Attachment 4 Drawings.pdf
PDF 15 MB Posted
- Solicitation number
- 1232SA26Q0470
About this file
This document is a technical drawing set for the 2026 PPW (Primary Pathogen Waste) Vaults Upgrade project at the United States Department of Agriculture, Agriculture Research Service, National Centers for Animal Health in Ames, Iowa.
The project involves upgrading three Pathogen Waste Vaults (PPW101B, PPW103, and PPW105) located on the NCAH campus. The primary scope of work entails replacing carbon steel piping sections with stainless steel piping while retaining existing fiberglass piping components. PPW101B is designated as the Base Bid, while PPW103 and PPW105 are identified as Alternative 1 and Alternative 2 respectively. The technical drawings provide detailed one-line diagrams, top-down views, side views, and internal photographs of each vault system. Each vault contains complex piping networks with isolation valves (VIS), single-wall pipes (PWS), and double-wall pipes (PWD) of varying diameters (2-inch and 4-inch). The drawings clearly identify which carbon steel sections require replacement and which fiberglass sections are to remain in place. Internal photographs document the current condition of the equipment, including visible corrosion and scale buildup on the existing carbon steel components. The technical specifications indicate multiple interconnected piping sections organized into identifiable sections (A through E) within each vault structure.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 1232SA26Q0470 Amend 3.pdf | ||
| Attachment 5 Questions from Industry REV 1.pdf | ||
| 1232SA26Q0470 Amend 2.pdf | ||
| Attachment 5 Questions from Industry.pdf | ||
| 1232SA26Q0470 Amend 1.pdf | ||
| SF 1442 1232SA26Q0470.pdf | ||
| Attachment 2 Specifications.docx | DOCX document | |
| SF 1442 1232SA26Q0470.pdf | ||
| Attachment 1 Statement of Work.docx | DOCX document | |
| Attachment 3 WD IA20250003 Mod 0 Dated 2 Jan 2026.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Location Coordinator:Contracting Officer Rep.:Contracting Officer:Engineering Project Manager:
Task
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet:
Designer:
Date:
Date:
UNITED STATES DEPARTMENT OF AGRICULTURE
AGRICULTURE RESEARCH SERVICE
NATIONAL CENTERS FOR ANIMAL HEALTH
Ben A'Hearn TBD Brandon Keith
2026 PPW Vaults Upgrade
Title Page
1/21/2026
Brandon Keith P01
25031 1 of 15
2026 PPW Vaults Upgrade
P01 Title Page
P02 Locations of PPWs on campus
P03 PPW Internal Details
P04 PPW101B Drawings
P05 PPW101B - One line
P06 PPW101B Internal pics
P07 PPW101B Views
P08 PPW103 Drawings
P09 PPW013 - One line
P10 PPW103 Views
P11 PPW103 Internal pics
P12 PPW105 Drawings
P13 PPW105 - One line
P14 PPW105 Views
P15 PPW105 Internal pics
FOR REVIEW
Drawing Title:
Drawing Number:
Sheet:
PPW105
(ALT 2)
PPW103
(ALT 1)
PPW101B
(BASE BID)
Locations of PPWs on campus PPW Locations on campus
P02
Sheet:
Typical for all PPW Vaults
PPW Internal Details
P03
Sheet:
PPW 101B Drawings and Details
PPW101B drawings
P04
Sheet:
2" AIR VENT
2" VIS-17
2" V
IS
-1
2"
P W
S-
TO
PPW-101A
FROM PPW-102, B20.
SERVES B20, B21,
B401, B403.
TO
PPW-101A
FROM PPW-102, B9
4" PWS-01
2" PWS-04
4" PWD-02
2" PWS-03
2" VIS-03
4" PWD-01
2" PWS-02
2" VIS-06
4" PWD-04
2" PWS-07
2" VIS-13
4" PWS-05
2" VIS-10
4" PWD-03
2" PWS-06
4" VIS-07
2" VIS-02 2" VIS-012" VIS-05 2" VIS-04
4" VIS-14
2" VIS-09 2" VIS-082" VIS-12 2" VIS-11
TO
PPW-101A
4" PWD-05
4" PWS-08
2" VIS-20
2" VIS-19 2" VIS-18
4" VIS-21
2" PWS-09
2" VIS-16
PPW101B - One line
VIS = Isolation Valve PWS = Single wall pipe PWD = Double wall pipe
PPW101B - One line
P05
Sheet:
Inside PPW101B - Looking South Inside PPW101B - Looking West PPW101B internal pics
P06
Sheet:
PPW101B Views
P07
N O
RT
H
Carbon Steel sections to be replaced with Stainless Steel
Fiberglass piping to remain
Carbon Steel sections to be replaced with Stainless Steel
Fiberglass piping to remain
PPW101B - Top down PPW101B - Side View
S ec tio n
A
S ec tio n
C
S ec tio n
D
Section B
Section E
Sheet:
PPW 103 Drawings and Details
PPW103 Drawings
P08
Sheet:
TO
PPW-102
FROM B9
TO
PPW-102
2" AIR VENT
2" VIS-17
2" V
IS
-1
2" VIS-16
2" PWS-10
4" PWS-01
2" PWS-04
4" PWD-02
2" PWS-03
4" PWD-01
2" VIS-06
2" PWS-08
4" PWD-04
2" PWS-07
2" VIS-13
2" PWS-09
4" PWS-05
4" PWD-03
2" VIS-03
2" PWS-02
2" VIS-10
2" PWS-06
FROM PPW-104, B20.
SERVES B20, B21,
B401, B403.
4" PWD-05
2" PWS-12
2" PWS-13
2" PWS-11
4" VIS-07
2" VIS-042" VIS-05 2" VIS-012" VIS-02
4" VIS-14
2" VIS-112" VIS-12 2" VIS-082" VIS-09
2" VIS-20
4" VIS-21
2" VIS-182" VIS-19
FROM PPW-104, B20.
SERVES B20, B21,
B401, B403.
PPW103 - One line
VIS = Isolation Valve PWS = Single wall pipe PWD = Double wall pipe
PPW013 - One line
P09
Sheet:
NORTH
PPW103 - Side Views
PPW103 - Top Down
Carbon Steel sections to be replaced with Stainless Steel
Carbon Steel sections to be replaced with Stainless SteelCarbon Steel sections to be replaced with Stainless Steel
Fiberglass piping to remain
Fiberglass piping to remain
Fiberglass piping to remain
Section BSection A
Section C Section D
Section E
PPW103 Views
P10
Sheet:
PPW105 - Looking Northeast PPW105 - Looking Southeast
PPW105 - Looking Southeast
PPW103 Internal pics
P11
Sheet:
PPW 105 Drawings and Details
PPW105 Drawings
P12
Sheet:
TO
PPW-104
FROM PPW-106, B20.
SERVES B20, B21,
B401, B403.
2" AIR VENT
2" VIS-10
4" PWS-01
2" VIS-08
2" VIS-09
2" PWS-04
4" PWD-02
2" PWS-03
2" VIS-03
4" PWD-01
2" PWS-05
2" VIS-06
4" VIS-07
2" VIS-042" VIS-05 2" VIS-012" VIS-02
PPW105 - One line
VIS = Isolation Valve PWS = Single wall pipe PWD = Double wall pipe
PPW105 - One line
P13
Sheet:
N O
RT
H PPW105 - Top View
PPW105 - Side View
Section A Section B
Carbon Steel sections to be replaced with Stainless Steel
Fiberglass piping to remain
Fiberglass piping to remain
Fiberglass piping to remain
PPW105 Views
P14
Sheet:
Inside PPW105 - Looking southeast Inside PPW105 - Looking northeast
PPW105 Internal pics
P15
File details come from the government source that posted it. Updated .