This document is a pre-renovation hazardous materials assessment report for Shed 7 of the Rocky Mountain Research Station located in Missoula, Montana. The report identifies asbestos-containing materials, lead-based paint, PCBs, and mercury-containing equipment found at the site. One material, cement asbestos board on walls and ceilings, was found to contain asbestos. Four fluorescent light tubes, CFLs, thermostats, and thermometers were identified as mercury-containing equipment. No lead-based paint or PCB-containing equipment were detected. The report provides locations and quantities of identified hazardous materials and recommends abatement of asbestos prior to renovation due to regulatory requirements. It also provides guidelines for proper handling and disposal of mercury-containing equipment.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Contract AG-82FT-P-15-0058 ACM Project NO.: IH-15-101 December 15, 2015
Report of Pre-Renovation Hazardous Materials Assessment – Rocky Mountain Research Station Shed 7
Subject Property:
Rocky Mountain Research Station 5775 U.S. Hwy 10 W.
Missoula, MT 59808
Contract: AG-82FT-P-15-0058
Prepared For:
United States Department of Agriculture U.S. Forest Service Rocky Mountain Research Station 240 W Prospect Street Fort Collins, CO 80526
Prepared By:
Abatement Contractors of Montana, LLC 208 Commerce St Missoula, MT 59807 Office: 406-549-8489 www.acm-contracting.com
Page 1 Contract AG-82FT-P-15-0058 Report for a Comprehensive Pre-Renovation Asbestos and Lead Hazardous Materials Assessment Shed 7 of the RMRS –Missoula, Montana. Project No.: IH 15-101
Table of Contents
1.0 INTRODUCTION
2.0 Scope of Work
3.0 Site Description
4.0 Asbestos Inspection
5.0 LEAD-BASED PAINT INSPECTION
5.1 Introduction
5.2 Methods
5.3 Findings
6.0 Mercury
7.0 Assumed PCBs
8.0 Quality Control & Quality Assurance
9.0 XRF
10.0 Summary of Findings:
10.1 Asbestos
10.2 Lead Based Paint
10.3 PCB-Containing Equipment
10.4 Mercury -Containing Equipment
11.0 Limitations
List of Tables
Table 1: Summary of ACM Section Shed 7
Table 2: Summary of LBP Section Shed 7
Page 2 Contract AG-82FT-P-15-0058
APPENDICIES
Appendix A – Sample Location Drawings Appendix B – ACBM & LBP Location Drawings Appendix C – Documentation of Accreditation Appendix D – XRF Performance characteristic sheet Appendix E – Data Summary Tables Appendix F – Analytical Reports Appendix G – PCB & Mercury Material List Appendix H – Photo Log of ACM and LBP
Page 3 Contract AG-82FT-P-15-0058
December 15, 2015
USDA Forest Service Attn: Corrie Kegel, PE 5775 U.S. Hwy 10 W.
Missoula, MT 59808
RE: Pre-renovation Inspection report for Asbestos, Lead & PCB Identification for
Shed 7 of the Rocky Mountain Research Station Located at 5775 U.S. Hwy 10 W, Missoula, MT 59808-9361
Attn: Corrie Kegel, Abatement Contractors of Montana, LLC (ACM) is pleased to provide the findings of the asbestos and lead-based paint inspection completed at the Rocky Mountain Research Station (RMRS), in Missoula, Montana. The inspection was performed from October through December, 2015 by Mr. Christopher Casas and Mr. Mike Foust; Montana Department of Environmental Quality (DEQ) accredited asbestos inspectors (MTA-4459) (MTA-2741) and Environmental Protection Agency (EPA) accredited lead based paint inspectors (MT-I-I148223-1) (MT-S-28404-2). Credentials are attached.
1.0 INTRODUCTION
The pre-renovation hazardous material assessment for the above referenced project was completed to confirm or deny the presence of asbestos. ACM collected a total of 4 bulk samples representing 2 homogeneous areas (HAs) of suspected asbestos-containing building materials (ACBM). Floor plan drawings with bulk sample locations are presented in Appendix A. Samples listed in Table 1 tested positive for asbestos.
Identification of regulated hazardous materials at the Shed 7 Wing was accomplished through physical inspection, bulk sampling, and collection of X-Ray Fluorescence (XRF) screening data of building materials within the site.
The inspection for asbestos-containing material (ACM) was conducted using the protocol developed for schools under the Asbestos Hazard Emergency Response Act (AHERA), as promulgated in Title 40, Code of Federal Regulations, Part 763 (40 CFR, Part 763.354). Classification of the identified asbestos-containing materials was performed under the guidelines for National Emission Standards for Hazardous Air Pollutants (NESHAP).
The lead-based paint inspection was conducted using the protocols developed by the United States Department of Housing and Urban Development (HUD). ACM used a field XRF analyzer to determine the presence or absence of LBP. HUD recognizes the XRF analyzer as the recommended method to determine lead in paint (HUD 1995, revised 1997 and 2000).
ACM completed an inspection for Polychlorinated Biphenyls (PCBs) within Shed 7 by an observational investigation to assess the quantity of PCBs.
Page 4 Contract AG-82FT-P-15-0058
Assessment Shed 7 of the RMRS –Missoula, Montana. Project No.: IH 15-101 ACM completed an inspection for mercury-containing equipment within the Shed 7 by an observational investigation to assess the quantity of mercury-containing equipment.
Our methods and findings for the Inspection and overall hazard assessment are presented in the following sections of this report.
A total of 3 separate HAs of suspect lead-containing surface coatings were identified at the site during the assessment. Three (3) HAs were determined through on-site XRF analysis to be NON-Lead-Based Paint and NON-LCP and therefore contain no amount of detectable lead.
Prior to initiating renovation activities at the site, an abatement plan should be prepared to address the containment, packaging handling, transport, and disposal of the regulated asbestos-containing materials, PCBs containing materials, and mercury-containing equipment identified at the site in order to satisfy regulatory requirements, as described in this report.
2.0 Scope of Work
The scope of work for this project included a hazardous materials assessment of building components throughout the accessible interior and exterior spaces of Shed 7. This work included visual assessment, sampling, and documentation of suspect and confirmed/assumed asbestos containing-building materials, lead-containing surface coatings, PCB’s, Mercury light tubes, thermostats as defined by the Environmental Protection Agency and State & local codes for Montana. This work also included recording the locations of the materials, estimated quantities +/- 10% of hazardous materials and recommendations for abatement of asbestos containing material and other hazardous materials. The scope of work included visual inspection for, but no sample collection of potential mercury-containing materials and potential PCB-containing equipment and materials. The purpose for conducting the inspection is to ensure all local, state and federal regulations related to hazardous waste are complied with during the upcoming renovation of Shed 7. ACM’s scope of work for this project did not include preparation of abatement plans or specification documents.
3.0 Site Description
The Rocky Mountain Research Station (RMRS) houses the Fire, Fuel and Smoke science program as well as the Missoula Fire Sciences Laboratory. The RMRS was constructed in 1960 complete with a combustion laboratory, a wet laboratory, maintenance garage spaces, and office spaces. The building is divided into A, B and C Wings. Wing A houses the combustion laboratory, the wet laboratory, the boiler room, the ac/refrigeration room, and the low velocity and high velocity wind tunnel laboratory.
Wing B houses the office spaces and Wing C houses the server room, office space, and a printing room. Shed 7 houses the water storage tank, and grounds keeping equipment.
Exterior of the Building:
The foundation is poured concrete; the exterior structural walls of Shed 7 are finished with Sheet metal over concrete/CMU structure. The roof over Shed 7 is comprised of sheet metal.
Page 5 Contract AG-82FT-P-15-0058
Assessment Shed 7 of the RMRS –Missoula, Montana. Project No.: IH 15-101
Interior of the Building:
The interior flooring of Shed 7 consists of bare concrete. The interior walls of Shed 7 are finished with Cement Asbestos board over metal framing. The ceilings of Shed 7 are completed with cement asbestos board (CAB).
4.0 Asbestos Inspection
Samples were obtained by trained and experienced individuals using techniques such as wet slicing, wet boring, and/or similar methods designed to limit contamination of the area during sampling. When applicable, the sampled area was sealed using duct tape or spry encapsulates as appropriate to the material being sampled.
The asbestos inspection was performed in accordance with the Administrative Rules of Montana (ARM), Occupational Health and Safety Administration (OSHA) 29 Code of Federal Regulation (CFR) 1926.1101(k), DEQ and the National Emission Standards for Hazardous Air Pollutants (NESHAP) 40 CFR 61, Subparts A and M.
As required prior to renovation or demolition of building materials, the asbestos inspection consisted of a detailed survey of all materials which will be disturbed during the demolition process. Suspect ACBM were visually identified and touched prior to sampling. The samples were placed into HA groups using a coding method to classify each material by type, texture, and date of application. Components of the inspection included:
• Identification of homogeneous suspect materials on a room-by-room basis
• Collection and analyses of bulk samples to confirm or deny the presence of asbestos
• Bulk samples were not collected from any homogeneous material made of fiberglass, wood, foam, glass, or rubber.
A minimum of three (3) samples were collected from random locations of each HA of suspect material.
Samples were collected from existing damaged materials, as applicable. Samples were placed in pre-labeled plastic containers for transport to the laboratory.
Samples were shipped, under chain-of-custody protocol for standard analyses to Sanair Technologies Laboratory, Inc. in Powhatan, Virginia, for bulk asbestos analysis utilizing Polarized Light Microscopy
(PLM). The samples were analyzed in accordance with EPA method 600/R93/116 and EPA 600/m4- 82/020.
The DEQ defines ACM as material containing more than 1% asbestos based on laboratory analysis for the material using the EPA method 600/R-93/116 (“Method for the Determination of Asbestos in Bulk Building Materials’) by Polarized Light Microscopy (PLM). Three categories of ACM have been defined in the
National Emissions Standards for Hazardous Air Pollutants (NESHAP) standard, which is established in Title 40, part 61, of the Code of Federal Regulations (40 CFR 61.141) and adopted by the DEQ in Title 17, Chapter 74, Subchapter 3, of the Administrative Rules of Montana (ARM 17.74.351). The NESHAP Category definitions are as follows;
Page 6 Contract AG-82FT-P-15-0058
Assessment Shed 7 of the RMRS –Missoula, Montana. Project No.: IH 15-101
• Category I Non-friable ACM - asbestos-containing packings, gaskets, resilient floor coverings, and asphalt roofing products containing more than one (1) percent (%) asbestos as determined using the method specified in appendix E, subpart E, 40 CFR 763, section 1 (PLM)
• Category II Non-friable ACM - any material, excluding Category I Non-friable ACM, containing more than 1% asbestos as determined using the method specified in appendix E, subpart E, 40 CFR 763, section 1, PLM that, when dry, cannot be crumbled, pulverized or reduced to powder by hand pressure.
• Regulated ACM (RACM) - a) friable asbestos material; b) Category I Non-friable ACM that has become friable; c) Category I Non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading; or d) category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation operations regulated by the subpart.
ACM collected 4 bulk samples representing 2 HAs of suspected ACBM. Table 1 summarizes analytical results for the building materials collected within the site. Additional information in Table 1 includes sample ID, building material description, sample location, and recommended response actions.
Table 1: Summary of ACM Shed 7
HA No.
HA
Description Location
Asbestos
Condition SQFT/LF Response Action
TRNST.1
cement asbestos board Walls of Shed 7
20% good condition non friable
1000 SQFT
(Intact Removal) prior to renovation
5.0 LEAD-BASED PAINT INSPECTION
The purpose of a lead assessment is to identify lead-containing surface coatings. Identification of Lead Containing Paint (LCP) and/or Lead Based Paint (LBP) is necessary to determine whether renovation/demolition workers may potentially be exposed to airborne lead concentrations exceeding permissible exposure limits (PEL) established by the OSHA. Characterization of leachable lead in the overall potential waste stream is necessary to determine proper handling and disposal of renovation waste materials required by the Resource Conservation and Recovery Act (RCRA).
HUD defines LBP as a surface coating containing lead in concentration greater than 1.00 (𝑚𝑔/𝑐𝑚2).
The presence of LBP on surfaces scheduled to be impacted during the renovation activities increases the potential for workers to be exposed to airborne lead in concentrations greater than the OSHA PEL of 50 micrograms per cubic meter (µg/m3), which is established in 29 CFR 1926.62. However, it is important to note that the presence of LCP’s (i.e. coatings which contain lead at concentrations less than the HUD criterion of 1.00 𝑚𝑔/𝑐𝑚2) may also present a potential exposure hazard for renovation workers.
Page 7 Contract AG-82FT-P-15-0058
Assessment Shed 7 of the RMRS –Missoula, Montana. Project No.: IH 15-101
As a result of the lead-based paint assessment conducted at the site, lead-based surface coatings (paints) were confirmed on the subject property as of the date of the assessment. The analytical results from this assessment effort identified the following lead-based paint (LBP) as defined by the EPA and/ or HUD standards
5.1 Introduction
A LBP assessment was conducted at Shed 7 of the RMRS for the client. The inspection was conducted by Mr. Christopher Casas, a certified Lead-Based Paint Inspector. The purpose for the inspection was to confirm or deny the presence of lead-based paint. As part of the inspection, a visual survey of the property and structure was conducted and all painted surfaces were inventoried.
The comprehensive LBP testing, conformed to HUD guide lines 24 CFR 35 section 35.930 (c), (d). LBP is defined by EPA regulations under Title X (Residential Lead-Based Paint Hazard Reduction Act of 1992) as containing lead concentrations above 1.0 mg/cm² when measured by a portable XRF instrument or 0.5% by weight (5,000 parts per million) when measured by laboratory analysis.
Since this project is non-HUD target housing, HUD Rules & regulations do not apply.
Explanations of regulations are detailed for workers that will be on the site as follows:
The Occupational Safety and Health Administration (OSHA) 29 CFR 1926.62 - Lead in Construction Standard does not define lead based coatings or materials but does establish safe airborne exposure limits for employees working with lead containing materials by permissible exposure limit (PEL). In summary; if any material or coating contains lead above 100 ppm then abatement, renovation, or demolition contractors must demonstrate worker health and safety due diligence.
This includes: lead awareness training for all affected employees, establishment of proper personal protective equipment (PPE), proper demarcation of effected work area(s), and performance of negative exposure assessment (NEA) lead air monitoring prior to downgrading any established PPE.
Relating to disposal of lead-containing waste, RCRA regulatory criteria for “total” lead in a waste stream is established in 40 CFR 261, Subpart C. The regulatory criteria are listed in milligrams per liter (mg/l) of dissolved lead in a solution (“wet basis”), as determined using the Toxicity Characteristic Leaching Procedure (TCLP) by EPA Method 1311.
5.2 Methods
ACM identified HAs of suspect LBP on interior and exterior surfaces for each of the site buildings, as described above, in general accordance with American Standards for Testing and Materials (ASTM) Method E 1729-05. ACM’s inspector distinguished HAs of suspect LBP visually and through field review of analytical data obtained using a Innov-X-Systems alpha-4000 XRF analyzer. As deemed appropriate by the inspector, multiple tests were taken within a given HA; in such instances, the highest observed concentration for tests representing a respective HA were reported.
The XRF utilizes an ionizing electrical source and internal calculations to provide direct-read lead data.
Analytical data obtained from a field-calibrated XRF are accepted as accurate by the EPA.
Page 8 Contract AG-82FT-P-15-0058
Assessment Shed 7 of the RMRS –Missoula, Montana. Project No.: IH 15-101
It should be noted that this instrument performs its own detector calibration upon startup, and it’s accuracy was checked against known standards set forth by the National Institute of Standards and Technology (NIST) prior to, during (at a four (4) hour interval), and following testing. The Performance Characteristic Sheet (PCS) is included in Appendix E.
5.3 Findings
ACM collected a total of Fourteen (14) XRF suspect lead coating assays & calibration readings for the lead based inspection of Shed 7. Any paint films with lead concentrations of 1.0 or greater were classified as Regulated Lead Containing Materials. In addition, the substrate condition was visually assessed at each assay test site. Additional paint or glaze coatings on the interior of the buildings were bulk sampled using destructive methods to verify the lead content in parts per million (ppm), summarized in Table 2. Results from ACM’s LBP assessment are summarized in the following sections for the site buildings.
ACM identified No HAs of suspect LBP, the HA was determined to be LBP as summarized below:
Table 2: Summary of LBP from XRF Analysis Shed 7
Component Location Material Description Quantity XRF Results
None Shed 7 N/A 0 0.00
% = Percentage < = Less Than Bold = LBP 0.5% by weight = HUD definition of lead-based paint
6.0 Mercury
A total of 4 suspected mercury-containing pieces of equipment were identified through visual observation associated with the site and were identified as being mercury-containing equipment during the assessment that include fluorescent light tubes, CFL’s, thermostats, thermometers in mechanical rooms, hallways, offices throughout the building.
Due to the age of the structure, a visual inspection for potential mercury-containing equipment such as mercury switches, thermostats and thermometers was conducted at the site. Mercury-containing equipment is listed in the universal waste regulated under the Resource Conservation and Recovery Act (RCRA) hazardous waste regulations. EPA’s universal waste regulations streamline hazardous waste management standards for designated “universal waste” which includes mercury-containing equipment to prevent the item from entering municipal trash; instead it can be collected and disposed of at a hazardous facility. The federal universal waste regulations are set forth in 40 CFR (273.9).
Page 9 Contract AG-82FT-P-15-0058
Assessment Shed 7 of the RMRS –Missoula, Montana. Project No.: IH 15-101 Mercury-containing equipment is a device or part of a device (including thermostats, temperature and pressure gauges. Universal waste regulations apply to mercury-containing equipment. Personal handling of this type of waste (i.e. disposed fluorescent light bulbs) must be trained regarding the proper handling and emergency response actions for the waste (mercury). It is recommended that the facility where the mercury-containing equipment is present participates in a management plan for the proper disposal and recycling of the hazardous waste. The hazardous waste must be containerized to protect it from damage and/or leakage, and the containers must be properly labeled to identify the type of universal waste (e.g. “Universal Waste – Mercury Thermostats” or ‘Waste-Mercury thermostat(s)’or “Used Mercury Thermostats”).
The transport of universal waste must include adequate packing materials to prevent breakage during storage, and handling in accordance with EPA and DOT regulations. Universal wastes may only be transported to other universal waste handlers, destinations facilities (e.g. disposal or recycling facilities).
Handling and transport of small quantities of universal waste do not need to be reported to the EPA;
however it is prudent to collect and document all receipts generated by the destination facilities.
ACM recommends the abatement design specification document be prepared to include requirements for removal, handling, and disposal of these materials. These tasks should be completed by the abatement contractor or other trained personnel.
7.0 Assumed PCBs
No suspected PCB-Containing Equipment was found or identified during the visual observation to be associated with Wing C and was not identified as being PCB-Containing Equipment during the assessment.
Current PCB regulations can be referenced in CFR 40 761. PCB-Containing equipment is currently listed under as a chemical substance under the Toxic substances Control Act (TSCA). The TSCA was established to control any substance determined to cause unreasonable risk to public health or the environment. PCB-Containing Fluorescent light ballasts identified in the assessment must be considered to be “PCB Bulk Product Waste”. During the visual assessment of the Ballasts within Shed 7, it was observed that all Ballasts are marked as non-PCB-containing.
8.0 Quality Control & Quality Assurance
ACM utilized a unique sample ID number to each bulk sample to help with elimination of microscopist’s potential bias. For example, if a numbering system indicates that seven samples are from the same room, a microposist may not be objective with each individual sample. Bulk samples obtained during the site inspection were identified and entered on sample summary sheets.
8.1 Chain-of-Custody Forms
In order to ensure that the samples are properly identified and tracked from the point of sample collection through receipt by the analytical laboratory, EPA requires that a chain-of-custody (COC) form be completed and accompany the samples. The COC contains essential items such as identification number, date, name of sampler and signature of recipient. Some laboratories request that COC forms they supply be used. These forms must be completed in the field and accompany the samples when
Page 10 Contract AG-82FT-P-15-0058
Assessment Shed 7 of the RMRS –Missoula, Montana. Project No.: IH 15-101 they leave possession of the inspector. Inspectors should fill in a new COC form if mistakes have been made (i.e. incorrect information transferred from sample containers to COC form).
8.2 Quality Control (QC) Samples
Collections of side-by-side duplicates are recommended at the rate of 1 QC sample/building or 1 QC sample/20 samples, whichever is larger. The laboratory should analyze duplicates without knowing which the QC samples are. The results of duplicates are compared to determine sampling analytical precision.
8.3 Accredited Laboratories
To diminish the likelihood of challenges to the accuracy of laboratory results ACM utilized an accredited laboratories for the analysis of bulk samples (per AHERA 40 CFR Part 763, Subpart E). A listing of accredited laboratories published by the EPA twice a year is available through the EPA regional Asbestos Coordinator or the TSCA hotline (202)-554-1404.
9.0 XRF
The XRF instrument was calibrated to the manufacturer’s standards prior to collecting field measurements and was checked periodically throughout the testing period against known NIST standards. All checks performed throughout the assessment were within 5% of one another. Overall, the precision, accuracy, method compliance, and completeness of the data set were determined to be acceptable based on the data submitted and reported. The XRF Performance Characteristic Sheet for the XRF used by ACM specifies the ranges where XRF results are positive, negative, or inconclusive. The Performance Characteristic Sheet for this instrument is attached in Appendix D.
10.0 Summary of Findings:
10.1 Asbestos
• Two (2) building materials suspected of containing asbestos were confirmed to not contain asbestos. If future renovation or demolition activities are planned these non-ACBM materials may remain in-place and be demolished with the reminder of the building.
• One (1) building materials suspected of containing asbestos were confirmed to contain greater than one percent (>1%) asbestos and are considered Asbestos Containing Building Materials.
These materials will require special abatement considerations prior to commencing renovation/selective demolition activates. Several options for asbestos abatement, in conjunction with demolition operations, may be considered for this project. The owner’s representative should work with the owner to develop a cost effective abatement/renovation/demolition plan, with considerations for the health and safety of the
Page 11 Contract AG-82FT-P-15-0058
Assessment Shed 7 of the RMRS –Missoula, Montana. Project No.: IH 15-101 abatement workers, the demolition personnel, and residents within the immediate vicinity of the demolition project.
• If abatement or renovation/selective demolition of the property is completed in accordance with current EPA and MDEQ-ACP guidelines, the services completed throughout the project will require asbestos qualified contractors and consultants to complete the work.
10.2 Lead Based Paint
• No Lead-Based Paint was Found within Shed 7
10.3 PCB-Containing Equipment
• No PCB-Containing Equipment was found within Shed 7
10.4 Mercury -Containing Equipment
• Confirmed mercury-containing equipment is listed per a room on the PCB and Mercury containing equipment drawing, and a complete summary of all identified PCBs are listed in Appendix G. Identified mercury-containing-equipment shall be disposed of at a hazardous facility, as stipulated in 40 CFR (273.9). The Mercury-Containing Equipment must be containerized to protect it from damage and/or leakage, and the containers must be properly labeled to identify the type of universal waste. The transport of Mercury-Containing Equipment must include adequate packing materials to prevent breakage during storage, and handling.
Handling and transport of small quantities of Mercury-Containing Equipment do not need to be reported to the EPA; however it is prudent to collect and document all receipts generated by the destination facilities.
Page 12 Contract AG-82FT-P-15-0058
11.0 Limitations
This asbestos and lead inspection summary was prepared based on information gathered during our site visits, phone conversations with the client and interpretations of laboratory results of bulk samples collected during the inspection. The inspection was comprehensive to the referenced building.
Supplemental inspection and sampling may be required if additional asbestos HAs are exposed during excavation, demolition, or if the scope of work is expanded to include additional buildings or buried/underground piping that have not been inspected or analyzed for asbestos or lead content.
If you have any questions regarding this report, please call me at 406.549.8489. We look forward to working with you in the future.
Sincerely, Christopher Casas Mike Foust Environmental Technician Project Manager
APPENDIX A
Sample Location Drawings
Bulk Sample Location of Suspect Asbestos Containing Material- SHED 7
Bulk Sample Location
WC.1 A
WC.1 B WC.1 C WTI.1 A WTI.1 BWT.1 C
APPENDIX B
ACBM, LBP & Mercury PCB Location Drawings
Asbestos Containing Material Location - SHED 7
Cement Asbestos Board
APPENDIX C
Documentation of Accreditation
APPENDIX D
XRF Performance characteristic sheet
APPENDIX E
XRF Data Summary Tables
Summary of XRF Field Data-Rocky Mountain Research Station - Shed 7
Missoula, MT
Shot Pass Fail Standard Date Pb Pb +/- Side Quadrant ComponentSubstrate Color Condition Notes Time
1 PASS 16-Dec-15 0.06 9:50:31
NIST STD Pass 16-Dec-15 1 0.01 NIST Standard - Red SRM 2573
NIST-
STND CAL 9:52:49
2 Negative 16-Dec-15 0.16 0.03 North Middle Pipes Metal Grey Intact
RMRS-
Shed 7 9:53:11
3 Negative 16-Dec-15 0.07 0.01 North Middle Pipes Metal Grey Intact
RMRS-
Shed 7 9:54:09
4 Negative 16-Dec-15 0.05 0.02 North Middle Pipes Metal Grey Intact
RMRS-
Shed 7 9:54:54
5 Negative 16-Dec-15 0 0.01 North Middle Wall Metal Green Intact
RMRS-
Shed 7 9:55:33
6 Negative 16-Dec-15 0 0.01 East Middle Wall Metal Green Intact
RMRS-
Shed 7 9:55:56
7 Negative 16-Dec-15 0 0 West Middle Wall Metal Green Intact
RMRS-
Shed 7 9:56:28
8 Negative 16-Dec-15 0 0.02 South Middle Wall Metal Green Intact
RMRS-
Shed 7 9:58:02
9 Negative 16-Dec-15 0 0 South Middle Door Metal Pink Intact
RMRS-
Shed 7 9:58:41
10 PASS 16-Dec-15 0.02 10:35:33
11 Negative 16-Dec-15 0 0.02 North Middle Wall Transite N/a Intact
RMRS-
Shed 7 10:55:16
12 Negative 16-Dec-15 0 0 North Middle WAll Transite N/a Intact
RMRS-
Shed 7 10:57:26
13 Negative 16-Dec-15 0 0.01 North Middle Wall Metal Green Intact
RMRS-
Shed 7 10:57:54
14 Negative 16-Dec-15 0.05 0 South Middle Wall Metal Green Intact
RMRS-
Shed 7 10:58:58
Indicates that the lead concentration of the HA is below the HUD definition of LBP (1.00 mg/cm^2). It is important to note that if this material is disturbed during the renovation process potential lead containnig dust may be created.
APPENDIX F
Analytical Reports
SanAir Technologies Laboratory
Analysis Report
Prepared for
Abatement Contractors of Montana, LLC
Report Date: 12/16/2015 Project Name: Rocky Mtn Station Project #: IH 15-101 SanAir ID#: 15039540
804.897.1177 www.sanair.com
SanAir Technologies Laboratory, Inc.
1551 Oakbridge Drive, Suite B, Powhatan, VA 23139
804.897.1177 Toll Free: 888.895.1177 Fax: 804.897.0070
Web: http://www.sanair.com E-mail: iaq@sanair.com
December 16, 2015
SanAir ID # 15039540 Project Name: Rocky Mtn Station
Project Number: IH 15-101
Dear Christopher Casas, We at SanAir would like to thank you for the work you recently submitted. The 4 sample(s) were received on Wednesday, December 16, 2015 via FedEx. The final report(s) is enclosed for the following sample(s): WTI.1A, WTI.1B, WTI.1C, WG.1
These results only pertain to this job and should not be used in the interpretation of any other job.
This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.
Sincerely, Sandra Sobrino Asbestos & Materials Laboratory Manager SanAir Technologies Laboratory
Final Report Includes:
- Cover Letter
- Analysis Pages
- Disclaimers and Additional Information sample conditions:
4 sample(s) in Good condition
Abatement Contractors of Montana, LLC
PO Box 8747
Missoula, MT 59807
SanAir Technologies Laboratory, Inc.
1551 Oakbridge Drive, Suite B, Powhatan, VA 23139
804.897.1177 Toll Free: 888.895.1177 Fax: 804.897.0070
Web: http://www.sanair.com E-mail: iaq@sanair.com
SanAir ID Number
15039540
FINAL REPORT
Name: Abatement Contractors of Montana, LLC Address: PO Box 8747
Missoula, MT 59807
Project Number:
P.O. Number:
Project Name:
IH 15-101
Rocky Mtn Station
Collected Date:
Received Date:
Report Date:
Analyst:
11/24/2015
12/16/2015 11:25:00 AM
12/16/2015 5:46:35 PM
Vaughan, Nathaniel
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components Asbestos
Certification
Analyst:
Analysis Date:
Approved Signatory:
Date: 12/16/2015 Page 2 of 3 12/16/2015
SanAir ID / Description Stereoscopic Appearance % Fibrous
Components % Non-Fibrous
Asbestos Fibers
WG.1 / 15039540-012
Window Glazing Shed 7
Grey
Non-Fibrous
Heterogeneous
100% Other None Detected
SanAir ID / Description
WTI.1A / 15039540-009
Water Tank Insulation. Shed
Stereoscopic Appearance
White
Non-Fibrous
Heterogeneou
% Fibrous Components
% Non-Fibrous
25% Cellulose
40% Glass
35% Other
Asbestos Fibers
None
SanAir ID / Description
WTI.1B / 15039540-010
Water Tank Insulation. Shed
Stereoscopic Appearance
White
Non-Fibrous
Heterogeneou
% Fibrous Components
% Non-Fibrous
25% Cellulose
40% Glass
35% Other
Asbestos Fibers
None
SanAir ID / Description
WTI.1C / 15039540-011
Water Tank Insulation. Shed
Stereoscopic Appearance
White
Non-Fibrous
Heterogeneou
% Fibrous Components
% Non-Fibrous
25% Cellulose
40% Glass
35% Other
Asbestos Fibers
None
APPENDIX G
PCB & Mercury Material List
PCB & MERCURY MATERIAL LIST
Client: USFS Research Station Building Name: Shed 7
Location
Shed 7
Quantity
Fluorescent
Light fixtures:
CFL’s
1x1 sq. light
Assumed PCB’s transformers
Mercury T-stats- Thermostats
Emergency lighting/exit
0 2 0 1 0 0
TOTAL 0 2 0 1 0 0
APPENDIX F
Photo Log of ACM, LBP & Mercury-PCB
Shed 7 asbestos & mercury pictures
Asbestos Identification
Cement asbestos board (transite) is located on the walls and ceiling
Small transformer on wall in shed 7
CFL lights contain mercury