USDA ARS Ft. Lauderdale AHUs - Final Turnover Drawings (Revised 04-29-21).pdf

PDF 20 MB Posted

Attached to
Fire alarm system upgrade Federal contract opportunity
Solicitation number
12405b23q0680
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery

About this file

This file contains final drawings related to upgrading the fire alarm system at a USDA Agricultural Research Service facility in Fort Lauderdale, Florida. The drawings are revised as of April 29, 2021 for the solicitation numbered 12405b23q0680 seeking offers to upgrade the fire alarm system. The Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery is the contracting agency. The opportunity type is a solicitation and the required products and services include upgrading the existing fire alarm system with revised drawings provided. A response is expected by interested contractors to perform the work by the specified due date.

View the file

Other files for this federal contract opportunity

Other files attached to Fire alarm system upgrade, newest first.
File Type Posted
Life Safety Plan - Bldg 17.pdf PDF
Bldg17 HVAC Drawings 2005 construction.pdf PDF
Serviceclauses.pdf PDF
Sol_12405B23Q0680FIRE.pdf PDF
15-4535scafl.txt TXT text file

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

G0.01

COVER SHEET

DRAWING NUMBER

DRAWING TITLE:

DRAWN BY:

GES PROJECT NO.:

DATE:

REGISTRATION:

REVISIONS:

PROJECT:

04/23/2021

F20-39

SUBMISSIONS:

UPGRADE AHU-1

& AHU-2

HOT/COLD DECK

MODULES

AGRICULTURAL RESEARCH SERVICES

PLAINS AREA

3225 College Avenue

Fort Lauderdale, FL 33314

USDA PROJECT NO.: AG-32SD-C-15-0044

ENGINEERING

PROGRAM MANAGEMENT

CONSTRUCTION MANAGEMENT

6700A ROCKLEDGE DRIVE SUITE 301

BETHESDA, MARYLAND 20817

T: 301.216.2871 (F) 301-216-9671 www.SalasObrien.com

AR EPM: VE

SOF

1. 95% CD SUBMISSION 10/30/20

2001742

KYLE J. CARTIER, P.E. 53269

GARY A. WILKERSON, P.E. 43167

JEFF A. KIRKMAN, P.E. 65629

ADAM S. LEVINE, P.E. 77010

expect a difference

SALAS O'BRIEN

3501 Quadrangle Boulevard, Suite 100

Orlando, Florida 32817

(407) 380-0400

CERT. OF AUTH. NO. 6106

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY KYLE J. CARTIER, PE ON DATE

INDICATED IN DIGITAL SIGNATURE USING A DIGITAL SIGNATURE.

PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE

SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.

2. FINAL TURNOVER 04/23/21

U.S. DEPARTMENT OF AGRICULTURE

AGRICULTURAL RESEARCH SERVICE PLAINS AREA

UPGRADE AHU-1 AND AHU-2

HOT/COLD DECK MODULES

FORT LAUDERDALE, FLORIDA

FINAL TURNOVER

APRIL 23, 2021

ENGINEERING

PROGRAM MANAGEMENT

CONSTRUCTION MANAGEMENT

6700A ROCKLEDGE DRIVE, SUITE 301

BETHESDA, MARYLAND 20817

(T) 301-216-2871 (F) 301-216-9671 www.SalasObrien.com

KEY PLANVICINITY MAP - FORT LAUDERDALE, FL

N

N

N

DRAWING INDEX

N

AutoCAD SHX Text

PROJECT SITE

AutoCAD SHX Text

PROJECT SITE

AutoCAD SHX Text

DWG

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

SHEET

AutoCAD SHX Text G0.01

AutoCAD SHX Text

COVER SHEET

AutoCAD SHX Text

AutoCAD SHX Text A1.1

AutoCAD SHX Text

MECHANICAL PENTHOUSE

AutoCAD SHX Text

AutoCAD SHX Text M0.1

AutoCAD SHX Text

SYMBOL LEGEND AND GENERAL NOTES - MECHANICAL

AutoCAD SHX Text

AutoCAD SHX Text M2.1

AutoCAD SHX Text

DEMO AND NEW FLOOR PLANS - MECHANICAL

AutoCAD SHX Text

AutoCAD SHX Text M2.2

AutoCAD SHX Text

PHASE 1- DEMO PENTHOUSE FLOOR PLAN - MECHANICAL

AutoCAD SHX Text

AutoCAD SHX Text M2.3

AutoCAD SHX Text

PHASE 2 - DEMO PENTHOUSE FLOOR PLAN - MECHANICAL

AutoCAD SHX Text

AutoCAD SHX Text M3.2

AutoCAD SHX Text

PHASE 1- NEW PENTHOUSE FLOOR PLAN - MECHANICAL

AutoCAD SHX Text

AutoCAD SHX Text M3.3

AutoCAD SHX Text

PHASE 2- NEW PENTHOUSE FLOOR PLAN - MECHANICAL

AutoCAD SHX Text

AutoCAD SHX Text M6.1

AutoCAD SHX Text

SCHEDULES - MECHANICAL

AutoCAD SHX Text

AutoCAD SHX Text M7.1

AutoCAD SHX Text

CONTROLS - MECHANICAL

AutoCAD SHX Text

AutoCAD SHX Text M7.2

AutoCAD SHX Text

CONTROLS - MECHANICAL

AutoCAD SHX Text

AutoCAD SHX Text M8.1

AutoCAD SHX Text

DETAILS - MECHANICAL

AutoCAD SHX Text

AutoCAD SHX Text M8.2

AutoCAD SHX Text

DETAILS - MECHANICAL

AutoCAD SHX Text

AutoCAD SHX Text E0.1

AutoCAD SHX Text

SYMBOL LEGEND AND GENERAL NOTES - ELECTRICAL

AutoCAD SHX Text

AutoCAD SHX Text E2.1

AutoCAD SHX Text

PHASE 1 - DEMOLITION PENTHOUSE FLOOR PLAN - ELECTRICAL

AutoCAD SHX Text

AutoCAD SHX Text E2.2

AutoCAD SHX Text

PHASE 2 - DEMOLITION PENTHOUSE FLOOR PLAN - ELECTRICAL

AutoCAD SHX Text

AutoCAD SHX Text E3.1

AutoCAD SHX Text

PHASE 1 - NEW FLOOR PLAN - ELECTRICAL

AutoCAD SHX Text

AutoCAD SHX Text E3.2

AutoCAD SHX Text

PHASE 1 - NEW PENTHOUSE FLOOR PLAN - ELECTRICAL

AutoCAD SHX Text

AutoCAD SHX Text E3.3

AutoCAD SHX Text

PHASE 2 - NEW PENTHOUSE FLOOR PLAN - ELECTRICAL

AutoCAD SHX Text

AutoCAD SHX Text E4.1

AutoCAD SHX Text

PHASE 1 - RISER DIAGRAM AND FEEDER SCHEDULE - ELECTRICAL

AutoCAD SHX Text

AutoCAD SHX Text E6.1

AutoCAD SHX Text

PHASE 1 - SCHEDULES - ELECTRICAL

AutoCAD SHX Text

AutoCAD SHX Text E6.2

AutoCAD SHX Text

PHASE 1 - SCHEDULES - ELECTRICAL

AutoCAD SHX Text

AutoCAD SHX Text E6.3

AutoCAD SHX Text

PHASE 2 - SCHEDULES - ELECTRICAL

AutoCAD SHX Text

AutoCAD SHX Text

AREA OF WORK

A1.1A1.1

TEST

CORES

ASSUMED ROOF COMPOSITION TO BE

INSULATED LIGHTWEIGHT CONCRETE ON

METAL DECK FOR R-14

MAIN ROOF

0"

PENTHOUSE ROOF

10' - 0"

A1.1 A1.1

A1.1 A1.1

2'

0" 5

A1.1A1.1

PHASE 2 - BASE BID IS TO BE 6"

OF MINERAL WOOL ATTACHED

TO UNDERSIDE OF ENTIRE

MECHANICAL PENTHOUSE

ROOF DECK. ADD ALTERNATE IS

TO PROVIDE PRICE TO ADD 1"

MINERAL WOOL BEYOND BASE

BID OF 6". DETAIL 1/A1.1 SIM.

PHASE 1: REMOVE EXISTING LOUVER. FILL IN HOLE WITH NEW CFMF

FRAMED WALL. NEW WALL TO BE FRAMED AS TO BE REMOVABLE

SHOULD LARGE PIECES OF EQUIPMENT NEED TO BE INSTALLED IN

MECHANICAL PENTHOUSE IN THE FUTURE.

PHASE 2: REMOVE 6'-0"x7'-4" INFILL WALL AND REPLACE

6'-0"x7'-4" NEW INFILL WALL.

SEE M-6.1 FOR NEW LOUVER.TO BE INSTALLED IN UPPER

PORTION OF EXISITNG OPENING. FOLLOW ALL

MANUFACTURER'S INSTALLATION AND NOA CRITERIA.PHASE 1: NEW INFILL WALL TO

BOTTOM OF NEW LOUVER

PHASE 2: NEW INFILL WALL TO

BOTTOM OF EXISTING LOUVER

8/ A1.1

PENTHOUSE ROOF

10' - 0"

ASSUMED ROOF COMPOSITION TO BE INSULATED LIGHT WEIGHT

CONCRETE R VALUE OF 14. REPORT SHOULD VERIFY THICKNESS AND

R-VALUE OF EXISTING ROOF INSULATION

PHASE 2 - VERIFY ROOF INSULATION THICKNESS AND TYPE MAKING TWO CORE HOLES

THROUGH MEMBRANE STOPPING AT THE METAL DECK AT THE HIGH AND LOW POINTS. AFTER

VERIFICATION, REINSTALL AND REPAIR MEMBRANE IN KEEPING WITH WARRANTY GUIDLINES.

(REF. 2/A1.1 FOR LOCATIONS.) ISSUE REPORT TO ARCHITECT. THE ARCHITECT WILL REVIEW TO

DETERMINE IF ADDITIONAL INSULATION IS REQUIRED. IF THE REPORT REVEALS LESS

INSULATION (I.E. R-VALUE), ADD MINERAL WOOL PER NOTES ON REFLECTED CEILING PLAN. R-38

IS THE OBJECTIVE. PROVIDE PRICING FOR 6" APPLICATION AND SEPARATE PRICING PER 1"

MOUNTED TO UNDERSIDE OF ROOF DECK ACROSS THE ENTIRE ROOM AFTER THE INITIAL 6".

PHASE 2 - REFER TO 6/A1.1 FOR BASE PIN

AND 7/A1.1 FOR MINERAL WOOL

SPECIFICATIONS. **

MAIN ROOF

0"

EXISITNG CMU WALL

EXISITING HEAD FLASHING

REUSE OR REPLACE

LIKE FOR LIKE.

NEW 12" TALL LOUVER. SEE

MECHANICAL SCHEDULE ON

M6.1

NEW 3" EIFS SYSTEM TO

MATCH

EXISTING ON NEW WALL

COVERING GAP LEFT

AFTER REMOVING LOUVER

WEATHER BARRIER

COMPATIBLE WITH

EXISTING.

3-5/8" COLD FORMED METAL

FRAMING TO MEET LOCAL

WIND LOAD CRITERIA

BY DELEGATED ENGINEER

PHASE 1: REMOVE EXISTING

LOUVER.

FILL IN HOLE WITH NEW

CFMF FRAMED WALL. NEW WALL

TO BE FRAMED AS TO BE

REMOVABLE.

PHASE 2:

AFTER INSTALLATION OF AHU2,

INFILL WALL IN SAME MANNER

AS PHASE 1 INFILL.

BACKER ROD AND

SEALANT

ALL SIDES OF INFILL

WALL PANEL.

INSIDE AND OUTSIDE

TOP, BOTTOM ,

LEFT AND RIGHT

PROTECT EXISTING

S/S FLASHING FOR

REUSE WITH INFILL

WALL

EXISTING ROOF

MEMBRANE

PROTECT FROM

DAMAGE

WHILE DOING NEW

WORK.

EXISTING EIFS SYSTEM

BEYOND. MATCH IN ALL

WAYS, THICKNESS, TEXTURE

COLOR AND PATTERN

RECESS NEW INFILL WALL

2" MINIMUM TO FACILITATE

REMOVAL AND

REPLACEMENT

IN THE FUTURE

EXTERIOR SHEATHING

BOTH SIDES WITH

LIQUID

APPLIED WEATHER

BARRIER

ON THE EXTERIOR

FACE.

3/4" EXTERIOR

GRADE PLYWOOD

ON INSIDE FACE

PAINTED TO

MATCH INTERIOR

COLOR OF

MECHANICAL

PENTHOUSE

3/4" EXTERIOR GRADE

PLYWOOD

ON INSIDE FACE

PAINTED TO

MATCH INTERIOR

COLOR OF

MECHANICAL

PENTHOUSE

EXTERIOR SHEATHING

BOTH SIDES WITH

LIQUID

APPLIED WEATHER

BARRIER

ON THE EXTERIOR

FACE.

BACKER ROD AND

SEALANT

ALL SIDES OF NEW

LOUVER

INSIDE AND OUTSIDE

TOP, BOTTOM ,

LEFT AND RIGHT

NEW SILL FLASHING

UNDER NEW LOUVER

BUG SCREEN

ATTACH DUCT TO INSIDE

EDGE

SET IN SEALANT

NEW C8X11.5 HEADER

3/4" X 5 1/2" EMBED TITEN

HD SCREW ANCHOR BY SIMPSON

STRONG TIE CENTERED IN EACH CELL

MAIN ROOF

0"

A1.1A1.1

PHASE 1 NOTES:

1. PRIOR TO CUTTING

EXISTING CMU WALL TO

ENLARGE OPENING:

2. NEW GROUT SHALL

BE FULLY INSTALLED AND

REACH DESIGN STRENGTH

3. NEW STEEL LINTEL

AND ALL ANCHORS SHALL BE

FULLY INSTALLED

PHASE 2 NOTES:

REMOVE 6'-0"x7'-4" INFILL WALL AND REPLACE 6'-0"x7'-4"

NEW INFILL

EXISTING GROUTED CELL AT JAMB

OPENING. VERIFY IN FIELD

INFILL EXISTING OPENING

NEW 88" X 12 LOUVER

EXISTING GROUTED HEADER

OVER OPENING

FIELD VERIFY

3/4"DIA X 5 1/2" EMBED TITEN HD

SCREW

ANCHORS BY SIMPSON STRONG TIE

CENTERED

IN EACH CELL

NEW GROUT IN TWO FULL

EXISTING CELLS AT JAMB

OPENING. PROVIDE GROUT

FROM TOP OF FLOOR TO

UNDERSIDE OF EXISTING

BOND BEAM(f'c=3000psi MIN)

7' - 4"

NEW C8X11.5 HEADER

E X

IS

T

IN

G

O P

E N

IN

G

6'

EXISTING OPENING

6' - 0"

16" MAX WIDENED OPENING

PROJECT:

UPGRADE AHU-1 &

AHU-2

HOT/COLD DECK

MODULES

AGRICULTURAL RESEARCH SERVICES

PLAINS AREA

3225 College Avenue

Fort Lauderdale, FL 33314

ENGINEERING

PROGRAM MANAGEMENT

CONSTRUCTION MANAGEMENT

6700A ROCKLEDGE DRIVE SUITE 301

BETHESDA, MARYLAND 20817

T: 301.216.2871 F:301-216-9671 www.SalasObrien.com

DRAWING NUMBER

DRAWING TITLE:

DRAWN BY:

GES PROJECT NO.:

DATE:

REGISTRATION:

REVISIONS:

04/23/2021

F20-39

SUBMISSIONS:

USDA PROJECT NO.: AG-32SD-C-15-0044

AR EPM: VE

1. 95% CD SUBMISSION 10/30/20

2. FINAL TURNOVER 04/23/21

LE/RR

A1.1

MECHANICAL

PENTHOUSE

111 N. MAGNOLIA AVENUE SUITE 1600 ORLANDO, FL 32801 T: 407.839.0414

1/8" = 1'-0"

PENTHOUSE ROOF

1/8" = 1'-0"

BUILDING SECTION - PENTHOUSE

1/8" = 1'-0"

REFLECTED CEILING PLAN - MAIN ROOF LEVEL

NTS

SPECIFICATION - MINERAL WOOL

1 1/2" = 1'-0"

ROOF DETAIL

NTS

SPECIFICATION - BASE PINS

1 1/2" = 1'-0"

INFILL DETAIL

**NOTE:

EXISTING ROOF APPEARS TO BE APPROXIMATELY R-14 AS INSTALLED.

VERIFY THICKNESS AND TYPE OF EXISTING INSULATION PER DETAIL 3/A1.1 PROVIDE REPORT TO

ARCHITECT FOR EVALUATION. REPORT SHOULD INCLUDE R-VALUE, THICKNESS, AND TYPE OF

INSULATION EXISTING ON ROOF .

BASE BID IS TO BE 6" OF MINERAL WOOL ATTACHED TO UNDERSIDE OF ENTIRE MECHANICAL

PENTHOUSE ROOF DECK. ADD ALTERNATE IS TO PROVIDE PRICE TO ADD 1" MINERAL WOOL BEYOND

BASE BID OF 6". DETAIL 1/A1.1 SIM.

SPRINKLER HEADS WILL NEED TO BE LOWERED BY THE SAME DISTANCE TO MAINTAIN THE REQUIRED

CLEARANCE FROM SPRINKLER HEAD TO SURFACE ABOVE.

PER 2020 FBC, ENERGY CODE TABLE C402.1.3, ROOF R-VALUE = R-35.

1/2" = 1'-0"

INTERIOR ELEVATION - NEW LOUVER

PHASING SUMMARY:

Phase 1 will replace AHU 1 and include all associated work. The wall opening that allows removal and replacement of large equipment work will also be completed in this phase.

Phase 2 will replace AHU-2 (and all associated work) and will include the air conditioning and insulation of the penthouse.

1. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND

OPERABLE HEATING, VENTILATION, AND AIR CONDITIONING (HVAC) SYSTEMS.

2. REFER TO TYPICAL DETAILS FOR ADDITIONAL INFORMATION REGARDING THE INSTALLATION OF DUCTWORK, PIPING, AND EQUIPMENT.

3. THE CONTRACTOR IS EXPECTED TO ORDER MATERIALS IN SUFFICIENT TIME TO AVOID DELAYING THE

COMPLETION OF THE PROJECT. DELAY IN DELIVERIES WILL NOT BE CONSIDERED A JUSTIFIABLE REASON FOR

SUBSTITUTION OF MATERIALS.

4. THE CONTRACTOR SHALL COMPLY WITH THE 2017 FLORIDA BUILDING CODE AND ALL OTHER APPLICABLE CODES

AND STANDARDS.

5. ALL REQUESTS FOR INFORMATION (RFI'S) SUBMITTED BY THE CONTRACTOR SHALL INCLUDE A PROPOSED

SOLUTION.

6. INSTALLATION OF EQUIPMENT SHALL COMPLY WITH EQUIPMENT MANUFACTURER'S INSTALLATION AND

CLEARANCE REQUIREMENTS. THE CONTRACTOR SHALL VERIFY INSTALLATION CLEARANCES WILL BE MAINTAINED

AND DISCREPANCIES SHALL BE REPORTED TO THE ENGINEER PRIOR TO THE ACQUISITION OF EQUIPMENT.

7. THE GENERAL CONTRACTOR SHALL COORDINATE THE WORK OF THE DIFFERENT TRADES SO THAT

INTERFERENCE BETWEEN HVAC, PIPING, EQUIPMENT, STRUCTURAL, AND ELECTRICAL WORK WILL BE AVOIDED.

ALL NECESSARY OFFSETS IN DUCTWORK, PIPING, AND FITTINGS REQUIRED TO INSTALL THE WORK PROPERLY

SHALL BE PROVIDED COMPLETE IN PLACE AT NO ADDITIONAL COST TO THE OWNER.

8. THE CONTRACTOR IS RESPONSIBLE TO REPAIR, AT HIS COST, ANY DAMAGED ITEMS DUE TO WORK PERFORMED.

DAMAGED ITEMS SHALL BE BROUGHT BACK TO LIKE-NEW CONDITION OR REPLACED WITH ORIGINAL.

9. DUCTWORK, PIPING, AND EQUIPMENT LOCATIONS SHOWN ARE SCHEMATIC. PRIOR TO EXCAVATION, LAYOUT AND

CONSTRUCTION OF THE MECHANICAL SYSTEMS, THE CONTRACTOR SHALL SUBMIT LAYOUT AND FABRICATION

SHOP DRAWINGS FOR APPROVAL. CONTRACTOR SHALL NOT COMMENCE WORK WITHOUT APPROVED SHOP

DRAWINGS ON THE CONSTRUCTION SITE.

10. INSULATE ALL SURFACES SUBJECT TO CONDENSATION.

11. REFER TO ARCHITECTURAL AND/OR STRUCTURAL SHEETS FOR LOUVER MOUNTING HEIGHTS.

12. ALL DUCTWORK DIMENSIONS SHOWN ON THE DRAWINGS ARE THE INTERNAL CLEAR DIMENSIONS.

13. INSIDE AREAS OF DUCTWORK VISIBLE THROUGH DIFFUSERS, REGISTERS, GRILLES, AND LOUVERS SHALL BE

PAINTED FLAT BLACK.

14. INSULATE ALL LOUVER PLENUMS AND BLANK-OFFS TO PREVENT CONDENSATION.

15. ALL NEW DUCTWORK SHALL BE GALVANIZED STEEL, EXTERNALLY INSULATED WITH 3.0 INCH THICK, 3/4 POUND

DENSITY FIBERGLASS DUCTWRAP WITH VAPOR BARRIER. INSTALLED R VALUE SHALL BE A MINIMUM OF 8.0. SEAL

ALL JOINTS AND SEAMS WITH GLASS FABRIC AND MASTIC MEETING UL 181.

16. PROVIDE COLD GALVANIZED PAINT ON ALL FIELD CUTS/WELDS OF GALVANIZED STEEL SUPPORTS AND THREADED

RODS.

17. ROUTE CONDENSATE TO FLOOR DRAIN AND TERMINATE INDIRECTLY.

18. THE REFRIGERANT PIPING SIZING AND ROUTING DESIGN SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.

THE CONTRACTOR SHALL TAKE INTO ACCOUNT LENGTH OF RUN, ELEVATION CHANGES, AND FIELD CONDITIONS.

PROVIDE ALL ACCESSORIES REQUIRED FOR "LONG-LINE" APPLICATIONS. CONTRACTOR SHALL SUBMIT

CALCULATIONS IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE MANUFACTURER.

19. THE BUILDING HAS A FIRE ALARM SYSTEM. PROVIDE A DUCT-MOUNTED SMOKE DETECTOR IN THE SUPPLY OF THE

AIR HANDLING UNIT. THE UNIT SHALL SHUT DOWN UPON ACTIVATION OF THE DEVICE. THE DUCT SMOKE

DETECTORS SHALL BE INSTALLED BY THE MECHANICAL CONTRACTOR. THE DUCT SMOKE DETECTORS SHALL BE

PROVIDED, WIRED, AND INTERFACED WITH THE FIRE ALARM SYSTEM BY THE ELECTRICAL CONTRACTOR.

20. ALL TEMPERATURE SENSORS/CONTROLS SHALL BE LOCATED TO ALLOW THE PARALLEL APPROACH BY A PERSON

IN A WHEELCHAIR AND MOUNTED 54" AFF. WHERE ONLY FORWARD APPROACH IS POSSIBLE, SENSORS/CONTROLS

SHALL BE MOUNTED 48" AFF.

21. THE CONTRACTOR SHALL PERFORM A COMPLETE CERTIFIED TEST AND BALANCE OF EACH MECHANICAL SYSTEM

IN ACCORDANCE WITH A NATIONAL STANDARD. SEE SPECIFICATIONS FOR DETAILS AND PROVIDE THREE (3)

WRITTEN COPIES OF THE COMPLETED TEST AND BALANCE REPORT TO THE OWNER AND ENGINEER FOR REVIEW

AND APPROVAL.

GENERAL NOTES

1. THIS PROJECT OCCURS IN AN EXISTING FACILITY THAT SHALL REMAIN IN OPERATION DURING CONSTRUCTION.

COORDINATION OF ALL WORK WITH THE OWNER SHALL BE REQUIRED. SCOPE OF WORK SHALL BE PERFORMED IN

PHASES. OUTAGES OF SHORT DURATION WILL BE ALLOWED AT THE SOLE DIRECTION OF THE OWNER.

2. THE CONTRACTOR SHALL VISIT THE SITE TO FAMILIARIZE HIMSELF WITH ALL EXISTING CONDITIONS.

3. THE WORK SHALL BE DONE COMPLETED IN TWO (2) PHASES. CONTRACTOR SHALL PROVIDE A SCHEDULE

INDICATING THE START DATE AND DURATION OF EACH PHASE OF CONSTRUCTION. THE SCHEDULE SHALL BE

REVIEWED BY THE OWNER AND DIRECTION GIVEN ON EACH UNIT REPLACEMENT.

4. IN GENERAL, THE MECHANICAL SCOPE OF PHASE 1 IS AS FOLLOWS:

a. EXISTING PENTHOUSE VENTILATION LOUVERS ARE TO BE REMOVED TO FACILITATE INSTALLATION OF

EQUIPMENT.

b. MULTI-ZONE AIR HANDLING UNIT AHU-1 SHALL BE REMOVED AND REPLACED WITH A UNIT OF EQUIVALENT OR

GREATER PERFORMANCE. INCLUDES MODIFICATIONS TO EQUIPMENT HOUSEKEEPING PAD, CHILLED WATER

CONNECTIONS, AND DUCTWORK CONNECTIONS.

c. PENTHOUSE DUCTWORK ASSOCIATED WITH AHU-1 SHALL BE DEMOLISHED AND REPLACED WITH NEW.

d. DUCT HEATERS DH 1-1, 1-2, 1-3, 1-4, 1-5 AND DUCT HUMIDIFIERS HUM 1-1, 1-2, 1-3, AND 1-4 INSTALLED IN ZONE

SUPPLY DUCTWORK WITHIN PENTHOUSE.

e. EXISTING OUTSIDE AIR INTAKE DUCTWORK DEMOLISHED AND NEW DUCTWORK CONNECTED TO AHU-1 AND

EXISTING OUTSIDE AIR INTAKE ROOF CAP.

f. NEW PRESSURIZATION CONTROL DUCTWORK AND FAN PRF 1-1 PROVIDED AND CONNECTED TO EXISTING

DISCHARGE LOUVER.

g. UPDATE CONTROLS AND SEQUENCES FOR THE INTEGRATION OF REPLACEMENT EQUIPMENT.

5. IN GENERAL, THE MECHANICAL SCOPE OF PHASE 1 IS AS FOLLOWS:

a. EXISTING PENTHOUSE VENTILATION LOUVERS ARE TO BE REMOVED TO FACILITATE INSTALLATION OF

EQUIPMENT.

b. MULTI-ZONE AIR HANDLING UNIT AHU-1 SHALL BE REMOVED AND REPLACED WITH A UNIT OF EQUIVALENT OR

GREATER PERFORMANCE. INCLUDES MODIFICATIONS TO EQUIPMENT HOUSEKEEPING PAD, CHILLED WATER

CONNECTIONS, AND DUCTWORK CONNECTIONS.

c. PENTHOUSE DUCTWORK ASSOCIATED WITH AHU-1 SHALL BE DEMOLISHED AND REPLACED WITH NEW.

d. DUCT HEATERS DH 1-1, 1-2, 1-3, 1-4, 1-5 AND DUCT HUMIDIFIERS HUM 1-1, 1-2, 1-3, AND 1-4 INSTALLED IN ZONE

SUPPLY DUCTWORK WITHIN PENTHOUSE.

e. EXISTING OUTSIDE AIR INTAKE DUCTWORK DEMOLISHED AND NEW DUCTWORK CONNECTED TO AHU-1 AND

EXISTING OUTSIDE AIR INTAKE ROOF CAP.

f. NEW PRESSURIZATION CONTROL DUCTWORK AND FAN PRF 1-1 CONNECTED TO EXISTING LOUVER.

g. UPDATE CONTROLS AND SEQUENCES FOR THE INTEGRATION OF REPLACEMENT EQUIPMENT.

6. THE FIELD PERSONNEL AT THE SITE WILL NEED SUFFICIENT TIME TO RELOCATE EXPERIMENTS AND TRANSITION

TO OTHER AREAS OF THE BUILDING PRIOR TO EACH AIR HANDING UNIT REPLACEMENT. IT WILL NOT BE POSSIBLE

FOR THE UNITS TO BE REPLACED AT THE SAME TIME AND THERE COULD BE A SIGNIFICANT TIME GAP BETWEEN

WHEN THE REPLACEMENT OF ONE UNIT IS COMPLETED AND THE SECOND UNIT REPLACEMENT BEGINS.

7. AREAS SERVED BY THE HVAC SYSTEMS MODIFIED IN THIS PROJECT INCLUDE SPACES RATED AS BIOHAZARD

SAFETY LEVELS 2 AND 3 (BSL-2 AND BSL-3). FIELD PERSONNEL MUST COORDINATE ANY ENTRY INTO THE

BSL-RATED SPACES WITH THE OWNER AND FOLLOW ALL SAFETY PROTOCOLS AS DIRECTED BY THE OWNER. ANY

PENETRATIONS IN AND OUT OF THE BSL-RATED SPACES MUST BE PROPERLY SEALED BY THE CONTRACTOR AND

THE FIELD PERSONNEL HAVE INDICATED THEY NEED TO BE PRESENT WHEN ANY OF THIS TYPE OF WORK IS BEING

PERFORMED IN ORDER TO APPROVE THE INSTALLATION/SEALING.

GENERAL PHASING NOTES

NOTES

1. THIS IS A GENERAL COMPILATION OF SYMBOLS AND NOT ALL SYMBOLS SHOWN MAY BE USED ON THE CONTRACT DRAWINGS.

2. SCREENED SYMBOLS OR TEXT (EXAMPLE: AHU) INDICATE EXISTING EQUIPMENT OR CONDITIONS.

3. SCREENED AND DASHED AND LINES INDICATE LINES HIDDEN IN VIEW.

DUCT SMOKE DETECTOR

THERMOSTAT

TEMPERATURE SENSOR

PIPING

MECHANICAL LEGEND

DESCRIPTION

GENERAL

SYMBOL DESCRIPTIONSYMBOL

EQUIPMENT NUMBER

SECTION NUMBER

TYPE OF EQUIPMENT

DETAIL NUMBER

REFERENCE NOTE

AIR FLOW AMOUNT (CFM)

UNDER CUT DOOR

AIR DEVICE TAG

SHEET SECTION APPEARS

SHEET DETAIL APPEARS

X

X

X

X-X

X

X-X

UC

POINT OF DISCONNECTION

POINT OF CONNECTION

HVAC

DESCRIPTIONSYMBOL

BELL MOUTH TAP W/MVD

SQUARE TO ROUND DUCT TRANSITION

DUCT RISE OR DROP IN DIRECTION OF FLOW

RETURN INLET (SEE AIR DEVICE SCHEDULE)

EXHAUST INLET (SEE AIR DEVICE SCHEDULE)

SUPPLY OUTLET (SEE AIR DEVICE SCHEDULE)

MVD HAS REMOTE CONTROL IN RIGID CEILING

SUPPLY DUCT DOWN

EXHAUST DUCT DOWN

RETURN DUCT DOWN

DUCT CONTINUES

FIRE DAMPER (HORIZONTAL)

DUCT ACCESS DOOR - TOP

MANUAL VOLUME DAMPER

SUPPLY DUCT RISER

RETURN DUCT RISER

EXHAUST DUCT RISER

FLEXIBLE DUCT

SINGLE LINE DUCTWORK

TERMINAL UNIT

MOTORIZED DAMPER

CROSS HATCHED AREA = MINIMUM CLEARANCE

FOR HEATER ACCESS. MAINTAIN CLEARANCE.

FIRE DAMPER (VERTICAL)

BACKDRAFT DAMPER

BDD

MVD

FD

FD

LINEAR DIFFUSER

ELBOW W/TURNING VANES

HUMIDISTAT

REFRIGERANT SENSOR

CARBON DIOXIDE SENSOR

CARBON MONOXIDE SENSOR

NITROGEN OXIDE SENSOR

SMOKE DAMPER (HORIZONTAL)SD

SD SMOKE DAMPER (VERTICAL)

COMBINATION FIRE/SMOKE DAMPER (HORIZONTAL)F/SD

F/SD COMBINATION FIRE/SMOKE DAMPER (VERTICAL)

ROTATING BEACON LIGHT

PIPE CONTINUATION

PIPE ELBOW DOWN

PIPE ELBOW UP

BLIND FLANGE

CAPPED LINE

HOSE END CONNECTION

DIRECTION OF FLOW IN PIPE

PIPE TEE DOWN

PIPE TEE UP

UNION

BALL VALVE

BUTTERFLY VALVE (MANUAL)

BUTTERFLY VALVE (MOTORIZED)

GATE VALVE

GLOBE VALVE

TRIPLE DUTY VALVE

PLUG VALVE

2-WAY DDC CONTROL VALVE

3-WAY DDC CONTROL VALVE

BALANCING VALVE WITH PRESSURE TAPS

PRESSURE REDUCING VALVE

PRESSURE RELIEF VALVE

FLOW BALANCING VALVE

MANUAL AIR RELIEF VENT

AUTOMATIC AIR RELIEF VENT

FLEXIBLE CONNECTION

CHECK VALVE

Y-STRAINER

PRESSURE/TEMPERATURE TEST PORT

PRESSURE GAUGE

THERMOMETER

PUMP

BASKET STRAINER W/ CLAMPED COVER

SUCTION DIFFUSER

DUCT-MOUNTED SMOKE DETECTOR

DUCT ACCESS DOOR - BOTTOM

DUCT ACCESS DOOR - SIDE

24x12

24x12Ø

24Ø ROUND DUCT, DIAMETER SHOWN (IN INCHES)

RECTANGULAR DUCT, FIRST FIGURE IS

DIMENSION OF SIDE SHOWN (IN INCHES)

FLAT OVAL DUCT, FIRST FIGURE IS

DIMENSION OF SIDE SHOWN (IN INCHES)

SMOKE DETECTOR A/V ANNUNCIATOR

OS&Y GATE VALVE

BALANCING VALVE

FLOW METER

CS-A

100 CFM

MARK - TYPE OR (INxIN)

AIRFLOW (CFM)

1 D1

OR

SS/12X6

100 CFM

OR

CO

AN

CO

NO

H

SD

R

T

TS

SD

M

M

M

M

S

SOLENOID CONTROL VALVE

HVAC DESIGN DATA

LOCATION

0.75

21.0

15.8

SUMMER WINTER

FORT LAUDERDALE, FLORIDA

OUTDOOR AIR

DESIGN

CONDITIONS

91 4778

DB

(DEG F)

WB

(DEG F)

DB

(DEG F)

SUMMER WINTERINDOOR AIR

DESIGN

CONDITIONS

(TYPICAL/MAX)

70/95 75/9550%/90%

DB

(DEG F)

RELATIVE

HUMIDITY

DB

(DEG F)

ALL UNITS

WALL R-VALUE

ROOF R-VALUE

WINDOW S.C. 0.40

BUILDING CONSTRUCTION

WINDOW U-FACTOR

NOTES

THIS IS AN EXISTING BUILDING AND THE VALUES LISTED ARE ESTIMATES

BASED ON THE EXISTING CONSTRUCTION AND HAVE NOT BEEN FIELD

VERIFIED.

SOME OF THE CONDITIONED ENVIRONMENTS OF THIS BUILDING ARE

INSECTORIES CONTROLLED TO HIGH TEMPERATURE AND/OR HIGH

HUMIDITY CONDITIONS FOR THE PURPOSES OF SIMULATING OUTDOOR

ENVIRONMENTS. TYPICAL VALUES ARE DESCRIPTIVE OF HUMAN

OCCUPANCY SPACES AND MAXIMUM VALUES ARE REPRESENTATIVE OF

THE HIGHEST LIMIT OF SPACE DESIGN CONDITIONS.

ABBREVIATIONS

ci = CONTINUOUS INSULATION

LS = LINEAR SYSTEM

CLIMATE ZONE 1A

EXISTING AIR DEVICE TAGX

M0.1

SYMBOL LEGEND

AND GENERAL

NOTES -

MECHANICAL

DRAWING NUMBER

DRAWING TITLE:

DRAWN BY:

GES PROJECT NO.:

DATE:

REGISTRATION:

REVISIONS:

PROJECT:

04/23/2021

F20-39

SUBMISSIONS:

UPGRADE AHU-1

& AHU-2

HOT/COLD DECK

MODULES

AGRICULTURAL RESEARCH SERVICES

PLAINS AREA

3225 College Avenue

Fort Lauderdale, FL 33314

USDA PROJECT NO.: AG-32SD-C-15-0044

ENGINEERING

PROGRAM MANAGEMENT

CONSTRUCTION MANAGEMENT

6700A ROCKLEDGE DRIVE SUITE 301

BETHESDA, MARYLAND 20817

T: 301.216.2871 (F) 301-216-9671 www.SalasObrien.com

AR EPM: VE

SOF

1. 95% CD SUBMISSION 10/30/20

2001742

KYLE J. CARTIER, P.E. 53269

GARY A. WILKERSON, P.E. 43167

JEFF A. KIRKMAN, P.E. 65629

ADAM S. LEVINE, P.E. 77010

expect a difference

SALAS O'BRIEN

3501 Quadrangle Boulevard, Suite 100

Orlando, Florida 32817

(407) 380-0400

CERT. OF AUTH. NO. 6106

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY KYLE J. CARTIER, PE ON DATE

INDICATED IN DIGITAL SIGNATURE USING A DIGITAL SIGNATURE.

PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE

SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.

2. FINAL TURNOVER 04/23/21

AutoCAD SHX Text

DROP

AutoCAD SHX Text

RISE

M2.1

DEMOLITION AND NEW FLOOR PLAN - MECHANICAL

1/8"=1'-0"

FF

FF

FF

FF

FF

EF

TU

TU

TU

TT

T

T

T

TU

X

130 CFM

X

110 CFM

X

50 CFM

X

260 CFM

X

345 CFM

X

345 CFM

X

320 CFM

6" CHR

6" CHS

X

100 CFM

X

40 CFM

X

520 CFM

X

100 CFM

X

100 CFM

X

190 CFM

EF

X

110 CFM

X

100 CFM

X

50 CFM

X

650 CFM

X

700 CFM

(TYP 6)

X

485 CFM

(TYP 6)

X

485 CFM

(TYP 6)

X

485 CFM

(TYP 6)

X

570 CFM

(TYP 6)

X

420 CFM

X

420 CFM

X

420 CFM

X

260 CFM

X

510 CFM

X

90 CFM

X

150 CFM

X

390 CFM

X

250 CFM

X

230 CFM

X

100 CFM

X

160 CFM

X

300 CFM

X

400 CFM

X

120 CFM

X

150 CFM

X

90 CFM

X

60 CFM

X

60 CFM

X

50 CFM

X

400 CFM

X

400 CFM

X

400 CFM

X

400 CFM

FF

FF

T

H

T

H

T

H

T

H

T H

T

T

2 2 2 2 2

X

X

X700 CFM

X

2960 CFM

X

2960 CFM

X

2960 CFM

X

3470 CFM

X

260 CFM

X

50 CFM

X

50 CFM

MQ5 Q13 Q12 Q11 Q10

Q15

Q16

Q7

Q5

Q14

Q4

Q3

Q6

Q2

Q1

Q8

MQ3

MQ9

MQ4

MQ1

MQ6

MQ8

MQ7

MQ2

PHASE 2

PHASE 1

GENERAL NOTES

1. WORK OCCURRING IN EITHER PHASE 1 OR PHASE 2 IS INDICATED

ON THE PLAN AND THE AREA IN WHICH EACH PHASE OF WORK

OCCURS IS DEMARCATED.

2. BALANCE AIR DEVICES SERVED BY NEW AIR HANDLING UNIT

SYSTEMS TO AIRFLOW VALUES INDICATED.

3. DUCT SYSTEMS SHOWN ON THIS PLAN ARE NOT TO BE MODIFIED

AS PART OF THIS PROJECT EXCEPT FOR THE POSITIONING OF AIR

BALANCING DEVICES TO ACHIEVE AIRFLOW VALUES AS INDICATED.

4. COORDINATE INSTALLATION OF NEW CONTROL CONDUIT WITH

BUILDING MANAGEMENT AND SEAL ALL PENETRATIONS TO MEET

OWNER REQUIREMENTS IN ORDER TO MAINTAIN EXISTING

BIOHAZARD SAFETY LEVEL ENVELOPE SEALING REQUIREMENTS.

REFERENCE NOTES

DEMOLISH EXISTING THERMOSTAT. PROVIDE NEW ZONE

TEMPERATURE SENSOR AND RELATIVE HUMIDITY SENSOR IN

APPROXIMATELY THE SAME LOCATION.

EXISTING TO REMAIN RETURN AIR FILTER RACK.

EXISTING TO REMAIN AND BE RE-USED WI-FI ENABLED REMOTE

TEMPERATURE AND HUMIDITY SENSOR. SENSOR IS MOBILE AND

FREE TO BE LOCATED THROUGHOUT SPACE AS REQUIRED BY

USER.

M2.1

DEMO AND NEW

FLOOR PLANS -

MECHANICAL

DRAWING NUMBER

DRAWING TITLE:

DRAWN BY:

GES PROJECT NO.:

DATE:

REGISTRATION:

REVISIONS:

PROJECT:

04/23/2021

F20-39

SUBMISSIONS:

UPGRADE AHU-1

& AHU-2

HOT/COLD DECK

MODULES

AGRICULTURAL RESEARCH SERVICES

PLAINS AREA

3225 College Avenue

Fort Lauderdale, FL 33314

USDA PROJECT NO.: AG-32SD-C-15-0044

ENGINEERING

PROGRAM MANAGEMENT

CONSTRUCTION MANAGEMENT

6700A ROCKLEDGE DRIVE SUITE 301

BETHESDA, MARYLAND 20817

T: 301.216.2871 (F) 301-216-9671 www.SalasObrien.com

AR EPM: VE

SOF

1. 95% CD SUBMISSION 10/30/20

2001742

KYLE J. CARTIER, P.E. 53269

GARY A. WILKERSON, P.E. 43167

JEFF A. KIRKMAN, P.E. 65629

ADAM S. LEVINE, P.E. 77010

expect a difference

SALAS O'BRIEN

3501 Quadrangle Boulevard, Suite 100

Orlando, Florida 32817

(407) 380-0400

CERT. OF AUTH. NO. 6106

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY KYLE J. CARTIER, PE ON DATE

INDICATED IN DIGITAL SIGNATURE USING A DIGITAL SIGNATURE.

PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE

SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES.

2. FINAL TURNOVER 04/23/21

M2.2

PHASE 1 - DEMO PENTHOUSE FLOOR PLAN - MECHANICAL

1/4"=1'-0"

FROM

FF-2

AH

AH

DN

DN

DN

DN

DN

DN

EF

FF

FF

x x

Ø

26x18

38x22

Ø

Ø

30x36

44x36

22x22 x x

58x36

DN

MVD

MVD

MVD

MVD

Ø x

24x22

24x22

24x22

34x22

18x14

8x26

22"Ø

12x12

16x14

TO FF-1

38x22

12x12 x

DN

TO EF-1

AND EF-2

40x22

Ø x

COLD ROOM

CONDENSING UNIT

AH

GROWTH CHAMBER

CONDENSING UNITS

FOG SYSTEM

PUMPS 1 & 2

CONTROL PANELS

FOG CONTROLLER

FOG VALVE BOARD

TEF-5

C H

S

C H

R

4" CHS

4" CHR

2"

2"

4"

3" CHS

3" CHR

3"

3"

1/2"

3/8" FOG LINE TO MQ5

3/8" FOG LINE TO Q10

3/8" FOG LINE TO Q11

3/8" FOG LINE TO Q12

3/8" FOG LINE TO Q13

26x1826x1826x18

3/8" FOG LINE (TYP)

12x12

ROOF

INTAKE

12x12

ROOF

INTAKE

LV

X-2

LV

X-1

D1

D2

D3

(TYP)

D4

D5

D6

D6

3/4"DOMESTIC WATER

D3

LV

X

D9

LV

X

D9

D8

REFERENCE NOTES - DEMOLITION

REMOVE AIR HANDLING UNIT AND ASSOCIATED INERTIA PAD.

DEMOLISH PORTIONS OF EXISTING HOUSEKEEPING PAD TO MODIFY

IT IN PREPARATION OF INSTALLATION OF NEW AIR HANDLING UNIT

AND INERTIA PAD.

DEMOLISH EXISTING SUPPLY, RETURN, RELIEF AND OUTSIDE AIR

DUCTWORK, ACCESSORIES, HANGERS, SUPPORTS AND SENSORS

UP TO INDICATED POINTS OF DISCONNECTION. TEMPORARILY CAP

REMAINING DUCTWORK. COORDINATE WITH OWNER TO PROVIDE

APPROPRIATE SEALING OF DUCTWORK, PIPING AND CONDUIT

SYSTEMS THAT SERVE THE BIOHAZARD SAFETY RATED ZONES. DO

NOT DEMOLISH OR MODIFY EXISTING FILTERS OR FILTER FRAMES.

ISOLATE BRANCH CHILLED WATER PIPING SERVING UNIT AHU-1

FROM MAIN. DEMOLISH BRANCH AND COIL PIPING, SENSORS,

APPURTENANCES, AND SUPPORTS BACK TO ISOLATION VALVES.

DEMOLISH EXISTING CONDENSATE PIPING FROM UNIT AHU-1.

FLOOR DRAINS ARE EXISTING TO REMAIN.

DEMOLISH DUCTWORK CONNECTED TO LOUVER AND GRAVITY

VENTILATOR. LOUVER AND GRAVITY VENTILATOR ARE EXISTING TO

REMAIN AND BE REUSED.

DEMOLISH EXISTING FOG SYSTEM, INCLUDING CONTROLS, PUMPS,

PIPING AND SUPPORTS. DEMOLISH PIPING UP TO WALL

PENETRATION, THEN FILL WALL OPENING AND CAP AND SEAL PER

OWNER REQUIREMENTS.

DISCONNECT AND REMOVE CONTROLS CONNECTIONS FOR

DEVICES ASSOCIATED WITH AHU-1 FROM EXISTING TRANCE UNIT

CONTROLLERS AND BUILDING MANAGEMENT SYSTEM. CONTROL

PANELS ARE TO REMAIN AND BE RE-USED.

DEMOLISH EXISTING LOUVER. OPENING TO BE MODIFIED AND USED

FOR TRANSPORTING OF EQUIPMENT INTO SPACE DURING

CONSTRUCTION ACTIVITIES. REFER TO PHASE 2 - NEW PENTHOUSE

FLOOR PLAN 1 ON SHEET M3.3 AND ARCHITECTURAL PLANS FOR

NEW LOUVER AND WALL MODIFICATION INFORMATION.

D1

D2

D3

D4

D5

D6

D7

D8

D9

GENERAL NOTES

1. IN GENERAL, THE MECHANICAL SCOPE OF PHASE 1 IS AS

FOLLOWS:

a. EXISTING PENTHOUSE VENTILATION LOUVERS ARE TO BE

REMOVED TO FACILITATE INSTALLATION OF EQUIPMENT.

b. MULTI-ZONE AIR HANDLING UNIT AHU-1 SHALL BE REMOVED

AND REPLACED WITH A UNIT OF EQUIVALENT OR GREATER

PERFORMANCE. INCLUDES MODIFICATIONS TO EQUIPMENT

HOUSEKEEPING PAD, CHILLED WATER CONNECTIONS, AND

DUCTWORK CONNECTIONS.

c. PENTHOUSE DUCTWORK ASSOCIATED WITH AHU-1 SHALL BE

DEMOLISHED AND REPLACED WITH NEW.

d. DUCT HEATERS DH 1-1, 1-2, 1-3, 1-4, 1-5 AND DUCT HUMIDIFIERS

HUM 1-1, 1-2, 1-3, AND 1-4 INSTALLED IN ZONE SUPPLY

DUCTWORK WITHIN PENTHOUSE.

e. EXISTING OUTSIDE AIR INTAKE DUCTWORK DEMOLISHED AND

NEW DUCTWORK CONNECTED TO AHU-1 AND EXISTING

OUTSIDE AIR INTAKE ROOF CAP.

f. NEW PRESSURIZATION CONTROL DUCTWORK AND FAN PRF 1-1

PROVIDED AND CONNECTED TO EXISTING DISCHARGE LOUVER.

g. UPDATE CONTROLS AND SEQUENCES FOR THE INTEGRATION

OF REPLACEMENT EQUIPMENT.

2. SYSTEM COMPONENTS LOCATED OUTSIDE OF THE PENTHOUSE

SPACE ARE NOT INCLUDED IN THE PROJECT UNLESS

SPECIFICALLY NOTED ON SHEET M2.1 AND SHALL NOT BE

MODIFIED. THIS INCLUDES, BUT IS NOT LIMITED TO THE CHILLERS ,

PUMPS, CHEMICAL TREATMENT AND BUILDING CHILLED WATER

DISTRIBUTION PIPING, ZONE FILTER RACKS, AND ZONE SUPPLY

AND RETURN DUCTWORK LOCATED OUTSIDE THE PENTHOUSE.

M2.2

PHASE 1- DEMO

PENTHOUSE FLOOR

PLAN -

MECHANICAL

DRAWING NUMBER

DRAWING TITLE:

DRAWN BY:

GES PROJECT NO.:

DATE:

REGISTRATION:

REVISIONS:

PROJECT:

04/23/2021

F20-39

SUBMISSIONS:

UPGRADE AHU-1

& AHU-2

HOT/COLD DECK

MODULES

AGRICULTURAL RESEARCH SERVICES

PLAINS AREA

3225 College Avenue

Fort Lauderdale, FL 33314

USDA PROJECT NO.: AG-32SD-C-15-0044

ENGINEERING

PROGRAM MANAGEMENT

CONSTRUCTION MANAGEMENT

6700A ROCKLEDGE DRIVE SUITE 301

BETHESDA, MARYLAND 20817

T: 301.216.2871 (F) 301-216-9671 www.SalasObrien.com

AR EPM: VE

SOF

1. 95% CD SUBMISSION 10/30/20

2001742

KYLE J. CARTIER, P.E. 53269

GARY A. WILKERSON, P.E. 43167

JEFF A. KIRKMAN, P.E. 65629

ADAM S. LEVINE, P.E. 77010

expect a difference

SALAS O'BRIEN

3501 Quadrangle Boulevard, Suite 100

Orlando, Florida 32817

(407) 380-0400

CERT. OF AUTH. NO. 6106

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY KYLE J. CARTIER, PE ON DATE

INDICATED IN DIGITAL SIGNATURE USING A DIGITAL SIGNATURE.

PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE

M2.2

PHASE 1 - DEMO PENTHOUSE FLOOR PLAN - MECHANICAL

1/4"=1'-0"

FROM

FF-2

AH

DN

EF

FF

FF

26x18

38x22

30x36

44x36

DN

MVD

MVD

12x12

16x14

TO FF-1

38x22 x

DN

TO EF-1

AND EF-2

40x22

Ø x

COLD ROOM

CONDENSING UNIT

AH

GROWTH CHAMBER

CONDENSING UNITS

FOG SYSTEM

PUMPS 1 & 2

CONTROL PANELS

FOG CONTROLLER

FOG VALVE BOARD

TEF-5

C H

S

C H

R

4" CHS

4" CHR

2"

2"

4"

3" CHS

3" CHR

3"

3"

1/2"

3/8" FOG LINE (TYP)

12x12

ROOF

INTAKE

LV

X-2

LV

X-1

D1

D2

D3

(TYP)

D4

D5

D6

D6

D7

D7

D7

D7

D7

D7

D7

3/4"DOMESTIC WATER

D6

D8

D10

M2.3

PHASE 2 - DEMO PENTHOUSE FLOOR PLAN - MECHANICAL

1/4"=1'-0"

D9 D9

D5

FROM

FF-2

AH

DN

EF

FF

FF

26x18

38x22

30x36

44x36

DN

MVD

MVD

12x12

16x14

TO FF-1

38x22 x

DN

TO EF-1

AND EF-2

40x22

Ø x

COLD ROOM

CONDENSING UNIT

AH

GROWTH CHAMBER

CONDENSING UNITS

FOG SYSTEM

PUMPS 1 & 2

CONTROL PANELS

FOG CONTROLLER

FOG VALVE BOARD

TEF-5

C H

S

C H

R

4" CHS

4" CHR

2"

2"

4"

3" CHS

3" CHR

3"

3"

1/2"

3/8" FOG LINE (TYP)

12x12

ROOF

INTAKE

LV

X-2

LV

X-1

D1

D2

D3

(TYP)

D4

D5

D6

D6

D7

D7

D7

D7

D7

D7

D7

3/4"DOMESTIC WATER

D6

D8

D10

D9 D9

D5 x x

Ø

Ø

Ø x x

26x1826x1826x18

AHU

HUM

1-3

HUM

1-2

HUM

1-4

HUM

1-1

DH

1-4

DH

1-2

DH

1-3

DH

1-5

DH

1-1

38x18

Ø

24x22 x

16x16 x x

18x30

18x30

18x30

22x22

34x70

16x16

1-1/4" CD

SD

SD

SD

SD

SD

PRF

1-1 AFMS

16x16

1/2"Ø DOM. WATER

1/2"Ø DOM. WATER (TYP 3)

3/4"Ø CD

3/4"Ø CD

4"

VFD FOR PRF 1-1

REFERENCE NOTES - DEMOLITION

REMOVE AIR HANDLING UNIT AND ASSOCIATED INERTIA PAD.

DEMOLISH PORTIONS OF EXISTING HOUSEKEEPING PAD TO MODIFY

IT IN PREPARATION OF INSTALLATION OF NEW AIR HANDLING UNIT

AND INERTIA PAD.

DEMOLISH EXISTING SUPPLY, RETURN, RELIEF AND OUTSIDE AIR

DUCTWORK, ACCESSORIES, HANGERS, SUPPORTS AND SENSORS

UP TO INDICATED POINTS OF DISCONNECTION. TEMPORARILY CAP

REMAINING DUCTWORK. COORDINATE WITH OWNER TO PROVIDE

APPROPRIATE SEALING OF DUCTWORK, PIPING AND CONDUIT

SYSTEMS THAT SERVE THE BIOHAZARD SAFETY RATED ZONES. DO

NOT DEMOLISH OR MODIFY EXISTING FILTERS OR FILTER FRAMES.

ISOLATE BRANCH CHILLED WATER PIPING SERVING UNIT AHU-2

FROM MAIN. DEMOLISH BRANCH AND COIL PIPING, SENSORS,

APPURTENANCES, AND SUPPORTS BACK TO ISOLATION VALVES.

DEMOLISH EXISTING CONDENSATE PIPING FROM UNIT AHU-2.

FLOOR DRAINS ARE EXISTING TO REMAIN.

DEMOLISH DUCTWORK CONNECTED TO LOUVER AND GRAVITY

VENTILATOR. LOUVER AND GRAVITY VENTILATOR ARE EXISTING TO

REMAIN AND BE REUSED.

DEMOLISH EXISTING FOG SYSTEM, INCLUDING CONTROLS, PUMPS,

PIPING AND SUPPORTS. DEMOLISH PIPING UP TO WALL

PENETRATION, THEN FILL WALL OPENING AND CAP AND SEAL PER

OWNER REQUIREMENTS.

DEMOLISH EXISTING ROOF-MOUNTED EXHAUST FAN AND CAP

CURB. CURB CAP SHALL BE CONSTRUCTED OF SHEETMETAL AND

INSULATED TO A SUFFICIENT THICKNESS TO PREVENT

CONDENSATION (MINIMUM OF 2-INCHES OF INSULATION).

EXISTING MODIFIED WALL OPENING CREATED IN PHASE 1 TO BE

USED FOR TRANSPORTING OF EQUIPMENT INTO SPACE DURING

CONSTRUCTION ACTIVITIES. REFER TO PHASE 2 - NEW PENTHOUSE

FLOOR PLAN 1 ON SHEET M3.3 AND ARCHITECTURAL PLANS FOR

WALL MODIFICATION INFORMATION.

DISCONNECT AND REMOVE CONTROLS CONNECTIONS FOR

DEVICES ASSOCIATED WITH AHU-2 FROM EXISTING TRANCE UNIT

CONTROLLERS AND BUILDING MANAGEMENT SYSTEM. CONTROL

PANELS ARE TO REMAIN AND BE RE-USED.

D1

D2

D3

D4

D5

D6

D7

D8

D9

D10

GENERAL NOTES

1. IN GENERAL, THE MECHANICAL SCOPE OF PHASE 2 IS AS

FOLLOWS:

a. NEW OUTDOOR AIR INTAKE LOUVER LV-1 INSTALLED IN THE

MODIFIED WALL OPENING CREATED BY DEMOLITION OF

PENTHOUSE VENTILATION LOUVER IN PHASE 1.

b. MULTI-ZONE AIR HANDLING UNIT AHU-2 SHALL BE REMOVED

AND REPLACED WITH A UNIT OF EQUIVALENT OR GREATER

PERFORMANCE. INCLUDES MODIFICATIONS TO EQUIPMENT

HOUSEKEEPING PAD, CHILLED WATER CONNECTIONS, AND

DUCTWORK CONNECTIONS.

c. PENTHOUSE DUCTWORK ASSOCIATED WITH AHU-2 SHALL BE

DEMOLISHED AND REPLACED WITH NEW.

d. DUCT HEATERS DH 2-1 AND 2-2 AND DUCT HUMIDIFIER HUM 2-1

INSTALLED IN ZONE SUPPLY DUCTWORK WITHIN PENTHOUSE.

e. EXISTING OUTSIDE AIR INTAKE DUCTWORK DEMOLISHED AND

NEW DUCTWORK CONNECTED TO AHU-2 AND EXISTING

OUTSIDE AIR INTAKE ROOF CAP.

f. NEW PRESSURIZATION CONTROL DUCTWORK AND FAN PRF 2-1

CONNECTED TO EXISTING DISCHARGE LOUVER.

g. UPDATE CONTROLS AND SEQUENCES FOR THE INTEGRATION

OF REPLACEMENT EQUIPMENT.

h. PROVIDE NEW MINI-SPLIT AIR CONDITIONING SYSTEMS

AC-1/CU-1, AC-2/CU-2 AND THEIR ASSOCIATED DUCTWORK,

CONTROL DAMPERS, REFRIGERANT PIPING AND CONDENSATE

PIPING TO PROVIDE CONDITIONED AIR TO THE PENTHOUSE

SPACE. EXHAUST FAN EF-5 REMOVED AND REPLACED WITH

NEW ROOF MOUNTED FAN IN ALTERNATE LOCATION TO

PROVIDE VENTILATION TO CONDITIONED PENTHOUSE.

i. EXISTING FOG SYSTEM AND PIPING REMOVED. PIPES ROUTED

OUTSIDE PENTHOUSE TO BE ABANDONED IN PLACE AND

SEALED AIRTIGHT.

2. SYSTEM COMPONENTS LOCATED OUTSIDE OF THE PENTHOUSE

SPACE ARE NOT INCLUDED IN THE PROJECT UNLESS

SPECIFICALLY NOTED ON SHEET M2.1 AND SHALL NOT BE

MODIFIED. THIS INCLUDES, BUT IS NOT LIMITED TO THE CHILLERS ,

PUMPS, CHEMICAL TREATMENT AND BUILDING CHILLED WATER

DISTRIBUTION PIPING, ZONE FILTER RACKS, AND ZONE SUPPLY

AND RETURN DUCTWORK LOCATED OUTSIDE THE PENTHOUSE.

M2.3

PHASE 2 - DEMO

PENTHOUSE FLOOR

PLAN -

MECHANICAL

DRAWING NUMBER

DRAWING TITLE:

DRAWN BY:

GES PROJECT NO.:

DATE:

REGISTRATION:

REVISIONS:

PROJECT:

04/23/2021

F20-39

SUBMISSIONS:

UPGRADE AHU-1

& AHU-2

HOT/COLD DECK

MODULES

AGRICULTURAL RESEARCH SERVICES

PLAINS AREA

3225 College Avenue

Fort Lauderdale, FL 33314

USDA PROJECT NO.: AG-32SD-C-15-0044

ENGINEERING

PROGRAM MANAGEMENT

CONSTRUCTION MANAGEMENT

6700A ROCKLEDGE DRIVE SUITE 301

BETHESDA, MARYLAND 20817

T: 301.216.2871 (F) 301-216-9671 www.SalasObrien.com

AR EPM: VE

SOF

1. 95% CD SUBMISSION 10/30/20

2001742

KYLE J. CARTIER, P.E. 53269

GARY A. WILKERSON, P.E. 43167

JEFF A. KIRKMAN, P.E. 65629

ADAM S. LEVINE, P.E. 77010

expect a difference

SALAS O'BRIEN

3501 Quadrangle Boulevard, Suite 100

Orlando, Florida 32817

(407) 380-0400

CERT. OF AUTH. NO. 6106

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY KYLE J. CARTIER, PE ON DATE

INDICATED IN DIGITAL SIGNATURE USING A DIGITAL SIGNATURE.

PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE

M3.2

PHASE 1 - NEW PENTHOUSE FLOOR PLAN - MECHANICAL

1/4"=1'-0"

FROM

FF-2

FF

FF

26x18

30x36

44x36

DN

TO FF-1

x

DN

TO EF-1

AND EF-2

40x22

Ø x

COLD ROOM

CONDENSING UNIT

AH

GROWTH CHAMBER

CONDENSING UNITS

CONTROL PANELS

TEF-5

C H

S

C H

R

4" CHS

4" CHR

2"

2"

4"

3" CHS

3" CHR

3"

3"

1/2"

LV

X-2

LV

X-1

3/4"DOMESTIC WATER

x x

Ø

Ø

Ø x x

26x1826x1826x18

AHU

HUM

1-3

HUM

1-2

HUM

1-4

HUM

1-1

DH

1-4

DH

1-2

DH

1-3

DH

1-5

DH

1-1

6 6

38x18

Ø

24x22 x

16x16 x x

18x30

18x30

18x30

22x22

34x70

16x16

1-1/4" CD

4" CHWS/R

SD

SD

SD

SD

SD

PRF

1-1

AFMS

16x16

1/2"Ø DOM. WATER

1/2"Ø DOM. WATER (TYP 3)

3/4"Ø CD

3/4"Ø CD

4"

VFD FOR PRF 1-1

INSTALL NEW AIR HANDLING UNIT WITH INTEGRAL RAIL ON

VIBRATION ISOLATION PADS ON EXISTING HOUSEKEEPING PAD.

PROVIDE NEW SUPPLY AND RETURN CHILLED WATER BRANCH

PIPING CONNECTING CHILLED WATER SUPPLY AND RETURN MAINS

TO NEW AIR HANDLING UNIT AHU-1. PROVIDE SHUT OFF VALVES IN

ACCESSIBLE AREA AND SENSORS AND APPURTENANCES AS

INDICATED ON CONTROLS SHEET AND DETAILS.

PROVIDE NEW CONDENSATE PIPING FROM UNIT DRAIN

CONNECTION AND ROUTE TO FLOOR DRAIN AND TERMINATE

INDIRECTLY.

UNIT MOUNTED CONTROL PANEL AND VFD PANEL WITH INTEGRAL

DISCONNECT AND SINGLE POINT POWER CONNECTION FOR FAN

ARRAY.

CONNECT TO EXISTING DOMESTIC WATER PIPING AND ROUTE 3/4"

PIPING HIGH IN SPACE TO STEAM GENERATORS HUM 1-1, 1-2, 1-3

AND 1-4 AND CONNECT. PROVIDE BRANCH CONNECTION WITH

ISOLATION VALVE FOR PHASE 2 INSTALLATION OF BRANCH PIPING

TO HUM 2-1.

INSTALL NEW DUCT HEATER IN STRAIGHT RUN OF ZONE SUPPLY

DUCT 48" DOWNSTREAM OF ANY OTHER ACCESSORIES OR DUCT

TRANSITIONS, 48" UPSTREAM OF ANY HUMIDIFIER STEAM

MANIFOLDS AND 24" UPSTREAM OF ANY DUCT TRANSITIONS OR

ELBOWS. PROVIDE 36" OF MAINTENANCE CLEARANCE IN FRONT OF

DUCT HEATER CONTROL PANEL.

INSTALL STEAM GENERATOR ON WALL OR RACK. PROVIDE 36" OF

FRONT ACCESS CLEARANCE AND AT MINIMUM OF 24" OF

CLEARANCE ABOVE GENERATOR. PROVIDE 1-3/4 STEAM PIPING

AND ROUTE FROM TOP CONNECTION OF GENERATOR TO

ASSOCIATED DUCT-MOUNTED STEAM MANIFOLD. ROUTE PIPING

TIGHT TO BOTTOM OF STRUCTURE TO MAXIMIZE CLEARANCE.

ROUTE INSULATED STEAM PIPING FROM STEAM GENERATOR TO

DUCT-MOUNTED STEAM INJECTOR. ROUTE STEAM INJECTOR

CONDENSATE DRAIN PIPING BACK TO STEAM GENERATOR AND

CONNECT. ROUTE HORIZONTALLY AND VERTICALLY AS PER DETAIL

4 ON SHEET M8.1.

CONNECT NEW DUCTWORK TO EXISTING. PROVIDE DUCT

TRANSITIONS AS REQUIRED TO ACHIEVE CONNECTION.

COORDINATE WORK WITH OWNER TO ENSURE CONTAINMENT

PROTOCOLS ARE MET WHILE DUCTWORK SERVING THE BIOHAZARD

SAFETY ZONES IS BEING MODIFIED.

OPENING TO BE MODIFIED TO ALLOW TRANSPORT OF AIR

HANDLING UNIT SECTIONS FROM ROOF INTO PENTHOUSE SPACE

FOR INSTALLATION. REFER TO ARCHITECTURAL SHEET FOR MORE

INFORMATION.

TAP RETURN DUCT WITH 16x16 RELIEF AIR DUCT, ROUTE

VERTICALLY THEN TURN HORIZONTAL AND CONNECT TO

PRESSURE RELIEF FAN. ROUTE FROM DISCHARGE OF PRESSURE

RELIEF FAN TO DISCHARGE LOUVER AT WALL. PROVIDE A

MOTORIZED DAMPER, AIRFLOW MONITORING STATION, MANUAL

BALANCING DAMPER AND ALL DUCT TRANSITIONS REQUIRED FOR

ROUTING AND CONNECTIONS TO EQUIPMENT.

CONNECT NEW AHU-1 CONTROL DEVICES TO EXISTING TRANE UNIT

CONTROL PANELS AND BUILDING MANAGEMENT SYSTEM.

INSTALL NEW SUPPLY DUCTWORK AND ACCESSORIES TIGHT TO

BOTTOM OF STRUCTURE. COORDINATE HEIGHT AND LOCATION OF

NEW DUCTWORK WITH PHASE 2. DEMOLITION AND NEW

CONSTRUCTION WORK IN PHASE 2 SHALL NOT REQUIRE THE

DISABLING OR REMOVAL OF PHASE 1 WORK.

REFERENCE NOTES - NEW

GENERAL NOTES

1. IN GENERAL, THE MECHANICAL SCOPE OF PHASE 1 IS AS

FOLLOWS:

a. EXISTING PENTHOUSE VENTILATION LOUVERS ARE TO BE

REMOVED TO FACILITATE INSTALLATION OF EQUIPMENT.

b. MULTI-ZONE AIR HANDLING UNIT AHU-1 SHALL BE REMOVED

AND REPLACED WITH A UNIT OF EQUIVALENT OR GREATER

PERFORMANCE. INCLUDES MODIFICATIONS TO EQUIPMENT

HOUSEKEEPING PAD, CHILLED WATER CONNECTIONS, AND

DUCTWORK CONNECTIONS.

c. PENTHOUSE DUCTWORK ASSOCIATED WITH AHU-1 SHALL BE

DEMOLISHED AND REPLACED WITH NEW.

d. DUCT HEATERS DH 1-1, 1-2, 1-3, 1-4, 1-5 AND DUCT HUMIDIFIERS

HUM 1-1, 1-2, 1-3, AND 1-4 INSTALLED IN ZONE SUPPLY

DUCTWORK WITHIN PENTHOUSE.

e. EXISTING OUTSIDE AIR INTAKE DUCTWORK DEMOLISHED AND

NEW DUCTWORK CONNECTED TO AHU-1 AND EXISTING

OUTSIDE AIR INTAKE ROOF CAP.

f. NEW PRESSURIZATION CONTROL DUCTWORK AND FAN PRF 1-1

CONNECTED TO EXISTING LOUVER.

g. UPDATE CONTROLS AND SEQUENCES FOR THE INTEGRATION

OF REPLACEMENT EQUIPMENT.

2. SYSTEM COMPONENTS LOCATED OUTSIDE OF THE PENTHOUSE

SPACE ARE NOT INCLUDED IN THE PROJECT UNLESS

SPECIFICALLY NOTED ON SHEET M2.1 AND SHALL NOT BE

MODIFIED. THIS INCLUDES, BUT IS NOT LIMITED TO THE CHILLERS ,

PUMPS, CHEMICAL TREATMENT AND BUILDING CHILLED WATER

DISTRIBUTION PIPING, ZONE FILTER RACKS, AND ZONE SUPPLY

AND RETURN DUCTWORK LOCATED OUTSIDE THE PENTHOUSE.

M3.2

PHASE 1- NEW

PENTHOUSE FLOOR

PLAN -

MECHANICAL

DRAWING NUMBER

DRAWING TITLE:

DRAWN BY:

GES PROJECT NO.:

DATE:

REGISTRATION:

REVISIONS:

PROJECT:

04/23/2021

F20-39

SUBMISSIONS:

UPGRADE AHU-1

& AHU-2

HOT/COLD DECK

MODULES

AGRICULTURAL RESEARCH SERVICES

PLAINS AREA

3225 College Avenue

Fort Lauderdale, FL 33314

USDA PROJECT NO.: AG-32SD-C-15-0044

ENGINEERING

PROGRAM MANAGEMENT

CONSTRUCTION MANAGEMENT

6700A ROCKLEDGE DRIVE SUITE 301

BETHESDA, MARYLAND 20817

T: 301.216.2871 (F) 301-216-9671 www.SalasObrien.com

AR EPM: VE

SOF

1. 95% CD SUBMISSION 10/30/20

2001742

KYLE J. CARTIER, P.E. 53269

GARY A. WILKERSON, P.E. 43167

JEFF A. KIRKMAN, P.E. 65629

ADAM S. LEVINE, P.E. 77010

expect a difference

SALAS O'BRIEN

3501 Quadrangle Boulevard, Suite 100

Orlando, Florida 32817

(407) 380-0400

CERT. OF AUTH. NO. 6106

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY KYLE J. CARTIER, PE ON DATE

INDICATED IN DIGITAL SIGNATURE USING A DIGITAL SIGNATURE.

PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE

FROM

FF-2

FF

FF

26x18

30x36

44x36

DN

TO FF-1

x

DN

TO EF-1

AND EF-2

40x22

Ø x

COLD ROOM

CONDENSING UNIT

AH

GROWTH CHAMBER

CONDENSING UNITS

CONTROL PANELS

C H

S

C H

R

4" CHS

4" CHR

2"

2"

4"

3" CHS

3" CHR

3"

3"

1/2"

LV

X-2

LV

X-1

3/4"DOMESTIC WATER

x x

Ø

Ø

Ø x x

26x1826x1826x18

AHU

AHU

DH

2-2

DH

2-1

HUM

2-1

HUM

1-3

HUM

1-2

HUM

1-4

HUM

1-1

DH

1-4

DH

1-2

DH

1-3

DH

1-5

DH

1-1 x

22x26

38x18

44x22 x

16x16

Ø

24x22 x

16x16 x x

18x30

18x30

18x30

22x22

34x70

16x16

1-1/4" CD

1-1/4" CD

2-1/2" CHWS/R

16x14

SD

SD

SD

SD

SD

SD

SD

PRF

1-1

PRF

2-1

AFMS

AFMS

16x16

16x16

3/4"Ø DOM. WATER

1/2"Ø DOM. WATER

1/2"Ø DOM. WATER

1/2"Ø CD

1/2"Ø DOM. WATER (TYP 3)

3/4"Ø CD

3/4"Ø CD

4"

VFD FOR PRF 1-1

VFD FOR PRF 2-1

AC

AC

CU

CU

EF

12x10 x

8x6

8x6

8x6

54x8 54x8

LV

R

R

RRR

R

R

R

M

3/4"Ø CD

3/4"Ø CD

TS

T T

M

M3.3

PHASE 2 - NEW PENTHOUSE FLOOR PLAN - MECHANICAL

1/4"=1'-0"

INSTALL NEW AIR HANDLING UNIT WITH INTEGRAL RAIL ON

VIBRATION ISOLATION PADS ON EXISTING HOUSEKEEPING PAD.

PROVIDE NEW SUPPLY AND RETURN CHILLED WATER BRANCH

PIPING CONNECTING CHILLED WATER SUPPLY AND RETURN MAINS

TO NEW AIR HANDLING UNIT. PROVIDE SHUT OFF VALVES IN

ACCESSIBLE AREA AND SENSORS AND APPURTENANCES AS

INDICATED ON CONTROLS SHEET AND DETAILS.

PROVIDE NEW CONDENSATE PIPING FROM UNIT DRAIN

CONNECTION AND ROUTE TO FLOOR DRAIN AND TERMINATE

INDIRECTLY. FOR CONDENSATE PIPING ASSOCIATED WITH AC-1

AND AC-2 ROUTE PIPING UP HIGH WITHIN PENTHOUSE TO AVOID

TRIPPING HAZARDS. ROUTE TO PROXIMITY OF FLOOR DRAIN, THEN

ROUTE DOWN TO FLOOR AND TERMINATE INDIRECTLY INTO FLOOR

DRAIN.

UNIT MOUNTED CONTROL PANEL AND VFD PANEL WITH INTEGRAL

DISCONNECT AND SINGLE POINT POWER CONNECTION FOR FAN

ARRAY.

CONNECT TO EXISTING DOMESTIC WATER PIPING BRANCH AT

ISOLATION VALVE PROVIDED IN PHASE 1 AND ROUTE 3/4" PIPING

HIGH IN SPACE TO STEAM GENERATOR HUM 2-1 AND CONNECT.

INSTALL NEW DUCT HEATER IN STRAIGHT RUN OF ZONE SUPPLY

DUCT 48" DOWNSTREAM OF ANY OTHER ACCESSORIES OR DUCT

TRANSITIONS, 48" UPSTREAM OF ANY HUMIDIFIER STEAM

MANIFOLDS AND 24" UPSTREAM OF ANY DUCT TRANSITIONS OR

ELBOWS. PROVIDE 36" OF MAINTENANCE CLEARANCE IN FRONT OF

DUCT HEATER CONTROL PANEL.

INSTALL STEAM GENERATOR ON WALL OR RACK. PROVIDE 36" OF

FRONT ACCESS CLEARANCE AND AT MINIMUM OF 24" OF

CLEARANCE ABOVE GENERATOR. PROVIDE 1-3/4 STEAM PIPING

AND ROUTE FROM TOP CONNECTION OF GENERATOR TO

ASSOCIATED DUCT-MOUNTED STEAM MANIFOLD. ROUTE PIPING

TIGHT TO BOTTOM OF STRUCTURE TO MAXIMIZE CLEARANCE.

ROUTE INSULATED STEAM PIPING FROM STEAM GENERATOR TO

DUCT-MOUNTED STEAM INJECTOR. ROUTE STEAM INJECTOR

CONDENSATE DRAIN PIPING BACK TO STEAM GENERATOR AND

CONNECT. ROUTE HORIZONTALLY AND VERTICALLY AS PER DETAIL

4 ON SHEET M8.1.

CONNECT NEW DUCTWORK TO EXISTING. PROVIDE DUCT

TRANSITIONS AS REQUIRED TO ACHIEVE CONNECTION.

COORDINATE WORK WITH OWNER TO ENSURE CONTAINMENT

PROTOCOLS ARE MET WHILE DUCTWORK SERVING THE BIOHAZARD

SAFETY ZONES IS BEING MODIFIED.

OPENING WAS CREATED AND MODIFIED IN PHASE 1 TO ALLOW

TRANSPORT OF AIR HANDLING UNIT SECTIONS FROM ADJACENT

ROOF INTO PENTHOUSE SPACE FOR INSTALLATION. INSTALL NEW

LOUVER LV-1 AT MAXIMUM HEIGHT WITHIN OPENING. REFER TO

ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR WALL

MODIFICATIONS AND NEW WALL INFILL DETAILS.

TAP RETURN DUCT WITH 16x16 RELIEF AIR DUCT, ROUTE

VERTICALLY THEN TURN HORIZONTAL AND CONNECT TO

PRESSURE RELIEF FAN. ROUTE FROM DISCHARGE OF PRESSURE

RELIEF FAN TO DISCHARGE LOUVER AT WALL. PROVIDE A

MOTORIZED DAMPER, AIRFLOW MONITORING STATION, MANUAL

BALANCING DAMPER AND ALL DUCT TRANSITIONS REQUIRED FOR

ROUTING AND CONNECTIONS TO EQUIPMENT.

PROVIDE LOUVER BACK-PAN FULL SIZE OF OUTSIDE AIR INTAKE

LOUVER LV-1. TAP OUTSIDE AIR DUCTWORK FROM BACKPAN AND

ROUTE TIGHT TO BOTTOM OF STRUCTURE FOR DISTRIBUTION TO

MINI-SPLIT AIR HANDLING UNITS AC-1 AND AC-2.

INSTALL NEW HORIZONTAL MINI-SPLIT AIR CONDITIONERS TIGHT TO

BOTTOM OF STRUCTURE AND IN LOCATION FREE OF

INTERFERENCE OF MANUFACTURER RECOMMENDED CLEARANCES.

PROVIDE SHORT SECTION OF RETURN AIR DUCT FULL SIZE OF UNIT

INTAKE CONNECTION. CONNECT OUTSIDE AIR DUCTWORK TO

RETURN AIR DUCTWORK. PROVIDE WELDED WIRE MESH ON

RETURN DUCT INLET AND UNIT DISCHARGE. MOUNT UNIT

THERMOSTAT TO INDOOR UNIT CASING OR RETURN AIR

DUCTWORK IN ACCESSIBLE LOCATION.

ROUTE REFRIGERANT PIPING TIGHT TO BOTTOM OF STRUCTURE

FROM MINI-SPLIT AIR CONDITIONER TO EXTERIOR WALL.

PENETRATE WALL TO EXTERIOR AND ROUTE REFRIGERANT PIPING

DOWN WALL AND ACROSS ROOF TO RACK-MOUNTED CONDENSING

UNIT AND CONNECT. PRIME AND PAINT JACKET TO MATCH WALL

COLOR. PROVIDE HANGERS AND/OR SUPPORTS FOR REFRIGERANT

PIPING EVERY 5 FEET OF HORIZONTAL SPAN, EVERY 5 FEET OF

VERTICAL RISE, AND EVERY 5 FEET ACROSS THE ROOF WITH MIRO

INDUSTRIES MODEL 1.5 PIPE SUPPORTS OR EQUIVALENT. SEAL

WALL PENETRATION AIR AND WATER TIGHT. PROVIDE ALUMINUM

WEATHERPROOF JACKET ON EXTERIOR REFRIGERANT PIPING.

NEW MINI-SPLIT AIR CONDITIONING SYSTEM CONDENSING UNIT

MOUNTED ON EQUIPMENT ROOF-RACK. SEE DETAIL 4 ON SHEET

M8.2 FOR MORE INFORMATION. MAINTAIN MANUFACTURER'S

RECOMMENDED CLEARANCES BETWEEN CONDENSING UNIT AND

AND OTHER ROOF MOUNTED EQUIPMENT.

PROVIDE NEW ROOF-MOUNTED DOWNBLAST EXHAUST FAN

INSTALLED ON ROOF CURB. CONNECT GALVANIZED STEEL

EXHAUST DUCT TO INLET OF EXHAUST FAN FULL SIZE OF

CONNECTION AND EXTEND DUCTWORK VERTICALLY INTO SPACE

TO 12 INCHES BELOW DECK AND LEAVE OPEN TO SPACE. PROVIDE

WELDED WIRE MESH ON DUCT INLET.

WALL-MOUNTED TEMPERATURE SENSOR FOR REPORTING OF

PENTHOUSE TEMPERATURE TO BMS.

PROVIDE MANUAL BALANCING DAMPER AND 2-POSITION

MOTORIZED CONTROL DAMPER IN OUTSIDE AIR BRANCH DUCT

CONNECTED TO EACH AIR CONDITIONING UNIT (AC-1 AND AC-2).

ADJUST MANUAL BALANCING DAMPER TO PROVIDE SCHEDULED

OUTSIDE AIRFLOW PER UNIT SCHEDULE. REFER TO CONTROLS

SEQUENCE FOR OPERATION OF MOTORIZED CONTROL DAMPER.

OPENING TO BE FILLED BY ARCHITECTURAL INSULATED IN-FILL

WALL. REFER TO ARCHITECTURAL SHEET FOR ADDITIONAL

INFORMATION.

CONNECT NEW AHU-2 CONTROL DEVICES TO EXISTING TRANE UNIT

CONTROL PANELS AND BUILDING MANAGEMENT SYSTEM.

CONNECT NEW 1/2" DIA. DOMESTIC WATER LINE TO EXISTING

PHASE 1 BRANCH ISOLATION VALVE AND ROUTE TO STEAM

GENERATOR HUM 2-1.

REFERENCE NOTES - NEW

GENERAL NOTES

1. IN GENERAL, THE MECHANICAL SCOPE OF PHASE 2 IS AS FOLLOWS:

a. NEW OUTDOOR AIR INTAKE LOUVER LV-1 INSTALLED IN THE MODIFIED WALL OPENING

CREATED BY DEMOLITION OF PENTHOUSE VENTILATION LOUVER IN PHASE 1.

b. MULTI-ZONE AIR HANDLING UNIT AHU-2 SHALL BE REMOVED AND REPLACED WITH A

UNIT OF EQUIVALENT OR GREATER PERFORMANCE. INCLUDES MODIFICATIONS TO

EQUIPMENT HOUSEKEEPING PAD, CHILLED WATER CONNECTIONS, AND DUCTWORK

CONNECTIONS.

c. PENTHOUSE DUCTWORK ASSOCIATED WITH AHU-2 SHALL BE DEMOLISHED AND

REPLACED WITH NEW.

d. DUCT HEATERS DH 2-1 AND 2-2 AND DUCT HUMIDIFIER HUM 2-1 INSTALLED IN ZONE

SUPPLY DUCTWORK WITHIN PENTHOUSE.

e. EXISTING OUTSIDE AIR INTAKE DUCTWORK DEMOLISHED AND NEW DUCTWORK

CONNECTED TO AHU-2 AND EXISTING OUTSIDE AIR INTAKE ROOF CAP.

f. NEW PRESSURIZATION CONTROL DUCTWORK AND FAN PRF 2-1 CONNECTED TO

EXISTING DISCHARGE LOUVER.

g. UPDATE CONTROLS AND SEQUENCES FOR THE INTEGRATION OF REPLACEMENT

EQUIPMENT.

h. PROVIDE NEW MINI-SPLIT AIR CONDITIONING SYSTEMS AC-1/CU-1, AC-2/CU-2 AND

THEIR ASSOCIATED DUCTWORK, CONTROL DAMPERS, REFRIGERANT PIPING AND

CONDENSATE PIPING TO PROVIDE CONDITIONED AIR TO THE PENTHOUSE SPACE.

EXHAUST FAN EF-5 REMOVED AND REPLACED WITH NEW ROOF MOUNTED FAN IN

ALTERNATE LOCATION TO PROVIDE VENTILATION TO CONDITIONED PENTHOUSE.

i. EXISTING FOG SYSTEM AND PIPING REMOVED. PIPES ROUTED OUTSIDE PENTHOUSE

TO BE ABANDONED IN PLACE AND SEALED AIRTIGHT.

2. SYSTEM COMPONENTS LOCATED OUTSIDE OF THE PENTHOUSE SPACE ARE NOT

INCLUDED IN THE PROJECT UNLESS SPECIFICALLY NOTED ON SHEET M2.1 AND SHALL

NOT BE MODIFIED. THIS INCLUDES, BUT IS NOT LIMITED TO THE CHILLERS , PUMPS,

CHEMICAL TREATMENT AND BUILDING CHILLED WATER DISTRIBUTION PIPING, ZONE

FILTER RACKS, AND ZONE SUPPLY AND RETURN DUCTWORK LOCATED OUTSIDE THE

PENTHOUSE.

M3.3

PHASE 2- NEW

PENTHOUSE FLOOR

PLAN -

MECHANICAL

DRAWING NUMBER

DRAWING TITLE:

DRAWN BY:

GES PROJECT NO.:

DATE:

REGISTRATION:

REVISIONS:

PROJECT:

04/23/2021

F20-39

SUBMISSIONS:

UPGRADE AHU-1

& AHU-2

HOT/COLD DECK

MODULES

AGRICULTURAL RESEARCH SERVICES

PLAINS AREA

3225 College Avenue

Fort Lauderdale, FL 33314

USDA PROJECT NO.: AG-32SD-C-15-0044

ENGINEERING

PROGRAM MANAGEMENT

CONSTRUCTION MANAGEMENT

6700A ROCKLEDGE DRIVE SUITE 301

BETHESDA, MARYLAND 20817

T: 301.216.2871 (F) 301-216-9671 www.SalasObrien.com

AR EPM: VE

SOF

1. 95% CD SUBMISSION 10/30/20

2001742

KYLE J. CARTIER, P.E. 53269

GARY A. WILKERSON, P.E. 43167

JEFF A. KIRKMAN, P.E. 65629

ADAM S. LEVINE, P.E. 77010

expect a difference

SALAS O'BRIEN

3501 Quadrangle Boulevard, Suite 100

Orlando, Florida 32817

(407) 380-0400

CERT. OF AUTH. NO. 6106

THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY KYLE J. CARTIER, PE ON DATE

INDICATED IN DIGITAL SIGNATURE USING A DIGITAL SIGNATURE.

PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND THE

MODEL

MANUFACTURER

TYPE

ELECTRIC DUCT HEATER SCHEDULE

MARK

LOCATION

AMPS

HEATER

VOLTS/PHASE/HZ

CAPACITY (KW)

STAGES

GENERAL

ACCESSORIES

NOTES

ACCESSORIES (PROVIDE THE FOLLOWING)

1. AUTOMATIC RESET THERMAL CUTOUT

2. DIFFERENTIAL PRESSURE AIRFLOW SWITCH

3. DE-ENERGIZING MAGNETIC CONTACTORS

4. CONTROL TRANSFORMER

5. INTEGRAL DISCONNECT SWITCH

NOTES

1. FLANGED DUCT CONNECTION

INDEECO

2,910

DUCT HEATER

DH-1-1

ZONE SUPPLY DUCT

26.0

208/3/60

72.3

1-5

AIR FLOW (CFM)

STATIC PRESSURE (IN.W.G.)

HP OR WATTS

DRIVE/TYPE

VOLTAGE/PHASE/HZ

UNIT REQUIREMENTS

OPERATING WEIGHT (LBS)

ACCESSORIES

NOTES

ACCESSORIES (PROVIDE THE FOLLOWING)

NOTES

MARK

MODEL

MANUFACTURER

FAN

FAN SCHEDULE

LOCATION

APPLICATION

1. ONE VARIABLE FREQUENCY DRIVE WITH INTEGRAL DISCONNECT AND BYPASS. VFD

SHALL BE MOUNTED ON WALL OR RACK AND NOT ON THE UNIT.

2. BACKDRAFT DAMPER

3. FLEXIBLE DUCT CONNECTIONS

4. VIBRATION ISOLATORS

5. INTEGRAL DISCONNECT SWITCH

1. FAN IS CONTROLLED BY BMS TO RELIEVE PRESSURE IN ASSOCIATED AIR HANDLING

UNIT SYSTEM.

2. INTERLOCK FAN WITH OPERATION OF CONDENSING UNITS CU-1 AND CU-2

COMPRESSORS. UPON ACTIVATION OF EITHER OR BOTH UNITS, FAN SHALL ENERGIZE

AND SHALL RUN. ONCE BOTH CU-1 AND CU-2 ARE OFF, EXHAUST FAN EF-5 SHALL STOP.

MAXIMUM SONES

0.15

115/1/60

50 W

DIRECT/CENT.

1-5

PRF-1-1

GREENHECK

SQ-95-D

PENTHOUSE

RELIEF

5.6

MULTI-ZONE AIR HANDLING UNITS

LOCATION

COOLING COIL

FAN SIZE AND TYPE

HP/RPM PER FAN

TOTAL AIR FLOW (CFM)

OUTSIDE AIR FLOW (CFM)

ENT AIR TEMP (DB/WB)

SENSIBLE/TOTAL CAPACITY (MBH)

ESP/TSP (IN.W.G.)

MANUFACTURER

MODEL

FAN

MARK

ENT/LVG WATER TEMP (DEG F)

FILTERS

WATER FLOW (GPM)

UNIT REQUIREMENTS

AREA (SF)

NOTES

FILTER EFFICIENCY

MIN FACE AREA (SF)

1. ONE VARIABLE FREQUENCY DRIVE PER FAN MOTOR. VFDS SHALL BE MOUNTED IN ENCLOSURE ON UNIT WITH COMMON

ENCLOSURE WITH INTEGRAL DISCONNECT AND BYPASS.

2. PREMIUM EFFICIENCY OPEN DRIP PROOF FAN MOTORS RATED FOR VFD OPERATION.

3. GROUNDED SHAFT FOR MOTORS POWERED BY VFD.

4. DOUBLE WALL INSULATED SECTIONS.

5. STAINLESS STEEL…

This is the start of the file's text. The full file is on GovTribe.