This document is a Standard Form 30 Amendment of Solicitation/Modification of Contract for a 50kW/kVA Lighting Inverter with maintenance bypass cabinet. The amendment addresses vendor questions about the solicitation, providing clarifications on key technical specifications. Specific details include:
The solicitation requires a 50kW inverter with an internal 3-circuit breaker maintenance bypass, backlit LCD display, and BACnet network capability. Vendors asked about power capacity, power factor, and system configuration. The government confirmed they need an internal bypass due to space restrictions, require a 0.8 power factor, and will accept a 40kVA unit with 1.0 power factor as equivalent to the 50kVA unit. The period of performance is from 06/27/2025 to 08/27/2025, with quotes due by 13 June 2025 at 3:00pm Central Time. The solicitation is issued by the USDA Agricultural Research Service, targeted for small businesses under NAICS code 335311.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SOW .pdf | ||
| Supply Provisions and Clauses.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(x)
1232SA25Q0125
x x copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE
RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR
OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
x
ARS-126125
AMES IA 50010
P.O. BOX 70
1920 DAYTON AVENUE
MWA NATIONAL ANIMAL DISEASE CENTER
ARS-1232SA
BELTSVILLE MD 20705
RM 3-2102
5601 SUNNYSIDE AVENUE
USDA ARS ACQUISITION AND PROPERTY D
05/29/20250002
13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
12. ACCOUNTING AND APPROPRIATION DATA (If required) is not extended.is extended, Items 8 and 15, and returning
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
FACILITY CODE CODE
10B. DATED (SEE ITEM 13)
10A. MODIFICATION OF CONTRACT/ORDER NO.
9B. DATED (SEE ITEM 11)
9A. AMENDMENT OF SOLICITATION NO.
CODE
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)
7. ADMINISTERED BY (If other than Item 6)CODE 6. ISSUED BY
PAGE OF PAGES
4. REQUISITION/PURCHASE REQ. NO.3. EFFECTIVE DATE2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO. (If applicable)
1. CONTRACT ID CODE
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
05/29/2025
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority) appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
E. IMPORTANT: Contractor is not is required to sign this document and return __________________ copies to the issuing office.
ORDER NO. IN ITEM 10A.
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)
15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED
(Signature of person authorized to sign) (Signature of Contracting Officer)
LAM V. PHAM
STANDARD FORM 30 (REV. 11/2016)
Prescribed by GSA FAR (48 CFR) 53.243
Previous edition unusable
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
The purpose of this amendment is to answer questions proposed by vendors about solicitation. They are below:
Q: In an effort to keep pricing down, is 48KW enough capacity for your load? Please keep in mind, we recommend between 20-25% extra capacity from load size to incorporate for any inrush that may occur?
A: We do not want to decrease the kW. Our current unit is a 50kW and that is what we need in a replacement.
Q: The spec says "unit shall have a 3-circuit breaker adjacent maintenance bypass."
(screen shot below) - I'm not quite sure what is being asked for here. Is it 3 internal aux Continued ...
Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .
ITEM NO. SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
NAME OF OFFEROR OR CONTRACTOR
2 2
CONTINUATION SHEET
REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF
(A) (B) (C) (D) (E) (F)
1232SA25Q0125/0002
breakers or an external maintenance (something else perhaps)? As an FYI, our 3-phase inverters come standard with an internal maintenance bypass. We can do an external bypass if there are no internal aux breakers being used, but it will add cost and footprint. I recommend sticking with the standard internal option.
A: Due to the space restrictions in the room, we cannot have an external bypass. We will require an internal bypass.
Q: Could you please confirm if this configuration is acceptable or if the requirement strictly calls for a true UPS system equivalent to the Galaxy VS UPS?
A: Our current unit serves as both UPS and lighting inverter for lighting and other 208/120V electrical panels throughout the building. From what I can see from this configuration, this unit would meet the need.
Q: Also, please advise if the additional features such as backlit LCD display, maintenance bypass with 3 circuit breakers, BACnet network capability, and size constraints are fully met or required.
A: The backlit LCD display will be required.
The 3-breaker maintenance bypass needs to be internal to the unit, no external bypass. BACnet capability is required. From the attached specifications, it appears that this unit would fit in the space.
Q: What is the power factor of the existing system?
A: 0.8
Q: The 50kW inverter, with batteries, at 1.0 PF is 10" to long for the pad. If the existing system has a PF of .8, then a 40kW system with a
1.0 PF which would fit the pad, is equivalent to
the 50kW system at .8 PF. Please let me know what power factor is required.
A: If the 40kVA unit with PF of 1 is the equivalent of the 50kVA unit with PF of 0.8, then the 40kVA will be acceptable.