Attachment 1_Design Drawings.pdf
PDF 4 MB Posted
- Solicitation number
- 1232SA26Q0681
About this file
This document is a set of architectural drawings and specifications for Building 005 Exterior Envelope and Other Repairs at the Physiology and Pathology of Tree Fruit Research Laboratory in Wenatchee, Washington, operated by the U.S. Department of Agriculture Agricultural Research Service. The project is identified under A-E Contract No. 12639521D0053 and A-E Task Order No. 12905B24F0144.
The BASE BID scope includes removal and replacement of metal roofing panels, removal and replacement of an existing sink, addressing safety concerns for interior panels through refastening or removal of damaged panels, and provision of exterior lights on the east, west, and south facades. BID OPTION 1 requires removal and replacement of interior personnel doors, frames, and hardware in Rooms 104 and 105. BID OPTION 2 involves removal of ceiling panels, wall panels, and insulation in Room 105, provision of spray foam insulation with intumescent paint application, and removal and reinstallation of lights to perform the work. The work must comply with the 2018 Washington State Existing Building Code under Alteration-Level 1 standards, with repairs performed in-kind with no additions or alterations to existing spaces. The contractor is required to field-verify all dimensions and existing conditions prior to performing work and to repair any existing construction damaged during demolition or new construction per Specification Section 02 41 00. The drawing set includes 18 sheets covering demolition and new construction floor plans, roof plans, elevations, building sections, details, door schedules, plumbing layouts, and electrical plans with lighting details.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 2_Design Specifications.pdf | ||
| Sol_1232SA26Q0681.pdf | ||
| Attachment 3_Davis-Bacon Act WD WA20260103.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
TITLE SHEET
T101
WENATCHEE BUILDING REPAIRS
AGRICULTURAL RESEARCH SERVICE
U.S. DEPARTMENT OF AGRICULTURE
LOCATION MAPVICINITY MAP
A. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING
CONDITIONS PRIOR TO PERFORMING WORK OR FABRICATION OR PURCHASE
OF EQUIPMENT, MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS SHALL BE
BROUGHT TO THE CONTRACTING OFFICER'S ATTENTION FOR RESOLUTION
BEFORE PROCEEDING WITH ANY CONSTRUCTION, FABRICATION, OR
EQUIPMENT PURCHASE.
B. THE CONTRACTOR SHALL REPAIR ALL EXISTING CONSTRUCTION TO REMAIN
THAT HAS BEEN DAMAGED BY THE DEMOLITION, DECONSTRUCTION, OR NEW
CONSTRUCTION AS SPECIFIED IN SPECIFICATION SECTION 02 41 00.
N W
ES
TE
R N
A
VE
PHYSIOLOGY AND PATHOLOGY OF TREE
FRUITS RESEARCH LABORATORY
1104 N. WESTERN AVE.
WENATCHEE, WA
SEATTLE
EVERETT
MOUNT VERNON
BELLINGHAM
WENATCHEE
YAKIMA
PASCO
WALLA WALLA
PULLMAN
SPOKANE
TACOMA
OLYMPIA
VANCOUVER
LOCATION
PROJECT
BUILDING 005
PROJECT DESCRIPTION
PROJECT A - BUILDING 005 EXTERIOR ENVELOPE AND OTHER REPAIRS
CODE ANALYSIS B005:
THE REPAIR WORK AT BUILDING 005 WILL COMPLY WITH THE PRESCRIPTIVE
METHOD AND LIMITATIONS INDICATED IN THE 2018 WASHINGTON STATE EXISTING
BUILDING CODE (WSEBC), ALTERATION - LEVEL 1 FOR WORK TO BE PERFORMED
AT THIS FACILITY. PER CHAPTER 7, ALTERATION - LEVEL 1 THIS PROJECT IS TO
COMPLY WITH SECTION 602 AND ANY OTHER CHAPTERS AND SECTIONS
INCLUDED IN THE WSEBC OR THE WASHINGTON STATE BUILDING CODE AS
REQUIRED. WORK BEING PERFORMED AT THIS FACILITY IS TO REMOVE AND
REPLACE EXISTING MATERIALS AND EQUIPMENT IN-KIND. THERE WILL BE NO
ADDITIONS OR ALTERATIONS TO EXISTING SPACES.
GENERAL NOTES BUILDING CODE ANALYSIS
PHYSIOLOGY AND PATHOLOGY OF TREE
FRUIT RESEARCH LABORATORY
WENATCHEE, WA
A-E CONTRACT NO.: 12639521D0053
A-E TASK ORDER NO.: 12905B24F0144
BUILDING 005 – EXTERIOR ENVELOPE AND OTHER REPAIRS WILL INCLUDE BUT NOT LIMITED TO THE
FOLLOWING ITEMS:
BASE BID:
· REMOVE AND REPLACE METAL ROOFING PANELS.
· REMOVE AND REPLACE EXISTING SINK.
· ADDRESS SAFETY CONCERNS FOR INTERIOR PANELS (REFASTENING OR REMOVAL OF DAMAGED
PANELS).
· PROVIDE EXTERIOR LIGHTS ON EAST, WEST, AND SOUTH FACADES AS SHOWN.
BID OPTION 1:
· REMOVE AND REPLACE INTERIOR PERSONNEL DOORS, FRAMES, AND HARDWARE IN ROOMS 104 AND 105.
BID OPTION 2:
· REMOVE CEILING PANELS, WALL PANELS, AND INSULATION IN ROOM 105. PROVIDE SPRAY FOAM
INSULATION AND APPLY INTUMESCENT PAINT. REMOVE AND REINSTALL LIGHTS TO PERFORM THE WORK.
DRAWING NO.
INDEX OF DRAWINGS
SHEET NO. TITLE
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
DRAWING INDEX
T102
TITLE SHEET
DRAWING INDEX
DEMO FLOOR PLAN
DEMO ROOF PLAN
DEMO ELEVATIONS
DEMO BUILDING SECTIONS
FLOOR PLAN
ROOF PLAN
ELEVATIONS
BUILDING SECTIONS
DETAILS AND DOOR SCHEDULE
PLUMBING FLOOR PLAN
PLUMBING SCHEDULES AND DETAILS
ELECTRICAL NOTES AND ABBREVIATIONS
LEGEND
ELECTRICAL DEMO PLAN
ELECTRICAL FLOOR PLAN
LIGHTING DETAILS
T101
T102
AD101
AD151
AD201
AD301
A101
A151
A201
A301
A501
P101
P601
E001
E002
ED101
E101
E201
'-1
0"
EX
IS
TI
N G
A D
D
IT
IO
N
21'-6"
EXISTING ADDITION
'-5
40'
40'
'-9
SHOP
MEZZANINE
103 102
2 2
AD301
AD301
GENERAL NOTES
GRAPHIC SCALE
A. THE CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS AND EXISTING CONDITIONS PRIOR
TO PERFORMING ANY WORK OR FABRICATION
OR PURCHASE OF EQUIPMENT, MATERIALS,
AND ASSEMBLIES. ANY DEVIATIONS SHALL BE
BROUGHT TO THE CONTRACTING OFFICER'S
ATTENTION FOR RESOLUTION BEFORE
PROCEEDING WITH ANY CONSTRUCTION,
FABRICATION, OR EQUIPMENT PURCHASE.
B. ALL UTILITIES AFFECTED BY DEMOLITION SHALL
BE REINSTALLED IN THE WORK OR CAPPED
AND TERMINATED IN ACCORDANCE WITH
CODES.
C. CONTRACTOR SHALL PROVIDE TEMPORARY
STRUCTURAL SUPPORTS FOR EXISTING
CONSTRUCTION DURING THE WORK (IF
REQUIRED).
D. THE CONTRACTOR SHALL REPAIR ALL EXISTING
CONSTRUCTION TO REMAIN THAT HAS BEEN
DAMAGED BY THE DEMOLITION,
DECONSTRUCTION, OR NEW CONSTRUCTION
AS SPECIFIED IN SPECIFICATION SECTION 02 41
00.
E. ALL EXTERIOR OVERHEAD DOORS, PERSONNEL
DOORS, AND WINDOWS TO REMAIN IN PLACE.
1'-0'
06' 6'3'
SCALE: 3/16" =
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
DEMO FLOOR PLANS
AD101
SCALE:
BUILDING 005 - DEMO
FLOOR PLAN
3/16" = 1'-0"
AD101
SCALE:
BUILDING 005 - DEMO
MEZZANINE PLAN
3/16" = 1'-0"
AD101
KEYED NOTESX
1. REMOVE EXISTING SINK. SEE PLUMBING.
2. EXISTING WALL PANELS FROM FLOOR TO
CEILING TO REMAIN.
3. REMOVE EXISTING INTERIOR WALL PANELS
FROM THE CEILING DOWN TO THE JOINT
LINE AT APPROXIMATELY 12' ABOVE
FINISHED FLOOR. EXISTING WALL PANELS
FROM FLOOR TO THE JOINT LINE AT
APPROXIMATELY 12' TO REMAIN.
4. EXISTING ELECTRICAL PANELS TO REMAIN.
EXISTING WALL PANELS ABOVE ELECTRICAL
PANELS TO REMAIN.
5. BID OPTION 1: REMOVE EXISTING DOORS
AND FRAMES.
6. BID OPTION 2: REMOVE INTERIOR WALL
PANELS AND INSULATION. SEE ELECTRICAL
FOR MORE INFORMATION.
7. EXISTING METAL WALL PANELS APPROX. 9'
ABOVE FINISHED FLOOR TO REMAIN.
0"
EX
IS
TI
N G
A D
D
IT
IO
N
21'-6"
EXISTING ADDITION
'-5
40'
3 3
GENERAL NOTES
GRAPHIC SCALE
A. THE CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS AND EXISTING CONDITIONS PRIOR
TO PERFORMING ANY WORK OR FABRICATION
OR PURCHASE OF EQUIPMENT, MATERIALS, AND
ASSEMBLIES. ANY DEVIATIONS SHALL BE
BROUGHT TO THE CONTRACTING OFFICER'S
ATTENTION FOR RESOLUTION BEFORE
PROCEEDING WITH ANY CONSTRUCTION,
FABRICATION, OR EQUIPMENT PURCHASE.
B. ALL UTILITIES AFFECTED BY DEMOLITION SHALL
BE REINSTALLED IN THE WORK OR CAPPED AND
TERMINATED IN ACCORDANCE WITH CODES.
C. CONTRACTOR SHALL PROVIDE TEMPORARY
STRUCTURAL SUPPORTS FOR EXISTING
CONSTRUCTION DURING THE WORK.
D. THE CONTRACTOR SHALL REPAIR ALL EXISTING
CONSTRUCTION TO REMAIN THAT HAS BEEN
DAMAGED BY THE DEMOLITION,
DECONSTRUCTION, OR NEW CONSTRUCTION AS
SPECIFIED IN SPECIFICATION SECTION 02 41 00.
E. BUILDING 005 HAS A FINISHED INTERIOR THAT
WILL REQUIRE THE CONTRACTOR TO PROVIDE
PROTECTION FROM THE WEATHER AND
CONSTRUCTION DEBRIS DURING THE
DEMOLITION AND REPLACEMENT OF THE
EXTERIOR ROOF SYSTEM.
1'-0'
06' 6'3'
SCALE: 3/16" =
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
DEMO ROOF PLAN
AD151
SCALE:
BUILDING 005
DEMO ROOF PLAN
3/16" = 1'-0"
AD151
KEYED NOTESX
1. REMOVE EXISTING METAL ROOF PANELS.
2. EXISTING ADDITION ROOF TO REMAIN.
3. EXISTING AWNING OVER PERSONNEL DOOR
TO REMAIN.
4. EXISTING CANOPY OVER HVAC EQUIPMENT
TO REMAIN.
5. REMOVE TRANSLUCENT PANELS.
6. REMOVE ROOF VENTS.
7. REMOVE, STORE, AND PROTECT FLUE TO
PERFORM WORK.
EXISTING METAL WALL
PANELS TO REMAIN,
TYP. ALL
EXISTING ADDITION EXISTING ADDITION
EXISTING ADDITION
REMOVE EXISTING
METAL ROOF
REMOVE EXISTING METAL ROOF
REMOVE EXISTING
METAL ROOF
EXISTING METAL WALL PANELS
TO REMAIN, TYP. ALL
EXISTING WINDOWS
TO REMAIN, TYP. ALL
EXISTING OVERHEAD
DOORS TO REMAIN
REMOVE EXISTING
EXTERIOR LIGHT
REMOVE EXISTING
METAL ROOF
EXISTING AWNING OVER
PERSONNEL DOOR TO REMAIN EXISTING AWNING OVER
HVAC UNIT TO REMAIN
EXISTING AWNING
OVER PERSONNEL
DOOR TO REMAIN
'-1
0"
EXISTING PERSONNEL
DOOR TO REMAIN, TYP. ALL
'-1
0"
EXISTING ADDITION METAL
ROOF TO REMAIN
EXISTING ADDITION METAL
ROOF TO REMAIN
EXISTING ADDITION
METAL ROOF TO
REMAIN
REMOVE ROOF VENTS, TYP.
REMOVE ROOF VENTS, TYP.REMOVE ROOF VENTS, TYP.
REMOVE ROOF VENTS, TYP.
EXISTING CHAIN LINK
FENCE TO REMAIN
EXISTING FALSE
OPENING TO REMAIN
GENERAL NOTES
GRAPHIC SCALE
A. THE CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS AND EXISTING CONDITIONS PRIOR
TO PERFORMING ANY WORK OR FABRICATION
OR PURCHASE OF EQUIPMENT, MATERIALS, AND
ASSEMBLIES. ANY DEVIATIONS SHALL BE
BROUGHT TO THE CONTRACTING OFFICER'S
ATTENTION FOR RESOLUTION BEFORE
PROCEEDING WITH ANY CONSTRUCTION,
FABRICATION, OR EQUIPMENT PURCHASE.
B. ALL UTILITIES AFFECTED BY DEMOLITION SHALL
BE REINSTALLED IN THE WORK OR CAPPED AND
TERMINATED IN ACCORDANCE WITH CODES.
C. CONTRACTOR SHALL PROVIDE TEMPORARY
STRUCTURAL SUPPORTS FOR EXISTING
CONSTRUCTION DURING THE WORK.
D. THE CONTRACTOR SHALL REPAIR ALL EXISTING
CONSTRUCTION TO REMAIN THAT HAS BEEN
DAMAGED BY THE DEMOLITION,
DECONSTRUCTION, OR NEW CONSTRUCTION AS
SPECIFIED IN SPECIFICATION SECTION 02 41 00.
E. BUILDING 005 HAS A FINISHED INTERIOR THAT
WILL REQUIRE THE CONTRACTOR TO PROVIDE
PROTECTION FROM THE WEATHER AND
CONSTRUCTION DEBRIS DURING THE
DEMOLITION AND REPLACEMENT OF THE
EXTERIOR ROOF SYSTEM.
1'-0'
06' 6'3'
SCALE: 3/16" =
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
DEMO ELEVATIONS
AD201
SCALE:
BUILDING 005
DEMO NORTH ELEVATION
3/16" = 1'-0"
AD201 SCALE:
BUILDING 005
DEMO EAST ELEVATION
3/16" = 1'-0"
AD201
SCALE:
BUILDING 005
DEMO SOUTH ELEVATION
3/16" = 1'-0"
AD201 SCALE:
BUILDING 005
DEMO WEST ELEVATION
3/16" = 1'-0"
AD201
1"
38'-9 1/2"
4' -3
EXISTING PLYWOOD WALL (APPROX. 4' HIGH) TO REMAIN
REMOVE EXISTING METAL ROOF PANELS
EXISTING 2X @ 21" O.C. ATTACHED TO ROOF PURLINS TO REMAIN
EXISTING WALL GIRTS TO REMAIN
EXISTING 6" ROOF PURLINS TO REMAIN
EXISTING METAL
WALL PANELS
TO REMAIN
4' -3
40'
9"
EXISTING STRUCTURE TO REMAIN
EXISTING TONGUE AND GROOVE WALL PANELS TO REMAIN
EXISTING 1X3 ATTACHED TO 2X TO REMAIN
REMOVE EXISTING INTERIOR WALL PANELS FROM THE
CEILING DOWN TO THE JOINT LINE AT APPROXIMATELY
12' A.F.F.; INSULATION AND WOOD SUBSTRATE TO REMAIN
SHOP
EXISTING WALL
INSULATION TO
REMAIN
EXISTING ROOF BATT INSULATION TO REMAIN
8" EXISTING
STRUCTURE TO
REMAIN
EXISTING TONGUE AND GROOVE
CEILING PANELS TO REMAIN
EXISTING 1X3 @16" O.C.
ATTACHED TO 2X TO REMAIN
REMOVE ROOF VENTS, TYP.
EXISTING METAL ROOF
PANELS TO REMAIN
EXISTING METAL
WALL PANELS TO
REMAIN
EXISTING STRUCTURE TO REMAIN
EXISTING CONCRETE CURB TO REMAIN
REMOVE EXISTING CEILING PANELS
AND INSULATION ABOVE PANELS
REMOVE EXISTING WALL PANELS AND
INSULATION BEHIND PANELS
21'-6"
9'
GENERAL NOTES
GRAPHIC SCALE
A. THE CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS AND EXISTING CONDITIONS PRIOR
TO PERFORMING ANY WORK OR FABRICATION OR
PURCHASE OF EQUIPMENT, MATERIALS, AND
ASSEMBLIES. ANY DEVIATIONS SHALL BE
BROUGHT TO THE CONTRACTING OFFICER'S
ATTENTION FOR RESOLUTION BEFORE
PROCEEDING WITH ANY CONSTRUCTION,
FABRICATION, OR EQUIPMENT PURCHASE.
B. ALL UTILITIES AFFECTED BY DEMOLITION SHALL
BE REINSTALLED IN THE WORK OR CAPPED AND
TERMINATED IN ACCORDANCE WITH CODES.
C. CONTRACTOR SHALL PROVIDE TEMPORARY
STRUCTURAL SUPPORTS FOR EXISTING
CONSTRUCTION DURING THE WORK.
D. THE CONTRACTOR SHALL REPAIR ALL EXISTING
CONSTRUCTION TO REMAIN THAT HAS BEEN
DAMAGED BY THE DEMOLITION,
DECONSTRUCTION, OR NEW CONSTRUCTION AS
SPECIFIED IN SPECIFICATION SECTION 02 41 00.
E. BUILDING 005 HAS A FINISHED INTERIOR THAT
WILL REQUIRE THE CONTRACTOR TO PROVIDE
PROTECTION FROM THE WEATHER AND
CONSTRUCTION DEBRIS DURING THE DEMOLITION
AND REPLACEMENT OF THE EXTERIOR ROOF
SYSTEM.
1'-0'
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
DEMO BUILDING SECTIONS
AD301
SCALE:
SHOP SIDE
DEMO BUILDING SECTION
3/8" = 1'-0"
AD301 SCALE:
ROOM 105 - BID OPTION 2
DEMO BUILDING SECTION
3/8" = 1'-0"
AD301
0"
EX
IS
TI
N G
A D
D
IT
IO
N
21'-6"
EXISTING ADDITION
'-5
40'
40'
'-9
SHOP
MEZZANINE
103 102
4 4
A301
A301
104A
104B
105A
GENERAL NOTES
GRAPHIC SCALE
A. THE CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS AND EXISTING CONDITIONS PRIOR
TO PERFORMING ANY WORK OR FABRICATION
OR PURCHASE OF EQUIPMENT, MATERIALS,
AND ASSEMBLIES. ANY DEVIATIONS SHALL BE
BROUGHT TO THE CONTRACTING OFFICER'S
ATTENTION FOR RESOLUTION BEFORE
PROCEEDING WITH ANY CONSTRUCTION,
FABRICATION, OR EQUIPMENT PURCHASE.
B. ALL UTILITIES AFFECTED BY DEMOLITION SHALL
BE REINSTALLED IN THE WORK OR CAPPED
AND TERMINATED IN ACCORDANCE WITH
CODES.
C. CONTRACTOR SHALL PROVIDE TEMPORARY
STRUCTURAL SUPPORTS FOR EXISTING
CONSTRUCTION DURING THE WORK (IF
REQUIRED).
D. THE CONTRACTOR SHALL REPAIR ALL EXISTING
CONSTRUCTION TO REMAIN THAT HAS BEEN
DAMAGED BY THE DEMOLITION,
DECONSTRUCTION, OR NEW CONSTRUCTION
AS SPECIFIED IN SPECIFICATION SECTION 02 41
00.
E. ALL EXTERIOR OVERHEAD DOORS, PERSONNEL
DOORS, AND WINDOWS TO REMAIN IN PLACE.
1'-0'
06' 6'3'
SCALE: 3/16" =
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
FLOOR PLANS
A101
SCALE:
BUILDING 005
FLOOR PLAN
3/16" = 1'-0"
A101
SCALE:
BUILDING 005
MEZZANINE PLAN
3/16" = 1'-0"
A101
KEYED NOTESX
1. PROVIDE SINK. SEE PLUMBING.
2. PROVIDE MINIMUM OF 6 FASTENERS TO
SECURELY FASTEN EACH EXISTING WALL
PANEL (FROM CONCRETE CURB TO CEILING)
TO THE EXISTING WOOD SUBSTRATE. SEE
DETAIL 5/A501.
3. PROVIDE A MINIMUM OF 6 FASTENERS TO
SECURELY FASTEN EACH EXISTING WALL
PANEL (FROM CONCRETE CURB TO THE
JOINT LINE AT APPROXIMATELY 12') TO THE
EXISTING WOOD SUBSTRATE. PROVIDE
PAINTED GYPSUM BOARD FROM THE JOINT
LINE AT APPROXIMATELY 12' TO ROOF DECK
(TO COVER THE EXISTING BATT INSULATION).
4. PROVIDE A MINIMUM OF 6 FASTENERS TO
SECURELY FASTEN EACH EXISTING WALL
PANEL (FROM FLOOR TO CEILING) TO THE
EXISTING WOOD SUBSTRATE. SEE DETAIL
5/A501.
5. BID OPTION 1: PROVIDE INSULATED STEEL
DOORS AND FRAMES TO FIT INTO EXISTING
OPENING. CONTRACTOR MUST VERIFY
OPENING SIZE.
6. BID OPTION 2: PROVIDE MINIMUM 3"
CLOSED-CELL SPRAY FOAM INSULATION
FROM TOP OF CONCRETE CURB TO CEILING.
PROVIDE INTUMESCENT PAINT TO EXPOSED
SPRAY FOAM INSULATION.
7. BID OPTION 2: PROVIDE MINIMUM 3"
CLOSED-CELL SPRAY FOAM INSULATION
FROM TOP OF CONCRETE CURB TO
EXISTING METAL PANEL (APPROX. 9' ABOVE
FINISHED FLOOR). PROVIDE INTUMESCENT
PAINT TO EXPOSED SPRAY FOAM
INSULATION.
8. PROVIDE MINIMUM OF 6 FASTENERS TO
SECURELY FASTEN EACH EXISTING CEILING
PANEL TO THE EXISTING WOOD SUBSTRATE.
SEE DETAIL 5/A501.
0"
EX
IS
TI
N G
A D
D
IT
IO
N
21'-6"
EXISTING ADDITION
'-5
40'
3 3
A501
A501
A501
3 COMPONENT AND CLADDING LOAD DIAGRAM
a a aa a a
WALLS h≤ 60°
GABLE 7° < 8 ≤ 45°
a = 5.0 FT.
a
GENERAL NOTES
GRAPHIC SCALE
A. THE CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS AND EXISTING CONDITIONS PRIOR
TO PERFORMING ANY WORK OR FABRICATION
OR PURCHASE OF EQUIPMENT, MATERIALS,
AND ASSEMBLIES. ANY DEVIATIONS SHALL BE
BROUGHT TO THE CONTRACTING OFFICER'S
ATTENTION FOR RESOLUTION BEFORE
PROCEEDING WITH ANY CONSTRUCTION,
FABRICATION, OR EQUIPMENT PURCHASE.
B. ALL UTILITIES AFFECTED BY DEMOLITION SHALL
BE REINSTALLED IN THE WORK OR CAPPED AND
TERMINATED IN ACCORDANCE WITH CODES.
C. CONTRACTOR SHALL PROVIDE TEMPORARY
STRUCTURAL SUPPORTS FOR EXISTING
CONSTRUCTION DURING THE WORK.
D. THE CONTRACTOR SHALL REPAIR ALL EXISTING
CONSTRUCTION TO REMAIN THAT HAS BEEN
DAMAGED BY THE DEMOLITION,
DECONSTRUCTION, OR NEW CONSTRUCTION AS
SPECIFIED IN SPECIFICATION SECTION 02 41 00.
E. BUILDING 005 HAS A FINISHED INTERIOR THAT
WILL REQUIRE THE CONTRACTOR TO PROVIDE
PROTECTION FROM THE WEATHER AND
CONSTRUCTION DEBRIS DURING THE
DEMOLITION AND REPLACEMENT OF THE
EXTERIOR ROOF SYSTEM.
1'-0'
06' 6'3'
SCALE: 3/16" =
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
ROOF PLAN
A151
SCALE:
BUILDING 005
ROOF PLAN
3/16" = 1'-0"
A151
KEYED NOTESX
1. PROVIDE STANDING SEAM METAL ROOF
PANELS TO MATCH THE EXISTING SLOPE.
PROVIDE CONTINUOUS THERMAL BREAK /
THERMAL BLOCKING (MIN. R-5 VALUE
BLOCKING) BETWEEN METAL PANELS AND
STRUCTURAL STEEL AT CLIPS.
2. EXISTING ADDITION ROOF TO REMAIN.
3. EXISTING AWNING OVER PERSONNEL DOOR
TO REMAIN.
4. EXISTING CANOPY OVER HVAC EQUIPMENT
TO REMAIN.
5. RECONNECT EXISTING FLUE AND PROVIDE
FLASHING. SEE DETAIL 4/A501.
6. PROVIDE RIDGE CAP.
SCALE:
STRUCTURAL LOAD DIAGRAM
NOT TO SCALE
A151
EXISTING ADDITION EXISTING ADDITION
EXISTING ADDITION
PROVIDE STANDING SEAM METAL ROOF
PROVIDE STANDING SEAM METAL ROOF
PROVIDE STANDING
SEAM METAL ROOF
PROVIDE EXTERIOR LIGHT (SEE ELECTRICAL)
PROVIDE EXTERIOR LIGHT (SEE ELECTRICAL)PROVIDE EXTERIOR LIGHT
(SEE ELECTRICAL)
PROVIDE STANDING
SEAM METAL ROOF
'-1
0"
PROVIDE RIDGE CAP
PROVIDE RIDGE CAP
PROVIDE RIDGE CAP
PROVIDE RIDGE CAP
'-1
0"
GENERAL NOTES
GRAPHIC SCALE
A. THE CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS AND EXISTING CONDITIONS PRIOR TO
PERFORMING ANY WORK OR FABRICATION OR
PURCHASE OF EQUIPMENT, MATERIALS, AND
ASSEMBLIES. ANY DEVIATIONS SHALL BE BROUGHT
TO THE CONTRACTING OFFICER'S ATTENTION FOR
RESOLUTION BEFORE PROCEEDING WITH ANY
CONSTRUCTION, FABRICATION, OR EQUIPMENT
PURCHASE.
B. ALL UTILITIES AFFECTED BY DEMOLITION SHALL BE
REINSTALLED IN THE WORK OR CAPPED AND
TERMINATED IN ACCORDANCE WITH CODES.
C. CONTRACTOR SHALL PROVIDE TEMPORARY
STRUCTURAL SUPPORTS FOR EXISTING
CONSTRUCTION DURING THE WORK.
D. THE CONTRACTOR SHALL REPAIR ALL EXISTING
CONSTRUCTION TO REMAIN THAT HAS BEEN
DAMAGED BY THE DEMOLITION, DECONSTRUCTION,
OR NEW CONSTRUCTION AS SPECIFIED IN
SPECIFICATION SECTION 02 41 00.
E. BUILDING 005 HAS A FINISHED INTERIOR THAT WILL
REQUIRE THE CONTRACTOR TO PROVIDE
PROTECTION FROM THE WEATHER AND
CONSTRUCTION DEBRIS DURING THE DEMOLITION
AND REPLACEMENT OF THE EXTERIOR ROOF
SYSTEM.
1'-0'
06' 6'3'
SCALE: 3/16" =
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
ELEVATIONS
A201
SCALE:
BUILDING 005
NORTH ELEVATION
3/16" = 1'-0"
A201 SCALE:
BUILDING 005
EAST ELEVATION
3/16" = 1'-0"
A201
SCALE:
BUILDING 005
SOUTH ELEVATION
3/16" = 1'-0"
A201 SCALE:
BUILDING 005
WEST ELEVATION
3/16" = 1'-0"
A201
38'-9 1/2"
4' -3
PROVIDE STANDING SEAM METAL ROOF PANELS
EXISTING 6" ROOF PURLINS TO REMAIN
4' -3
40'
9"
EXISTING METAL WALL
PANELS TO REMAIN
EXISTING PLYWOOD WALL (APPROX. 4' HIGH) TO REMAIN
SECURELY FASTEN THE EXISTING TONGUE AND
GROOVE WALL PANELS WITH A MINIMUM OF 6
FASTENERS PER PANEL TO THE WOOD SUBSTRATE
EXISTING STRUCTURE TO REMAIN
EXISTING 1X3 ATTACHED TO 2X TO REMAIN
EXISTING WALL GIRTS TO REMAIN
EXISTING 2X @ 21" O.C. ATTACHED TO ROOF PURLINS TO REMAIN
SECURELY FASTEN THE REMAINING
TONGUE AND GROOVE WALL PANELS
WITH A MINIMUM OF 6 FASTENERS
PER PANEL TO THE WOOD SUBSTRATE
SHOP
EXISTING WALL
INSULATION TO REMAIN
EXISTING ROOF INSULATION TO REMAIN
PROVIDE 6" (MIN. R-19) BATT INSULATION
ALONG ROOF RIDGE
PROVIDE GYPSUM WALL BOARD WITH LEVEL 3
FINISH WHERE PANELS WERE REMOVED;
SECURELY FASTEN TO THE WOOD SUBSTRATE
EXISTING STRUCTURE
IN FOREGROUND
PROVIDE DRIP
FLASHING
PROVIDE RIDGE CAP
'-1
1"
EXISTING
STRUCTURE
TO REMAIN
SECURELY FASTEN THE EXISTING
TONGUE AND GROOVE CEILING PANELS
WITH A MINIMUM OF 6 FASTENERS PER
PANEL TO THE WOOD SUBSTRATE
EXISTING 1X3 @16" O.C.
ATTACHED TO 2X TO REMAIN
8"
EXISTING METAL ROOF
PANELS TO REMAIN
EXISTING METAL
WALL PANELS TO
REMAIN
EXISTING STRUCTURE TO REMAIN
PROVIDE MINIMUM 3" CLOSED-CELL SPRAY FOAM INSULATION
FROM TOP OF CONCRETE CURB TO ROOF DECK
PROVIDE MINIMUM 4" CLOSED-CELL SPRAY
FOAM INSULATION TO METAL ROOF PANELS AND
EXISTING STRUCTURE. APPLY INTUMESCENT
PAINT TO EXPOSED SPRAY FOAM INSULATION.
EXISTING CONCRETE CURB TO REMAIN
PROVIDE 2-1/2" METAL STUDS @ 16" O.C.; ALIGN TO CONCRETE
CURB EDGE; EXTEND TO ROOF SPRAY FOAM INSULATION
PROVIDE 5/8" ABUSE RESISTANT GYPSUM WALL BOARD;
ATTACH TO METAL STUDS; OVERLAP 3" ON CONCRETE CURB
9'
GENERAL NOTES
GRAPHIC SCALE
A. THE CONTRACTOR SHALL FIELD VERIFY ALL
DIMENSIONS AND EXISTING CONDITIONS PRIOR TO
PERFORMING ANY WORK OR FABRICATION OR
PURCHASE OF EQUIPMENT, MATERIALS, AND
ASSEMBLIES. ANY DEVIATIONS SHALL BE BROUGHT
TO THE CONTRACTING OFFICER'S ATTENTION FOR
RESOLUTION BEFORE PROCEEDING WITH ANY
CONSTRUCTION, FABRICATION, OR EQUIPMENT
PURCHASE.
B. ALL UTILITIES AFFECTED BY DEMOLITION SHALL BE
REINSTALLED IN THE WORK OR CAPPED AND
TERMINATED IN ACCORDANCE WITH CODES.
C. CONTRACTOR SHALL PROVIDE TEMPORARY
STRUCTURAL SUPPORTS FOR EXISTING
CONSTRUCTION DURING THE WORK.
D. THE CONTRACTOR SHALL REPAIR ALL EXISTING
CONSTRUCTION TO REMAIN THAT HAS BEEN
DAMAGED BY THE DEMOLITION, DECONSTRUCTION,
OR NEW CONSTRUCTION AS SPECIFIED IN
SPECIFICATION SECTION 02 41 00.
E. BUILDING 005 HAS A FINISHED INTERIOR THAT WILL
REQUIRE THE CONTRACTOR TO PROVIDE
PROTECTION FROM THE WEATHER AND
CONSTRUCTION DEBRIS DURING THE DEMOLITION
AND REPLACEMENT OF THE EXTERIOR ROOF
SYSTEM.
1'-0'
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
BUILDING SECTIONS
A301
SCALE:
SHOP SIDE
BUILDING SECTION
3/8" = 1'-0"
A301 SCALE:
ROOM 105 - BID OPTION 2
BUILDING SECTION
3/8" = 1'-0"
A301
SCULPTED
RAKE TRIM
STITCH SCREW
AT 12" O.C. (TYP.) CONTINUOUS
TAPE SEAL
STANDING SEAM
ROOFING PANEL
STITCH SCREW
AT 12" O.C. (TYP.)
CLOSURE EXISTING
STRUCTURE
EXISTING ROOF PURLINS
STANDING SEAM
ROOFING PANEL
METAL RIDGE CAP FLASHING
PANEL CLOSURELOCKRIVET AT 12" O.C.
BOTH SIDES
EXISTING INSULATION
TO REMAIN
EXISTING METAL
WALL PANELS TO
REMAIN
STANDING SEAM
ROOFING PANEL TO
MATCH EXISTING
SLOPE
EXISTING EAVE STRUT
EXISTING METAL
WALL PANELS TO
REMAIN
INSULATION
APPROPRIATE
FOR STACK
TEMPERATURE
4'' MIN. FLANGE
SHEET-METAL RAIN COLLAR
TEMPERATURE- APPROPRIATE
SEALANT
STAINLESS-STEEL DRAWBAND
SEALANT
SHEET-METAL
FLASHING
COLLAR
8'' M
IN
FL
AS
HI
NG
HE
IG
HT
GASKETED FASTENERS—
SECURE FLASHING
COLLAR FLANGE TO ROOF
PANEL
HIGH TEMPERATURE
UNDERLAYMENT
SET SHEET-METAL COLLAR
IN CONTINUOUS BEAD OF
SEALANT
METAL ROOF PANEL
ROOF SUBSTRATE
PROVIDE 6" (MIN. R-19) BATT
INSULATION ALONG ROOF RIDGE
PANEL WIDTH
PA
NE
L H
EI
GH
T
(V
AR
IE
S)
2"
2"
PROVIDE MINIMUM (6) DRYWALL
SCREWS PER PANEL LOCATED
2" FROM EDGE; (2) AT TOP OF
PANEL, (2) MIDDLE OF PANEL,
AND (2) AT BOTTOM OF PANEL
PROVIDE PERIMETER
EDGE METAL FLASHING
WITH CONTINUOUS CLEAT
MARK B
2'-8"
MARK A
5'
7' 7'
DOOR AND FRAME SCHEDULE
DOOR FIRE
RATING
FRAME HARDWARE
SET NOTES
NUMBER MARK WD HGT THK MTL FINISH MTL FINISH
104A A 5'-0" 7'-0" 1 3/4" HM PAINT STEEL PAINT HW-2 1
104B B 2'-8" 7'-0" 1 3/4" HM PAINT STEEL PAINT HW-1 1
105A C 3'-0" 7'-0" 1 3/4" HM PAINT STEEL PAINT HW-1 1
NOTES:
1. INSULATED.
ABBREVIATIONS:
HM HOLLOW METAL
MARK C
3'
7'
DOOR AS
SCHEDULED
METAL FRAME AS
SPECIFIED
STUD TRACK
EXISTING STUD WALL
METAL FRAME AS
SPECIFIED
DOOR AS
SCHEDULED
JAMB ANCHOR.
(3) PER JAMB
EXISTING TONGUE
AND GROOVE
WALL PANEL
2"
HEAD
2"
JAMB
EXISTING TONGUE
AND GROOVE WALL
PANEL
DOOR AS SCHEDULED
EXISTING SLAB
THRESHOLD SET IN BED
OF SEALANT W/MIN. (3)
1/4" DIA. ANCHORS
DOOR SWEEP
SILL
METAL FRAME AS
SPECIFIED
2"
GENERAL NOTES
GRAPHIC SCALE
A. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND
EXISTING CONDITIONS PRIOR TO PERFORMING ANY WORK OR
FABRICATION OR PURCHASE OF EQUIPMENT, MATERIALS, AND
ASSEMBLIES. ANY DEVIATIONS SHALL BE BROUGHT TO THE
CONTRACTING OFFICER'S ATTENTION FOR RESOLUTION
BEFORE PROCEEDING WITH ANY CONSTRUCTION,
FABRICATION, OR EQUIPMENT PURCHASE.
B. ALL UTILITIES AFFECTED BY DEMOLITION SHALL BE
REINSTALLED IN THE WORK OR CAPPED AND TERMINATED IN
ACCORDANCE WITH CODES.
C. CONTRACTOR SHALL PROVIDE TEMPORARY STRUCTURAL
SUPPORTS FOR EXISTING CONSTRUCTION DURING THE WORK.
D. THE CONTRACTOR SHALL REPAIR ALL EXISTING
CONSTRUCTION TO REMAIN THAT HAS BEEN DAMAGED BY THE
DEMOLITION, DECONSTRUCTION, OR NEW CONSTRUCTION AS
SPECIFIED IN SPECIFICATION SECTION 02 41 00.
E. BUILDING 005 HAS A FINISHED INTERIOR THAT WILL REQUIRE
THE CONTRACTOR TO PROVIDE PROTECTION FROM THE
WEATHER AND CONSTRUCTION DEBRIS DURING THE
DEMOLITION AND REPLACEMENT OF THE EXTERIOR ROOF
SYSTEM.
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
DETAILS AND DOOR SCHEDULE
A501
SCALE:
ROOF RIDGE DETAIL
1-1/2" = 1'-0"
A501 SCALE:
ROOF EAVE DETAIL
1-1/2" = 1'-0"
A501 SCALE:
ROOF RAKE TRIM DETAIL
1-1/2" = 1'-0"
A501
08" 8"
1'-0'SCALE: 1-1/2" =
4"
SCALE:
FLUE PENETRATION DETAIL
NOT TO SCALE
A501
SCALE:
EXISTING CEILING/WALL
PANEL FASTENER DETAIL
1-1/2" = 1'-0"
A501 SCALE:
DOOR DETAILS
NOT TO SCALE
A501 SCALE:
DOOR SCHEDULE
NOT TO SCALE
A501
SHOP
103 102
SHOP
103 102
GENERAL NOTES
LEGEND
A. EXISTING EQUIPMENT SHOWN ON THESE
DRAWINGS ARE FOR PROJECT SCOPE
CLARIFICATION. ALL EXISTING, PIPING
AND APPURTENANCES ARE NOT SHOWN
ON PLANS.
SCALE:
BUILDING 005
DEMO FLOOR PLAN
3/16" = 1'-0"
P101
KEYED NOTESX
1. DEMOLISH EXISTING SINK, DRAIN, AND
FAUCET. ROUGH IN AND POINT OF USE
ELECTRIC WATER HEATER TO REMAIN FOR
CONNECTION TO NEW WORK.
2. PROVIDE 2 COMPARTMENT STAINLESS
STEEL SINK, DRAIN, AND FAUCET. CONNECT
TO EXISTING DOMESTIC COLD WATER LINE
AND SANITARY LINE IN WALL. ANCHOR SINK
TO THE WALL IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS.
CONNECT TO EXISTING POINT OF USE
WATER HEATER. MODIFY EXISTING WATER
HEATER TO ACCOMMODATE NEW WORK.
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
PLUMBING FLOOR PLAN
P101
GRAPHIC SCALE
1'-0'
06' 6'3'
SCALE: 3/16" =
DEMO
SCALE:
BUILDING 005
FLOOR PLAN
3/16" = 1'-0"
P101
P-2
AutoCAD SHX Text
NORTH
AutoCAD SHX Text
PPM
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text Agricultural
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DATE
AutoCAD SHX Text c
AutoCAD SHX Text P.A.
AutoCAD SHX Text
FIRM
AutoCAD SHX Text
NO.
AutoCAD SHX Text
EPM
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
USDA
AutoCAD SHX Text
BY
AutoCAD SHX Text
AGRICULTURAL RESEARCH SERVICE
AutoCAD SHX Text
OF
AutoCAD SHX Text
THE
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
JOB #
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
AutoCAD SHX Text Johnson M Adams
AutoCAD SHX Text
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
AutoCAD SHX Text
USDA AGRICULTURAL RESEARCH SERVICE
AutoCAD SHX Text
WENATCHEE BUILDING REPAIRS
AutoCAD SHX Text
TREE FRUIT RESEARCH LABORATORY
AutoCAD SHX Text
WENATCHEE, WA
AutoCAD SHX Text 12 18
AutoCAD SHX Text 3/21/25
AutoCAD SHX Text
JEH
AutoCAD SHX Text
JTP
AutoCAD SHX Text
JGM
AutoCAD SHX Text
PWA AAO ACQ/PER PROP
AutoCAD SHX Text
800 BUCHANAN STREET
AutoCAD SHX Text
ALBANY, CA 94710
AutoCAD SHX Text
XXX
AutoCAD SHX Text 4924-M
AutoCAD SHX Text
LANE
AutoCAD SHX Text
XXX
AutoCAD SHX Text
CUSHMAN
AutoCAD SHX Text
XXX
AutoCAD SHX Text
NORTH
Emilie Oakes Sam WA Seal
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
PLUMBING SCHEDULES AND DETAILS
P601
P-1
MARK DESCRIPTION CW HW MIN. WASTE REMARKSVENT
PLUMBING FIXTURE SCHEDULE
DOUBLE COMPARTMENT SINK 1-1/2"1/2" 1/2" 2" PROVIDE TYPE 304 STAINLESS STEEL 2 COMPARTMENT SINK WITH
GALVINIZED STEEL LEGS AND ADJUSTABLE BULLET FEET. PROVIDE
WITH 2 GPM AERATOR,CHROME-PLATED BRASS CONSTRUCTED
SWINGING SPOUT.
SCALE:
TWO COMPARTMENT SINK DETAIL
NOT TO SCALE
P601
SS STRAINER BASKET
WITH STRAINER
SANITARY TEE
CONNECT TO EXISTING
SANITARY
INSULATED TRAP
2" MIN.
DWV 90 ELBOW
2 COMPARTMENT
STAINLESS STEEL SINK
AND FAUCET PER
FIXTURE SCHEDULE
1/2" X 3/8" ANGLE STOP
VALVE DOMESTIC COLD
WATER SUPPLY
DWV PIPING 2" MIN.
3/8" MIN. BRAIDED SS
SUPPLY OR COPPER
TUBING PER SPEC
EXISTING WATER
HEATER TO REMAIN
3/8" DOMESTIC HOT
WATER SUPPLY
AutoCAD SHX Text
PPM
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text Agricultural
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DATE
AutoCAD SHX Text c
AutoCAD SHX Text P.A.
AutoCAD SHX Text
FIRM
AutoCAD SHX Text
NO.
AutoCAD SHX Text
EPM
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
USDA
AutoCAD SHX Text
BY
AutoCAD SHX Text
AGRICULTURAL RESEARCH SERVICE
AutoCAD SHX Text
OF
AutoCAD SHX Text
THE
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
JOB #
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
AutoCAD SHX Text Johnson M Adams
AutoCAD SHX Text
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
AutoCAD SHX Text
USDA AGRICULTURAL RESEARCH SERVICE
AutoCAD SHX Text
WENATCHEE BUILDING REPAIRS
AutoCAD SHX Text
TREE FRUIT RESEARCH LABORATORY
AutoCAD SHX Text
WENATCHEE, WA
AutoCAD SHX Text 13 18
AutoCAD SHX Text 3/21/25
AutoCAD SHX Text
JEH
AutoCAD SHX Text
JTP
AutoCAD SHX Text
JGM
AutoCAD SHX Text
PWA AAO ACQ/PER PROP
AutoCAD SHX Text
800 BUCHANAN STREET
AutoCAD SHX Text
ALBANY, CA 94710
AutoCAD SHX Text
XXX
AutoCAD SHX Text 4924-M
AutoCAD SHX Text
LANE
AutoCAD SHX Text
XXX
AutoCAD SHX Text
CUSHMAN
AutoCAD SHX Text
XXX
Emilie Oakes Sam WA Seal
ELECTRICAL GENERAL NOTES:
1. THE WORK MUST CONFORM WITH ALL REQUIREMENTS OF:
· NFPA 70, NATIONAL ELECTRICAL CODE (NEC) (2020); (ERTA 1-2024); (TIA-24-1)
· NFPA 101, LIFE SAFETY CODE (2024)
· NFPA 780, STANDARDS FOR INSTALLATION OF LIGHTNING PROTECTION SYSTEMS (2023)
· IEEE C2, NATIONAL ELECTRICAL SAFETY CODE (NESC) (2023)
· UFC 1-200-01, DOD BUILDING CODE (GENERAL BUILDING REQUIREMENTS),
· UFC 1-200-02, HIGH PERFORMANCE AND SUSTAINABLE BUILDING REQUIREMENTS
· UFC 3-501-01, ELECTRICAL ENGINEERING
· UFC 3-520-01 INTERIOR ELECTRICAL SYSTEMS
· UFC 3-530-01, INTERIOR AND EXTERIOR LIGHTING AND CONTROLS
· UFC 3-550-01, EXTERIOR ELECTRICAL POWER DISTRIBUTION
· UFC 3-560-01, OPERATION AND MAINTENANCE: ELECTRICAL SAFETY
· UFC 3-575-01, LIGHTNING AND STATIC ELECTRICITY PROTECTION SYSTEMS
· UFC 3-580-01, TELECOMMUNICATIONS BUILDING CABLING SYSTEMS PLANNING AND DESIGN
· UFC 4-010-01, DOD ANTITERRORISM STANDARDS FOR BUILDINGS
· UFC 4-011-06, CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS
· ASHRAE 90.1, ENERGY STANDARD FOR BUILDINGS EXCEPT LOW-RISE RESIDENTIAL BUILDINGS (2019)
*CRITERIA AND STANDARDS LISTED ALSO INCLUDE SPECIFIED STANDARDS AND RELATED SECTIONS AS PART OF THE DESIGN.
2. MINIMUM RACEWAY SIZE MUST BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT RACEWAY FILL RATIO TO LESS THAN 40% FULL FOR FEEDERS
AND 20% FOR BRANCH CIRCUITS IAW CNIFR REQUIREMENTS.
3. THE ELECTRICAL CONTRACTOR MUST CAREFULLY COORDINATE WORK WITH OTHER TRADES THROUGH THE GENERAL CONTRACTOR AND MUST BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE FOR RECESSED LUMINAIRES AND CORRECT ROUGH-IN
LOCATIONS OF ELECTRICAL CONNECTIONS.
4. VERIFY DOOR SWINGS WITH ARCHITECTURAL DRAWINGS BEFORE ROUGHING IN WALL SWITCHES. SWITCHES IN THE SAME LOCATION MUST BE GANGED
TOGETHER IN ONE COMMON BACKBOX AND MUST HAVE ONE COMMON FACE PLATE.
5. ALL FEEDERS AND BRANCH CIRCUITS MUST INCLUDE A GREEN INSULATED GROUND CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTIPLE BRANCH CIRCUITS IN ONE RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR.
6. VERIFY LUMINAIRE, CEILING MOUNTED OCCUPANCY SENSOR LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS AND DIMENSIONS PRIOR TO INSTALLATION. VERIFY EXACT LOCATIONS OF MOTORS AND EQUIPMENT BEFORE ROUGHING-IN.
7. EXISTING ELECTRICAL WORK (NOT SHOWN) MUST REMAIN, UNLESS INDICATED OTHERWISE. SHOULD ANY EXISTING ELECTRICAL POWER, LIGHTING OR AUXILIARY CIRCUIT, FEEDER OR EQUIPMENT BE SEVERED, DISCONNECTED OR DELETED IN THE PROCESS OF CONSTRUCTION OR REMODELING WHICH IS DONE AS A RESULT OF CONTRACT PLANS AND SPECIFICATIONS, AND UNLESS SPECIFICALLY DESIGNATED BY THE DRAWINGS TO BE DELETED, THEN SAID CIRCUIT OR FEEDER MUST BE RESTORED TO WORKING CONDITION. THE RESTORATION MUST INCLUDE RE-ROUTING, RELOCATION, RECONNECTION OR REPLACEMENT AS MAY BE REQUIRED BY THE NEW WORK. ANY SUCH WORK REQUIRED MUST BE INCLUDED IN THE CONTRACT AND NO EXTRA COMPENSATION
WILL BE GRANTED.
8. NEW WORK MUST BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER, SIMILAR ITEMS OF NEW WORK MUST BE CHECKED AGAINST EXISTING
WORK
9. REFER TO ONE-LINE DIAGRAMS, SCHEDULES AND RISER DIAGRAMS FOR CONDUCTOR AND CONDUIT SIZES NOT SHOWN ON PLANS.
10. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS AND SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.
11. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT EQUIPMENT FROM ALL CONNECTIONS, REMOVE FROM THE OWNER'S SITE, AND DISPOSE OF IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST OF DISPOSAL IS ENTIRELY THE CONTRACTOR'S RESPONSIBILITY.
12. ALL CONDUCTORS ARE COPPER UNLESS SPECIFICALLY NOTED AS ALUMINUM.
13. CONTRACTOR MUST FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS BEFORE PROCUREMENT OF ANY MATERIALS AND
DEVELOPMENT OF ANY SHOP DRAWINGS OR SUBMITTALS.
14. PROVIDE LABELS ON ALL RECEPTACLES, WALL MOUNTED LIGHT SWITCHES/OCCUPANCY SENSORS AND JUNCTION BOXES INDICATING THE SOURCE PANEL & CIRCUIT(S). TEXT MUST BE BLACK, 1/4" IN HEIGHT PRINTED ON A CLEAR LABEL. HANDWRITTEN LABELS ARE NOT PERMITTED EXCEPT FOR JUNCTION BOXES LOCATED ABOVE FINISHED CEILING WHICH CAN BE HANDWRITTEN WITH AN INDELIBLE MARKER.
15. ALL EQUIPMENT PADS FOR INTERIOR ELECTRICAL EQUIPMENT MUST BE FLUSH WITH FRONT SIDE OF EQUIPMENT AND EXTEND AT LEAST 2" BEYOND
THE FOOTPRINT OF THE EQUIPMENT ON ALL OTHER SIDES.
ELECTRICAL ABBREVIATIONS:
A OR AMP
ACC
AC
AC
AF
AFF
AFG
AHU
AIC
AL
AM
ASYM
AT
ATS
AUTO
AWG
B
BC
BCW
BFF
BFG
BLDG
BMGB
C
CAT
CB
CCT
CCTV
CFCI
CH
CHWCP
CHWP
CHWSP
CKT
CMH
CMS
CP
CPT
CRAC
CRI
CT
CT
CU
CWP
D
DC
DF
DH or DUH
DHWCP
DISC
DOAS
DPST
DPDT
DSCU
DSHP
DSS
DWBP
DX
EC
ECB
EF
ELEC
EMH
EMT
E or EMER
EPA
EQUIP
ERV
ERU
EXIST or EX
EUH
EXP
EWC
EWH
F
FACP
FCU
FLEX
FWE
G OR GND
GFGI
GFI
GRS
GUH
GWH
H or HT
HAC
HOA
HP
HP
HT
HVU
HWCP
HWP
HWRP
HWSP
AMPERE(S)
AIR COOLED CHILLER
ALTERNATING CURRENT
AIR COMPRESSOR / AIR CURTAIN
AMP FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMMETER
ASYMMETRICAL
AMP TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AMERICAN WIRE GAUGE
BOILER
BRANCH CONTROLLER
BARE COPPER WIRE
BELOW FINISHED FLOOR
BELOW FINISHED GRADE
BUILDING
BUILDING MASTER GROUNDING BUSBAR
CONDUIT
CATEGORY
CIRCUIT BREAKER
CORRELATED COLOR TEMPERATURE
CLOSED CIRCUIT TELEVISION
CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CHILLER
CHILLED WATER CIRCULATING PUMP IN A PRIMARY-SECONDARY SYSTEM
CHILLED WATER PUMP
CHILLED WATER SUPPLY PUMP IN A PRIMARY-SECONDARY SYSTEM
CIRCUIT
COMMUNICATIONS MANHOLE
COMBINATION MOTOR STARTER
CONDENSATE PUMP
CONTROL POWER TRANSFORMER
COMPUTER ROOM AC UNIT
COLOR RENDERING INDEX
CURRENT TRANSFORMER
COOLING TOWER
COPPER OR CONDENSING UNIT
CONDENSER WATER PUMP
DEPTH
DIRECT CURRENT
DESTRATIFICATION FAN
DUCT HEATERS
DOMESTIC HOT WATER CIRCULATING PUMP
DISCONNECT SWITCH
DEDICATED OUTSIDE AIR SYSTEM (UNIT)
DOUBLE POLE SINGLE THROW
DOUBLE POLE DOUBLE THROW
DUCTLESS SPLIT CONDENSING UNIT (POWERS THE DSS INDOOR UNIT)
DUCTLESS SPLIT HEAT PUMP (POWERS THE DSS INDOOR UNIT)
DUCTLESS SPLIT SYSTEM (INDOOR UNIT)
DOMESTIC WATER BOOSTER PUMP
DIRECT EXPANSION (DX) COOLING COIL
EMPTY CONDUIT
ENCLOSED CIRCUIT BREAKER
EXHAUST FAN
ELECTRICAL
ELECTRICAL MANHOLE
ELECTRICAL METALLIC TUBING
EMERGENCY
EFFECTIVE PROJECTED AREA
EQUIPMENT
ENERGY RECOVERY VENTILATOR
ENERGY RECOVERY UNIT
EXISTING
ELECTRIC UNIT HEATER
EXPLOSION PROOF
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FUSE
FIRE ALARM CONTROL PANEL
FAN COIL UNIT
FLEXIBLE
FURNISHED WITH EQUIPMENT
GROUND
GOVERNMENT FURNISHED GOVERNMENT INSTALLED
GROUND FAULT INTERRUPTER
GALVANIZED RIGID STEEL CONDUIT
GAS UNIT HEATER
GAS WATER HEATER
HEIGHT
HEATED AIR CURTAIN
HAND-OFF AUTOMATIC
HORSE POWER
HEAT PUMP (OUTDOOR PORTION OF SPLIT SYSTEM HEAT PUMP, USE CU FOR STANDARD
DX OUTDOOR UNIT)
HEAT TRACKING
HEATING/VENTILATING UNIT
HEATING WATER CIRCULATING PUMP IN A PRIMARY-SECONDARY SYSTEM
HEATING WATER SUPPLY IN A PRIMARY-ONLY SYSTEM
HOT WATER RECIRCULATION PUMP
HEATING WATER SUPPLY PUMP IN A PRIMARY-SECONDARY SYSTEM
HWUH
HZ
IAW
IDS
IMC
IRH
J OR JB
K
KAIC
KCM OR KCMIL
KEF
KH
KV
KVA
KW
KWHR
L
LA
LAN
LAV
LM
LTG
MAU
MAX
MCA
MCB or MB
MCC
MGB
MH
MIN
MLO
MOD
MT or MTD
MRS
N
NEC
NEMA
NFPA
NC
NESC
NL
NO
NTS
P
PA
PBB
PDU
PF
PH
PIU
PMT
PNL
PTAC
PVC
RBB
RECEPT or RECP
RF
RH
RMC
RMS
RTU
RVNR
SA
SBB
SCCR
SD
SF
S/N
SP
SPD
SPDT
SPEC
SPST
SWBD
SWGR
TEBC
TMGB
TOL
TP
TYP
U
UH
UG
UIO
UL
UTP
V
VA
VAV
VEF
VM
VRF
W
WC
WEF
WH
WHDM
WSHP
WP
WPIU
XFMR
Z
HOT WATER UNIT HEATER
HERTZ
IN ACCORDANCE WITH
INTRUSION DETECTION SYSTEM
INTERMEDIATE METAL CONDUIT
INFRARED HEATER
JUNCTION BOX
KILO
THOUSAND AMPERE INTERRUPTING CAPACITY
THOUSAND OF CIRCULAR MILS
KITCHEN EXHAUST FAN
KITCHEN HOOD
KILOVOLT
KILOVOLT-AMPERES
KILOWATT
KILOWATT-HOUR
LENGTH
LIGHTNING ARRESTOR
LOCAL AREA NETWORK
LAVATORY
LOCKHEED MARTIN
LIGHTING
MAKE-UP AIR UNIT
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN GROUND BAR
MANHOLE or MOUNTING HEIGHT
MINIMUM
MAIN LUGS ONLY
MOTOR OPERATED DAMPER
MOUNT or MOUNTED
MOTOR RATED SWITCH
NEUTRAL
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
NORMALLY CLOSED
NATIONAL ELECTRICAL SAFETY CODE
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
POLE(S) or PUMP
PUBLIC ADDRESS
PRIMARY BONDING BUSBAR
POWER DISTRIBUTION UNIT
POWER FACTOR
PHASE
VAV TERMINAL UNIT WITH PARALLEL OR SERIES FAN (PRIMARY INDUCTION UNIT)
PAD MOUNTED TRANSFORMER
PANEL OR PANELBOARD
PACKAGED THRU-WALL AIR CONDITIONER
POLYVINYL CHLORIDE
RACK BONDING BUSBAR
RECEPTACLE
RETURN FAN
RADIANT HEATERS (ELECTRIC)
RIGID METAL CONDUIT
ROOT MEAN SQUARE
ROOF TOP UNIT
REDUCED VOLTAGE NON-REVERSING
SURGE ARRESTOR
SECONDARY BONDING BUSBAR
SHORT CIRCUIT CURRENT RATING
SMOKE DAMPER
SUPPLY FAN
SOLID NEUTRAL
SUMP PUMP
SURGE PROTECTIVE DEVICE
SINGLE POLE DOUBLE THROW
SPECIFICATIONS
SINGLE POLE SINGLE THROW
SWITCHBOARD
SWITCHGEAR
TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR
THERMAL OVERLOAD
TWISTED PAIR
TYPICAL
URINAL
UNIT HEATER
UNDERGROUND
UNLESS INDICATED OTHERWISE
UNDERWRITERS LABORATORY
UNSHIELDED TWISTED PAIR
VOLTS
VOLT AMPERES
VAV TERMINAL UNIT
VEHICLE EXHAUST FAN
VOLTMETER
VARIABLE REFRIGERANT FLOW SYSTEM
WATTS or WIRE or WIDTH
WATER CLOSET
WELDING EXHAUST FAN
WATER HEATER
WATTHOUR DEMAND METER
WATER SOURCE HEAT PUMP
WEATHERPROOF
WEATHERPROOF IN USE
TRANSFORMER
IMPEDANCE
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
ELECTRICAL NOTES AND ABBREVIATIONS
E001 iPad iPad
LA-1
ELECTRICAL LEGEND
1. ALL EQUIPMENT AND DEVICES ARE TO BE FLUSH MOUNTED UNLESS
OTHERWISE NOTED.
2. DEVICES NOTED AS "GFI" MUST BE GROUND FAULT CIRCUIT
INTERRUPTING DEVICES.
3. DEVICES NOTED AS "WP" MUST BE GFI AND WEATHERPROOF.
4.
PROVIDE UNSWITCHED POWER TO EMERGENCY BATTERY
PACKS.
SINGLE-POLE, SINGLE-THROW SWITCH. MOUNT CENTERLINE
OF BOX AT 45"A.F.F. UNLESS NOTED OTHERWISE.
PE
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNTED 18" A.F.F. TO
CENTERLINE OF BOX UNLESS NOTED OTHERWISE.
PHOTOCELL.
SURFACE MOUNTED/SUSPENDED LINEAR
FIXTURE.
CEILING MOUNTED EXIT SIGN. PROVIDE CHEVRONS AS
INDICATED BY ARROWS.
CONDUIT AND WIRING RECEPTACLES
SWITCHES
NOTE: THE NUMBER BESIDE THE SYMBOL IS THE CIRCUIT NUMBER. THE LETTER
BESIDE THE SYMBOL IS THE FIXTURE TYPE DESCRIBED IN THE LIGHT FIXTURE
SCHEDULE.
LUMINAIRES (SEE LIGHT FIXTURE SCHEDULE)LEGEND GENERAL NOTES
MISCELLANEOUS
CIRCUITRY RUN IN STRAIGHT LINE SEGMENTS SIGNIFIES
EXPOSED SURFACE-MOUNTED RACEWAY (SEE
SPECIFICATIONS).
HOMERUN TO PANELBOARD. ARC DENOTES CONCEALED
CIRCUITRY. TEXT DENOTES PANELBOARD NAME WITH
CIRCUIT NUMBER. DEVICES HAVING CIRCUIT NUMBERS
LOCATED BESIDE THEM MAY NOT SHOW THE CIRCUIT
NUMBERS AT THE HOMERUN ARROWS.
SURFACE MOUNTED/SUSPENDED EMERGENCY FIXTURE.
DEVICES NOTED AS "WPIU" MUST BE GFI AND WEATHERPROOF IN USE.
5.
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
LEGEND
E002
LED WALL MOUNTED FIXTURE
LED WALL MOUNTED EMERGENCY FIXTURE
DISCONNECT SWITCH EXISTING TO REMAIN.
GEAR
ETR
108T
UT-1
MSB-EX
A-EX
ALL WORK IN THIS AREA SHALL
BE UNDER BID OPTION 2.
EX
EX
EX
EX
EX
EX
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
ELECTRICAL DEMO PLAN
ED101
X
1. EXISTING TO REMAIN ELECTRICAL PANEL.
2. EXISTING SECURITY LIGHT. DEMOLISH LIGHT, CONDUIT
AND WIRE TO NEAREST JUNCTION BOX. MAINTAIN
EXISTING CIRCUIT FUNCTIONALITY FOR ANY OTHER
DEVICES ON THE EXISTING CIRCUIT AS REQUIRED.
3. REMOVE ALL EXISTING LIGHT FIXTURES IN ROOM 105.
PROTECT AND STORE FIXTURES FOR RE-USE. (BID
OPTION 2)
4. DEMOLISH ALL RECEPTACLES AND LIGHTING
CONTROLS IN ROOM 105. DEMOLISH CONDUIT AND
CIRCUITRY BACK TO NEAREST ASSOCIATED JUNCTION
BOX. SEE E-101 FOR NEW RECEPTACLE AND CIRCUITRY
PROVISIONS. (BID OPTION 2)
SCALE:
BUILDING 005
ELECTRICAL DEMO PLAN
3/16" = 1'-0"
ED-101
1. BEFORE EXTERIOR ARCHITECTURAL WORK, ALL
ELECTRICAL EQUIPMENT MOUNTED TO THE EXTERIOR
WALL MUST BE DISCONNECTED , REMOVED AND
PROTECTED. THE EQUIPMENT MUST BE RE-INSTALLED
DURING THE NEW WORK OF THIS PROJECT.
2. ANY EXPOSED DISCONNECTED WIRING MUST BE
TEMPORARILY PROTECTED OR ENCLOSED. BREAKERS
FEEDING REMOVED EQUIPMENT MUST BE TURNED OFF,
LOCKED AND TAGGED.
3. BEFORE INTERIOR ARCHITECTURAL WORK IN ROOM 105,
ALL ELECTRICAL EQUIPMENT MOUNTED ON THE WALLS
AND CEILINGS TO BE REMOVED, MUST BE
DISCONNECTED, REMOVED AND PROTECTED. THE
EQUIPMENT MUST BE RE-INSTALLED DURING THE NEW
WORK OF THIS PROJECT. ALL SUPPORTING
INFRASTRUCTURE INCLUDING CONDUIT AND WIRE ON
SURFACES TO BE REMOVED MUST BE DEMOLISHED
BACK TO THE SOURCE.
4. ALL RECEPTACLES ON WALLS ARE TO BE DEMOLISHED
AND REPLACED WITH NEW.
ALL WORK IN THIS AREA SHALL
BE UNDER BID OPTION 2.
ETR ETR
ETR
ETR
ETR
108T
UT-1
MSB-EX
A-EX
W1
W1
W1E
W1E
W1
ALL WORK IN THIS AREA SHALL
BE UNDER BID OPTION 2.
B-EX B-EX
B-EX B-EX
B-EX B-EX
B-EX
B-EX
EXIT-EX
EX
EX
EX
EX
EX
EX
EX
A-EX-2. UTILIZE EXISTING
SPARE 20/1 BREAKER IN
PANEL A-EX TO FEED
NEW EXTERIOR LIGHTS
PE
ETRETR
ETR
ETR
ETR
W1E @ 7' a.f.f
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
ELECTRICAL FLOOR PLANS
E101
X
SCALE:
BUILDING 005
ELECTRICAL PLAN
3/16" = 1'-0"
E-101
1. EXISTING TO REMAIN ELECTRICAL PANEL.
2. PROVIDE NEW WALL MOUNTED EXTERIOR LIGHT
FIXTURES. PROVIDE NEW INTERIOR SURFACE MOUNTED
CONDUIT TO FIXTURE. INSTALL 2 #12, #12 (G) COPPER IN
3/4" CONDUIT.
3. MOUNT LIGHT FIXTURE AT 11'10" A.F.F. DO NOT MOUNT
UNDERNEATH EXHAUST.
4. INSTALL STORED EXISTING LIGHT FIXTURES IN ROOM
105. (BID OPTION 2)
5. PROVIDE NEW RECEPTACLES. PROVIDE NEW 3/4" EMT
CONDUIT AND 2#12, #12(G) FROM JUNCTION BOX. (BID
OPTION 2)
6. PROVIDE NEW 20A TOGGLE SWITCH TO CONTROL
LIGHTS IN THIS ROOM. PROVIDE NEW 3/4" EMT CONDUIT
AND 2 #12, #12(G) FROM JUNCTION BOX. (BID OPTION 2)
1. WORK ON SHOWN IS TO BE DONE IN COORDINATION
WITH THE NEW EXTERIOR ARCHITECTURAL WORK.
2. WORK SHOWN SHALL BE DONE IN COORDINATION WITH
THE NEW INTERIOR ARCHITECTURAL WORK.
LUMINAIRE SCHEDULE
CALLOUT SYMBOL LAMP DESCRIPTION BALLAST MOUNTING MODEL INPUT
WATTS
VOLTS NOTE 1 NOTE 2 NOTE 3 QUANTITY
W1 (1) ELECTRONIC WALL @ 11'10" 30 120V 1P 2W 3
W1E (1) WALLPACK FIXTURE. VERIFY MOUNTING HEIGHT ELECTRONIC 30 120V 1P 2W 2
WITH 120V BATTERY PACK.
A.F.G
WALL @ 11'10"
A.F.G
WALLPACK FIXTURE. VERIFY MOUNTING HEIGHT
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-CAST ALUMINUM WITH INTEGRAL PASSIVE COOLING MECHANISM.
HEAT SINK MUST BE INCORPORATED DIRECTLY INTO HOUSING OR DRIVER
COMPARTMENT TO ENSURE MAXIMUM HEAT TRANSFER AND DISSIPATION.
2. FINISH - MULTI-STAGE PRE-TREATMENT, FINISHED WITH BAKED-ON POLYESTER
POWDER COAT. IP66 RATED. FINISH IS DARK BRONZE.
3. POWER SUPPLY/LED DRIVER - CLASS 1 DRIVER MUST OPERATE AT 120/277 VOLTS,
50/60 HZ, POWER FACTOR GREATER THAN 0.9 AND THD LESS THAN 20% AT FULL LOAD.
MINIMUM EFFICACY MUST BE 60 LM/W AT MAXIMUM 600mA OPERATING CURRRENT.
4. LED OPTICAL ASSEMBLY - PRECISION MOLDED ACRYLIC LENS PROVIDED FOR MULTIPLE
HIGH-POWERED LEDS. BUG UPLIGHT RATING OF U0. MINIMUM COLOR RENDERING
INDEX(CRI) MUST BE 70 FOR CORRELATED COLOR TEMPERATURE OF 4000K.
5. CERTIFICATION - UL AND/OR ETL LISTED FOR DAMP OR WET LOCATIONS (FOR EXTERIOR
WALL MOUNT) AND RoHS COMPLIANT.
6. OPTIONS - VARIOUS LUMEN OUTPUT RATINGS AS INDICATED.
7. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE
THAT MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE
A CERTAIN MANUFACTURER OR PREFERENCE.
LED WALL MOUNTED FIXTURE
FIXTURE TYPE: W1, W1E
U
D A
S
B005 EXT. ENVELOPE & OTHER REPAIRS
LIGHTING DETAILS
E201
8. 120V BATTERY PACK WITH SELF DIAGNOSTIC TESTING FEATURE RATED FOR 90 MINUTES
SHALL BE PROVIDED FOR FIXTURE TYPE 'W1E'. BATTERY PACK SHALL BE RATED FOR
-20 DEGREES C MIN.
| Project A Arch |
| Sheets and Views |
| T101-T101 |
| T102-T102 |
| A101-AD101 |
| A151-AD151 |
| A201-AD201 |
| A301-AD301 |
| A101-A101 |
| A151-A151 |
| A201-A201 |
| A301-A301 |
| A501-A501 |
| PLUMB Project A |
| Sheets and Views |
| P-101-P101 |
| P-601-P601 |
| 4924-M Elec Proj A |
| Sheets and Views |
| E-001 |
| E-002 |
| ED-101 |
| E-101 |
| E-201 |
File details come from the government source that posted it. Updated .