Attachment 4 - Government Response to Questions.pdf
PDF 84 KB Posted
- Attached to
- Wolf Creek JCC Heat pump, HVAC, Umpqua Dorm
- Solicitation number
- 12441925Q0045
- Issued by
-
Department of Agriculture Forest Service
About this file
This document is a Questions and Answers (Q&A) file for a USDA Forest Service project. The Q&A covers key details about a new contract requirement, including confirmation that there is no incumbent contractor and this is a first-time procurement. The project involves specific technical aspects such as replacing a floor-mounted water heater while retaining existing buffer and expansion tanks, and implementing local HVAC controls with thermostats without a building management system integration. Additional project details include confirmation of no asbestos concerns in the buildings, which have been tested by the Department of Labor. For offers over $150,000, a bid guarantee is required, and alternative payment protections may be applicable as referenced in FAR 52.228-13.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 12441925Q0045 Amendment 0001.pdf | ||
| Attachment 2 - Specifications.pdf | ||
| 12441925Q0045.pdf | ||
| Attachment 1 - Drawings.pdf | ||
| Attachment 3 - Wage Determination.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Item Question USDA FS Response 1 Who is the incumbent? There is no incumbent. This is a new requirement.
2 What is the past Contract Award #? N/A. See response to Item #1.
3 Has the budget been approved for this contract? Our intent is to fully fund this contract.
4 Are you guys just looking to replace the floor mounted water heater? The buffer tanks and expansion tank are to remain? That is correct. The buffer or expansion tanks will remain.
5 HVAC controls should just be local control with thermostats correct? No DDC integration into a BMS front end?
There is no building management system in the buildings on this project. Thermostat locations shown on drawing M2.0
6 Any asbestos concerns? No, all building have been tested by DOL.
7 Are there any bid, performance, or payment bonds required for this project? A bid guarantee is required if the offer is over $150,000. See L.2(2)(a)(v).
See FAR 52.228-13 for Alternative Payment Protections.