Water
NONCOMMUNITY PUBLIC WATER SUPPLY SANITARY SURVEY REPORT
X. Comments/Rccommendations
Yes No NJA
D-241 5/89 Authority: Aa 399, P.A. 1976
Water Softeners
) Tastall Vacuwm breaker on hose bibb leLakd ia çacage arouad hoiler bakflow preventec
)Tastal sreened veot fuel olo tuk
Tanks Containing Hazardous Matcrial Imigation Systems Fire Protection Systems Others (explain)
X1. Drawing (include all buildings, drives, roads, wels, storm and sanitary sewers, sewage disposal facilities, chemical storage areas, buried fuel tanks, arrow indicating north, ctc.) or attacha site plan.
Suvyd By Tasers
Adminstrahe
Bu.lding
Geraye
M-23
Dale -18% Dale Last Surveyed, wSSN: 200743/
Yes, No NJA
Weil s5gul. oil sny
)100 _al. fuel tok
White Copy- MDPH Copy
Ieak dete toS
Agency uleskra ve psit Heal th Dept.
Pink Copy - Locul Hcalth Dept. Copy Yellow Copy -Owner's Copy
EXISTING PARKING LOT
STATE HIGHWAY - M28
RANGER DISTRICT OFFICE
GARAGE
CONTAINER BOX
(PAINT BUILDING)
SHED
GAS TANKS
DUMPSTER
TREE LINE
TREE LINE
FENCED AREA
STORAGE SHED
GAS HOUSE
SIGN
SIGN
SIGN
FLAG POLE
CONC. APRON
CP-1
CP-3
CP-2
CATCH BASIN
CATCH BASIN
STORM MH
CONC. APRON
EX STORM PIPE OUTLET
INV = 1164.55
ELECTRIC PEDESTAL
WATER SHUT-OFF
WELL HEAD
ELECTRIC PEDESTAL
CATCH BASIN
SANITARY MH
SANITARY MH
LIFT STATION
PEDESTAL
PROPANE TANK
CP-4 SANITARY MH
MONITORING WELL
MONITORING WELL
WATER SHUT-OFF
PARKING LOT LIGHTING
PARKING LOT LIGHTING
UG ELECTRIC
(VERIFY)
W W W W W W W
W W W W W W
W
W
W
W W
W W
W
UG WATER LINE
(VERIFY)
STORAGE SHED
E E
E E
E
E
E
E
E
E S
S
S
EDGE OF GRAVEL
EDGE OF ASPHALT
ELEC PANEL
GAS VALVE
SEPTIC TANK
(VERIFY LOCATION)
WATER SHUT-OFF WATER SHUT-OFF
MONITORING WELL
A/C UNIT
ELEC PANEL
STORM MH
EXSTMH2
RIM = 1173.17
INV OUT = 1167.17 (NE)
INV IN = 1167.72 (NW)
INV IN = 1167.67 (SW)
EXSTMH1
RIM = 1177.94
INV OUT = 1171.04 (NE)
INV IN = 1171.64 (NW)
INV IN = 1172.44 (SW)
INV IN = 1171.29 (S)
SANITARY LINE
(VERIFY LOCATION)
SANITARY LINE AND FORCE MAIN
(VERIFY LOCATION)
F.FL. EL. = 1188.94
LANDSCAPING
H
AR
R
ISO
N
STR
EET
FEDERAL FOREST HIGHWAY 16
.08 MILES TO THE INTERSECTION
GAS TANKS
MONITORING WELL
S
S
S
S
S
S
S
S
S
S
S
SANITARY MH (FIELD VERIFY LOCATION)
SANITARY LINE AND FORCE MAIN
(VERIFY LOCATION)
SANITARY LINE
(VERIFY LOCATION)
SANITARY MANHOLES. NOT SHOWN
ON PLANS (FIELD VERIFY LOCATION)
CONTROL POINT
NORTHING EASTING
626607.4280 25770439.5860
626815.6540 25770451.0240
626755.9200 25770314.8270
626608.5870 25770586.9040
POINT ELEV.
1180.11 1174.70 1179.54 1180.14
DRAWN
DESIGNER
STAMPS, LOGOS, AND SEALS
PROJECT NAME
DRAWING TITLE
CHECKED
ARCHIVE NO.DATE
PROJECT NO.
DRAWING SHEET NO.
OFSHEET
United States Department of Agriculture Forest Service
/27
/23
:4 5 M
AR
KS
UR
PR
EN
AN
T C:
\U
SE
RS
\M
AR
KS
UR
PR
EN
AN
T\
BO
X\
BU
IL
DI
NG
SF
AC
IL
IT
IE
S\
-K
EN
TO
N
RD
\A
DM
IN
\12
-A
DM
IN
OF
FI
CE
\20
K
EN
TO
N
PA
RK
IN
G
LO
T
RE
CO
NS
TR
UC
TI
ON
\3-
IM
PL
EM
EN
TA
TI
ON
\1-
DE
SI
GN
\P
S& E\
1-
PR
EL
IM
_P S&
E\
PL
AN
S_
DR
AW
IN
GS
\C
AD
F
IL
ES
\K
EN
TO
N
PA
RK
IN
G
LO
T
- T
MA
KI
B
AS
E
MA
P.
DW
G;
(R09)
EASTERN REGION
KENTON RANGER
DISTRICT
PARKING LOT
PHASE 2
OTTAWA NATIONAL
FOREST
KENTON RANGER DISTRICT
EXISTING SITE PLAN
M. SURPRENANT
M. SURPRENANT
B. HEWITT
Feet 0 20 40
N
S
W E ericjohnson Cross-Out ericjohnson Cross-Out ericjohnson Highlight ericjohnson Highlight ericjohnson Highlight
{ "type": "Form", "isBackSide": false }
{ "type": "Form", "isBackSide": false }
File details come from the government source that posted it. Updated .